You are on page 1of 6

GRAPHIC SYMBOL FOR INSTRUMENTATION ITEMS

SYMBOL DESCRIPTION
DEVICE MOUNTEDON PANEL
BOARDOR PANEL MOUNTEDDEVICE - DEVICE MOUNTEDINSIDE PANEL
FIELDOR LOCALLY MOUNTEDDEVICE
PROGRAMMEDFUNCTION NOT NORMALLY ACCESSIBLE TO OPERATOR
PROGRAMMEDFUNCTION ACCESSIBLE THROUGH OPERATOR'S INTERFACE DEVICE
PLC INPUT OR OUTPUT POINT
XOR
A
INTERLOCKING
EXCLUSIVE OR
ALTERNATOR
OR OR
AND AND
S MOTOR STARTER
P PURGE
L COMPLEX LOGIC
COMPUTER LOGIC SYSTEM
TERMINAL OR TRANSITION POINT
FLOAT SWITCH
PARTIAL FLUME
MIXER
SEAL
OFF PAGE CONNECTOR
PROCESS MACHINERY MOTOR
VENTURI OR INSERT FLOWTUBE
IN-LINE FLOWELEMENT (PROPELLER TYPE)
IN-LINE FLOWELEMENT (MAGNETIC TYPE)
IN-LINE FLOWELEMENT (ULTRA SONIC)
FLOWORIFICE
TURBIDITY METER
ROTOMETER
PUMP
BLOWER
GENERAL USE DISCONNECTING SWITCH
TIME CLOSEDCONTACT ON ENERGIZATION
TIME OPENEDCONTACT ON ENERGIZATION
TIME OPENEDCONTACT ON DE-ENERGIZATION
TIME CLOSEDCONTACT ON DE-ENERGIZATION
FLOAT ACTUATEDSWITCH - NO
FLOAT ACTUATEDSWITCH - NC
PRESSURE ACTUATEDSWITCH - NC
PRESSURE ACTUATEDSWITCH - NO
FLOWACTUATEDSWITCH - NO
FLOWACTUATEDSWITCH - NC
TEMPERATURE SWITCH - NO
TEMPERATURE SWITCH - NC
LIMIT SWITCH (PROXIMITY TYPE) - NORMALLY OPEN
LIMIT SWITCH (PROXIMITY TYPE) - NORMALLY OPEN - HELDCLOSED
LIMIT SWITCH (PROXIMITY TYPE) - NORMALLY CLOSED- HELDOPEN
LIMIT SWITCH (PROXIMITY TYPE) - NORMALLY CLOSED
CONTROL RELAY CONTACT - NORMALLY OPEN
CONTROL RELAY CONTACT - NORMALLY CLOSED
LIGHTING ARRESTOR
ETI ELAPSEDTIME INDICATOR
SYMBOL DESCRIPTION
T TIMING RELAY COIL
TIMING RELAY COIL (OFF DELAY)
1
T
G INDICATING LIGHT
PUSH-TO-TEST INDICATING LIGHT
BATTERY
X1 X2
SECONDARY TRANSFORMER
VARIABLE RESISTOR
RESISTOR
MOLDEDCASE CIRCUIT BREAKER
SPEEDSWITCH
MOMENTARY PUSHBUTTON OPERATOR - NORMALLY CLOSED
MOMENTARY PUSHBUTTON OPERATOR - NORMALLY OPEN
SELECTOR SWITCH - NORMALLY OPEN
PUSHBUTTON OPERATOR WITH MUSHROOMHEAD
SOLENOIDOR CLUTCH
THERMAL OVERLOAD
FIELDLOCATED
TERMINAL POINT
LOWVOLTAGE FUSE
FUSIBLE TERMINAL BLOCK
CIRCUIT BREAKER WITH STAB CONNECTION
CONTROL POWER TRANSFORMER
TWO COIL LATCHING RELAY
CR
L
CR
U
RECEPTACLE
SELECTOR SWITCH OPERATOR WITH FUNCTION SHOWN
HAND
OFF
AUTO
FOC
FOPP
FOC-DI(X)
FOC-DO(X)
