VENTILATION DESIGN WORK SHEET


Organization:

Elevation:
Temperature:

Location: Shop: 1 Duct Segment Identification 1a 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

Factor:

0 Feet Date: 70 Degrees F Drawing No. Designer:

Velocity Pressure Calculation Method


Type of Duct (GALV=Galvinzied) (BLK=Black Iron, Al, SS) Volumetric Flowrate: (See Design Criteria) cfm Minimium Transport Velocity (See Design Criteria) fpm Duct Diameter (Round Duct) inches Duct Area Sq. Ft. Actual Duct Velocity fpm Duct Velocity Pressure (Vd/4005)^2 = VP "wg H Slot Area Sq. Ft. O S Slot Velocity fpm O L Slot Velocity Pressure "wg D O Slot Loss Factor (ACGIH Vent Manual Chapter 10) T Acceleration Factor 0 or 1 S S Plenum Loss per VP U Plenum SP C Duct Entry Loss Factor (See Design Specifications) T Acceleration Factor (if Vd>Vs; 1) 1 or 0 I Duct Entry Loss per VP O Duct Entry Loss "wg N Other Loss "wg Hood Static Pressure (SPh) "wg Straight Duct Length feet Friction Factor (Hf) Friction Loss per VP No. of 90 Degree Elbows Elbow Loss per VP (See Table Below or ACGIH, Fig 5-13) Number of Entries Entry Loss per VP (See Table Below or ACGIH, Fig 5-14) Special Fittings Loss Factors Duct Loss per VP Duct Loss "wg Duct SP Loss "wg Cumulative Static Pressure "wg Governing Static Pressure "wg Corrected Volumetric Flowrate (Balanced) cfm Resultant Velocity Pressure "wg Corrected Velocity (Based on the Governing SP) fpm

PERTINENT EQUATIONS:
R/D 0.5

0.75

90 Degree Round Elbow Loss Fact 1

Page 1

Vent-Design

Q corr. = Q Design (SP gov./ SP duct)^1/2 VP r = ((Q1 + Q2)/(4005(A1 + A2)))^2 = (Q1/Q3)*VP1 + (Q2/Q3)*VP2 or

Stamped 5- Piece 4- Piece 3- Piece

0.71

0.9

0.33 0.46 0.5 0.54

0.22 0.33 0.37 0.42

Hf

= 0.0307(V^0.533)/(Q^0.612) = GALV in Line 1a = 0.0425(V^0.465)/(Q^0.602) = BLK in Line 1a

60 elbow = 2/3 loss 45 elbow = 1/2 loss 30 elbow = 1/3 loss Branch Entry Loss Factors Angle Factor 15 0.09 30 0.18 45 0.28 60 0.44 90 1

FSP = TP ME = =

FSP Ce
SPh VP he

= SP outlet - SP inlet - VP inlet = Coefficient of Entry = (VP / SPh)^1/2 or 1 (for perfect hood - No losses) = Hood Static Pressure = (V/4005)^2 = Velocity Pressure = Entry Loss
= SPh - he

ME

BHP =

= Fh x VP

TP

= Total Pressure

= SP + VP

SP; VP = Static Pressure; Velocity Pressure Vd = Duct Velocity

Fan Specifications Blade Type: Size: RPM: HP:

Existing

Page 2

Vent-Design

30-Mar-14

gree Round Elbow Loss Factors 1.5 2

2.5

Page 3

Vent-Design

0.15 0.24 0.27 0.34

0.13 0.19 0.24 0.33

0.12 0.17 0.23 0.33

Fan Static Pressure


FSP + VP out = Mechanical efficiency (Usually .5 - .65) 1 Q x TP = 6356 x ME Q=

#VALUE! #VALUE!

0 #VALUE! Delta in SP: Delta in SP(1):

#VALUE! #VALUE!

Required Tubeaxial

######