PROJECT : DLF Capital Green - SBM, New Delhi

Design Summary sheet and Equipment selection


(SPLIT AIR-CONDITIONING SYSTEM)

2.0 TR / 510 CFM

Totat

Qty

1.5 TR / 450 CFM

CFM

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Monsoon Dehumidified
CFM

FT

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Sqft

( Hi-wall

1.5 TR / 450 CFM

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

Equipment selection
unit)

AREA

Tower - 1 / 18

Qty

Qty

TR

CFM

KW

KW

KW

KW

Stilt floor
FLAT -1

1.1

Living & Dining

290

2.22

1119

747

1020

5.2

5.2

1.2

Master Bed Room - 1

157

1.08

593

390

510

2.6

2.6

1.3

Bed Room - 2

120

0.68

358

252

330

1.3

1.3

1.4

Bed Room - 3

120

0.68

358

252

1.3

Sub Total

687

4.66

2428

1641

330

8.0

2190

1.3
10.4

FLAT-5

2.1

Living & Dining

290

1.99

983

640

900

3.9

3.9

2.2

Master Bed Room - 1

157

0.85

454

276

1.5

450

1.95

1.95

2.3

Bed Room - 2

120

0.54

274

187

330

1.3

1.3

2.4

Bed Room - 3

120

0.54

274

187

330

1.3

1.3

Sub Total

687

3.92

1985

1290

6.5

2010

8.5

Total

1374

8.58

4413

2931

14.5

4200

18.9

Typical floor ( 1st to 3rd & 12th to 20th floor)


FLAT -1

1.1

Living & Dining

290

2.22

1119

747

1020

5.2

5.2

1.2

Master Bed Room - 1

157

1.08

593

390

510

2.6

2.6

1.3

Bed Room - 2

120

0.68

358

252

330

1.3

1.3

1.4

Bed Room - 3

120

0.68

358

252

330

1.3

Sub Total

687

4.66

2428

1641

8.0

2190

1.3
10.4

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-44

P-021,031

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 1 / 18

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Living & Dining

355

2.45

1247

813

1020

5.2

5.2

2.2

Master Bed Room - 1

200

1.05

568

363

510

2.6

2.6

2.3

Bed Room - 2

120

0.82

438

292

1.5

450

1.95

1.95

2.4

Bed Room - 3

140

1.00

545

345

2.6

Sub Total

815

5.32

2798

1813

CONDITIONED SPACE

FLAT-2

1.5 TR / 450 CFM

SUMMER REF. LOAD

2.1

1.0 TR / 330 CFM

HEIGHT

( Hi-wall

AREA

Equipment selection
unit)

510

9.5

2490

Power reqd. ( single phase)

2.6
12.4

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-45

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 1 / 18

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Living & Dining

516

2.69

1337

861

1020

5.2

5.2

3.2

Master Bed Room - 1

226

1.14

619

376

510

2.6

2.6

3.3

Bed Room - 2

153

0.84

450

281

1.5

450

1.95

1.95

3.4

Bed Room - 3

148

0.91

487

321

1.5

450

1.95

1.95

3.5

Bed Room - 4

160

0.95

512

299

510

2.6

2.6

Sub Total

1203

6.53

3405

2138

11.0

2940

1020

5.2

5.2

1.5

450

1.95

1.95

330

1.3

1.3

1.5

450

1.95

1.95

8.0

2250

CONDITIONED SPACE

FLAT-3

Power reqd. ( single phase)

S163

14.3

FLAT-4

4.1

Living & Dining

269

2.10

1049

674

4.2

Master Bed Room - 1

148

0.86

463

286

4.3

Bed Room - 2

120

0.70

368

236

4.4

Bed Room - 3

150

0.83

445

271

Sub Total

687

4.49

2325

1467

1.5 TR / 450 CFM

SUMMER REF. LOAD

3.1

1.0 TR / 330 CFM

HEIGHT

( Hi-wall

AREA

Equipment selection
unit)

1
1
1
1

10.4

FLAT-5

2.1

Living & Dining

290

1.99

983

640

900

3.9

3.9

2.2

Master Bed Room - 1

157

0.85

454

276

1.5

450

1.95

1.95

2.3

Bed Room - 2

120

0.54

274

187

330

1.3

1.3

2.4

Bed Room - 3

120

0.54

274

187

330

1.3

1.3

Sub Total

687

3.92

1985

1290

6.5

2010

8.5

48948

299.04

155292

100188

60

96

156

516.0

142560

670.8

S185

Total ( 1st to 3rd &


12th to 20th floor)

Typical floor ( 4th to 11th floor)


FLAT -1

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-46

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 1 / 18

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Living & Dining

290

2.22

1119

747

1020

5.2

5.2

1.2

Master Bed Room - 1

157

1.08

593

390

510

2.6

2.6

1.3

Bed Room - 2

120

0.68

358

252

330

1.3

1.3

1.4

Bed Room - 3

120

0.68

358

252

1.3

Sub Total

687

4.66

2428

1641

CONDITIONED SPACE

1.5 TR / 450 CFM

SUMMER REF. LOAD

1.1

1.0 TR / 330 CFM

HEIGHT

( Hi-wall

AREA

Equipment selection
unit)

Power reqd. ( single phase)

P-111,061,101

330

8.0

2190

1.3
10.4

FLAT-2

2.1

Living & Dining

355

2.45

1247

813

1020

5.2

5.2

2.2

Master Bed Room - 1

200

1.05

568

363

510

2.6

2.6

2.3

Bed Room - 2

120

0.82

438

292

1.5

450

1.95

1.95

2.4

Bed Room - 3

140

1.00

545

345

2.6

Sub Total

815

5.32

2798

1813

510

9.5

2490

2.6
12.4

FLAT-3

3.1

Living & Dining

516

2.69

1337

861

1020

5.2

5.2

3.2

Master Bed Room - 1

226

1.14

619

376

510

2.6

2.6

3.3

Bed Room - 2

153

0.84

450

281

1.5

450

1.95

1.95

3.4

Bed Room - 3

148

0.91

487

321

1.5

450

1.95

1.95

3.5

Bed Room - 4

160

0.95

512

299

2.6

Sub Total

1203

6.53

3405

2138

510

11.0

2940

2.6

1020

5.2

5.2

1.5

450

1.95

1.95

14.3

FLAT-4

4.1

Living & Dining

269

2.10

1049

674

4.2

Master Bed Room - 1

148

0.86

463

286

S114

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-47

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Bed Room - 3

150

0.83

445

271

Sub Total

687

4.49

2325

1467

Totat

4.4

2.0 TR / 510 CFM

236

1.5 TR / 450 CFM

368

1.0 TR / 330 CFM

0.70

Power reqd. ( single phase)

Total CFM

Monsoon Dehumidified
CFM

( Hi-wall

Total TR

Summer Dehumidified
CFM

120

2.0 TR / 510 CFM

SUMMER REF. LOAD

Bed Room - 2

CONDITIONED SPACE

1.5 TR / 450 CFM

HEIGHT

4.3

Equipment selection
unit)
1.0 TR / 330 CFM

AREA

Tower - 1 / 18

330

1.3

1.3

1.5

450

1.95

1.95

8.0

2250

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

S114

1
1
1

10.4

FLAT-5

2.1

Living & Dining

290

1.99

983

640

2.2

Master Bed Room - 1

233

1.16

628

367

2.3

Bed Room - 2

120

0.54

274

187

2.4

Bed Room - 3

120

0.54

274

187

330

Sub Total

763

4.23

2159

1381

7.0

2070

9.1

33240

201.84

104920

67520

40

56

112

348.0

95520

452.4

Total ( 4th to 11th


floor)

2
1

21st floor
FLAT -1

1.1

Living & Dining

290

2.42

1236

869

1020

5.2

5.2

1.2

Master Bed Room - 1

157

1.19

656

456

510

2.6

2.6

1.3

Bed Room - 2

120

0.77

407

302

1.5

450

1.95

1.95

1.4

Bed Room - 3

120

0.77

407

302

1.5

450

1.95

1.95

Sub Total

687

5.15

2706

1929

9.0

2430

11.7

FLAT-2

2.1

Living & Dining

355

2.69

1390

961

1020

5.2

5.2

2.2

Master Bed Room - 1

200

1.19

648

446

510

2.6

2.6

2.3

Bed Room - 2

120

0.90

486

343

1.5

450

1.95

1.95

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-48

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Totat

2153

2.0 TR / 510 CFM

3125

1.5 TR / 450 CFM

5.88

1.0 TR / 330 CFM

403

Power reqd. ( single phase)

Total CFM

601

( Hi-wall

Total TR

1.10

1.5 TR / 450 CFM

1.0 TR / 330 CFM

815

Monsoon Dehumidified
CFM

Sub Total

Summer Dehumidified
CFM

140

Equipment selection
unit)
2.0 TR / 510 CFM

Bed Room - 3

SUMMER REF. LOAD

2.4

CONDITIONED SPACE

HEIGHT

AREA

Tower - 1 / 18

510

2.6

2.6

9.5

2490

4.5

1350

5.85

5.85

12.4

FLAT-3

3.1

Living & Dining

516

3.04

1544

1077

3.2

Master Bed Room - 1

226

1.29

709

470

510

2.6

2.6

3.3

Bed Room - 2

153

0.95

512

345

510

2.6

2.6

3.4

Bed Room - 3

148

1.01

547

383

510

2.6

2.6

3.5

Bed Room - 4

160

1.06

576

366

2.6

Sub Total

1203

7.35

3888

2641

510

12.5

3390

2.6
16.25

FLAT-4

4.1

Living & Dining

269

2.28

1157

787

1020

5.2

5.2

4.2

Master Bed Room - 1

148

0.96

522

348

510

2.6

2.6

4.3

Bed Room - 2

120

0.78

416

286

1.5

450

1.95

1.95

4.4

Bed Room - 3

150

0.94

505

334

510

2.6

2.6

Sub Total

687

4.96

2600

1755

9.5

2490

12.35

FLAT-5

2.1

Living & Dining

290

2.19

1099

761

1020

5.2

5.2

2.2

Master Bed Room - 1

157

0.96

517

341

510

2.6

2.6

2.3

Bed Room - 2

120

0.62

323

237

330

1.3

1.3

2.4

Bed Room - 3

120

0.62

323

237

330

1.3

Sub Total

687

4.39

2262

1576

8.0

2190

10.4

Total

4079

27.73

14581

10054

18

48.5

12990

63.1

1.3

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-49

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

537

Totat

2.0 TR / 510 CFM

255270

1.5 TR / 450 CFM

927

Power reqd. ( single phase)


1.0 TR / 330 CFM

2.0 TR / 510 CFM

1.5 TR / 450 CFM

1.0 TR / 330 CFM

Monsoon Dehumidified
CFM

Summer Dehumidified
CFM

279206 180693 106 162 289

( Hi-wall

Total CFM

87641

Equipment selection
unit)

Total TR

Grand Total

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 1 / 18

1205

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-50

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CFM

Total TR

TR

Power reqd. ( single phase)

2.0 TR / 510 CFM

FT

( Hi-wall

1.5 TR / 450 CFM

Sqft

Equipment selection
unit)
1.0 TR / 330 CFM

Summer Dehumidified
CFM

Stilt floor
FLAT -1

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 2

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

1.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

1.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

1.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

696

4.93

2576

1
1
0

1.5

450

9.0

2430

11.7

FLAT-3

2.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

2.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

2.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

696

4.93

2576

1
1
0

1.5

450

9.0

2430

11.7

FLAT -4

1.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

1.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

1.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

1.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

696

4.93

2576

1
1
0

1.5

450

9.0

2430

11.7

FLAT-6

2.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

2.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

2.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.82

438

1.5

450

1.95

1.95

Sub Total

696

4.93

2576

9.0

2430

1
1
0

11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-48

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

1.5 TR / 450 CFM

2.0 TR / 510 CFM

CFM

Qty

Qty

Qty

TR

CFM

KW

KW

KW

10304

12

36.0

9720

Totat

1.0 TR / 330 CFM

TR
19.7

Total TR

Total CFM

Power reqd. ( single phase)

2.0 TR / 510 CFM

( Hi-wall

1.5 TR / 450 CFM

FT

Summer Dehumidified
CFM

Sqft
2784

Equipment selection
unit)
1.0 TR / 330 CFM

Total

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 2

KW
46.8

Typical floor ( 1st to 3rd & 12th to 23rd floor)


FLAT -1

1.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

1.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

1.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

1.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

696

4.93

2576

1
1
0

1.5

450

9.0

2430

11.7

FLAT-2

2.1

Living & Dining

344

2.31

1196

1020

5.2

5.2

2.2

Master Bed Room - 1

140

0.97

527

510

2.6

2.6

2.3

Bed Room - 2

120

0.84

454

1.95

1.95

Sub Total

604

4.12

2177

1
0

1.5

450

7.5

1980

9.8

FLAT-3

3.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

3.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

3.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

3.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

696

4.93

2576

T142

1
1
0

1.5

450

9.0

2430

11.7

FLAT-4

4.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

4.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

4.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

4.4

Bed Room - 3

120

0.82

438

1.5

450

1.95

1.95

Sub Total

696

4.93

2576

9.0

2430

1
1
0

11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-49

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CFM

Total TR

TR

Power reqd. ( single phase)

2.0 TR / 510 CFM

FT

( Hi-wall

1.5 TR / 450 CFM

Sqft

Equipment selection
unit)
1.0 TR / 330 CFM

FLAT-5

Summer Dehumidified
CFM

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 2

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

2.1

Living & Dining

355

2.19

1069

2.2

Master Bed Room - 1

135

0.68

353

2.3

Bed Room - 2

120

0.70

369

2.4

Bed Room - 3

120

0.70

369

Sub Total

730

4.27

2160

1020

5.2

5.2

1.5

450

1.95

1.95

330

1.3

1.3

1.3

1.3

T015,T165

330

7.5

2130

1020

510

1.5

450

9.8

FLAT-6

2.1

Living & Dining

295

2.19

1096

2.2

Master Bed Room - 1

161

1.10

604

2.3

Bed Room - 2

120

0.82

438

2.4

Bed Room - 3

120

0.82

438

1.5

450

Sub Total

696

4.93

2576

9.0

2430

11.7

61770

421.7

219615

30

150

255

765.0

207450

994.5

1020

510

1.5

450

Total ( 1st to 3rd &


12th to 23rd floor)

5.2

5.2

2.6

2.6

1.95

1.95

1.95

1.95

Typical floor ( 4th to 11th floor)


FLAT -1

1.1

Living & Dining

295

2.19

1096

1.2

Master Bed Room - 1

161

1.10

604

1.3

Bed Room - 2

120

0.82

438

1.4

Bed Room - 3

120

0.82

438

Sub Total

696

4.93

2576

1
1

1
1
1
0

1.5

450

9.0

2430

5.2

5.2

2.6

2.6

1.95

1.95

1.95

1.95
11.7

FLAT-2

2.1

Living & Dining

344

2.31

1196

1020

5.2

5.2

2.2

Master Bed Room - 1

140

0.97

527

510

2.6

2.6

2.3

Bed Room - 2

120

0.84

454

1.5

450

1.95

1.95

Sub Total

604

4.12

2177

7.5

1980

1
0

T052

9.8

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-50

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CFM

Total TR

TR

Power reqd. ( single phase)

2.0 TR / 510 CFM

FT

( Hi-wall

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Sqft

Equipment selection
unit)
1.0 TR / 330 CFM

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 2

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

FLAT-3

3.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

3.2

Master Bed Room - 1

161

1.10

604

510

2.6

2.6

3.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

3.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

696

4.93

2576

1
1
0

1.5

450

9.0

2430

11.7

FLAT-4

4.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

4.2

Master Bed Room - 1

225

1.22

665

510

2.6

2.6

4.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

4.4

Bed Room - 3

120

0.82

438

1.95

1.95

Sub Total

760

5.05

2637

1
1
0

1.5

450

9.0

2430

1020

5.2

5.2

1.5

450

1.95

1.95

330

1.3

1.3

1.3

1.3

11.7

FLAT-5

2.1

Living & Dining

355

2.19

1069

2.2

Master Bed Room - 1

135

0.68

353

2.3

Bed Room - 2

120

0.70

369

2.4

Bed Room - 3

120

0.70

369

Sub Total

730

4.27

2160

330

7.5

2130

9.8

FLAT-6

2.1

Living & Dining

295

2.19

1096

1020

5.2

5.2

2.2

Master Bed Room - 1

225

1.22

665

510

2.6

2.6

2.3

Bed Room - 2

120

0.82

438

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.82

438

1.5

450

1.95

1.95

Sub Total

760

5.05

2637

9.0

2430

T066
1
1
0

11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-51

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

33968

Total CFM

CFM

Total TR

TR

Power reqd. ( single phase)

2.0 TR / 510 CFM

FT

( Hi-wall

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Sqft

Equipment selection
unit)
1.0 TR / 330 CFM

Total ( 4th to 11th


floor)

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 2

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

226.8

118104

16

80

136

408.0

110640

530.4

24th floor
FLAT -1

1.1

Living & Dining

295

2.39

1215

1020

5.2

5.2

1.2

Master Bed Room - 1

161

1.21

669

510

2.6

2.6

1.3

Bed Room - 2

120

0.90

486

1.5

450

1.95

1.95

1.4

Bed Room - 3

120

0.90

486

1.95

1.95

Sub Total

696

5.40

2856

1
1
0

1.5

450

9.0

2430

11.7

FLAT-2

2.1

Living & Dining

344

2.54

1334

1020

5.2

5.2

2.2

Master Bed Room - 1

140

1.07

583

510

2.6

2.6

2.3

Bed Room - 2

120

0.92

502

2.6

Sub Total

604

4.53

2419

510

8.0

2040

2.6
10.4

FLAT-3

3.1

Living & Dining

295

2.39

1215

1020

5.2

5.2

3.2

Master Bed Room - 1

161

1.21

669

510

2.6

2.6

3.3

Bed Room - 2

120

0.90

486

1.5

450

1.95

1.95

3.4

Bed Room - 3

120

0.90

486

1.5

450

1.95

1.95

Sub Total

696

5.4

2856

9.0

2430

11.7

FLAT-4

4.1

Living & Dining

295

2.39

1215

1020

5.2

5.2

4.2

Master Bed Room - 1

161

1.21

669

510

2.6

2.6

4.3

Bed Room - 2

120

0.90

486

1.5

450

1.95

1.95

4.4

Bed Room - 3

120

0.90

486

1.5

450

1.95

1.95

Sub Total

696

5.4

2856

9.0

2430

T244
1
1
0

11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-52

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CFM

Total TR

TR

Power reqd. ( single phase)