FOC-AI(X)
FOC-AO(X)
DISCRETE INPUT TO FIBER CONVERTER (PROVIDE WITH 120VAC P/S FIBER
CONVERTER TO DISCRETE OUTPUT (PROVIDE WITH 120VAC P/S (WEEDEOTEC -
2S07/2H07 WITH 120 VAC P/S) QUANTITY (X) AS NOTEDON DRAWINGS
ANALOG INPUT TO FIBER CONVERTER
FIBER CONVERTER TO ANALOG INPUT (WEEDEOTEC 2T14/2R14 WITH POWER SUPPLY
AS REQUIRED) QUANTITY (X) AS NOTEDON DRAWINGS
FIBER OPTIC CONVERTER - TYPE ANDSTYLE AS NOTED
FIBER OPTIC PATCH PANEL CONNECTORS ANDQUANTITY AS NOTED
1I
0117
PROCESSOR #1, INPUT RACK 0, SLOT (OR GROUP) 1, BIT 17
EXAMPLE OF P&ID I/O SYMBOL
NOTE: THE PLC I/O ADDRESS SHALL BE USEDAS THE
WIRING TAG SCHEME FOR ALL PANEL ANDFIELD
CONTROL WIRING. COORDINATE WITH ELECTRICAL
CONTRACTOR.
GRAPHIC SYMBOLS FOR VALVES
SYMBOL DESCRIPTION
PLUG VALVE
PNEUMATIC DIAPHRAGMOR POSITIONER (THROTTLING)
PNEUMATIC DIAPHRAGMOR POSITIONER (OPEN-SHUT)
STROKE OR POSITION ACTUATOR CYLINDER (THROTTLING)
STROKE OR POSITION ACTUATOR CYLINDER (OPEN-SHUT)
MOTOR OPERATED(THROTTLING)
MOTOR OPERATED(OPEN - SHUT)
SLIDE-STOP GATE
SLUICE GATE
AIR SET ASSEMBLY
BALL VALVE
GLOBE VALVE
GATE VALVE OR KNIFE GATE
CHECK VALVE
BUTTERFLY VALVE, DAMPER OR LOUVER
TWO - WAY SOLENOIDVALVE OPERATOR
ELECTRONICALLY CONTROLLEDCHECK VALVE
TWO - WAY SOLENOIDVALVE OPERATOR - DETENTED
THREE - WAY SOLENOIDVALVE OPERATOR
FOUR - WAY SOLENOIDVALVE OPERATOR
MANIFOLDSTYLE BLOCK I/O SOLENOIDVALVE - DUAL COILS
ABBREVIATIONS
SYMBOL DESCRIPTION
R RESET
T TRIP
AS AIR SUPPLY
DO DISSOLVEDOXYGEN
GS GAS SUPPLY
HS HYDRAULIC SUPPLY
NS NITROGEN SUPPLY
ORP OXYGEN REDUCTION POTENTIAL
SS STEAMSUPPLY
SP SET POINT
WS WATER SUPPLY
PV PROCESS VARIABLE
F.O. FAIL OPEN
F.C. FAIL CLOSE
SBPP SCREEN BUILDING PROCESSOR PANEL
TFBMPP TERTIARY FILTER BUILDING MAIN PROCESSOR PANEL
HVACP HEATING VENTILATION AIR CONDITIONING CONTROL PANEL - I/O
MD MAIN DISCONNECT
GAIN OR PROPORTIONAL CONTROL
INTEGRAL OR RESET CONTROL
D DERIVATIVE OR RATE CONTROL
%
V VELOCITY ALGORITHM
1-0 ON - OFF CONTROL
SQUARE ROOT EXTRACTOR
E ADDOR TOTALIZE
SUBTRACT OR DIFFERENCE
> HIGHEST MEASUREDVARIABLE
< LOWEST MEASUREDVARIABLE
E/I , I/P CONVERT ONE TO ANOTHER
* , / MULTIPLY, DIVIDE
N BIAS OR REVERSING
f(x) CHARACTERIZE - (EQUATION / /D/%/ETC.)
