1.The Weight of theTP48200A: 110 kg (242.55 lb) (excluding the weight of the power supply unit (PSU) and
storage batteries) .
TP48200A 110kg
2. Cabinet dimensions (excluding the base) : 1500 mm x 600 mm x 650 mm (59.06 in. x 23.62 in. x 25.59 in.) (height
x width x depth)
1500mm600mm650mm
3. Dimensions of the base : 100 mm x 600 mm x 650 mm (3.94 in. x 23.62 in. x 25.59 in.) (height x width x depth)
100mm600mm650mm
Socket wrench
Drill holes and install expansion sleeves.
1. The outputs of the TP48200A-H15A1 (TP48200A for short) can be customized. The picture is for reference only.
TP48200A-H15A1TP48200A
2. The local cable colors prevail. The cable colors in the figure are for reference only.
Battery temperature sensor
Installing the Cabinet. /
Cable outlet
Installing Batteries /
+ - + - + - + -
Installing batteries, pay attention to the positive and negative pole of the battery. Then connecting copper bars or cables .
The battery temperature sensor is installed on the side panel interior by default. If the storage batteries match the battery
temperature sensor, installing the battery temperature sensor on the battery terminal.
TP48200A-H15A1 V300R001
TP48200A-H15A1 V300R001
Quick Installation Guide
Issue: 02
Date: 2012-12-05
02
2012-12-05
NOTE /
Cabinet Appearance /
NOTE /
Battery rack
Installing the TP48200A /
Fix the installation hole
Spring washer /
Flat washer /
Socket wrench
16mm
(0.63 in.)
52mm~60mm
(2.05 in. ~2.36 in.)
Bolt /
Expansion sleeve
M12 x 60 (4pcs)
Before installation, switch all circuit breakers to the OFF position.
OFF
CAUTION /
1. Before installing power cables for storage batteries , remove one copper bar or cable from each battery string.
2. Do not bind the AC power cables, DC power cables, signal cables, and communications cable together.
Connect cables in the following sequence: s1 s2 d1 d2 d3 a1
s1 s2 d1 d2 d3 a1
CAUTION /
(Optional) Installing signal cables to dry contacts, Boolean values, and sensor ports. /
1. Press the white contact plates slightly using a flat-head screwdriver. Then, insert the two wires on the other end of the
signal cable into the corresponding ports, and pull out the screwdriver to fasten the dry contact signal cable.
2. Connect the sensor cable to the corresponding ports on the monitoring user interface module. ( See the sensor pin
definitions in the TP48200A-H15A1 User Manual.)
PinTP48200A-
H15A1
All ports in this manual are protected by a security mechanism/
(Optional) Installing the RS232, RS485, or FE Cable / RS232RS485FE
1. When in-band monitoring is required , connect the COM_ 485/232 port on the SMU to the communications equipment
over a cable with an RJ45 connector.
RJ45COM_ 485/232
2. When out-of-band monitoring is required, connect the FE port on the SMU to the communications equipment over a
cable with an RJ45 connector.
RJ45FE
Dry contact
White
Contact
plate
NOTE /
Installation hole
Front /
Wall or platformedge
Ground
+ - + - + - + -
Space for PSU
s2
ACDB
a1
s1,s2
d1
d2
Sensor
Element management
system(EMS)
Secondary load
Primary load
d1 d2
Maintenance
socket
L
d3
N
d3
s1
Battery circuit
breakers
Circuit breaker
of the Socket
a1
RTN+
-48V
Port Type / Silkscreen / Description /
Sensor ports /
TEM_HUM Temperature and humidity sensor /
WATER Water sensor /
TEMP1 Connected to environment temperature sensor
and used for fan speed adjustment
TEMP2 Reserved /
GATE Door status sensor /
SMOKE Smoke sensor /
BTEMP Battery temperature sensor /
Boolean value input ports / DIN1 Boolean value input 1 / 1
DIN2 Boolean value input 2 / 2
DIN3 Boolean value input 3 / 3
DIN4 Boolean value input 4 / 4
DIN5 Boolean value input 5 / 5
DIN6 Boolean value input 6 / 6
Dry contact output ports /
Default mode (Close: alarm; Open: normal) can
be modified as required.
ALM1 AC power failure alarm /
ALM2 DC undervoltage alarmor DC overvoltage alarm
ALM3 Rectifier faults alarm /
ALM4 SPD failure alarm/
ALM5 Fuse burn-out alarm /
ALM6 Battery temperature alarms /
ALM7 Door alarms /
ALM8 TCU alarms /
Communication Port / COM RS485/RS232
Verifying the Installation /
SN / Check Item /
1
The TP48200A is installed properly and the cables are connected properly. (Cables fastened by screws
are not easily removable.)
2
Cables are arranged neatly and bound properly by using cable ties.