2.0 TR / 510 CFM

FT

( Hi-wall

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Sqft

Equipment selection
unit)
1.0 TR / 330 CFM

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 2

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

FLAT-5

2.1

Living & Dining

355

2.39

1212

2.2

Master Bed Room - 1

135

0.77

408

1.5

450

1.95

1.95

2.3

Bed Room - 2

120

0.78

417

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.78

417

1.95

1.95

Sub Total

730

4.72

2454

1020

5.2

5.2

1
0

1.5

450

8.5

2370

11.1

FLAT-6

2.1

Living & Dining

295

2.39

1215

1020

5.2

5.2

2.2

Master Bed Room - 1

161

1.21

669

510

2.6

2.6

2.3

Bed Room - 2

120

0.90

486

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.90

486

1.5

450

1.95

1.95

Sub Total

696

5.40

2856

9.0

2430

11.7

Total

4118

30.9

16297

11

18

52.5

14130

68.3

102640

699.0

364320

Grand Total

1
1

46 249 421 1261.5 341940

1640.0

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-53

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single


phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall

1.5 TR / 450 CFM

HEIGHT

CONDITIONED SPACE

AREA

Equipment selection
unit)

Qty

Qty

TR

CFM

KW

KW

KW

KW

Stilt floor
FLAT -1

1.1

Living & Dining

322

2.19

1094

1020

5.2

5.2

1.2

Master Bed Room - 1

161

0.97

525

510

2.6

2.6

1.3

Bed Room - 2

107

0.66

344

330

1.3

1.3

1.4

Bed Room - 3

120

0.69

364

330

1.3

1.3

Sub Total

710

4.51

2327

8.0

2190

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

U001

10.4

FLAT-2

2.1

Living & Dining

290

1.99

982

2.2

Master Bed Room - 1

161

0.97

525

2.3

Bed Room - 2

107

0.66

344

2.4

Bed Room - 3

120

0.69

364

Sub Total

678

4.31

2215

2
1

330

7.0

2070

9.1

FLAT -5

1.1

Living & Dining

300

1.83

885

900

3.9

3.9

1.2

Master Bed Room - 1

161

0.89

474

1.5

450

1.95

1.95

1.3

Bed Room - 2

120

0.59

304

330

1.3

1.3

1.4

Bed Room - 3

120

0.59

304

330

1.3

1.3

Sub Total

701

3.90

1967

6.5

2010

8.5

Total

2089

12.7

6509

21.5

6270

28.0

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-53

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

SUMMER REF. LOAD

Summer Dehumidified
CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Power reqd. ( single


phase)

HEIGHT

CONDITIONED SPACE

( Hi-wall

AREA

Equipment selection
unit)

Sqft

FT

TR

CFM

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

Typical floor ( 1st to 3rd & 12th to 25th floor)


FLAT -1

1.1

Living & Dining

322

2.19

1094

1020

5.2

5.2

1.2

Master Bed Room - 1

161

0.97

525

510

2.6

2.6

1.3

Bed Room - 2

107

0.66

344

330

1.3

1.3

1.4

Bed Room - 3

120

0.69

364

330

1.3

1.3

Sub Total

710

4.51

2327

8.0

2190

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

10.4

FLAT-2

2.1

Living & Dining

290

1.99

982

2.2

Master Bed Room - 1

161

0.97

525

2.3

Bed Room - 2

107

0.66

344

Bed Room - 3

120

0.69

364

Sub Total

678

4.31

2215

U-222

330

7.0

2070

9.1

FLAT-3

3.1

Living & Dining

333

2.14

1065

1020

5.2

5.2

3.2

Master Bed Room - 1

193

0.96

514

510

2.6

2.6

3.3

Bed Room - 2

120

0.80

427

1.5

450

1.95

1.95

3.4

Bed Room - 3

120

0.80

427

1.5

450

1.95

1.95

Sub Total

766

4.7

2433

9.0

2430

U-263

1
1
0

11.7

FLAT-4

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-54

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single


phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall

1.5 TR / 450 CFM

HEIGHT

CONDITIONED SPACE

AREA

Equipment selection
unit)

Qty

Qty

TR

CFM

KW

KW

KW

KW

4.1

Living & Dining

300

2.27

1144

1020

5.2

5.2

4.2

Master Bed Room - 1

161

1.05

571

510

2.6

2.6

4.3

Bed Room - 2

120

0.75

397

1.5

450

1.95

1.95

4.4

Bed Room - 3

120

0.75

397

1.5

450

1.95

1.95

Sub Total

701

4.82

2509

9.0

2430

U-234

1
1
0

11.7

FLAT-5

2.1

Living & Dining

300

1.83

885

900

3.9

3.9

2.2

Master Bed Room - 1

161

0.89

474

1.5

450

1.95

1.95

2.3

Bed Room - 2

120

0.59

304

330

1.3

1.3

2.4

Bed Room - 3

120

0.59

304

1.3

1.3

Sub Total

701

3.90

1967

330

6.5

2010

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

8.5

FLAT-6

2.1

Living & Dining

333

1.95

953

2.2

Master Bed Room - 1

193

0.99

530

2.3

Bed Room - 2

120

0.68

355

2.4

Bed Room - 3

120

0.68

355

330

Sub Total

766

4.30

2193

7.0

2070

9.1

73474

451.2

231948

136

187

187

790.5

224400

1027.7

Total ( 1st to 3rd &


12th to 25th floor)

2
1

Typical floor ( 4th to 11th floor)

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-55

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single


phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall

1.5 TR / 450 CFM

HEIGHT

CONDITIONED SPACE

AREA

Equipment selection
unit)

Qty

Qty

TR

CFM

KW

KW

KW

KW

FLAT -1

1.1

Living & Dining

322

2.19

1094

1020

5.2

5.2

1.2

Master Bed Room - 1

225

1.33

730

510

2.6

2.6

1.3

Bed Room - 2

107

0.66

344

330

1.3

1.3

1.4

Bed Room - 3

120

0.69

364

330

1.3

1.3

Sub Total

774

4.87

2532

8.0

2190

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

10.4

FLAT-2

2.1

Living & Dining

290

1.99

982

2.2

Master Bed Room - 1

161

0.97

525

2.3

Bed Room - 2

107

0.66

344

Bed Room - 3

120

0.69

364

Sub Total

678

4.31

2215

2
1

330

7.0

2070

9.1

FLAT-3

3.1

Living & Dining

333

2.14

1065

1020

5.2

5.2

3.2

Master Bed Room - 1

193

0.96

514

510

2.6

2.6

3.3

Bed Room - 2

120

0.80

427

1.5

450

1.95

1.95

3.4

Bed Room - 3

120

0.80

427

1.5

450

1.95

1.95

Sub Total

766

4.7

2433

9.0

2430

2.27

1144

1020

4
4.1

11.7

FLAT-4
Living & Dining

300

5.2

5.2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-56

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

161

1.05

571

4.3

Bed Room - 2

120

0.75

397

4.4

Bed Room - 3

120

0.75

397

Sub Total

701

4.82

2509

Qty

Qty

TR

CFM

KW

KW

KW

KW

510

2.6

2.6

1.5

450

1.95

1.95

1.5

450

1.95

1.95

9.0

2430

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

1
1
0

11.7

FLAT-5

2.1

Living & Dining

300

1.83

885

2.2

Master Bed Room - 1

225

1.15

626

2.3

Bed Room - 2

120

0.59

304

2.4

Bed Room - 3

120

0.59

304

Sub Total

765

4.16

2119

Totat

Master Bed Room - 1

2.0 TR / 510 CFM

4.2

1.5 TR / 450 CFM

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single


phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall

1.5 TR / 450 CFM

HEIGHT

CONDITIONED SPACE

AREA

Equipment selection
unit)

2
1

330

7.0

2070

900

3.9

3.9

510

2.6

2.6

330

1.3

1.3

1.3

1.3

9.1

FLAT-6

2.1

Living & Dining

333

1.95

953

2.2

Master Bed Room - 1

193

0.99

530

2.3

Bed Room - 2

120

0.68

355

2.4

Bed Room - 3

120

0.68

355

330

Sub Total

766

4.30

2193

7.0

2070

9.1

35600

217.3

112008

64

80

96

376.0

106080

488.8

Total ( 4th to 11th


floor)

2
1

26th floor
FLAT -1

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-57

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single


phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall

1.5 TR / 450 CFM

HEIGHT

CONDITIONED SPACE

AREA

Equipment selection
unit)

Qty

Qty

TR

CFM

KW

KW

KW

KW

1.1

Living & Dining

322

2.41

1223

1020

5.2

5.2

1.2

Master Bed Room - 1

161

1.08

589

510

2.6

2.6

1.3

Bed Room - 2

107

0.73

387

1.5

450

1.95

1.95

1.4

Bed Room - 3

120

0.77

412

1.95

1.95

Sub Total

710

4.99

2611

1
1
0

1.5

450

9.0

2430

11.7

FLAT-2

2.1

Living & Dining

290

2.19

1098

1020

5.2

5.2

2.2

Master Bed Room - 1

161

1.08

589

510

2.6

2.6

2.3

Bed Room - 2

107

0.73

387

1.5

450

1.95

1.95

Bed Room - 3

120

0.77

412

1.95

1.95

Sub Total

678

4.77

2486

U-272

1
1
0

1.5

450

9.0

2430

11.7

FLAT-3

3.1

Living & Dining

333

2.37

1198

1020

5.2

5.2

3.2

Master Bed Room - 1

193

1.09

591

510

2.6

2.6

3.3

Bed Room - 2

120

0.88

475

1.5

450

1.95

1.95

3.4

Bed Room - 3

120

0.88

475

1.95

1.95

Sub Total

766

5.22

2739

2.47

1264

U-273

4
4.1

1
1
0

1.5

450

9.0

2430

1020

11.7

FLAT-4
Living & Dining

300

5.2

5.2

U-274

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-58

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

161

1.16

636

4.3

Bed Room - 2

120

0.83

446

4.4

Bed Room - 3

120

0.83

446

Sub Total

701

5.29

2792

Totat

Master Bed Room - 1

2.0 TR / 510 CFM

4.2

1.5 TR / 450 CFM

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single


phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall

1.5 TR / 450 CFM

HEIGHT

CONDITIONED SPACE

AREA

Equipment selection
unit)

Qty

Qty

TR

CFM

KW

KW

KW

KW

510

2.6

2.6

1.5

450

1.95

1.95

1.95

1.95

U-274

1
1
0

1.5

450

9.0

2430

11.7

FLAT-5

2.1

Living & Dining

300

2.03

1005

1020

5.2

5.2

2.2

Master Bed Room - 1

161

0.99

539

510

2.6

2.6

2.3

Bed Room - 2

120

0.67

352

330

1.3

1.3

2.4

Bed Room - 3

120

0.67

352

1.3

Sub Total

701

4.36

2248

U-275

330

8.0

2190

1.3
10.4

FLAT-6

2.1

Living & Dining

333

2.59

1329

1020

5.2

5.2

2.2

Master Bed Room - 1

193

1.12

608

510

2.6

2.6

2.3

Bed Room - 2

120

0.76

403

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.76

403

1.5

450

1.95

1.95

Sub Total

766

5.23

2743

9.0

2430

11.7

Total

4322

29.9

15619

10

18

53.0

14340

68.9

115485

711.0

366084

U-276

Grand Total

1
1

208 282 305 1241.0 351090

#####

Pl. note the U-value considered for cooling load analysis for residential blocks :

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-59

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 3

SUMMER REF. LOAD

Summer Dehumidified
CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Power reqd. ( single


phase)

HEIGHT

CONDITIONED SPACE

( Hi-wall

AREA

Equipment selection
unit)

Sqft

FT

TR

CFM

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-60

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 4

9
9
9
9

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

2
2.1
2.2
2.3
2.4

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

1
1.1
1.2
1.3
1.4

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT -6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

1
1
2

Total

2806

18.9

9846

Typical floor ( 1st to 3rd & 12th to 25th floor)


FLAT -1
Living & Dining
322
9
2.13
Master Bed Room - 1
140
9
1.04
Bed Room - 2
120
9
0.82
Bed Room - 3
120
9
0.82
Sub Total
702
4.81

1060
568
437
437
2502

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

968
451
333
397
2149

1
1.1
1.2
1.3
1.4

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

280
140
120
140
680

9
9
9
9

1.97
0.84
0.64
0.75
4.20

Totat

322
140
120
120
702

2.0 TR / 510 CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

1
1.1
1.2
1.3
1.4

1.5 TR / 450 CFM

Qty

1.0 TR / 330 CFM

1.0 TR / 330 CFM

CFM

Total CFM

Summer Dehumidified
CFM

TR

Total TR

SUMMER REF. LOAD

FT

CONDITIONED SPACE

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

12

34.0

9240

2
1

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

1
1
2

2
1
1
1
2

2
1
1
1
2

2
1

1
1
2

2
1
1
1

Power reqd. ( single phase)

2.0 TR / 510 CFM

HEIGHT

Sqft

( Hi-wall

1.5 TR / 450 CFM

AREA

Equipment selection
unit)

1
4

44.2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-58

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 4

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

1
1
2

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.41
1.04
0.75
0.89
5.09

1221
564
399
479
2663

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

479.9

249186

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

1.97
0.84
0.64
0.75
4.20

968
451
333
397
2149

Total ( 1st to 3rd &


12th to 25th floor)

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

72913

Typical floor ( 4th to 11th floor)


FLAT -1
Living & Dining
322
Master Bed Room - 1
140
Bed Room - 2
120
Bed Room - 3
120
Sub Total
702
FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

280
140
120
140
680

9
9
9
9

9
9
9
9

Totat

300
161
120
120
701

2.0 TR / 510 CFM

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

1.5 TR / 450 CFM

Qty

1.0 TR / 330 CFM

CFM

Total CFM

TR

Total TR

FT

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2
1
1
1
2

2
1

Power reqd. ( single phase)

2.0 TR / 510 CFM

Sqft

CONDITIONED SPACE

( Hi-wall

1.5 TR / 450 CFM

1.0 TR / 330 CFM

2
2.1
2.2
2.3
2.4

Summer Dehumidified
CFM

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

4
4.1
4.2
4.3
4.4

HEIGHT

3
3.1
3.2
3.3
3.4

AREA

Equipment selection
unit)

1
1
2

2
1

1
1
2

4
2
1.5
1.5
9.0

85

170

255

850.0

234600

2
1

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

1
1
2

2
1
1
1

1
4

1105.0

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-59

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 4

9
9
9
9

2.26
1.18
0.67
0.67
4.78

1140
640
351
351
2482

1
1
2

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.41
1.04
0.75
0.89
5.09

1221
564
399
479
2663

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

226.8

117752

2.35
1.13
0.90
0.90
5.28

1190
624
485
485
2784

2.16
0.94
0.72
0.85
4.67

1080
507
381
453
2421

Total ( 4th to 11th


floor)

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

34824

26th floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

280
140
120
140
680

9
9
9
9

Totat

300
225
120
120
765

2.0 TR / 510 CFM

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

1.5 TR / 450 CFM

Qty

1.0 TR / 330 CFM

CFM

Total CFM

TR

Total TR

FT

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2
1
1
1
2

2
1

Power reqd. ( single phase)

2.0 TR / 510 CFM

Sqft

CONDITIONED SPACE

( Hi-wall

1.5 TR / 450 CFM

1.0 TR / 330 CFM

2
2.1
2.2
2.3
2.4

Summer Dehumidified
CFM

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

4
4.1
4.2
4.3
4.4

HEIGHT

3
3.1
3.2
3.3
3.4

AREA

Equipment selection
unit)

1
1
2

2
1

1
1
2

4
2
1.5
1.5
9.0

40

80

120

400.0

110400

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1
1
2

2
1

1
1
2

520.0

V-271

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-60

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 4

1260
644
393
393
2690

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.46
1.17
0.75
0.75
5.13

1260
644
393
393
2690

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.64
1.17
0.83
0.99
5.63

1361
641
447
535
2984

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.35
1.13
0.90
0.90
5.28

1190
624
485
485
2784

Total

4289

31.1

16353

114832

756.8

393137

Grand Total

Totat

2.46
1.17
0.75
0.75
5.13

2.0 TR / 510 CFM

9
9
9
9

1.5 TR / 450 CFM

300
161
120
120
701

1.0 TR / 330 CFM

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
2
9.5

1020
510
450
510
2490

0
0
0
0

0
0
1.95
0

5.2
2.6
0
2.6

5.2
2.6
1.95
2.6
12.4

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

14640

2
1

1
1
2

2
1
1
0

Power reqd. ( single phase)

2.0 TR / 510 CFM

2
2.1
2.2
2.3
2.4

Sqft

CONDITIONED SPACE

( Hi-wall

1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

1
1
2

SUMMER REF. LOAD

4
4.1
4.2
4.3
4.4

Qty

HEIGHT

3
3.1
3.2
3.3
3.4

CFM

AREA

Equipment selection
unit)

1
4

2
1

1
1
2

4
2
1.5
1.5
9.0

11

19

54.5

129 265 406 1338.5 368880

V-273

V-276

70.9

1740.1

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-61

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

1
1.1
1.2
1.3
1.4

1
1.1
1.2
1.3
1.4

1
1.1
1.2
1.3
1.4

2
2.1
2.2

1060
568
437
437
2502

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT -6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

Total

2806

18.9

9846

Typical floor ( 1st to 3rd & 12th to 24th floor)


FLAT -1
322
9
2.13
Living & Dining
Master Bed Room - 1
140
9
1.04
Bed Room - 2
120
9
0.82
Bed Room - 3
120
9
0.82
Sub Total
702
4.81