SYMBOL DEMOLITION
INSTRUMENTATION LINE SYMBOLS
ELECTRICAL SIGNAL
AIR LINE/PNEUMATIC SIGNAL
HYDRAULIC SIGNAL
ELECTROMAGNETIC OR SONIC SIGNAL
SOFTWARE SIGNAL
CONNECTION TO PROCESS, OR MECHANICAL LINK
ETHERNET COMMUNICATION SIGNAL-UNSHIELDEDTWISTEDPAIR (UTP)-SPEED
AS INDICATED
ETHERNET FIBER OPTIC COMMUNICATIONS SIGNAL
PLC REMOTE I/O FIBER OPTIC COMMUNICATION SIGNAL
ETHERNET VIDEO FIBER OPTIC
I.S.A. STANDARD LETTER FUNCTIONS
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
ANALYSIS, ANALOG
BURNER, FLAME
CONDUCTIVITY, COMMAND
DENSITY, SPECIFIC GRAVITY
VOLTAGE
FLOWRATE
GAGING
HAND, MANUAL
CURRENT
POWER
TIME, TIME SCHEDULE
LEVEL, LIGHT
MOISTURE, HUMIDITY
OVERLOAD
PRESSURE, VACUUM
QUANTITY
RADIOACTIVITY
SPEED, FREQUENCY, SOLENOID
TEMPERATURE, TURBIDITY
MULTIVARIABLE
VIBRATION, VISCOSITY
WEIGHT, FORCE
POSITION
ALARM
BATCH
CONTROL (FEEDBACK TYPE)
PRIMARY ELEMENT
RATIO
GLASS
HIGH
INDICATE
SCAN
CONTROL (NO FEEDBACK)
LOW
MIDDLE, MODULATE
ORIFICE
POINT
TOTALIZE, INTEGRATE
RECORD, PRINT, RECEIVE
SWITCH
TRANSMIT, TRANSFORM
MULTIFUNCTION
VALVE, DAMPER, LOUVER
DRIVE, ACTUATE
RELAY, COMPUTE
SYMBOL FIRST LETTER SUCCEEDING LETTERS
INPUT POINT
XXX
EXISTING PANEL TERMINAL
NUMBER ANDFIELDWIRING
WHICH CONTRACTOR SHALL
FIELDVERIFY
XXX
D
01 I1OO1
XXX XXX
01201 01
WHICH CONTRACTOR SHALL
NUMBER ANDFIELDWIRING
EXISTING PANEL TERMINAL
FIELDVERIFY
OUTPUT POINT
OUTPUT RACK 1,
SLOT 2, BIT 01
SLOT 0, BIT 01
INPUT RACK 1,
1. PRIOR TO SUBMITTING A BIDFOR THE WORK DETAILEDUNDER THIS CONTRACT, BIDDER SHALL VISIT THE REMOTE SITES. THE BIDDER SHALL
FULLY ACQUAINT ONESELF WITH EXISTING FIELDCONDITIONS AT EACH SITE. NO BULLETINS WILL BE WRITTEN FOR WORK DUE TO LACK OF
VERIFICATION OF EXISTING SITE CONDITIONS ANDWIRING.
2. NO WIRES SHALL BE TERMINATEDTO TERMINAL STRIPS, OR OTHER EQUIPMENT WITHOUT FIRST VERIFYING SIGNAL TYPE. DAMAGES
RESULTING IN LACK OF VERIFICATION SHALL BE BORNE BY THE CONTRACTOR. CONTRACTOR SHALL COORDINATE SIGNAL TYPE AND
VOLTAGE WITH I/O CARDS SHOWN.