3
The storage battery is connected properly.
4
Check for short circuits between the live wire and the ground cable, between the live wire and the neutral
wire, between the RTN+ and the 48 V busbar. Rectify short circuits before powering on the TP48200A.
RTN+-48V
Powering On and Commissioning the TP48200A /
Troubleshooting /
Trouble Symptoms
1. Make sure the AC input circuit breaker is in the ON position.
on
2. Make sure the AC input voltage is in the range of the PSU working space.
PSU
3. After above 2 steps, the trouble still exist, plug the PSU out then plug in to restart the PSU.
2PSU
4. After above 3 steps , the trouble still exist, change a new one.
3PSU
518129
www.huawei.com
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base Bantian Longgang
Shenzhen 518129
Peoples Republic of China
www.huawei.com
Switch the AC input circuit breaker to the ON position, measure the voltage between L wiring and N wiring terminal .
The voltage must range from200 V to 240 V. The rated voltage is 220 V.
ONLN200V~240V220V
Switch the LLVD and BLVD branches to the ON positions , Measure whether the voltage between RTN+ and the 48 V
check points. The voltage must range from42 V to 58 V. The rated voltage is 53.5 V. Check whether the loads work
normally. If the loads work abnormally, rectify the fault according to the relevant user Manual.
ON42V~58V53.5V
Switch the circuit breakers for the Maintenance socket, AC input, battery route, primary load, and secondary load as
required.
Check whether the EMS can receive the information fromthe power system. If not, check whether the IP address is set
correctly .
IP
Observe the operation of the power system for 15 minutes. If no alarms are generated, and current/voltage parameters
of the storage battery and loads are set properly, then re-install the cover of the distribution unit, lock the door to the
cabinet, give the key of the cabinet door to the customer, and clean the site before leaving.
15LCD
d3
Measure the voltage across the input ports of AC input circuit breakers. The voltage must range from 200 V to 240 V.
The rated voltage is 220 V. If not, ask professionals to rectify the fault.
200V~240V220V
To avoid damaging storage batteries, connect mains to the TP48200A only after correctly setting the storage battery
parameters on the SMU.
CAUTION /
Switch the AC input circuit breakers to the ON positions. Check whether the voltage between the RTN+ busbar and the
-48 V copper bar are the same as the storage battery voltage and the voltage displayed on the monitoring unit. If not,
ask professionals to rectify the fault.
ON
Setting parameters on the SMU. /
Button / Description /
or
Allows you to view menu items and set the value of a menu item by pressing or .
Returns to the previous menu without saving the settings of the current menu item.
Enters the main menu from the standby screen, enters a submenu from the main menu, or saves
the settings of a submenu item.
Enter Enter
Enter
1. The preset username is admin and the preset password is 001. /admin001
2. After a menu is displayed, the standby screen is displayed and the LCD screen becomes dark if you do not press
any button within 5 minutes.
5LCD
3. You need to log in again if you do not press any button with 8 minutes. / 8
Main Menu
Second-Level Menu
Third-Level Menu
Default Value
Settings
Comm Para
NetEco Main IP / NetEcoIP -
NetEco Bak IP / NetEco IP -
NetEco Port / NetEco 31220
SystemPara
LUI Language / LUI ENGLISH /
Set Time Zone / GMT +0800
Quick Setting
Qty of Battery / - 1
Rated Capacity / - 150Ah
Set Date / - 2000-01-28
Set Time / - -
IP Address / IP - -
Subnet Mask / - -
Gateway / - -
1. Set the NetEco Main IP, NetEco Bak IP, NetEco Port, LUI Language and Set Time Zone according to actual conditions.
NetEcoIP NetEco IP NetEco LUI
2. Set the Qty of Battery, Rated Capacity, Set Date and Set Time according to actual conditions. (Always set Qty of Battery
to 1 and set Rated Capacity to the total capacity of all battery strings.)
(1
)
3. Obtain the IP Address, Subnet Mask and Gateway fromthe EMS.
IP
Reinstall the removed copper bar or cable of the storage battery. /
Switch the storage battery circuit breakers in the PDU to the ON positions. / ON
Switch the AC input circuit breakers to the OFF positions. / OFF
d3
4. Set battery fuse break alarm "Enable/Disable" status
/
Main
Menu
Second-Level
Menu
Third-Level Menu
Fourth-Level Menu
Set Value
Settings
AlarmSetting
Site Summary
Battery Fuse 2 Break/2
Battery Fuse 3 Break/3
Battery Fuse 4 Break/4
Battery Fuse 5 Break/5
Battery Fuse 6 Break/6
Battery Fuse 7 Break/7
Battery Fuse 8 Break/8
Battery Fuse 9 Break/9
Battery Fuse10 Break/10
Battery Fuse 11 Break/11
Battery Fuse 12 Break/12