1060
568
437
437
2502

FLAT-2
Living & Dining
Master Bed Room - 1

968
451

280
140

9
9

1.97
0.84

Totat

2.13
1.04
0.82
0.82
4.81

2.0 TR / 510 CFM

9
9
9
9

1.5 TR / 450 CFM

322
140
120
120
702

1.0 TR / 330 CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

Total CFM

CFM

Total TR

TR

2.0 TR / 510 CFM

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

Summer Dehumidified
CFM

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

AREA

Tower - 5

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2
1
1
1
2

2
1
1
1
2

2
1

1
1
2

4
2
1.5
1.5
9.0

12

34.0

9240

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

3
1.5

900
450

0
0

3.9
1.95

0
0

3.9
1.95

1
1
2

2
1

A-004

44.2

A-141

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-63

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

FT

TR

CFM

Qty

Bed Room - 2
Bed Room - 3
Sub Total

120
140
680

9
9

0.64
0.75
4.20

333
397
2149

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.41
1.04
0.75
0.89
5.09

1221
564
399
479
2663

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

451.7

234528

2.13
1.04
0.82
0.82
4.81

1060
568
437
437
2502

Total ( 1st to 3rd &


12th to 24th floor)

1
1.1
1.2
1.3
1.4

68624

Typical floor ( 4th to 11th floor)


FLAT -1
322
Living & Dining
Master Bed Room - 1
140
Bed Room - 2
120
Bed Room - 3
120
Sub Total
702

9
9
9
9

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

Qty

TR

CFM

KW

KW

KW

KW

330
450
2130

1.3
0

0
1.95

0
0

1
1.5
7.0

1.3
1.95
9.1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1
4

2
1
1
1
2

2
1
1
1
2

2
1

( Hi-wall unit) Power reqd. ( single phase)

2.0 TR / 510 CFM

2
2.1
2.2
2.3
2.4

Sqft

CONDITIONED SPACE

Equipment selection
1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

1.0 TR / 330 CFM

4
4.1
4.2
4.3
4.4

Summer Dehumidified
CFM

3
3.1
3.2
3.3
3.4

SUMMER REF. LOAD

2.3

HEIGHT

AREA

Tower - 5

1
1
2

2
1

1
1
2

4
2
1.5
1.5
9.0

80

160

240

800.0

220800

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

1
1
2

1040.0

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-64

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

4
4.1
4.2
4.3
4.4

2
2.1
2.2
2.3
2.4

2
2.1
2.2
2.3
2.4

968
451
333
397
2149

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
225
120
120
765

9
9
9
9

2.26
1.18
0.67
0.67
4.78

1140
640
351
351
2482

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.06
0.67
0.67
4.66

1140
579
351
351
2421

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.41
1.04
0.75
0.89
5.09

1221
564
399
479
2663

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.13
1.04
0.82
0.82
4.81

Total ( 4th to 11th


floor)

1
1.1

25th floor
FLAT -1
Living & Dining

34824

322

Totat

1.97
0.84
0.64
0.75
4.20

2.0 TR / 510 CFM

9
9
9
9

1.5 TR / 450 CFM

280
140
120
140
680

1.0 TR / 330 CFM

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

Total CFM

CFM

Total TR

TR

2.0 TR / 510 CFM

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

Summer Dehumidified
CFM

3
3.1
3.2
3.3
3.4

SUMMER REF. LOAD

2
2.1
2.2
2.3

HEIGHT

AREA

Tower - 5

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1
1

1
4

2
1
1
1
2

2
1
1
1
2

2
1

1
1
2

1060
568
437
437
2502

1
1
2

4
2
1.5
1.5
9.0

226.8

117752

40

80

120

400.0

110400

2.35

1190

1020

2
1

520.0

5.2

5.2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-65

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

624
485
485
2784

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

280
140
120
140
680

9
9
9
9

2.16
0.94
0.72
0.85
4.67

1080
507
381
453
2421

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.46
1.17
0.75
0.75
5.13

1260
644
393
393
2690

FLAT -4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.46
1.17
0.75
0.75
5.13

1260
644
393
393
2690

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.64
1.17
0.83
0.99
5.63

1361
641
447
535
2984

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.35
1.13
0.90
0.90
5.28

1190
624
485
485
2784

Total

4289

31.1

16353

Totat

1.13
0.90
0.90
5.28

2.0 TR / 510 CFM

9
9
9

1.5 TR / 450 CFM

140
120
120
702

1.0 TR / 330 CFM

Master Bed Room - 1


Bed Room - 2
Bed Room - 3
Sub Total

1.0 TR / 330 CFM

CFM

Total CFM

2
2.1
2.2
2.3
2.4

TR

Total TR

2
2.1
2.2
2.3
2.4

FT

Qty

1
1
2

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1.5
1.5
9.0

510
450
450
2430

0
0
0

0
1.95
1.95

2.6
0
0

2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
2
9.5

1020
510
450
510
2490

0
0
0
0

0
0
1.95
0

5.2
2.6
0
2.6

5.2
2.6
1.95
2.6
12.4

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

14640

2
1

1
1
2

2
1

1
1
2

2
1

1
1
2

2
1
1
0

( Hi-wall unit) Power reqd. ( single phase)

2.0 TR / 510 CFM

4
4.1
4.2
4.3
4.4

Sqft

CONDITIONED SPACE

Equipment selection
1.5 TR / 450 CFM

3
3.1
3.2
3.3
3.4

Summer Dehumidified
CFM

2
2.1
2.2
2.3

SUMMER REF. LOAD

1.2
1.3
1.4

HEIGHT

AREA

Tower - 5

1
4

2
1

1
1
2

4
2
1.5
1.5
9.0

11

19

54.5

70.9

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-66

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Grand Total

110543

728.5

378479

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CFM

Total TR

TR

2.0 TR / 510 CFM

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Sqft

Equipment selection
1.0 TR / 330 CFM

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 5

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

124 255 391 1288.5 355080

1675.1

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-67

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

4
4.1
4.2

MONSOON REF. LOAD

3
3.1
3.2
3.3
3.4

SUMMER REF. LOAD

2
2.1
2.2
2.3

TOTAL OCCUPANCY

1
1.1
1.2
1.3
1.4

LIGHT LOAD

1
1.1
1.2
1.3
1.4

EQPT. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
161
120
120
723

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

1.99
0.85
0.67
0.67
4.18

1.55
0.58
0.56
0.56
3.25

974
454
350
350
2128

632
270
268
268
1438

FLAT -5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

1.83
0.89
0.59
0.59
3.90

1.47
0.60
0.45
0.45
2.97

885
474
304
304
1967

590
279
202
202
1273

1
1
2

Total

1424

8.1

6.2

4095

2711

1.99
0.85
0.67
0.67
4.18

1.55
0.58
0.56
0.56
3.25

974
454
350
350
2128

632
270
268
268
1438

2.19
0.97
0.66
0.69
4.51

1.81
0.74
0.55
0.59
3.69

1101
525
344
364
2334

792
366
262
281
1701

1.94
0.93
0.66
0.66
4.19

1.53
0.63
0.48
0.48
3.12

945
494
345
345
2129

617
291
219
219
1346

2.27
1.05

1.75
0.74

1144
571

759
366

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Typical floor ( 1st to 3rd & 12th to 26th floor)


FLAT -1
Living & Dining
322
9
5 CFM/person + 0.06 CFM/sqft.
Master Bed Room - 1
161
9
5 CFM/person + 0.06 CFM/sqft.
Bed Room - 2
120
9
5 CFM/person + 0.06 CFM/sqft.
Bed Room - 3
120
9
5 CFM/person + 0.06 CFM/sqft.
Sub Total
723
FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

FLAT-4
Living & Dining
Master Bed Room - 1

300
161

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

300
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

10
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-68

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

AREA

Tower - 6

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1
1
1
2

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

3.9
1.95
0
0

0
0
0
0

900
450
330
330
2010

0
0
1.3
1.3

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

13.0

4020

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

4
2
1
1
8.0

5.2
2.6
1.3
1.3
10.4

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.45

2
2

4
4

1020
1020

0
0

0
0

5.2
5.2

5.2
5.2

2
1

2
1
1
1
2

2
1
1
1
2

2
1
1
1
2

16.9

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TOTAL OCCUPANCY

SUMMER REF. LOAD

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

Bed Room - 2
Bed Room - 3
Sub Total

120
120
701

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.75
0.75
4.82

0.57
0.57
3.63

397
397
2509

272
272
1669

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

1.83
0.89
0.59
0.59
3.90

1.47
0.60
0.45
0.45
2.97

885
474
304
304
1967

590
279
202
202
1273

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

1.95
0.98
0.68
0.68
4.29

1.54
0.68
0.50
0.50
3.22

953
527
355
355
2190

625
323
229
229
1406

1
1
2

466.0

357.8

238626

158994

180

234

1.99
1.14
0.67
0.67
4.47

1.55
0.75
0.56
0.56
3.42

974
618
350
350
2292

632
358
268
268
1526

2.19
0.97
0.66
0.69
4.51

1.81
0.74
0.55
0.59
3.69

1101
525
344
364
2334

792
366
262
281
1701

1.94
0.93
0.66
0.66
4.19

1.53
0.63
0.48
0.48
3.12

945
494
345
345
2129

617
291
219
219
1346

10
2
2
2

78030

Typical floor ( 4th to 11th floor)


FLAT -1
Living & Dining
322
Master Bed Room - 1
225
Bed Room - 2
120
Bed Room - 3
120
Sub Total
787

9
9
9
9

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-69

Totat

200
100
100
100

10
2
2
2

2.0 TR / 510 CFM

300
100
100
100

200
100
100
100

1.5 TR / 450 CFM

55%
55%
55%
55%

300
100
100
100

1.0 TR / 330 CFM

3
3.1
3.2
3.3
3.4

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

Total CFM

2
2.1
2.2
2.3

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

Total TR

1
1.1
1.2
1.3
1.4

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Qty

1
1
2

Qty

Qty

TR

CFM

KW

KW

KW

KW

450
450
2940

0
0

1.95
1.95

0
0

1.5
1.5
11.0

1.95
1.95
14.3

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

144

819.0

238140

3
2
1
1
7.0

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3
9.1

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

4
2
1
1
8.0

5.2
2.6
1.3
1.3
10.4

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.45

2
1
1
1
2

2
1

2
1
1
1
2

2
1
1
1
2

2
1
1
1
2

( Hi-wall unit) Power reqd. ( single phase)

2.0 TR / 510 CFM

Total ( 1st to 3rd &


12th to 26th floor)

INSIDE DESIGN CONDITIONS

1.0 TR / 330 CFM

CONDITIONED SPACE

Equipment selection
1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

LIGHT LOAD

2
2.1
2.2
2.3
2.4

EQPT. LOAD

4.3
4.4

HEIGHT

AREA

Tower - 6

1064.7

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TOTAL OCCUPANCY

SUMMER REF. LOAD

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

2
2.1
2.2
2.3
2.4

LIGHT LOAD

2
2.1
2.2
2.3
2.4

EQPT. LOAD

4
4.1
4.2
4.3
4.4

HEIGHT

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

2.27
1.05
0.75
0.75
4.82

1.75
0.74
0.57
0.57
3.63

1144
571
397
397
2509

759
366
272
272
1669

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
225
120
120
765

9
9
9
9

1.83
1.15
0.59
0.59
4.16

1.47
0.76
0.45
0.45
3.13

885
626
304
304
2119

590
363
202
202
1357

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

1.95
0.98
0.68
0.68
4.29

1.54
0.68
0.50
0.50
3.22

953
527
355
355
2190

625
323
229
229
1406

1
1
2

211.5

161.7

108584

72040

80

88

2.20
0.96
0.75
0.75
4.66

1.77
0.69
0.65
0.65
3.76

1104
518
399
399
2420

767
337
318
318
1740

2.39
1.08
0.73
0.77
4.97

2.01
0.86
0.63
0.67
4.17

1218
589
387
412
2606

914
433
306
331
1984

2.16

1.76

1079

756

Total ( 4th to 11th


floor)

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

3
3.1

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

35704

27th floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
161
120
120
723

9
9
9
9

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

FLAT-3
Living & Dining

333

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%

300
100
100
100

300
100
100
100

300

200
100
100
100

200
100
100
100

200

10
2
2
2

10
2
2
2

10

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-70

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

AREA

Tower - 6

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
2

4
4
1.5
1.5
11.0

1020
1020
450
450
2940

0
0
0
0

0
0
1.95
1.95

5.2
5.2
0
0

5.2
5.2
1.95
1.95
14.3

3
2
1
1
7.0

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3
9.1

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

80

372.0

106800

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

1020

5.2

5.2

2
1
1
1
2

2
1

1
1
2

2
1

1
1
2

483.6

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

Master Bed Room - 1


Bed Room - 2
Bed Room - 3
Sub Total

193
120
120
766

9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%

100
100
100

100
100
100

2
2
2

1.06
0.74
0.74
4.7

0.76
0.57
0.57
3.66

572
393
393
2437

371
269
269
1665

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.47
1.16
0.83
0.83
5.29

1.97
0.86
0.66
0.66
4.15

1264
636
446
446
2792

885
433
322
322
1962

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.03
0.99
0.67
0.67
4.36

1.68
0.71
0.54
0.54
3.47

1005
539
352
352
2248

715
346
252
252
1565

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

2.18
1.11
0.76
0.76
4.81

1.77
0.82
0.58
0.58
3.75

1087
605
403
403
2498

764
404
279
279
1726

Total

4335

28.8

23.0

15001

10642

119493

714.4

548.7

366306

Grand Total

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-71

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Watt

1.0 TR / 330 CFM

RH
(Max)

Total CFM

Inside temp.
(deg F +/-2)

Total TR

Monsoon Dehumidified
CFM

Ventilation air

2.0 TR / 510 CFM

Summer Dehumidified
CFM

FT

INSIDE DESIGN CONDITIONS

Qty

1
1
2

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1.5
1.5
9.0

510
450
450
2430

0
0
0

0
1.95
1.95

2.6
0
0

2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

14340

2
1

1
1
2

2
1
1
1
2

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

MONSOON REF. LOAD

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

SUMMER REF. LOAD

2
2.1
2.2
2.3
2.4

TOTAL OCCUPANCY

2
2.1
2.2
2.3
2.4

LIGHT LOAD

4
4.1
4.2
4.3
4.4

EQPT. LOAD

3.2
3.3
3.4

HEIGHT

AREA

Tower - 6

2
1

1
1
2

4
2
1.5
1.5
9.0

10

18

53.0

244387 266 338 242 1257.0 363300

68.9

1634.1

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Qty

Totat

CFM

2.0 TR / 510 CFM

CFM

1.5 TR / 450 CFM

TR

1.0 TR / 330 CFM

TR

Total CFM

1.0 TR / 330 CFM

(No.)

Total TR

Monsoon Dehumidified
CFM

Watt

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Watt

( Hi-wall

1.5 TR / 450 CFM

MONSOON REF. LOAD

Inside temp.
RH
(deg F +/-2) (Max)

SUMMER REF. LOAD

Ventilation air

TOTAL OCCUPANCY

FT

LIGHT LOAD

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
unit)

EQPT. LOAD

CONDITIONED
SPACE

HEIGHT

AREA

Tower - 7 / 12

Qty

Qty

TR

CFM

KW

KW

KW

KW

5.2

1
1.1

Stilt floor
FLAT -1
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

1.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

1.3
1.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

2
2.1

FLAT-3
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

2.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

1
1.1

FLAT -4
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

1.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

1.3
1.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

2
2.1

FLAT-6
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

2.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

Total

2784

19.7

14.9

10304

6892

Typical floor ( 1st to 3rd & 12th to 24th floor)


FLAT -1

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-72

1
1
2

1
1
2

1
1
2

510

2.6

2.6

450
450
2430

1.95
1.95

0
0

1.5
1.5
9.0

0
0

1
1
2

1.95
1.95
11.7

12

36.0

9720

46.8

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Qty

Totat

CFM

2.0 TR / 510 CFM

CFM

1.5 TR / 450 CFM

TR

1.0 TR / 330 CFM

TR

Total CFM

1.0 TR / 330 CFM

(No.)

Total TR

Monsoon Dehumidified
CFM

Watt

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Watt

( Hi-wall

1.5 TR / 450 CFM

MONSOON REF. LOAD

Inside temp.
RH
(deg F +/-2) (Max)

SUMMER REF. LOAD

Ventilation air

TOTAL OCCUPANCY

FT

LIGHT LOAD

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
unit)

EQPT. LOAD

CONDITIONED
SPACE

HEIGHT

AREA

Tower - 7 / 12

Qty

Qty

TR

CFM

KW

KW

KW

KW

1.1

Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

1.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

1.3
1.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

2
2.1

FLAT-2
Living & Dining

344

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

2.31

1.71

1196

773

1020

5.2

5.2

2.2

Master Bed Room - 1

140

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.97

0.70

527

344

510

2.6

2.6

2.3

Bed Room - 2
Sub Total

120
604

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.84
4.12

0.63
3.04

454
2177

304
1421

1.5
7.5

450
1980

1.95

1.95
9.8

3
3.1

FLAT-3
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

3.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

3.3
3.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

4
4.1

FLAT-4
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

4.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

4.3
4.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

2
2.1

FLAT-5
Living & Dining

355

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1069

685

2.2

Master Bed Room - 1

135

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.68

0.50

353

228

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
730

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.70
0.70
4.27

0.51
0.51
3.23

369
369
2160

234
234
1381

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-73

1
1
2

1
1

1
1
2

1
1
2

1
1
2

1020

5.2

5.2

1.5

450

1.95

1.95

330
330
2130

1.3
1.3

0
0

0
0

1
1
7.5

1.3
1.3
9.8

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Qty

Totat

CFM

2.0 TR / 510 CFM

CFM

1.5 TR / 450 CFM

TR

1.0 TR / 330 CFM

TR

Total CFM

1.0 TR / 330 CFM

(No.)