3. WITHIN CONTROL PANELS, NAMEPLATES SHALL BE PROVIDEDTO INDICATE DIFFERENT VOLTAGE LEVELS WITHIN PANELS. ALSO, A NAME
TAG (YELLOWBACKGROUND, REDLETTERING) SHALL BE LOCATEDON THE FRONT OF EVERY PANEL INDICATING THAT WHEN MAIN PANEL
DISCONNECTED120V IS STILL PRESENT FROMFIELDDEVICES (YELLOWWIRING/ISOLATEDINPUT CARDS.)
4. PHENOLIC TAGS ON FACE OF CONTROL PANELS TO HAVE WHITE BACKGROUNDANDBLACK LETTERING (EXCEPT WARNING TAGS; YELLOW
BACKGROUNDREDLETTERING).
5. PROVIDE SAFETY COVERS ON ALL 480V MOLDEDCASE MAIN CIRCUIT BREAKERS TO INSULATE THE INCOMING CABLES ANDSIDE
CONDUCTORS FROMCONTACT. (TYP. FOR ALL CONTROL PANELS.) PROVIDE BREAKER LOCKS FOR ALL PUMP CIRCUIT BREAKERS (MCP)AND
MAIN PANEL BREAKERS.
6. REFER TO WIRING DIAGRAMS FOR ADDITIONAL INFORMATION ON ISOLATEDI/O. A COMMON NEUTRAL MAY BE USEDFOR SEVERAL ISOLATED
INPUTS FROMTHE SAME STARTER. PROVIDE NEUTRAL J UMPERS WIRES WITHIN THE PANEL AS REQUIRED.
7. ELECTRICAL MATERIALS ANDEQUIPMENT ITEMS SHOWN IN LIGHT LINE WEIGHTS ON THE DRAWINGS ARE EXISTING ITEMS TO REMAIN.
ELECTRICAL MATERIALS ANDEQUIPMENT ITEMS SHOWN IN HEAVY LINE WEIGHTS ARE NEWTHIS CONTRACT.
8. ITEMS SHOWN CROSSHATCHED(OR NOTEDTO BE DEMOLISHED) ON THE DRAWINGS ARE EXISTING ITEMS TO BE REMOVED, FROMSITE BY
CONTRACTOR.
9. INSTALL A SINGLE CONDUCTOR INSULATED(RHW, THHN, OR XHHW) COPPER GROUNDWIRE IN EACH CONDUIT, SIZE AS SHOWN ON
DRAWINGS, OR AS A MINIMUMPER THE NATIONAL ELECTRICAL CODE. THIS GROUNDWIRE SHALL BE CONNECTEDAT EACH ENDTO THE
EQUIPMENT GROUND. THIS ALSO INCLUDES INSTRUMENTATION DEVICES SUCH AS LEVEL, PRESSURE, FLOWTRANSMITTERS, LIMIT
SWITCHES, CONDUITS, NETWORK ANDI/O CABLES.
10. THE FOLLOWING EXAMPLE COMPONENT IDENTIFICATION SHALL BE USEDAS APPROPRIATE:
(F) FIELDMOUNTED, NOT AT STARTER OR OTHER CONTROL PANELS
(S) STARTER PANEL MOUNTED
(MCP) AT MAIN CONTROL PANEL
(1) AT CONTROL PANEL NO.1
(2) AT CONTROL PANEL NO.2
(TCP) AT TEMPERATURE CONTROL PANEL
11. REFER TO DETAIL SHEETS. CONTRACTOR SHALL FURNISH ANDINSTALL HARDWARE ANDAPPURTENANCES (I.E. PIPE TAPS, WETWELL
BUBBLER TUBES, VALVES, COPPER TUBING, BALL VALVES, PNEUMATIC PIPING, SPOOL PIECES, ETC.) FOR FIELDDEVICES SHOWN
(FLOWMETERS, PRESSURE TRANSMITTERS, LEVEL TRANSMITTERS, ETC.). WORK SHALL BE COORDINATEDWITH OTHER TRADES
(MECHANICAL INSTRUMENTATION, ETC.) CONTRACTOR SHALL BE RESPONSIBLE FOR SYSTEMCOORDINATION ANDINSTALLATION.