Total TR

Monsoon Dehumidified
CFM

Watt

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Watt

( Hi-wall

1.5 TR / 450 CFM

MONSOON REF. LOAD

Inside temp.
RH
(deg F +/-2) (Max)

SUMMER REF. LOAD

Ventilation air

TOTAL OCCUPANCY

FT

LIGHT LOAD

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
unit)

EQPT. LOAD

CONDITIONED
SPACE

HEIGHT

AREA

Tower - 7 / 12

Qty

Qty

TR

CFM

KW

KW

KW

KW

5.2

2
2.1

FLAT-6
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

2.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

1.95
1.95

0
0

1.5
1.5
9.0

0
0

1
1
2

1.95
1.95
11.7

449.8

338.4

234256

155104

32

160

272

816.0

221280

Total ( 1st to 3rd &


12th to 24th floor)

65888

1060.8

1
1.1

Typical floor ( 4th to 11th floor)


FLAT -1
295
Living & Dining

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

1.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

1.3
1.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

2
2.1

FLAT-2
Living & Dining

344

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

2.31

1.71

1196

773

1020

5.2

5.2

2.2

Master Bed Room - 1

140

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.97

0.70

527

344

510

2.6

2.6

2.3

Bed Room - 2
Sub Total

120
604

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.84
4.12

0.63
3.04

454
2177

304
1421

450
1980

1.95

1.5
7.5

1.95
9.8

3
3.1

FLAT-3
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

1020

5.2

5.2

3.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.10

0.79

604

392

510

2.6

2.6

3.3
3.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
4.93

0.61
0.61
3.72

438
438
2576

298
298
1723

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-74

1
1
2

1
1

1
1
2

5.2

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Qty

4
4.1

FLAT-4
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

4.2

Master Bed Room - 1

225

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.22

0.81

665

393

4.3
4.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
760

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
5.05

0.61
0.61
3.74

438
438
2637

298
298
1724

2
2.1

FLAT-5
Living & Dining

355

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1069

685

2.2

Master Bed Room - 1

135

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.68

0.50

353

228

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
730

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.70
0.70
4.27

0.51
0.51
3.23

369
369
2160

234
234
1381

2
2.1

FLAT-6
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.19

1.71

1096

735

2.2

Master Bed Room - 1

225

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.22

0.81

665

393

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
760

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.82
0.82
5.05

0.61
0.61
3.74

438
438
2637

298
298
1724

226.8

169.5

118104

77568

Total ( 4th to 11th


floor)

33968

1
1
2

Totat

CFM

2.0 TR / 510 CFM

CFM

1.5 TR / 450 CFM

TR

1.0 TR / 330 CFM

TR

Total CFM

1.0 TR / 330 CFM

(No.)

Total TR

Monsoon Dehumidified
CFM

Watt

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Watt

( Hi-wall

1.5 TR / 450 CFM

MONSOON REF. LOAD

Inside temp.
RH
(deg F +/-2) (Max)

SUMMER REF. LOAD

Ventilation air

TOTAL OCCUPANCY

FT

LIGHT LOAD

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
unit)

EQPT. LOAD

CONDITIONED
SPACE

HEIGHT

AREA

Tower - 7 / 12

Qty

Qty

TR

CFM

KW

KW

KW

KW

1020

5.2

5.2

510

2.6

2.6

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

1020

5.2

5.2

1.5

450

1.95

1.95

0
0

0
0

330
330
2130

1.3
1.3

1
1
7.5

1.3
1.3
9.8

1020

5.2

5.2

1
1
2

510

2.6

2.6

450
450
2430

1.95
1.95

0
0

1.5
1.5
9.0

0
0

1
1
2

1.95
1.95
11.7

16

80

136

408.0

110640

530.4

1
1.1

25th floor
FLAT -1
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.39

1.92

1215

858

1020

5.2

5.2

1.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.21

0.90

669

459

510

2.6

2.6

1.3
1.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.90
0.90
5.40

0.70
0.70
4.22

486
486
2856

348
348
2013

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

FLAT-2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-75

1
1
2

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Qty

Totat

CFM

2.0 TR / 510 CFM

CFM

1.5 TR / 450 CFM

TR

1.0 TR / 330 CFM

TR

Total CFM

1.0 TR / 330 CFM

(No.)

Total TR

Monsoon Dehumidified
CFM

Watt

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Watt

( Hi-wall

1.5 TR / 450 CFM

MONSOON REF. LOAD

Inside temp.
RH
(deg F +/-2) (Max)

SUMMER REF. LOAD

Ventilation air

TOTAL OCCUPANCY

FT

LIGHT LOAD

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
unit)

EQPT. LOAD

CONDITIONED
SPACE

HEIGHT

AREA

Tower - 7 / 12

Qty

Qty

TR

CFM

KW

KW

KW

KW

2.1

Living & Dining

344

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

2.54

1.96

1334

917

1020

5.2

5.2

2.2

Master Bed Room - 1

140

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.07

0.80

583

402

510

2.6

2.6

2.3

Bed Room - 2
Sub Total

120
604

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.92
4.53

0.71
3.47

502
2419

355
1674

1
4

2
8.0

510
2040

2.6

2.6
10.4

3
3.1

FLAT-3
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.39

1.92

1215

858

1020

5.2

5.2

3.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.21

0.90

669

459

510

2.6

2.6

3.3
3.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.90
0.90
5.4

0.70
0.70
4.22

486
486
2856

348
348
2013

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

4
4.1

FLAT-4
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.39

1.92

1215

858

1020

5.2

5.2

4.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.21

0.90

669

459

510

2.6

2.6

4.3
4.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.90
0.90
5.4

0.70
0.70
4.22

486
486
2856

348
348
2013

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

2
2.1

FLAT-5
Living & Dining

355

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.39

1.90

1212

833

1020

5.2

5.2

2.2

Master Bed Room - 1

135

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.77

0.60

408

285

1.5

450

1.95

1.95

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
730

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.78
0.78
4.72

0.59
0.59
3.68

417
417
2454

285
285
1688

1
1
3

450
450
2370

0
0

1.95
1.95

0
0

1.5
1.5
8.5

1.95
1.95
11.1

2
2.1

FLAT-6
Living & Dining

295

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

300

200

10

2.39

1.92

1215

858

1020

5.2

5.2

2.2

Master Bed Room - 1

161

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

1.21

0.90

669

459

510

2.6

2.6

2.3
2.4

Bed Room - 2
Bed Room - 3
Sub Total

120
120
696

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.90
0.90
5.40

0.70
0.70
4.22

486
486
2856

348
348
2013

450
450
2430

0
0

1.95
1.95

0
0

1.5
1.5
9.0

1.95
1.95
11.7

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-76

1
1
2

1
1
2

1
1
2

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total

Grand Total

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Inside temp.
RH
(deg F +/-2) (Max)

SUMMER REF. LOAD

Ventilation air

TOTAL OCCUPANCY

FT

( Hi-wall

LIGHT LOAD

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
unit)

EQPT. LOAD

CONDITIONED
SPACE

HEIGHT

AREA

Tower - 7 / 12

Watt

Watt

(No.)

TR

TR

CFM

CFM

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

4118

30.9

24.0

16297

11414

11

18

52.5

14130

106758

727.1

546.8

378961 250978 48 259 438 1312.5 355770

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-77

Power reqd. ( single phase)

68.3

1706.3

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

3
3.1
3.2
3.3

SUMMER REF. LOAD

2
2.1
2.2
2.3

TOTAL OCCUPANCY

1
1.1
1.2
1.3
1.4

LIGHT LOAD

2
2.1
2.2
2.3
2.4

EQPT. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

Stilt floor
FLAT -3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

2.30
1.07
0.69
0.69
4.75

1.77
0.75
0.54
0.54
3.60

1163
584
362
362
2471

769
372
253
253
1647

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.30
1.07
0.69
0.69
4.75

1.77
0.75
0.54
0.54
3.60

1163
584
362
362
2471

769
372
253
253
1647

1
1
2

Total

1402

9.5

7.2

4942

3294

2.09
1.04
0.80
0.80
4.73

1.76
0.74
0.66
0.66
3.82

1038
566
427
427
2458

760
369
325
325
1779

1.97
0.84
0.64
0.75
4.20

1.53
0.58
0.47
0.53
3.11

968
451
333
397
2149

629
275
211
246
1361

2.30
1.07
0.69

1.77
0.75
0.54

1163
584
362

769
372
253

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Typical floor ( 1st to 3rd & 12th to 21st floor)


FLAT -1
Living & Dining
322
9
5 CFM/person + 0.06 CFM/sqft.
Master Bed Room - 1
140
9
5 CFM/person + 0.06 CFM/sqft.
Bed Room - 2
120
9
5 CFM/person + 0.06 CFM/sqft.
Bed Room - 3
120
9
5 CFM/person + 0.06 CFM/sqft.
Sub Total
702
FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

280
140
120
140
680

9
9
9
9

FLAT -3
Living & Dining
Master Bed Room - 1
Bed Room - 2

300
161
120

9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-77

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

AREA

Tower - 8 / 11

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

4
2
1
1
8.0

5.2
2.6
1.3
1.3
10.4

16.0

4380

2
1

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

4
2
1

1020
510
330

0
0
1.3

0
0
0

5.2
2.6
0

5.2
2.6
1.3

2
1

1
1
2

2
1
1
1

1
4

2
1
1

20.8

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

SUMMER REF. LOAD

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

2
2.1
2.2
2.3
2.4

TOTAL OCCUPANCY

2
2.1
2.2
2.3
2.4

LIGHT LOAD

4
4.1
4.2
4.3
4.4

EQPT. LOAD

3.4

HEIGHT

AREA

Tower - 8 / 11

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

Bed Room - 3
Sub Total

120
701

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2

55%

100

100

0.69
4.75

0.54
3.60

362
2471

253
1647

1
2

330
2190

1
8.0

1.3

1.3
10.4

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.30
1.07
0.69
0.69
4.75

1.77
0.75
0.54
0.54
3.6

1163
584
362
362
2471

769
372
253
253
1647

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.44
1.04
0.76
0.91
5.15

1.86
0.82
0.56
0.66
3.90

1243
564
404
489
2700

811
404
266
319
1800

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.09
1.04
0.80
0.80
4.73

1.76
0.74
0.66
0.66
3.82

1038
566
427
427
2458

760
369
325
325
1779

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

368.0

284.1

191191

130169

2.09
1.04
0.80
0.80
4.73

1.76
0.74
0.66
0.66
3.82

1038
566
427
427
2458

760
369
325
325
1779

1.97

1.53

968

629

CONDITIONED SPACE

Total ( 1st to 3rd &


12th to 21st floor)

1
1.1
1.2
1.3
1.4

2
2.1

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

55757

Typical floor ( 4th to 11th floor)


FLAT -1
Living & Dining
322
Master Bed Room - 1
140
Bed Room - 2
120
Bed Room - 3
120
Sub Total
702
FLAT-2
Living & Dining

INSIDE DESIGN CONDITIONS

280

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2

55%
55%
55%
55%

55%

300
100
100
100

300

200
100
100
100

200

10
2
2
2

10

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-78

Equipment selection

2
1
1
1
2

2
1

1
1
2

2
1

( Hi-wall unit) Power reqd. ( single phase)

1
1
2

4
2
1.5
1.5
9.0

65

130

195

650.0

179400

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

900

3.9

3.9

1
1
2

845.0

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

Master Bed Room - 1


Bed Room - 2
Bed Room - 3
Sub Total

140
120
140
680

9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%

100
100
100

100
100
100

2
2
2

0.84
0.64
0.75
4.20

0.58
0.47
0.53
3.11

451
333
397
2149

275
211
246
1361

FLAT -3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
225
120
120
765

9
9
9
9

2.30
1.18
0.69
0.69
4.86

1.77
0.79
0.54
0.54
3.64

1163
640
362
362
2527

769
383
253
253
1658

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.30
1.07
0.69
0.69
4.75

1.77
0.75
0.54
0.54
3.6

1163
584
362
362
2471

769
372
253
253
1647

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.44
1.04
0.76
0.91
5.15

1.86
0.82
0.56
0.66
3.90

1243
564
404
489
2700

811
404
266
319
1800

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

2.09
1.04
0.80
0.80
4.73

1.76
0.74
0.66
0.66
3.82

1038
566
427
427
2458

760
369
325
325
1779

227.4

175.1

118104

80192

Total ( 4th to 11th


floor)

34824

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

22nd floor

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-79

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Watt

1.0 TR / 330 CFM

RH
(Max)

Total CFM

Inside temp.
(deg F +/-2)

Total TR

Ventilation air

2.0 TR / 510 CFM

Monsoon Dehumidified
CFM

FT

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

MONSOON REF. LOAD

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

2
2.1
2.2
2.3
2.4

TOTAL OCCUPANCY

4
4.1
4.2
4.3
4.4

LIGHT LOAD

3
3.1
3.2
3.3
3.4

EQPT. LOAD

2.2
2.3

HEIGHT

AREA

Tower - 8 / 11

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

450
330
450
2130

0
1.3
0

1.95
0
1.95

0
0
0

1.5
1
1.5
7.0

1.95
1.3
1.95
9.1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

110400

1
1

1
4

2
1
1
1
2

2
1
1
1
2

2
1

1
1
2

2
1

1
1
2

4
2
1.5
1.5
9.0

40

80

120

400.0

520.0

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
140
120
120
702

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

2.31
1.13
0.88
0.88
5.20

1.99
0.84
0.75
0.75
4.33

1167
623
475
475
2740

894
427
376
376
2073

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

280
140
120
140
680

9
9
9
9

2.16
0.94
0.72
0.85
4.67

1.73
0.68
0.55
0.63
3.59

1080
507
381
453
2421

746
333
261
304
1644

FLAT -3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.50
1.18
0.77
0.77
5.22

1.98
0.87
0.62
0.62
4.09

1283
648
410
410
2751

894
439
303
303
1939

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.50
1.18
0.77
0.77
5.22

1.98
0.87
0.62
0.62
4.09

1283
648
410
410
2751

894
439
303
303
1939

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

350
193
120
140
803

9
9
9
9

2.68
1.17
0.84
1.00
5.69

2.10
0.95
0.65
0.76
4.46

1384
641
452
546
3023

957
484
317
377
2135

FLAT-6
Living & Dining

322

2.31

1.99

1167

894

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

300

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

10

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-80

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Watt

1.0 TR / 330 CFM

RH
(Max)

Total CFM

Inside temp.
(deg F +/-2)

Total TR

Ventilation air

2.0 TR / 510 CFM

FT

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Monsoon Dehumidified
CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

Summer Dehumidified
CFM

2
2.1

MONSOON REF. LOAD

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

4
4.1
4.2
4.3
4.4

TOTAL OCCUPANCY

3
3.1
3.2
3.3
3.4

LIGHT LOAD

2
2.1
2.2
2.3

EQPT. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

AREA

Tower - 8 / 11

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1
4

4
2
1.5
2
9.5

1020
510
450
510
2490

0
0
0
0

0
0
1.95
0

5.2
2.6
0
2.6

5.2
2.6
1.95
2.6
12.4

1020

5.2

5.2

2
1

1
1
2

2
1

1
1
2

2
1

1
1
2

2
1
1
0

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

Master Bed Room - 1


Bed Room - 2
Bed Room - 3
Sub Total

140
120
120
702

9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%

100
100
100

100
100
100

2
2
2

1.13
0.88
0.88
5.20

0.84
0.75
0.75
4.33

623
475
475
2740

Total

4289

31.2

24.9

16426

96272

636.1

491.3

330663

Grand Total

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-81

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Monsoon Dehumidified
CFM

Watt

1.0 TR / 330 CFM

Summer Dehumidified
CFM

RH
(Max)

Total CFM

MONSOON REF. LOAD

Inside temp.
(deg F +/-2)

Total TR

SUMMER REF. LOAD

Ventilation air

2.0 TR / 510 CFM

TOTAL OCCUPANCY

FT

INSIDE DESIGN CONDITIONS

Qty

427
376
376
2073

1
1
2

11803

11

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

LIGHT LOAD

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

EQPT. LOAD

2.2
2.3
2.4

HEIGHT

AREA

Tower - 8 / 11

Qty

Qty

TR

CFM

KW

KW

KW

KW

510
450
450
2430

0
0
0

0
1.95
1.95

2.6
0
0

2
1.5
1.5
9.0

2.6
1.95
1.95
11.7

19

54.5

14640

225458 109 221 340 1120.5 308820

70.9

1456.7

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
171
140
120
731

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

1.79
0.87
0.68
0.94
4.28

1.44
0.60
0.49
0.67
3.20

858
463
354
508
2183

572
280
222
327
1401

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
171
140
120
731

9
9
9
9

1.79
0.87
0.68
0.94
4.28

1.44
0.60
0.49
0.67
3.20

858
463
354
508
2183

572
280
222
327
1401

FLAT -5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
130
140
120
690

9
9
9
9

1.99
0.96
0.79
0.94
4.68

1.70
0.76
0.64
0.67
3.77

978
523
420
508
2429

729
383
307
327
1746

FLAT -8
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
130
140
120
690

9
9
9
9

1.99
0.96
0.79
0.94
4.68

1.70
0.76
0.64
0.67
3.77

978
523
420
508
2429

729
383
307
327
1746

Total

2842

17.9

13.9

9224

6294

1.79
0.87
0.68
0.94

1.44
0.60
0.49
0.67

858
463
354
508

572
280
222
327

Typical floor ( 1st to 28th floor)


FLAT -1
Living & Dining
300
Master Bed Room - 1
171
Bed Room - 2
140
Bed Room - 3
120

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-82

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Watt

1.0 TR / 330 CFM

RH
(Max)

Total CFM

Inside temp.
(deg F +/-2)

Total TR

Ventilation air

2.0 TR / 510 CFM

Monsoon Dehumidified
CFM

FT

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

MONSOON REF. LOAD

1
1.1
1.2
1.3
1.4

SUMMER REF. LOAD

1
1.1
1.2
1.3
1.4

TOTAL OCCUPANCY

1
1.1
1.2
1.3
1.4

LIGHT LOAD

2
2.1
2.2
2.3
2.4

EQPT. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

AREA

Tower - 9-10

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

3
2
1.5
1.5
8.0

900
510
450
450
2310

0
0
0
0

3.9
0
1.95
1.95

0
2.6
0
0

3.9
2.6
1.95
1.95
10.4

900
510
450
450
2310

0
0
0
0

3.9
0
1.95
1.95

0
2.6
0
0

3.9
2.6
1.95
1.95
10.4

1
1

1
4

2
1
1
1

1
4

2
1

1
1
4

1
1
4

3
2
1.5
1.5
8.0

16

30.0

8880

3
1.5
1
1.5

900
450
330
450

2
1
1
1

39.0

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3.9
1.95
1.3
1.95

9
9
9
9

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
171
140
120
731

9
9
9
9

FLAT -5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
130
140
120
690

9
9
9
9

322
170
166
120

9
9
9
9

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

456

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

TOTAL OCCUPANCY

SUMMER REF. LOAD

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

TR

TR

CFM

CFM

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

Totat

322
170
166
120
778

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

(No.)

2.0 TR / 510 CFM

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Watt

1.5 TR / 450 CFM

9
9
9
9

Watt

1.0 TR / 330 CFM

322
170
166
120
778

LIGHT LOAD

HEIGHT

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

RH
(Max)

Total CFM

2
2.1
2.2
2.3
2.4

731

Inside temp.
(deg F +/-2)

Total TR

2
2.1
2.2
2.3
2.4

Sub Total

Ventilation air

2.0 TR / 510 CFM

4
4.1
4.2
4.3
4.4

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

3
3.1
3.2
3.3
3.4

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
1.0 TR / 330 CFM

2
2.1
2.2
2.3

CONDITIONED SPACE

AREA

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 9-10

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

4.28

3.20

2183

1401

7.0

2130

2.05
1.04
1.02
0.86
4.97

1.74
0.80
0.80
0.67
4.01

1013
565
553
461
2592

747
396
397
328
1868

2
1
1

4
2
2
1.5
9.5

1020
510
510
450
2490

0
0
0
0

0
0
0
1.95

5.2
2.6
2.6
0

5.2
2.6
2.6
1.95
12.4

2.05
1.04
1.02
0.86
4.97

1.74
0.80
0.80
0.67
4.01

1013
565
553
461
2592

747
396
397
328
1868

1020
510
510
450
2490

0
0
0
0

0
0
0
1.95

5.2
2.6
2.6
0

4
2
2
1.5
9.5

5.2
2.6
2.6
1.95
12.35

1.79
0.87
0.68
0.94
4.28

1.44
0.60
0.49
0.67
3.20

858
463
354
508
2183

572
280
222
327
1401

900
450
330
450
2130

0
0
1.3
0

3.9
1.95
0
1.95

0
0
0
0

3
1.5
1
1.5
7.0

3.9
1.95
1.3
1.95
9.1

1.99
0.96
0.79
0.94
4.68

1.70
0.76
0.64
0.67
3.77

978
523
420
508
2429

729
383
307
327
1746

3
2
1.5
1.5
8.0

900
510
450
450
2310

0
0
0
0

3.9
0
1.95
1.95

0
2.6
0
0

3.9
2.6
1.95
1.95
10.4

2.05
1.04
1.02
0.86

1.74
0.80
0.80
0.67

1013
565
553
461

747
396
397
328

2
1
1

4
2
2
1.5

0
0
0
0

0
0
1.95
0

2.6
2.6
0
0

2.92

2.27

1579

1121

5.5

1020
510
510
450
0
1470

2.6
2.6
1.95
0
7.2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-83

1
1

2
1
1
0

1
1

2
1
1
1

1
4

2
1

1
1
4

1
0

9.1

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

FLAT-7
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
170
166
120
778

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

2.05
1.04
1.02
0.86
4.97

1.74
0.80
0.80
0.67
4.01

1013
565
553
461
2592

747
396
397
328
1868

FLAT -8
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
130
140
120
690

9
9
9
9

1.99
0.96
0.79
0.94
4.68

1.70
0.76
0.64
0.67
3.77

978
523
420
508
2429

729
383
307
327
1746

1001.0

790.7

520212

364532

1.99
0.98
0.77
1.02
4.76

1.65
0.72
0.59
0.75
3.71

979
531
410
556
2476

698
352
280
378
1708

2.27
1.15
1.13
0.94
5.49

1.97
0.92
0.91
0.75
4.55

1142
633
620
509
2904

881
467
466
378
2192

2.27
1.15
1.13
0.94

1.97
0.92
0.91
0.75

1142
633
620
509

881
467
466
378

Total ( 1st to 28th


floor)

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

3
3.1
3.2
3.3
3.4

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

157696

29th Floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
171
140
120
731

9
9
9
9

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
170
166
120
778

9
9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3

322
170
166
120

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-84

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Watt

1.0 TR / 330 CFM

Monsoon Dehumidified
CFM

RH
(Max)

Total CFM

Summer Dehumidified
CFM

Inside temp.
(deg F +/-2)

Total TR

MONSOON REF. LOAD

Ventilation air

2.0 TR / 510 CFM

SUMMER REF. LOAD

FT

INSIDE DESIGN CONDITIONS

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

TOTAL OCCUPANCY

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

LIGHT LOAD

2
2.1
2.2
2.3
2.4

EQPT. LOAD

2
2.1
2.2
2.3
2.4

HEIGHT

AREA

Tower - 9-10

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1

2
1
1

4
2
2
1.5
9.5

1020
510
510
450
2490

0
0
0
0

0
0
0
1.95

5.2
2.6
2.6
0

5.2
2.6
2.6
1.95
12.4

900
510
450
450
2310

0
0
0
0

3.9
0
1.95
1.95

0
2.6
0
0

3.9
2.6
1.95
1.95
10.4

1
1
4

3
2
1.5
1.5
8.0

56

560

448

1792.0

498960

900
510
450
510
2370

0
0
0
0

3.9
0
1.95
0

0
2.6
0
2.6

3.9
2.6
1.95
2.6
11.1

1
2

3
2
1.5
2
8.5

4
2
2
2
10.0

1020
510
510
510
2550

0
0
0
0

0
0
0
0

5.2
2.6
2.6
2.6

2
1
1
1
5

5.2
2.6
2.6
2.6
13.0

2
1
1
1

4
2
2
2

1020
510
510
510

0
0
0
0

0
0
0
0

5.2
2.6
2.6
2.6

5.2
2.6
2.6
2.6

1
1
0

2329.6

9
9
9
9

322
170
166
120

9
9
9
9

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

TOTAL OCCUPANCY

SUMMER REF. LOAD

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

TR

TR

CFM

CFM

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

456

FLAT-7
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
170
166
120
778

9
9
9
9

FLAT -8
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
130
140
120
690

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

Totat

300
130
140
120
690

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

(No.)

2.0 TR / 510 CFM

FLAT -5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Watt

1.5 TR / 450 CFM

9
9
9
9

Watt

1.0 TR / 330 CFM

300
171
140
120
731

LIGHT LOAD

HEIGHT

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

RH
(Max)

Total CFM

2
2.1
2.2
2.3
2.4

778

Inside temp.
(deg F +/-2)

Total TR

2
2.1
2.2
2.3
2.4

Sub Total

Ventilation air

2.0 TR / 510 CFM

2
2.1
2.2
2.3
2.4

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
1.0 TR / 330 CFM

4
4.1
4.2
4.3
4.4

CONDITIONED SPACE

AREA

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 9-10

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

5.49

4.55

2904

2192

10.0

2550

1.99
0.98
0.77
1.02
4.76

1.65
0.72
0.59
0.75
3.71

979
531
410
556
2476

698
352
280
378
1708

3
2
1.5
2
8.5

900
510
450
510
2370

0
0
0
0

3.9
0
1.95
0

0
2.6
0
2.6

3.9
2.6
1.95
2.6
11.1

2.19
1.05
0.89
1.02
5.15

1.91
0.85
0.74
0.75
4.25

1098
575
476
556
2705

854
437
365
378
2034

1
4

4
2
1.5
2
9.5

1020
510
450
510
2490

0
0
0
0

0
0
1.95
0

5.2
2.6
0
2.6

5.2
2.6
1.95
2.6
12.4

2.27
1.15
1.13
0.94

1.97
0.92
0.91
0.75

1142
633
620
509

881
467
466
378

2
1
1
1

4
2
2
2

0
0
0
0

0
0
0
0

2.6
2.6
2.6
0

3.22

2.58

1762

1311

6.0

1020
510
510
510
0
1530

2.6
2.6
2.6
0
7.8

2.27
1.15
1.13
0.94
5.49

1.97
0.92
0.91
0.75
4.55

1142
633
620
509
2904

881
467
466
378
2192

4
2
2
2
10.0

1020
510
510
510
2550

0
0
0
0

0
0
0
0

5.2
2.6
2.6
2.6

2
1
1
1
5

5.2
2.6
2.6
2.6
13.0

2.19
1.05
0.89
1.02
5.15

1.91
0.85
0.74
0.75
4.25

1098
575
476
556
2705

854
437
365
378
2034

2
1

4
2
1.5
2
9.5

1020
510
450
510
2490

0
0
0
0

0
0
1.95
0

5.2
2.6
0
2.6

5.2
2.6
1.95
2.6
12.4

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-85

2
1
1
0

1
2

2
1
1
0

1
0

1
4

13

2.0 TR / 510 CFM

Totat

Monsoon Dehumidified
CFM

1.5 TR / 450 CFM

Summer Dehumidified
CFM

CFM

1.0 TR / 330 CFM

MONSOON REF. LOAD

CFM

Total CFM

SUMMER REF. LOAD

TR

Total TR

TOTAL OCCUPANCY

TR

2.0 TR / 510 CFM

LIGHT LOAD

(No.)

1.5 TR / 450 CFM

Grand Total

Watt

( Hi-wall unit) Power reqd. ( single phase)

1.0 TR / 330 CFM

Total

Watt

Equipment selection

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

5632

39.5

32.2

20836

15371

30

72.0

18900

93.6

166170

1058.4

836.8

550272

HEIGHT

CONDITIONED SPACE

AREA

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 9-10

Sqft

FT

INSIDE DESIGN CONDITIONS

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-86

386197 58 584 480 1894.0 526740

2462.2

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

3
3.1
3.2
3.3
3.4

SUMMER REF. LOAD

2
2.1
2.2
2.3

TOTAL OCCUPANCY

1
1.1
1.2
1.3
1.4

LIGHT LOAD

1
1.1
1.2
1.3
1.4

EQPT. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
161
120
120
723

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

1.99
0.90
0.67
0.67
4.23

1.55
0.63
0.56
0.56
3.30

974
482
350
350
2156

632
398
268
268
1566

FLAT -5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.06
1.10
0.69
0.69
4.54

1.65
0.78
0.53
0.53
3.49

1019
601
364
364
2348

695
386
247
247
1575

1
1
2

Total

1424

8.8

6.8

4504

3141

1.99
0.90
0.67
0.67
4.23

1.55
0.63
0.56
0.56
3.30

974
482
350
350
2156

632
398
268
268
1566

2.19
0.97
0.66
0.69
4.51

1.81
0.74
0.55
0.59
3.69

1101
525
344
364
2334

792
366
262
281
1701

1.94
0.93
0.66
0.66

1.53
0.63
0.48
0.48

945
494
345
345

617
291
219
219

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Typical floor ( 1st to 3rd & 12th to 28th floor)


FLAT -1
Living & Dining
322
9
5 CFM/person + 0.06 CFM/sqft.
Master Bed Room - 1
161
9
5 CFM/person + 0.06 CFM/sqft.
Bed Room - 2
120
9
5 CFM/person + 0.06 CFM/sqft.
Bed Room - 3
120
9
5 CFM/person + 0.06 CFM/sqft.
Sub Total
723
FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3

333
193
120
120

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-87

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Power reqd. ( single phase)

2.0 TR / 510 CFM

INSIDE DESIGN CONDITIONS

( Hi-wall unit)

1.5 TR / 450 CFM

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

AREA

Tower - 13

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

2
1
1
1
2

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

4
2
1
1
8.0

5.2
2.6
1.3
1.3
10.4

14.5

4200

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

3
1.5
1
1

900
450
330
330

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3.9
1.95
1.3
1.3

2
1

2
1
1
1
2

2
1
1
1
2

2
1
1
1

18.9

9
9
9
9

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

2
2.1
2.2

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

LIGHT LOAD

TOTAL OCCUPANCY

SUMMER REF. LOAD

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

TR

CFM

CFM

300
100
100
100

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

86700

Typical floor ( 4th to 11th floor)


FLAT -1
Living & Dining
322
Master Bed Room - 1
225
Bed Room - 2
120
Bed Room - 3
120
Sub Total
787
FLAT-2
Living & Dining
Master Bed Room - 1

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

55%
55%
55%
55%

TR

290
161

9
9
9
9

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%

300
100
100
100

300
100

200
100
100
100

200
100

10
2
2
2

10
2

Totat

300
161
120
120
701

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

(No.)

2.0 TR / 510 CFM

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Watt

1.5 TR / 450 CFM

9
9
9
9

Watt

1.0 TR / 330 CFM

300
161
120
120
701

RH
(Max)

Total CFM

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

Inside temp.
(deg F +/-2)

Total TR

766

Total ( 1st to 3rd & 12th


to 28th floor)

1
1.1
1.2
1.3
1.4

HEIGHT

Sub Total

Ventilation air

Power reqd. ( single phase)

2.0 TR / 510 CFM

2
2.1
2.2
2.3
2.4

FT

( Hi-wall unit)

1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

Sqft

INSIDE DESIGN CONDITIONS

Equipment selection
1.0 TR / 330 CFM

4
4.1
4.2
4.3
4.4

CONDITIONED SPACE

AREA

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Tower - 13

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

4.19

3.12

2129

1346

6.5

2010

2.27
1.05
0.75
0.75
4.82

1.75
0.74
0.57
0.57
3.63

1144
571
397
397
2509

759
366
272
272
1669

2
2

4
4
1.5
1.5
11.0

1020
1020
450
450
2940

0
0
0
0

0
0
1.95
1.95

5.2
5.2
0
0

5.2
5.2
1.95
1.95
14.3

2.06
1.10
0.69
0.69
4.54

1.65
0.78
0.53
0.53
3.49

1019
601
364
364
2348

695
386
247
247
1575

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1.95
0.98
0.68
0.68
4.29

1.54
0.68
0.50
0.50
3.22

953
527
355
355
2190

625
323
229
229
1406

1
1
2

3.9
0
0
0

0
2.6
0
0

900
510
330
330
2070

0
0
1.3
1.3

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

531.6

409.0

273320

185260

200

200

220

940.0

268200

1.99
1.18
0.67
0.67
4.51

1.55
0.79
0.56
0.56
3.46

974
640
350
350
2314

632
383
268
268
1551

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

2.19
0.97

1.81
0.74

1101
525

792
366

2
1

4
2

1020
510

0
0

0
0

5.2
2.6

5.2
2.6

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-88

1
1
2

2
1
1
1
2

2
1

2
1
1
1
2

8.45

1222.0

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

MONSOON REF. LOAD

Summer Dehumidified
CFM

Monsoon Dehumidified
CFM

1.0 TR / 330 CFM

Sqft

FT

Ventilation air

Inside temp.
(deg F +/-2)

RH
(Max)

Watt

Watt

(No.)

TR

TR

CFM

CFM

Qty

Bed Room - 2
Bed Room - 3
Sub Total

107
120
678

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.66
0.69
4.51

0.55
0.59
3.69

344
364
2334

262
281
1701

1
1
2

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

1.94
0.93
0.66
0.66
4.19

1.53
0.63
0.48
0.48
3.12

945
494
345
345
2129

617
291
219
219
1346

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.27
1.05
0.75
0.75
4.82

1.75
0.74
0.57
0.57
3.63

1144
571
397
397
2509

759
366
272
272
1669

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
225
120
120
765

9
9
9
9

2.06
1.42
0.69
0.69
4.86

1.65
0.98
0.53
0.53
3.69

1019
786
364
364
2533

695
497
247
247
1686

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

1.95
0.98
0.68
0.68
4.29

1.54
0.68
0.50
0.50
3.22

953
527
355
355
2190

625
323
229
229
1406

1
1
2

217.4

166.5

112072

74872

80

72

55%
55%
55%
55%

300
100
100
100

300
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

29th floor
FLAT -1

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-89

Totat

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

2.0 TR / 510 CFM

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

1.5 TR / 450 CFM

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

1.0 TR / 330 CFM

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

Total CFM

35704

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

Qty

Qty

TR

CFM

KW

KW

KW

KW

330
330
2190

1.3
1.3

0
0

0
0

1
1
8.0

1.3
1.3
10.4

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.45

4
4
1.5
1.5
11.0

1020
1020
450
450
2940

0
0
0
0

0
0
1.95
1.95

5.2
5.2
0
0

5.2
5.2
1.95
1.95
14.3

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

96

380.0

107760

2
1
1
1
2

2
2

1
1
2

2
1
1
1
2

Power reqd. ( single phase)

Total TR

Total ( 4th to 11th


floor)

INSIDE DESIGN CONDITIONS

( Hi-wall unit)

2.0 TR / 510 CFM

CONDITIONED SPACE

Equipment selection
1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

2
2.1
2.2
2.3
2.4

TOTAL OCCUPANCY

4
4.1
4.2
4.3
4.4

LIGHT LOAD

3
3.1
3.2
3.3
3.4

EQPT. LOAD

2.3

HEIGHT

AREA

Tower - 13

2
1

494.0

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

Living & Dining


Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
161
120
120
723

9
9
9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

55%
55%
55%
55%

300
100
100
100

200
100
100
100

10
2
2
2

2.20
1.01
0.75
0.75
4.71

1.77
0.74
0.65
0.65
3.81

1104
546
399
399
2448

767
366
318
318
1769

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

2.39
1.08
0.73
0.77
4.97

2.01
0.86
0.63
0.67
4.17

1218
589
387
412
2606

914
433
306
331
1984

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

2.16
1.06
0.74
0.74
4.7

1.76
0.76
0.57
0.57
3.66

1079
572
393
393
2437

756
371
269
269
1665

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.47
1.16
0.83
0.83
5.29

1.97
0.86
0.66
0.66
4.15

1264
636
446
446
2792

885
433
322
322
1962

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.26
1.21
0.77
0.77
5.01

1.86
0.89
0.61
0.61
3.97

1139
665
412
412
2628

820
454
297
297
1868

FLAT-6
Living & Dining
Master Bed Room - 1

333
193

9
9

2.18
1.11

1.77
0.82

1087
605

764
404

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.
5 CFM/person + 0.06 CFM/sqft.