12. ETHERNET ANDFIBER OPTIC TERMINATIONS SHALL BE PERFORMEDBY A QUALIFIEDREPRESENTATIVE OF CABLE MANUFACTURER, THE
CABLES SHALL BE TESTED. NO SPLICING SHALL BE PERMITTEDOF FIBER OPTIC CABLES, BETWEEN PANELS. ALL FIBERS SHALL BE
TERMINATEDAT PATCH PANELS, INCLUDING SPARES.
13. REFER TO THE CABLE MANUFACTURER'S RECOMMENDATIONS FOR MINIMUMBENDRADIUS FOR FIBER OPTIC CABLES. INSTALL NEWPULL
BOXES (PB) AS REQUIREDFOR CONDUITS. SIZE PULLBOXES AS REQUIREDPER FIBER OPTIC CABLE MANUFACTURERS RECOMMENDATIONS.
14. CONDUIT ENTERING CONTROL PANELS ANDELECTRICAL EQUIPMENT ENCLOSURES SHALL BE FILLEDWITH DUCT SEAL, INCLUDING
OPENINGS IN BOTTOMOF PANEL.
15. CABLES (INCLUDING FIBER, ETHERNET, CONTROL WIRE, ETC.) WHERE PASSING THROUGH A PULLBOX SHALL BE LABELEDANDCOMPLETELY
IDENTIFIEDWITH IDENTIFICATION NUMBERS ANDORIGINATION/DESTINATION. THIS ALSO INCLUDES ALL CABLE BUNDLES ENTERING
CONTROL PANELS, PULLBOXES, ETC.
16. CONTROL WIRES SHALL BE TAGGEDWITH THE PLC I/O ADDRESS IN THE FIELDANDAT THE PANEL.
17. FIBEROPTIC CABLE (FO, E-FO) SHALL BE 50/125 MICRON, ALL DIELECTRIC, CORNING ALTOS SERIES, WITH WATERBLOK GEL ANDSUITABLE
FOR INSTALLATION IN AN UNDERGROUND, WET CONDUIT, PROVIDE STRANDS AS SHOWN. TERMINATE ALL STRANDS. FOR THE FIBEROPTIC
CABLE SHOWN FOR ANALOG ANDDISCRETE I/O DEVICES, FIBER OPTIC CABLE SHALL BE (BELDEN M9B701 OR EQUAL) 2-STRANDBREAKOUT
STYLE LOOSE BUFFER OUTDOOR RATED(900 MICRON BUFFER DIAMETER). AT FIELDENCLOSURES, CONNECT DIRECTLY TO FOC-DI/DO/AI/AO
MODULES. PATCH PANELS NOT REQUIREDAT FIELDDEVICES.
18. THE FIELDDEVICES SHOWN ON THE P&ID'S, ELECTRICAL BACKGROUNDS, ANDDETAILS SHEETS MAKEUP THE FIELDDEVICE EQUIPMENT
REQUIREMENTS. NOT ALL FIELDDEVICES REQUIREDARE SHOWN ON THE P&ID'S.
19. UPS SELECTEDTO BE COMPATIBLE WITH SOLA MCR TRANSFORMERS. (TYP.)
20. CONDUIT ENTERING CONTROL PANELS ANDELECTRICAL EQUIPMENT ENCLOSURES SHALL BE FILLEDWITH DUCT SEAL, INCLUDING
OPENINGS IN BOTTOMOF PANELS, ANDEQUIPMENT.