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2
74'F+/-2
74'F+/-2

74'F+/-2
74'F+/-2

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%
55%
55%

55%
55%

300
100
100
100

300
100
100
100

300
100
100
100

300
100
100
100

300
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100
100
100

200
100

10
2
2
2

10
2
2
2

10
2
2
2

10
2
2
2

10
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-90

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Watt

1.0 TR / 330 CFM

RH
(Max)

Total CFM

Inside temp.
(deg F +/-2)

Total TR

Ventilation air

Power reqd. ( single phase)

2.0 TR / 510 CFM

FT

INSIDE DESIGN CONDITIONS

( Hi-wall unit)

1.5 TR / 450 CFM

Monsoon Dehumidified
CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

Summer Dehumidified
CFM

2
2.1
2.2

MONSOON REF. LOAD

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

4
4.1
4.2
4.3
4.4

TOTAL OCCUPANCY

3
3.1
3.2
3.3
3.4

LIGHT LOAD

2
2.1
2.2
2.3

EQPT. LOAD

1.1
1.2
1.3
1.4

HEIGHT

AREA

Tower - 13

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

2
1

4
2

1020
510

0
0

0
0

5.2
2.6

5.2
2.6

2
1

1
1
2

2
1

1
1
2

2
1

1
1
2

2
1

1
1
2

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

TR

CFM

CFM

Bed Room - 2
Bed Room - 3
Sub Total

120
120
766

9
9

5 CFM/person + 0.06 CFM/sqft.


5 CFM/person + 0.06 CFM/sqft.

74'F+/-2
74'F+/-2

55%
55%

100
100

100
100

2
2

0.76
0.76
4.81

0.58
0.58
3.75

403
403
2498

Total

4335

29.5

23.5

15409

128163

787.3

605.8

405305

Grand Total

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-91

Totat

(No.)

2.0 TR / 510 CFM

Watt

1.5 TR / 450 CFM

Monsoon Dehumidified
CFM

Watt

1.0 TR / 330 CFM

Summer Dehumidified
CFM

RH
(Max)

Total CFM

MONSOON REF. LOAD

Inside temp.
(deg F +/-2)

Total TR

SUMMER REF. LOAD

Ventilation air

Qty

279
279
1726
10974

Power reqd. ( single phase)

2.0 TR / 510 CFM

TOTAL OCCUPANCY

FT

INSIDE DESIGN CONDITIONS

( Hi-wall unit)

1.5 TR / 450 CFM

LIGHT LOAD

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

EQPT. LOAD

2.3
2.4

HEIGHT

AREA

Tower - 13

Qty

Qty

TR

CFM

KW

KW

KW

KW

450
450
2430

1.95
1.95

0
0

1.5
1.5
9.0

0
0

1
1
2

1.95
1.95
11.7

12

18

54.0

14580

274247 284 287 337 1388.5 394740

70.2

1805.1

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Totat

Qty

2.0 TR / 510 CFM

Qty

1.5 TR / 450 CFM

CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

TR

Total CFM

1.0 TR / 330 CFM

FT

Power reqd. ( single phase)

Total TR

Summer Dehumidified
CFM

Sqft

( Hi-wall unit)

2.0 TR / 510 CFM

SUMMER REF. LOAD

CONDITIONED
SPACE

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

Qty

TR

CFM

KW

KW

KW

KW

Stilt floor
FLAT -3

1.1

Living & Dining

290

1.91

934

900

3.9

3.9

1.2

Master Bed Room - 1

193

0.91

484

1.5

450

1.95

1.95

1.3

Bed Room - 2

120

0.58

296

330

1.3

1.3

1.4

Bed Room - 3

120

0.58

296

1.3

1.3

Sub Total

723

3.98

2010

330

6.5

2010

8.5

FLAT-4

2.1

Living & Dining

290

1.91

934

900

3.9

3.9

2.2

Master Bed Room - 1

193

0.91

484

1.5

450

1.95

1.95

2.3

Bed Room - 2

120

0.58

296

330

1.3

1.3

2.4

Bed Room - 3

120

0.58

296

330

1.3

1.3

Sub Total

723

3.98

2010

6.5

2010

8.5

Total

1446

8.0

4020

13.0

4020

16.9

1020

5.2

5.2

1.5

450

1.95

1.95

330

1.3

1.3

330

1.3

1.3

7.5

2130

Typical floor ( 1st to 3rd & 12th to 22nd floor)


FLAT -1

1.1

Living & Dining

300

2.20

1101

1.2

Master Bed Room - 1

161

0.81

427

1.3

Bed Room - 2

107

0.61

316

1.4

Bed Room - 3

120

0.59

305

Sub Total

688

4.21

2149

9.8

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-92

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

2.0 TR / 510 CFM

Totat

Qty

Qty

TR

CFM

KW

KW

KW

KW

1020

5.2

5.2

1.5

450

1.95

1.95

330

1.3

1.3

1.3

1.3

FLAT-2

2.1

Living & Dining

300

2.20

1101

2.2

Master Bed Room - 1

161

0.81

427

2.3

Bed Room - 2

107

0.61

316

Bed Room - 3

140

0.59

305

Sub Total

708

4.21

2149

1.5 TR / 450 CFM

Qty

1.0 TR / 330 CFM

CFM

Total CFM

1.0 TR / 330 CFM

TR

Total TR

Summer Dehumidified
CFM

FT

Power reqd. ( single phase)

2.0 TR / 510 CFM

SUMMER REF. LOAD

Sqft

( Hi-wall unit)

1.5 TR / 450 CFM

CONDITIONED
SPACE

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

330

7.5

2130

9.8

FLAT -3

3.1

Living & Dining

290

1.91

934

900

3.9

3.9

3.2

Master Bed Room - 1

193

0.91

484

1.5

450

1.95

1.95

3.3

Bed Room - 2

120

0.58

296

330

1.3

1.3

3.4

Bed Room - 3

120

0.58

296

1.3

Sub Total

723

3.98

2010

330

6.5

2010

1.3
8.45

FLAT-4

4.1

Living & Dining

290

1.91

934

900

3.9

3.9

4.2

Master Bed Room - 1

193

0.91

484

1.5

450

1.95

1.95

4.3

Bed Room - 2

120

0.58

296

330

1.3

1.3

4.4

Bed Room - 3

120

0.58

296

1.3

Sub Total

723

3.98

2010

L-024

330

6.5

2010

1.3
8.45

FLAT-5

2.1

Living & Dining

322

2.06

1017

1020

5.2

5.2

2.2

Master Bed Room - 1

161

0.97

523

510

2.6

2.6

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-93

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

376

2.3

Bed Room - 2

136

0.72

2.4

Bed Room - 3

120

0.79

422

Sub Total

739

4.54

2338

Totat

Qty

2.0 TR / 510 CFM

Qty

1.5 TR / 450 CFM

CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

TR

Total CFM

1.0 TR / 330 CFM

FT

Qty

TR

CFM

KW

KW

KW

KW

330

1.3

1.3

1.95

1.95

1
1

Power reqd. ( single phase)

Total TR

Summer Dehumidified
CFM

Sqft

( Hi-wall unit)

2.0 TR / 510 CFM

SUMMER REF. LOAD

CONDITIONED
SPACE

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

1.5

450

8.5

2310

11.1

FLAT-6

2.1

Living & Dining

322

2.06

1017

1020

5.2

5.2

2.2

Master Bed Room - 1

161

0.97

523

510

2.6

2.6

2.3

Bed Room - 2

136

0.72

376

330

1.3

1.3

2.4

Bed Room - 3

120

0.79

422

1.5

450

1.95

1.95

Sub Total

739

4.54

2338

8.5

2310

11.1

60480

356.4

181916

140

140

140

630.0

180600

819.0

Total ( 1st to 3rd &


12th to 22nd floor)

1
1

Typical floor ( 4th to 11th floor)


FLAT -1

1.1

Living & Dining

300

2.20

1101

1020

5.2

5.2

1.2

Master Bed Room - 1

232

1.15

621

510

2.6

2.6

1.3

Bed Room - 2

107

0.61

316

330

1.3

1.3

1.4

Bed Room - 3

120

0.59

305

1.3

Sub Total

759

4.55

2343

330

8.0

2190

1.3

1020

5.2

5.2

1.5

450

1.95

1.95

10.4

FLAT-2

2.1

Living & Dining

300

2.20

1101

2.2

Master Bed Room - 1

161

0.81

427

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-94

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Bed Room - 2

107

0.61

316

Bed Room - 3

140

0.59

305

Sub Total

708

4.21

2149

Totat

Qty

2.0 TR / 510 CFM

Qty

1.5 TR / 450 CFM

CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

TR

Total CFM

1.0 TR / 330 CFM

FT

Power reqd. ( single phase)

Total TR

Summer Dehumidified
CFM

Sqft

CONDITIONED
SPACE

( Hi-wall unit)

2.0 TR / 510 CFM

SUMMER REF. LOAD

2.3

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

Qty

TR

CFM

KW

KW

KW

KW

330

1.3

1.3

1.3

1.3

330

7.5

2130

9.8

FLAT -3

3.1

Living & Dining

290

1.91

934

900

3.9

3.9

3.2

Master Bed Room - 1

193

0.91

484

1.5

450

1.95

1.95

3.3

Bed Room - 2

120

0.58

296

330

1.3

1.3

3.4

Bed Room - 3

120

0.58

296

1.3

Sub Total

723

3.98

2010

330

6.5

2010

1.3
8.45

FLAT-4

4.1

Living & Dining

290

1.91

934

900

3.9

3.9

4.2

Master Bed Room - 1

193

0.91

484

1.5

450

1.95

1.95

4.3

Bed Room - 2

120

0.58

296

330

1.3

1.3

4.4

Bed Room - 3

120

0.58

296

1.3

Sub Total

723

3.98

2010

L-054

330

6.5

2010

1.3
8.45

FLAT-5

2.1

Living & Dining

322

2.06

1017

1020

5.2

5.2

2.2

Master Bed Room - 1

161

0.97

523

510

2.6

2.6

2.3

Bed Room - 2

136

0.72

376

330

1.3

1.3

2.4

Bed Room - 3

120

0.79

422

1.5

450

1.95

1.95

Sub Total

739

4.54

2338

8.5

2310

1
1
1

11.1

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-95

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

1.0 TR / 330 CFM

CFM

Total CFM

TR

Total TR

1.0 TR / 330 CFM

FT

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Sqft

( Hi-wall unit)

1.5 TR / 450 CFM

SUMMER REF. LOAD

CONDITIONED
SPACE

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

Qty

Qty

TR

CFM

KW

KW

KW

KW

FLAT-6

2.1

Living & Dining

322

2.06

1017

1020

5.2

5.2

2.2

Master Bed Room - 1

161

0.97

523

510

2.6

2.6

2.3

Bed Room - 2

136

0.72

376

330

1.3

1.3

2.4

Bed Room - 3

120

0.79

422

1.5

450

1.95

1.95

Sub Total

739

4.54

2338

8.5

2310

11.1

35128

206.4

105504

80

72

88

364.0

103680

473.2

Total ( 4th to 11th


floor)

1
1

23rd floor
FLAT -1

1.1

Living & Dining

300

2.40

1221

1020

5.2

5.2

1.2

Master Bed Room - 1

161

0.92

492

510

2.6

2.6

1.3

Bed Room - 2

107

0.68

359

330

1.3

1.3

1.4

Bed Room - 3

120

0.67

353

1.3

Sub Total

688

4.67

2425

330

8.0

2190

1.3
10.4

FLAT-2

2.1

Living & Dining

300

2.40

1221

1020

5.2

5.2

2.2

Master Bed Room - 1

161

0.92

492

510

2.6

2.6

2.3

Bed Room - 2

107

0.68

359

330

1.3

1.3

Bed Room - 3

140

0.67

353

330

1.3

Sub Total

708

4.67

2425

8.0

2190

1.3
10.4

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-96

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

Qty

1.0 TR / 330 CFM

CFM

Total CFM

TR

Total TR

1.0 TR / 330 CFM

FT

Power reqd. ( single phase)

2.0 TR / 510 CFM

Summer Dehumidified
CFM

Sqft

( Hi-wall unit)

1.5 TR / 450 CFM

SUMMER REF. LOAD

CONDITIONED
SPACE

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

Qty

Qty

TR

CFM

KW

KW

KW

KW

FLAT -3

3.1

Living & Dining

290

2.11

1050

1020

5.2

5.2

3.2

Master Bed Room - 1

193

1.04

561

510

2.6

2.6

3.3

Bed Room - 2

120

0.66

345

330

1.3

1.3

3.4

Bed Room - 3

120

0.66

345

1.3

Sub Total

723

4.47

2301

330

8.0

2190

1.3
10.4

FLAT-4

4.1

Living & Dining

290

2.11

1050

1020

5.2

5.2

4.2

Master Bed Room - 1

193

1.04

561

510

2.6

2.6

4.3

Bed Room - 2

120

0.66

345

330

1.3

1.3

4.4

Bed Room - 3

120

0.66

345

1.3

Sub Total

723

4.47

2301

330

8.0

2190

1.3
10.4

FLAT-5

2.1

Living & Dining

322

2.28

1147

1020

5.2

5.2

2.2

Master Bed Room - 1

161

1.08

588

510

2.6

2.6

2.3

Bed Room - 2

136

0.81

431

1.5

450

1.95

1.95

2.4

Bed Room - 3

120

0.87

470

1.95

1.95

Sub Total

739

5.04

2636

1
1
0

1.5

450

9.0

2430

11.7

FLAT-6

2.1

Living & Dining

322

2.28

1147

1020

5.2

5.2

2.2

Master Bed Room - 1

161

1.08

588

510

2.6

2.6

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-97

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

431

Totat

Qty

2.0 TR / 510 CFM

Qty

1.5 TR / 450 CFM

CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

TR

Total CFM

1.0 TR / 330 CFM

FT

Power reqd. ( single phase)

Total TR

Summer Dehumidified
CFM

Sqft

( Hi-wall unit)

2.0 TR / 510 CFM

SUMMER REF. LOAD

CONDITIONED
SPACE

HEIGHT

Equipment selection

AREA

Tower - 14 / 15

Qty

TR

CFM

KW

KW

KW

KW

1.5

450

1.95

1.95

1.95

1.95

2.3

Bed Room - 2

136

0.81

2.4

Bed Room - 3

120

0.87

470

1.5

450

Sub Total

739

5.04

2636

9.0

2430

11.7

Total

4320

28.4

14724

18

50.0

13620

65.0

101374

599.2

306164

232

222

246

Grand Total

1
1

1057.0 301920

1374.1

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-98

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

1
1.1
1.2
1.3
1.4

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

Summer Dehumidified
CFM

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

1
1.1
1.2
1.3
1.4

HEIGHT

Sqft

FT

TR

CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
161
107
120
710

9
9
9
9

2.19
0.97
0.66
0.69
4.51

1094
525
344
364
2327

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.27
1.05
0.75
0.75
4.82

1144
571
397
397
2509

FLAT -5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

1.83
0.89
0.59
0.59
3.90

885
474
304
304
1967

1
1
2

Total

2112

13.2

6803

Typical floor ( 1st to 3rd & 12th to 28th floor)


FLAT -1
Living & Dining
322
9
2.19
Master Bed Room - 1
161
9
0.97
Bed Room - 2
107
9
0.66
Bed Room - 3
120
9
0.69
Sub Total
710
4.51

1094
525
344
364
2327

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3

982
525
344
364

290
161
107
120

9
9
9
9

1.99
0.97
0.66
0.69

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

AREA

Tower - 16

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1020
1020
450
450
2940

0
0
0
0

0
0
1.95
1.95

5.2
5.2
0
0

4
4
1.5
1.5
11.0

5.2
5.2
1.95
1.95
14.3

3.9
1.95
0
0

0
0
0
0

900
450
330
330
2010

0
0
1.3
1.3

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

25.5

7140

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

3
2
1
1

900
510
330
330

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3

2
2

1
1
2

2
1

1
1
2

2
1
1
1

33.2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-97

M-282

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

86440

Typical floor ( 4th to 11th floor)


FLAT -1
Living & Dining
322
Master Bed Room - 1
225

9
9

Totat

9
9
9
9

2.0 TR / 510 CFM

333
193
120
120
766

1.5 TR / 450 CFM

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

1.0 TR / 330 CFM

Summer Dehumidified
CFM

678

Total CFM

SUMMER REF. LOAD

Sub Total

Total ( 1st to 3rd &


12th to 28th floor)

1
1.1
1.2

CFM

Total TR

2
2.1
2.2
2.3
2.4

TR

2.0 TR / 510 CFM

2
2.1
2.2
2.3
2.4

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

4
4.1
4.2
4.3
4.4

Sqft

Equipment selection
1.0 TR / 330 CFM

3
3.1
3.2
3.3
3.4

CONDITIONED SPACE

HEIGHT

AREA

Tower - 16

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

4.31

2215

7.0

2070

2.14
0.96
0.80
0.80
4.7

1065
514
427
427
2433

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2.27
1.05
0.75
0.75
4.82

1144
571
397
397
2509

1020
1020
450
450
2940

0
0
0
0

0
0
1.95
1.95

5.2
5.2
0
0

4
4
1.5
1.5
11.0

5.2
5.2
1.95
1.95
14.3

1.83
0.89
0.59
0.59
3.90

885
474
304
304
1967

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

1.95
0.99
0.68
0.68
4.30

953
530
355
355
2193

1
1
2

3.9
0
0
0

0
2.6
0
0

900
510
330
330
2070

0
0
1.3
1.3

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

530.8

272880

160

220

240

970.0

274200

2.19
1.33

1094
730

2
1

4
2

1020
510

1
1
2

2
2

1
1
2

2
1
1
1
2

2
1

9.1

1261.0

0
0

0
0

5.2
2.6

5.2
2.6

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-98

M-275

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

TR

CFM

Qty

Bed Room - 2
Bed Room - 3
Sub Total

107
120
774

9
9

0.66
0.69
4.87

344
364
2532

1
1
2

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

1.99
0.97
0.66
0.69
4.31

982
525
344
364
2215

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

2.14
0.96
0.80
0.80
4.7

1065
514
427
427
2433

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

2.27
1.05
0.75
0.75
4.82

1144
571
397
397
2509

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
225
120
120
765

9
9
9
9

1.83
1.15
0.59
0.59
4.16

885
626
304
304
2119

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3

333
193
120
120

9
9
9
9

1.95
0.99
0.68
0.68

953
530
355
355

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

2
2.1
2.2
2.3
2.4

FT

Qty

Qty

TR

CFM

KW

KW

KW

KW

330
330
2190

1.3
1.3

0
0

0
0

1
1
8.0

1.3
1.3
10.4

3
2
1
1
7.0

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3
9.1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
4
1.5
1.5
11.0