21. REFER TO I/O DRAWING LAYOUT FOR ADDITIONAL SIGNALS NOT SHOWN ON P&IDFLOWDIAGRAMS.
EXAMPLES OF I/O
GENERAL NOTES:
MICROLOGIX
1100
IA-8 AI/
AO
AI DI
8
1762-IA8
BLUMFIELD-REESE PROCESSOR PANEL
PROPOSEDWORK SHOWN IN BOLD
AQUA PROCESSOR PANEL
PROPOSEDWORK SHOWN IN BOLD
I/O RACK
5/40E BCM
I/O RACK
5/40E BCM
I/O RACK
AJ B
1791
16AC
BLOCK 1
RACK 5
GROUP 0
1791
NDC
BLOCK 2
RACK 5
GROUP 2
150OHMTERMINATION RESISTER
I/O RACK
5/40E
1791
16AC
BLOCK 1
RACK 5
GROUP 0
1791
NDC
BLOCK 2
RACK 5
GROUP 2
RACK
GROUP
150OHMTERMINATION RESISTER
BELDEN 9463 CABLE
BELDEN 9463 CABLE
KOCHVILLE PROCESSOR PANEL
PROPOSEDWORK SHOWN IN BOLD
1. PLC HARDWARE TO BE ROCKWELL AS SHOWN.
2. RADIO TO BE GEMDS AS SHOWN.
3. REFER TO WIRING DIAGRAMS ON SHEETS I-3 THRU I-6
FOR ADDITIONAL INFORMATION.
4. PROGRAMMING OF PLC'S, OPERATION INTERFACE
COMPUTERS (OWNERS EXISTING SCADA SYSTEM),
ANDRADIOS BY TETRATECH.
NOTES:
MICROLOGIX
1100
AI/
AO
INET-11
900MHZ
KMPP NEMA 4 ENCLOSURE
CAT-5E PATCH CABLES
CAT-5E PATCH CABLES
TRANSTECTOR 10/100-BASE-T
ETHERNET SURGE SUPPRESSOR
GEMDS-REMOTE
FURNISH J UMPER WITH RIGHT
ANGLE CONNECTOR AT RADIO
POLYPHASOR DSXL SERIES
1/2" SUREFLEX J UMPER
FURNISH GROUNDKIT
FOR GROUNDING RF CABLE
TIMES MICROWAVE LMR-400
CABLE-25 FEET IN TOTAL LENGTH
RFS CELLWAVE 10108-2 YAGI ANTENNA
ORIENT TO KOCHVILLE PUMP
STATION ACCESS POINT
KOCHVILLE, AND MICHIGAN AVE. PRESSURE
MONITORING STATION PROCESSOR PANEL
PROPOSEDWORK
BLOCK I/O MODULES
PROGRAMMING OF PLC'S,
RADIOS, OPERATOR
INTERFACE COMPUTERS
BY TETRA TECH.
GENERATOR RUNNING
GENERATOR FAULT
BLOCK 1
RACK 5
GROUP 0
120V
AC
IN 00
IN 01
IN 02
IN 03
IN 04
IN 05
IN 06
IN 07
IN 10
IN 11
IN 12
IN 13
IN 14
IN 15
IN 16
IN 17
BELDEN 9463 CABLES
REMOTE I/O CABLES
FROM PLC
OUT 00
OUT 01
OUT 02
OUT 03
OUT 04
OUT 05
OUT 06
OUT 07
OUT 10
OUT 11
OUT 12
OUT 13
OUT 14
OUT 15
OUT 16
OUT 17
120V AC
H
N
G
BLUE
CLR
SHLD
CONNECT TO
EXISTING UPS CIRCUIT
WITHIN PANEL
SIGNALS FROM
GENERATOR
SIGNALS FROM AUTOMATIC
TRANSFER SWITCH
SIGNALS FROM
TVSS SURGE UNIT
H N
GENERATOR OVER SPEED
GENERATOR OVER CRANK
LOWOIL PRESSURE
LOWCOOLANT TEMPERATURE
SPARE
SPARE
ATS IN NORMAL POSITION
ATS IN EMERGENCY POSITION
TVSS FAULT
SPARE
SPARE
SPARE
SPARE
SPARE
GENERATOR START/STOP
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
1
2
3
4
1
2
BLOCK 2
RACK 5
GROUP 2
I2600
I2601
I2602
I2603
O2600
O2601
1791-NDC
BLOCK I/O
4-20MA
SIGNALS
FROM
GENERATOR
BLOCK NO.2
POWER
DC+ DC- CR-20
CONNECT IN
PARALLEL WITH
START CONTACT
FROM ATS
SEE NOTE 1
1. LOCATE THE BLOCK MODULES, TERMINAL BLOCKS(COLOR CODEDAS
SPECIFIED), POWER SUPPLY, PANDUIT/WIRE COVERS, ANDASSOCIATED
DEVICES ON A SUBPLATE. SIZE SUBPLATE TO FIT ONTO EXISTING DOOR
INTERIOR.
2. WITHIN THE PANEL, FURNISH BRANCH CIRCUIT WIRING AS REQUIREDTO
CONNECT POWER, I/O CABLE, AS SHOWN. SECURE WIRING WIRING
BETWEEN PANEL ANDNEWDOOR SUBPLATE.
3. CONNECT INPUTS ANDOUTPUT AS SHOWN.
NOTES:
GENERATOR BATTERY VOLTAGE
GENERATOR OIL PRESSURE
GENERATOR CONSTANT
TEMPERATURE
SPARE
SPARE
SPARE
H N
H N
G
TO ANALOG BLOCK
GENERATOR RUNNING
GENERATOR FAULT
BLOCK 1
RACK 5
GROUP 0
120V
AC
IN 00
IN 01
IN 02
IN 03
IN 04
IN 05
IN 06
IN 07
IN 10
IN 11
IN 12
IN 13
IN 14
IN 15
IN 16
IN 17
BELDEN 9463 CABLES
REMOTE I/O CABLES
FROMPLC
OUT 00
OUT 01
OUT 02
OUT 03
OUT 04
OUT 05
OUT 06
OUT 07
OUT 10
OUT 11
OUT 12
OUT 13
OUT 14
OUT 15
OUT 16
OUT 17
120V AC
H
N
G
BLUE
CLR
SHLD
CONNECT TO
EXISTING UPS
CIRCUIT
WITHIN PANEL
SIGNALS FROM
GENERATOR
SIGNALS FROMAUTOMATIC
TRANSFER SWITCH
SIGNALS FROM
TVSS SIGNAL UNIT
H N
GENERATOR OVER SPEED
GENERATOR OVER CRANK
LOWOIL PRESSURE
LOWCOOLANT TEMPERATURE
SPARE
SPARE
ATS IN NORMAL POSITION
ATS IN EMERGENCY POSITION
TVSS FAULT
SPARE
SPARE
SPARE
SPARE
SPARE
GENERATOR START/STOP
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
1
2
3
4
1
2
BLOCK 2
RACK 5
GROUP 2
I2600
I2601
I2602
I2603
O2600
O2601
1791-NDC
BLOCK I/O
4-20MA
SIGNALS
FROM
GENERATOR
BLOCK NO.2
POWER
DC+ DC- CR-20
CONNECT IN
PARALLEL WITH
START CONTACT
FROMATS
SEE NOTE 1
1. LOCATE THE BLOCK MODULES, TERMINAL BLOCKS, POWER SUPPLY,
PANDUIT/WIRE COVERS, ANDASSOCIATEDDEVICES ON A SUBPLATE.
SIZE SUBPLATE TO FIT ONTO EXISTING DOOR INTERIOR.
2. WITHIN THE PANEL, FURNISH BRANCH CIRCUIT WIRING AS REQUIRED
TO CONNECT POWER, I/O CABLE, AS SHOWN. SECURE WIRING
WIRING BETWEEN PANEL ANDNEWDOOR SUBPLATE.
3. CONNECT INPUTS ANDOUTPUT AS SHOWN.
4. DEMOLISH EXISTING TELEMETRY EQUIPMENT ASSOCIATEDWITH
KOCHVILLE MICHIGAN AVE. PRESSURE MONITORING STATION.