1020
1020
450
450
2940

0
0
0
0

0
0
1.95
1.95

5.2
5.2
0
0

5.2
5.2
1.95
1.95
14.3

3
2
1
1
7.0

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3
9.1

3
2
1
1

900
510
330
330

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3

2
1
1
1
2

2
1

1
1
2

2
2

1
1
2

2
1
1
1
2

2
1
1
1

( Hi-wall unit) Power reqd. ( single phase)

2.0 TR / 510 CFM

2
2.1
2.2
2.3
2.4

Sqft

CONDITIONED SPACE

Equipment selection
1.5 TR / 450 CFM

4
4.1
4.2
4.3
4.4

1.0 TR / 330 CFM

3
3.1
3.2
3.3
3.4

Summer Dehumidified
CFM

2
2.1
2.2
2.3

SUMMER REF. LOAD

1.3
1.4

HEIGHT

AREA

Tower - 16

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-99

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

2.0 TR / 510 CFM

Totat

Summer Dehumidified
CFM

1.5 TR / 450 CFM

2
2.1
2.2

1.0 TR / 330 CFM

4
4.1
4.2
4.3
4.4

Total CFM

3
3.1
3.2
3.3
3.4

CFM

Total TR

2
2.1
2.2
2.3

TR

2.0 TR / 510 CFM

1
1.1
1.2
1.3
1.4

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Total ( 4th to 11th


floor)

Sqft

Equipment selection
1.0 TR / 330 CFM

Sub Total

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower - 16

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

766

4.30

2193

7.0

2070

9.1

35600

217.3

112008

64

80

104

392.0

110160

509.6

2.41
1.08
0.73
0.77
4.99

1223
589
387
412
2611

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2.19
1.08
0.73
0.77
4.77

1098
589
387
412
2486

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2.37
1.09
0.88
0.88
5.22

1198
591
475
475
2739

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

2.47
1.16
0.83
0.83
5.29

1264
636
446
446
2792

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

4
2
1.5
1.5
9.0

5.2
2.6
1.95
1.95
11.7

2.03
0.99

1005
539

2
1

4
2

1020
510

0
0

0
0

5.2
2.6

5.2
2.6

29th floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

322
161
107
120
710

9
9
9
9

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
161
107
120
678

9
9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

300
161
120
120
701

9
9
9
9

FLAT-5
Living & Dining
Master Bed Room - 1

300
161

9
9

1
1
2

2
1

1
1
2

2
1

1
1
2

2
1

1
1
2

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-100

M-302

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Summer Dehumidified
CFM

1.0 TR / 330 CFM

Sqft

FT

TR

CFM

Qty

Bed Room - 2
Bed Room - 3
Sub Total

120
120
701

9
9

0.67
0.67
4.36

352
352
2248

1
1
2

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

333
193
120
120
766

9
9
9
9

2.59
1.12
0.76
0.76
5.23

1329
608
403
403
2743

Total

4322

29.9

15619

128474

791.2

407310

Grand Total

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

( Hi-wall unit) Power reqd. ( single phase)

2.0 TR / 510 CFM

CONDITIONED SPACE

Equipment selection
1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

SUMMER REF. LOAD

2.3
2.4

HEIGHT

AREA

Tower - 16

Qty

Qty

TR

CFM

KW

KW

KW

KW

330
330
2190

1.3
1.3

0
0

0
0

1
1
8.0

1.3
1.3
10.4

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

14340

2
1

1
1
2

4
2
1.5
1.5
9.0

10

18

53.0

230 315 369 1440.5 405840

68.9

1872.7

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-101

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

AREA

HEIGHT

SUMMER REF. LOAD

Summer Dehumidified
CFM

Tower-17

Sqft

FT

TR

CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

2.22
1.08
0.68
0.68
4.66

1119
593
358
358
2428

3
3.1
3.2
3.3
3.4
3.5

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

2.22
1.08
0.68
0.68
4.66

1119
593
358
358
2428

4
4.1
4.2
4.3
4.4

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

1.99
0.85
0.54
0.54
3.92

983
454
274
274
1985

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

1.99
0.85
0.54
0.54
3.92

983
454
274
274
1985

1
1
2

Total

2748

17.2

8826

Typical floor ( 1st to 3rd & 12th to 24th floor)


FLAT -1
Living & Dining
290
9
2.22
Master Bed Room - 1
157
9
1.08
Bed Room - 2
120
9
0.68
Bed Room - 3
120
9
0.68

1119
593
358
358

1
1.1
1.2
1.3
1.4

4
4.1
4.2
4.3
4.4

1
1.1
1.2
1.3
1.4

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CONDITIONED SPACE

( Hi-wall unit) Power reqd. ( single phase)

1.0 TR / 330 CFM

Equipment selection

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1
1
2

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

4
2
1
1
8.0

5.2
2.6
1.3
1.3
10.4

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.45

3.9
1.95
0
0

0
0
0
0

900
450
330
330
2010

0
0
1.3
1.3

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.45

29.0

8400

2
1

4
2
1
1

1020
510
330
330

2
1
1
1
2

2
1
1
1
2

2
1

1
1

37.7

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-102

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

355
130
120
120
725

9
9
9
9

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

Totat

344
140
120
604

2.0 TR / 510 CFM

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Sub Total

1.5 TR / 450 CFM

Summer Dehumidified
CFM

687

1.0 TR / 330 CFM

SUMMER REF. LOAD

Sub Total

Total CFM

2
2.1
2.2
2.3
2.4

CFM

Total TR

2
2.1
2.2
2.3
2.4

TR

2.0 TR / 510 CFM

4
4.1
4.2
4.3
4.4

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

3
3.1
3.2
3.3
3.4

Sqft

Equipment selection
1.0 TR / 330 CFM

2
2.1
2.2
2.3

CONDITIONED SPACE

HEIGHT

AREA

Tower-17

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

4.66

2428

8.0

2190

2.23
0.86
0.73
3.82

1149
459
387
1995

4
1.5
1
6.5

1020
450
330
1800

0
0
1.3

0
1.95
0

5.2
0
0

5.2
1.95
1.3
8.5

2.22
1.08
0.68
0.68
4.66

1119
593
358
358
2428

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

4
2
1
1
8.0

5.2
2.6
1.3
1.3
10.4

1.99
0.85
0.54
0.54
3.92

983
454
274
274
1985

1
1
2

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.45

2.08
0.64
0.61
0.61
3.94

1024
332
315
315
1986

1
1
1
3

1020
330
330
330
2010

0
1.3
1.3
1.3

0
0
0
0

5.2
0
0
0

4
1
1
1
7.0

5.2
1.3
1.3
1.3
9.1

1.99
0.85
0.54
0.54
3.92

983
454
274
274
1985

900
450
330
330
2010

0
0
1.3
1.3

3.9
1.95
0
0

0
0
0
0

3
1.5
1
1
6.5

3.9
1.95
1.3
1.3
8.5

1
1
1

2
1
1
1
2

2
1

2
1
1
1
2

10.4

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-103

N-155,165

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

344
140
120
604

9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
233
120
120
763

9
9
9
9

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

355
130
120
120
725

9
9
9
9

Totat

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Sub Total

2.0 TR / 510 CFM

9
9
9
9

1.5 TR / 450 CFM

Summer Dehumidified
CFM

Typical floor ( 4th to 11th floor)


FLAT -1
Living & Dining
290
Master Bed Room - 1
157
Bed Room - 2
120
Bed Room - 3
120
Sub Total
687

1.0 TR / 330 CFM

2
2.1
2.2
2.3
2.4

65232

Total CFM

4
4.1
4.2
4.3
4.4

CFM

Total TR

3
3.1
3.2
3.3
3.4

TR

2.0 TR / 510 CFM

2
2.1
2.2
2.3

FT

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

1
1.1
1.2
1.3
1.4

Sqft

Equipment selection
1.0 TR / 330 CFM

Total ( 1st to 3rd &


12th to 24th floor)

SUMMER REF. LOAD

CONDITIONED SPACE

HEIGHT

AREA

Tower-17

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

398.7

204912

192

112

160

680.0

195360

2.22
1.08
0.68
0.68
4.66

1119
593
358
358
2428

2
1

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

2.23
0.86
0.73
3.82

1149
459
387
1995

4
1.5
1
6.5

1020
450
330
1800

0
0
1.3

0
1.95
0

5.2
0
0

5.2
1.95
1.3
8.5

2.22
1.08
0.68
0.68
4.66

1119
593
358
358
2428

4
2
1
1
8.0

1020
510
330
330
2190

0
0
1.3
1.3

0
0
0
0

5.2
2.6
0
0

5.2
2.6
1.3
1.3
10.4

1.99
1.16
0.54
0.54
4.23

983
628
274
274
2159

1
1
2

3
2
1
1
7.0

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3.9
2.6
1.3
1.3
9.1

2.08
0.64
0.61
0.61
3.94

1024
332
315
315
1986

1
1
1
3

4
1
1
1
7.0

1020
330
330
330
2010

0
1.3
1.3
1.3

0
0
0
0

5.2
0
0
0

5.2
1.3
1.3
1.3
9.1

1
1
2

2
1
1
1

2
1
1
1
2

2
1

884.0

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-104

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total ( 4th to 11th


floor)

1
1.1
1.2
1.3
1.4

2
2.1
2.2
2.3

3
3.1
3.2
3.3
3.4

4
4.1
4.2
4.3
4.4

Summer Dehumidified
CFM

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

SUMMER REF. LOAD

2
2.1
2.2
2.3
2.4

Sqft

FT

TR

CFM

290
233
120
120
763

9
9
9
9

1.99
1.16
0.54
0.54
4.23

983
628
274
274
2159

1
1
2

25.5

13155

12

2.42
1.19
0.77
0.77
5.15

1236
656
407
407
2706

2.46
0.95
0.81
4.22

1287
516
435
2238

2.42
1.19
0.77
0.77
5.15

1236
656
407
407
2706

2.28
0.96
0.78
0.94

1157
522
416
505

33832

25th floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Sub Total

344
140
120
604

9
9
9

FLAT-3
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
157
120
120
687

9
9
9
9

FLAT-4
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3

290
233
120
120

9
9
9
9

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Equipment selection
1.0 TR / 330 CFM

CONDITIONED SPACE

HEIGHT

AREA

Tower-17

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

900
510
330
330
2070

0
0
1.3
1.3

3.9
0
0
0

0
2.6
0
0

3
2
1
1
7.0

3.9
2.6
1.3
1.3
9.1

12

43.5

12330

2
1

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
0

5.2
2.6
1.95
1.95
11.7

4
2
1.5
7.5

1020
510
450
1980

0
0
0
0

0
0
1.95
1.95

5.2
2.6
0
7.8

5.2
2.6
1.95
9.75
19.5

4
2
1.5
1.5
9.0

1020
510
450
450
2430

0
0
0
0

0
1.95
1.95
3.9

2.6
0
0
7.8

2.6
1.95
1.95
11.7
18.2

4
2
1.5
2

1020
510
450
510

0
0
0

0
1.95
0

2.6
0
2.6

2.6
1.95
2.6

1
1
2

2
1
0

1
1

2
1

1
1
2

2
1
1
1

56.6

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-105

N-261

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

CFM

Total TR

Summer Dehumidified
CFM

TR

2.0 TR / 510 CFM

SUMMER REF. LOAD

FT

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

4.96

2600

9.5

2490

1.95

10

12.35
19.5

2.32
0.73
0.69
0.69
4.43

1166
384
363
363
2276

1
1
1
3

4
1.5
1.5
1.5
8.5

1020
450
450
450
2370

0
0
0
0

1.95
1.95
1.95
5.85

0
0
0
5.2

1.95
1.95
1.95
11.05
16.9

2.28
0.96
0.78
0.94
4.96

1157
522
416
505
2600

1
4

4
2
1.5
2
9.5

1020
510
450
510
2490

0
0
0
0

0
1.95
0
1.95

2.6
0
2.6
10

2.6
1.95
2.6
12.35

15126

10

19

53.0

14190

68.9

805.5

230280

1047.2

Sub Total

763

FLAT-5
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

355
130
120
120
725

9
9
9
9

FLAT-6
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Sub Total

290
233
120
120
763

9
9
9
9

Total

4229

28.9

106041

470.3

Grand Total

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

2
2.1
2.2
2.3
2.4

Sqft

Equipment selection
1.0 TR / 330 CFM

2
2.1
2.2
2.3
2.4

CONDITIONED SPACE

HEIGHT

AREA

Tower-17

2
1
1

242019 212 133 197

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-106

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

2
2.1
2.2
2.3

Summer Dehumidified
CFM

1
1.1
1.2
1.3
1.4

SUMMER REF. LOAD

1
1.1
1.2
1.3
1.4
1.5

HEIGHT

Sqft

FT

TR

CFM

Stilt floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Bed Room - 4
Sub Total

505
236
174
120
120
1155

9
9
9
9
9

2.94
1.49
1.10
0.66
0.65
6.8

1487
824
599
345
337
3592

1
1
2

Total

1155

6.8

3592

2.94
1.49
1.10
0.66
0.65
6.8

1487
824
599
345
337
3592

2.94
1.49
1.10
0.66
0.65
6.8

1487
824
599
345
337
3592

1
1
2

342.0

179600

100

150

3.28
1.65
1.22

1689
919
668

Typical floor ( 1st to 25th floor)


FLAT -1
Living & Dining
505
Master Bed Room - 1
236
Bed Room - 2
174
Bed Room - 3
120
Bed Room - 4
120
Sub Total
1155
FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Bed Room - 4
Sub Total
Total ( 1st to 25th
floor)

1
1.1
1.2
1.3

26th Floor
FLAT -1
Living & Dining
Master Bed Room - 1
Bed Room - 2

505
236
174
120
120
1155

9
9
9
9
9

9
9
9
9
9

57750

505
236
174

9
9
9

2.0 TR / 510 CFM

Total TR

Total CFM

1.0 TR / 330 CFM

1.5 TR / 450 CFM

2.0 TR / 510 CFM

Totat

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

AREA

Tower - 19 / 20

Qty

Qty

Qty

TR

CFM

KW

KW

KW

KW

1350
510
510
330
330
3030

0
0
0
1.3
1.3

5.85
0
0
0
0

0
2.6
2.6
0
0

4.5
2
2
1
1
10.5

5.85
2.6
2.6
1.3
1.3
13.7

10.5

3030

4.5
2
2
1
1
10.5

1350
510
510
330
330
3030

0
0
0
1.3
1.3

5.85
0
0
0
0

0
2.6
2.6
0
0

5.85
2.6
2.6
1.3
1.3
13.7

1350
510
510
330
330
3030

0
0
0
1.3
1.3

5.85
0
0
0
0

0
2.6
2.6
0
0

4.5
2
2
1
1
10.5

5.85
2.6
2.6
1.3
1.3
13.7

100

525.0

151500

6
3
2

1530
900
510

1
1

3
1
1
1
1
2

3
1
1

2
1

13.7

Q-261

Q-262,052,R-262,162

682.5

0
0
0

0
3.9
0

7.8
0
2.6

7.8
3.9
2.6

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-107

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(SPLIT AIR-CONDITIONING SYSTEM)

393
385
4054

FLAT-2
Living & Dining
Master Bed Room - 1
Bed Room - 2
Bed Room - 3
Bed Room - 4
Sub Total

505
236
174
120
120
1155

9
9
9
9
9

3.28
1.65
1.22
0.74
0.73
7.6

1689
919
668
393
385
4054

Total

2310

15.2

8108

61215

364.1

Grand Total

Totat

0.74
0.73
7.6

2.0 TR / 510 CFM

9
9

1.5 TR / 450 CFM

120
120
1155

1.0 TR / 330 CFM

Bed Room - 3
Bed Room - 4
Sub Total

Total CFM

CFM

Total TR

TR

2.0 TR / 510 CFM

FT

Qty

1
1
4

( Hi-wall unit) Power reqd. ( single phase)

1.5 TR / 450 CFM

Sqft

CONDITIONED SPACE

Equipment selection
1.0 TR / 330 CFM

Summer Dehumidified
CFM

2
2.1
2.2
2.3

SUMMER REF. LOAD

1.4

HEIGHT

AREA

Tower - 19 / 20

Qty

Qty

TR

CFM

KW

KW

KW

KW

450
450
3840

0
0

1.95
1.95

0
0

1.5
1.5
14.0

1.95
1.95
18.2

1530
900
510
450
450
3840

0
0
0
0
0

0
3.9
0
1.95
1.95

7.8
0
2.6
0
0

7.8
3.9
2.6
1.95
1.95
18.2

1
1
4

6
3
2
1.5
1.5
14.0

28.0

7680

563.5

162210

2
1

191300 102 161 110

36.4

732.6

Pl. note the U-value considered for cooling load analysis for residential blocks :
Exposed wall 0.36 BTU/hr.sqft.F ( 9 brick wall with both side plaster )
Exposed Glass 0.56 BTU/hr.sqft.F ( Single glass with inside venetion blind)
Uninsulated Roof 0.4 BTU/hr.sqft.F ( Inverted clay/pots with mud phuska)
Floor and ceiling -0.42 BTU/hr.sqft.F

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-108

Q-272,R-272

Total Capacity of
Indoor Unit

Selected Out door Unit

Power Comsumption

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 21 / 23

In TR

In HP

KW

12

13

12.00

13.00

10

11

Hi-Wll Type
SFt

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp. (deg RH


F +/-2)
(Max)

Watt Watt

(No.)

TR

TR

CFM

CFM

Unit
Qty.

Unit
Qty.

Unit
Qty.

Unit
Qty.

6.09

Typical Floor ( 1st to 3rd & 12th to 23rd floor)


1

FLAT-01

1.1

Living cum Dining Room

640

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.52

3.02

1736

1343

1.2

Master Bedroom

283

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.49

1.2

782

592

1.3

Bed Room-02

157

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.66

0.49

326

209

1.4

Bed Room-03

228

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.38

727

486

1.5

Bed Room-04

203

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.13

0.92

585

445

Sub Total

1511

8.18

6.63

4156

2.32
1.03
1

2.03

13.07

1
2

1.6

FLAT-02

2.1

Living cum Dining Room

658

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.32

2.57

1620

1086

2.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.69

1.16

891

561

2.3

Bed Room-02

213

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.92

0.64

468

284

2.4

Bed Room-03

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.73

0.54

367

233

1.03

2.5

Bed Room-04

143

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.63

0.48

310

202

1.03

Sub Total

1490

7.29

5.39

3656

10.47

10.00

11.00

TOTAL ( 1st to 3rd & 12th


to 23rd floor)

45015

232.1

180.3

117180

75

45

60

60

353.1

330

360

6.09

12

13

4.8

2.32

1.29

Typical Floor ( 4th to 11th floor)


1

FLAT-01

1.1

Living cum Dining Room

640

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.52

3.02

1736

1343

1.2

Master Bedroom

283

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.49

1.2

782

592

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-109

2.32

Total Capacity of
Indoor Unit

Selected Out door Unit

Power Comsumption

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 21 / 23

In TR

In HP

KW

1.03

12

13

12.00

13.00

12

13

Hi-Wll Type
SFt

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp. (deg RH


F +/-2)
(Max)

Watt Watt

(No.)

TR

TR

CFM

CFM

Unit
Qty.
1

1.3

Bed Room-02

157

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.66

0.49

326

209

1.4

Bed Room-03

228

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.38

727

486

1.5

Bed Room-04

203

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.13

0.92

585

445

Sub Total

1511

8.18

6.63

4156

Unit
Qty.

Unit
Qty.

Unit
Qty.

2.03

13.07

1
2

1.6

FLAT-02

2.1

Living cum Dining Room

678

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.42

2.63

1676

1115

2.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.69

1.16

891

561

2.3

Bed Room-02

261

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.3

0.87

677

405

2.4

Bed Room-03

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.73

0.54

367

233

1.03

2.5

Bed Room-04

143

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.63

0.48

310

202

1.03

Sub Total

1558

7.77

5.68

3921

11.21

12.00

13.00

TOTAL ( 4th to 11th floor)

24552

127.6

98.5

64616

40

16

32

40

194

192

208.0

6.09

14

15.5

14.00

15.50

4.8

2.32
1

2.03

24th floor
1

FLAT-01

1.1

Living cum Dining Room

640

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.95

3.47

1982

1599

1.2

Master Bedroom

283

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.68

1.4

891

705

1.3

Bed Room-02

157

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.77

0.6

387

272

1.4

Bed Room-03

228

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.53

1.16

814

578

2.03

1.5

Bed Room-04

203

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.26

1.06

663

526

2.03

Sub Total

1511

9.19

7.69

4737

13.50

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-110

2.32
1.03

Total Capacity of
Indoor Unit

Selected Out door Unit

Power Comsumption

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 21 / 23

In TR

In HP

KW

12

13

Hi-Wll Type

SFt

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp. (deg RH


F +/-2)
(Max)

Watt Watt

(No.)

TR

TR

CFM

CFM

3.76

3.04

1873

1349

Unit
Qty.

Unit
Qty.

Unit
Qty.

Unit
Qty.

6.09

FLAT-02

2.1

Living cum Dining Room

658

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

2.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.9

1.39

1015

690

2.3

Bed Room-02

213

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.06

0.79

550

370

2.4

Bed Room-03

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.84

0.64

426

295

2.5

Bed Room-04

143

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.73

0.58

365

259

Sub Total

1490

8.29

6.44

4229

10.99

12.00

13.00

TOTAL

3001

17.5

14.1

8966

24

26

28.5

Grand Total

72568

377.1

292.9

190762

118

65

92

108

572

548

597

2.58
0

1.29

1.03

Following conditions apply to the selection of indoor and out door capacity.

A-1

ADP Selected is 51F

A-2

Bypass factor considered is .15

A-3

Indoor quantity fixed.

A-4

Indoor rating may be modified by the contractor to suit the manufacturer"s standard specifications and sizing.

A-5

Refer the note pertaining to the selection of indoor units and thereof the capacity of the outdoor unit in the equipment selection sheet, annexed to this document.Under no circumstance would the capacity of outddor unit be changed due to the su
selected, based on manufaturer's standard sizing. (Consider elevating the diversity available in a residential application, rather than changing the outdoor capacity)

A-6

Out door quantity is also fixed per flat as described in tender document and selection sheet.

A-7

The above have to be read in conjunction with the intent of the design, and the modified selection, shall ensure the delivery of inside conditions as laid in the tender document.

A-8

De-ration of the out door unit has to be considered for 43.3 Deg C out door conditions.

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-111

Total Capacity of
Indoor Unit

Selected Out door Unit

Power Comsumption

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

INSIDE DESIGN CONDITIONS

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 21 / 23

In TR

In HP

KW

Hi-Wll Type
SFt

FT

MAX. TOTAL ACPH or 1 ACH

A-9

Diversity between the indoor and oput-door unit capacity assumed as 130% .

A-10

Selection criteria:

A-10.1 Indoor unit:

Inside temp. (deg RH


F +/-2)
(Max)

Watt Watt

(No.)

TR

TR

Match the de-humidified air quantity as mentioned in the design data summary.
If the same cannot be matched, then strike an equilibrium between the refrigeration demand and dehumidified air quantity.

A-10.2 Out-door unit

After de-ration (@ 8-10%) , the capacity of out-door unit shall not be less than the peak refrigeration demand of flat.

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-112

CFM

CFM

Unit
Qty.

Unit
Qty.

Unit
Qty.

Unit
Qty.

4.0 TR (1500 CFM)


Ductable Type

Total Capacity of
Indoor Unit

Selected Out door Unit

(600 CFM)
2.0 TR

(395 CFM)
1.6 TR

(388 CFM)
1.28 TR

(310 CFM)
0.8 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 21 / 23
Lift lobbies

Unit Qty.

In TR

In HP

6.5

Cassate Type

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

Inside temp. RH
Watt Watt
(deg F +/-2) (Max)

(No.)

TR

TR

CFM

CFM

Unit
Qty.

150

3.29

2.19

1740

1052

NIL

100

0.68

0.53

314

199

0.8

NIL

100

0.68

0.53

314

199

0.8

314

199

0.8

314

199

0.8

199

0.8

314

199

0.8

314

199

0.8

199

0.8

314

199

0.8

314

199

0.8

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

199

0.8

314

199

0.8

314

199

0.8

SFt/Unit

FT

MAX. TOTAL ACPH or 1 ACH

LIFT LOBBY
Entrace Lobby-Gr. Fl.

596

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

Lift Lobby-1st. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

Lift Lobby-2nd. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

Lift Lobby-3rd. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-4th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-5th. Fl.

83

Lift Lobby-6th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-7th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-8th. Fl.

83

Lift Lobby-9th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-10th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-11th. Fl.

83

Lift Lobby-12th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-13th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-14th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-15th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-16th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-17th. Fl.

83

Lift Lobby-18th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-19th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

5 CFM/person + 0.06 CFM/Sqft

5 CFM/person + 0.06 CFM/Sqft

5 CFM/person + 0.06 CFM/Sqft

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

76F+/-2

76F+/-2

76F+/-2

55%

55%

55%

55%

NIL

NIL

NIL

NIL

100

100

100

100

0.68

0.68

0.68

0.68

0.53

0.53

0.53

0.53

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-113

314

314

314

314

Unit
Qty.

Unit
Qty.

Unit
Qty.

10

4.0 TR (1500 CFM)


Ductable Type

Total Capacity of
Indoor Unit

Selected Out door Unit

(600 CFM)
2.0 TR

(395 CFM)
1.6 TR

(388 CFM)
1.28 TR

(310 CFM)
0.8 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 21 / 23
Lift lobbies

Unit Qty.

In TR

In HP

Cassate Type

21

Inside temp. RH
Watt Watt
(deg F +/-2) (Max)

(No.)

TR

TR

CFM

CFM

Unit
Qty.

0.68

0.53

314

199

0.8

314

199

0.8

314

199

0.8

0.53

314

199

1
1

0.68

0.53

314

199

0.8

20

15

9276

SFt/Unit

FT

MAX. TOTAL ACPH or 1 ACH

Lift Lobby-20th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

Lift Lobby-21th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

83
83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

22
23 Lift Lobby-22th. Fl.
Lift Lobby-23th. Fl.
24
Lift Lobby-24th. Fl.
25
Total

2588

76F+/-2

55%

NIL

100

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-114

25

Unit
Qty.

Unit
Qty.

Unit
Qty.

0.8

26

34

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Power Comsumption

Tower - 21 / 23
Lift lobbies

KW

11

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-115

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Power Comsumption

Tower - 21 / 23
Lift lobbies

KW

39

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-116

Total Capacity of
Indoor Unit

Selected Out door Unit

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower-22

In TR

In HP

Hi-Wll Type
SFt

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp. (deg RH


F +/-2)
(Max)

Watt Watt

(No.)

TR

TR

CFM

CFM

Unit
Qty.

Unit
Qty.

Unit
Qty.

Unit
Qty.

Typical Floor ( 1st to 27th floor)


1

FLAT-01

1.1

Living cum Dining Room

658

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.32

2.57

1620

1086

1.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.89

1.44

1006

717

2.58

1.3

Bed Room-02

213

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.91

0.63

461

279

1.29

1.4

Bed Room-03

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.73

0.54

366

234

1.5

Bed Room-04

143

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.61

0.47

300

197

Sub Total

1490

7.46

5.65

3753

4.8

10

1.03
1.03

10.73

2.32

1.29

10.00

FLAT-02

2.1

Living cum Dining Room

658

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.32

2.57

1620

1086

2.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.67

1.15

884

556

2.3

Bed Room-02

213

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.92

0.64

465

280

2.4

Bed Room-03

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.73

0.53

363

231

2.5

Bed Room-04

143

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.61

0.47

300

197

Sub Total

1490

7.25

5.36

3632

10.47

10.00

TOTAL ( 1st to 27th floor)

80460

397.2

297.3

199395

135

135

162

572.4

540

6.09

4.8

10

1.03
1.03

28th floor
1

FLAT-01

1.1

Living cum Dining Room

658

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.76

3.04

1837

1349

1.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

2.11

1.66

1130

846

1.3

Bed Room-02

213

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.05

0.78

543

364

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-115

2.58
1

1.6

12

Total Capacity of
Indoor Unit

Selected Out door Unit

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower-22

In TR

In HP
12

Hi-Wll Type
FT

MAX. TOTAL ACPH or 1 ACH

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

1.4

Bed Room-03

1.5

Bed Room-04

143

Sub Total

1490

Inside temp. (deg RH


F +/-2)
(Max)

SFt

Watt Watt

(No.)

TR

TR

CFM

CFM

100

0.84

0.64

425

296

100

0.71

0.57

355

254

8.47

6.69

4290

Unit
Qty.

Unit
Qty.

Unit
Qty.

Unit
Qty.

1.29

1
1

1.03
3

12.59

6.09

12.00

FLAT-02

2.1

Living cum Dining Room

658

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

300

300

12

3.76

3.04

1837

1349

2.2

Master Bedroom

322

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.89

1.38

1008

685

2.3

Bed Room-02

213

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

1.06

0.78

547

365

2.4

Bed Room-03

154

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.83

0.64

422

293

2.5

Bed Room-04

143

10.5

5 CFM/person + 0.06 CFM/Sqft

74F+/-2

55%

100

100

0.71

0.57

355

254

Sub Total

1490

8.25

6.41

4169

12.59

12.00

TOTAL

2980

16.7

13.1

8459

25

24

Grand Total

83440

413.9

310.4

207854

137

141

164

597.6

564

2.58
1

1.6

12

1.29

1.03

Following conditions apply to the selection of indoor and out door capacity.

A-1

ADP Selected is 51F

A-2

Bypass factor considered is .15

A-3

Indoor quantity fixed.

A-4

Indoor rating may be modified by the contractor to suit the manufacturer"s standard specifications and sizing.

A-5

Refer the note pertaining to the selection of indoor units and thereof the capacity of the outdoor unit in the equipment selection sheet, annexed to this document.Under no circumstance would the capacity of outddor unit be changed due to the su
based on manufaturer's standard sizing. (Consider elevating the diversity available in a residential application, rather than changing the outdoor capacity)

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-116

Total Capacity of
Indoor Unit

Selected Out door Unit

(600 CFM)
2.03 TR

(565 CFM)
1.6 TR

(511 CFM)
1.29 TR

(365 CFM)
1.03 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED SPACE

INSIDE DESIGN CONDITIONS

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower-22

In TR

In HP

Hi-Wll Type
SFt

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp. (deg RH


F +/-2)
(Max)

Watt Watt

(No.)

TR

TR

CFM

CFM

A-6

Out door quantity is also fixed per flat as described in tender document and selection sheet.

A-7

The above have to be read in conjunction with the intent of the design, and the modified selection, shall ensure the delivery of inside conditions as laid in the tender document.

A-8

De-ration of the out door unit has to be considered for 43.3 Deg C out door conditions.

A-9

Diversity between the indoor and oput-door unit capacity assumed as 130% .

A-10

Selection criteria:

A-10.1 Indoor unit:

Match the de-humidified air quantity as mentioned in the design data summary.
If the same cannot be matched, then strike an equilibrium between the refrigeration demand and dehumidified air quantity.

A-10.2 Out-door unit

After de-ration (@ 8-10%) , the capacity of out-door unit shall not be less than the peak refrigeration demand of flat.

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-117

Unit
Qty.

Unit
Qty.

Unit
Qty.

Unit
Qty.

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Power Comsumption

Tower-22

KW

11

11.00

11

11.00

594.0

13

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-118

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Power Comsumption

Tower-22

KW
13

13.00

13

13.00

26.0

620.0

be changed due to the sum-total of indoor units selected,

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-119

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Power Comsumption

Tower-22

KW

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-120

Total Capacity of
Indoor Unit

Selected Out door Unit

Power Comsumption

In TR

In HP

KW

10

11

4.0 TR (1500 CFM)


Ductable Type

(600 CFM)
2.0 TR

(395 CFM)
1.6 TR

(388 CFM)
1.28 TR

(310 CFM)
0.8 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED
SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 22
Lift lobbies

Unit
Qty.

6.5

Cassate Type

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

SFt/Unit

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp.
(deg F +/-2)

RH
(Max)

Watt Watt

LIFT LOBBY
Entrace Lobby-Gr. Fl.

596

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

Lift Lobby-1st. Fl.

83

Lift Lobby-2nd. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-3rd. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-4th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-5th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-6th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-7th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-8th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-9th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-10th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-11th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-12th. Fl.

83

Lift Lobby-13th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-14th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-15th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-16th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-17th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-18th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-19th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

5 CFM/person + 0.06 CFM/Sqft

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

76F+/-2

55%

55%

NIL

NIL

150
100

100

(No.)

TR

TR

CFM

CFM

Unit
Qty.

3.29

2.19

1740

1052

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

314

199

0.8

0.68

0.68

0.53

0.53

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.


An ISO 9001-2008 certified company
Page-118

314

314

Unit
Qty.

Unit
Qty.

Unit
Qty.

4.0 TR (1500 CFM)


Ductable Type

Total Capacity of
Indoor Unit

Selected Out door Unit

Power Comsumption

(600 CFM)
2.0 TR

(395 CFM)
1.6 TR

(388 CFM)
1.28 TR

(310 CFM)
0.8 TR

Monsoon
Dehumidified CFM

Summer Dehumidified
CFM

MONSOON REF. LOAD

SUMMER REF. LOAD

TOTAL OCCUPANCY

INSIDE DESIGN CONDITIONS

LIGHT LOAD

HEIGHT

AIR CONDITIONED
AREA

CONDITIONED
SPACE

EQPT. LOAD

PROJECT : DLF Capital Green - SBM, New Delhi


Design Summary sheet and Equipment selection
(VRV AIR-CONDITIONING SYSTEM)

Tower - 22
Lift lobbies

Unit
Qty.

In TR

In HP

KW

Cassate Type

21
22
23
24
25
26
27
28
29

SFt/Unit

FT

MAX. TOTAL ACPH or 1 ACH

Inside temp.
(deg F +/-2)

RH
(Max)

Watt Watt

Lift Lobby-20th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

Lift Lobby-21th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

Lift Lobby-22th. Fl.


Lift Lobby-23th. Fl.

83
83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

5 CFM/person + 0.06 CFM/Sqft

Lift Lobby-24th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

Lift Lobby-25th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

Lift Lobby-26th. Fl.


Lift Lobby-27th. Fl.

83
83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

0.53

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

0.68

Lift Lobby-28th. Fl.

83

5 CFM/person + 0.06 CFM/Sqft

76F+/-2

55%

NIL

100

Total

2920

(No.)

TR

TR

CFM

CFM

Unit
Qty.

100

0.68

0.53

314

199

0.8

NIL

100

0.68

0.53

314

199

0.8

55%

NIL

100

0.68

0.53

314

199

0.8

76F+/-2

55%

NIL

100

0.68

0.53

314

199

1
1

76F+/-2

55%

NIL

100

0.68

0.53

314

199

0.8

314

199

0.8

314

199

0.8

0.53

314

199

1
1

0.68

0.53

314

199

0.8

22

17

10532

HVAC Consulting Engineer : Dew Point Consultants Pvt. Ltd.