5. ALTERNATE #2-A
6. RELOCATE TO EXISTING PLC INPUTS WHERE AVAILABLE.
NOTES:
GENERATOR BATTERY
VOLTAGE
GENERATOR OIL
PRESSURE
GENERATOR COOLANT
TEMPERATURE
SPARE
SPARE
SPARE
H N
H N
G
TO ANALOG BLOCK
GENERATOR BATTERY VOLTAGE
GENERATOR OIL PRESSURE
GENERATOR COOLANT TEMPERATURE
07
06
05
04
03
02
01
00
8 POINT DISCRETE
INPUT CARD
1762-IA8
GENERATOR RUNNING
GENERATOR FAULT
GENERATOR OVERLOAD
GENERATOR OVER CRANK
GENERATOR LOWOIL PRESSURE
GENERATOR LOWCOOLANT
TEMPERATURE
SPARE
SPARE
1. INSTALL THE DIGITAL INPUT CARDAS SHOWN WITHIN THE EXISTING
BOOSTER STATION PROCESSOR PANEL. WIRE ALL I/O TO TERMINATE
STRIP INCLUDING SPARES.
2. WITHIN THE EXISTING PANEL, FURNISH TERMINAL BLOCKS(COLOR
CODEDAS SPECIFIED) ANDWIRING.
3. CONNECT INPUTS AS SHOWN.
NOTES:
EXISTING DRAWING FROM PREVIOUS
PROJ ECT NO. 200-12753-09001-W-1.
PROPOSED WORK SHOWN BOLD
AND/OR BUBBLED
NO.
LINE
L1 N
L1 N
EDCO SLA SERIES SURGE PROTECTION
LOCATE IN SEPARATE
NEMA 4X ENCLOSURE
BESIDE PANEL.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
ORANGE COLORED
OUTLET. LOCATE ON
SIDE OF PANEL.
ON-LINE UPS
350KVA
LIEBERT
1.0 AMP
24VDC P/S
+ -
1
2
2
1 SPARE
DISCHARGE PRESSURE
0-150 PSI
ANALOG INPUT/OUTPUT
CARD(2AI/2AO)
MICROLOGIX 11OO
1763-L16AWA
C
0
1
2
3
C
4
5
6
7
8
9
IA
I1
I2
C
0
1
2
3
4
5
FURNISH CONTROLLER WITH
MEMORY MODULE. (1763-MM1)
TO UPS
3PT. LATCH
SIZE: 30"H X 30"WX 20"DMINIMUM
PAINT INSIDE: GLOSS WHITE
PAINT OUTSIDE: SHERMAN WILLIAMS PILLAR WHITE (SW-4023)
PUSHBUTTON
FOR
STATION
MAINTENANCE
MICROLOGIX
1100
2
X
4
D
U
C
T
2
X
4
D
U
C
T
ETHERNET
SURGE
PROTECTION
LOOP POWER - 2 WIRE
TRANSMITTER POWER
DINRAIL MOUNTEDBREAKERS
THIS AREA.
FUSIBLE TERMINAL BLOCKS.
120VAC FROMEXISTING LIGHTING PANEL BOARD
1762-IF2OF2
24VDC
+ -
H1 N
SPARE
SPARE
NEWPRESSURE
TRANSMITTER
POWER ON
COOLING FAN
1. LOCATE THE NEWPRESSURE MONITORING PANEL ON THE BACK SIDE OF THE
BUILDING.
2. MOUNT PANEL ON STAINLESS STEEL STRUT SUPPORT RACK.
3. INSTALL A 20 FOOT , 2 INCH DIAMETER ALUMINUMMAST PIPE, YAGI ANTENNA, AND
25 FEET OF LMR CABLE.
4. SUPPORT PIPE TO SIDE OF PANEL ANDBRICK BUILDING WITH STAINLESS STEEL
STRUT ANDSUPPORT HARDWARE.
5. WEATHERPROOF THE CABLE ENDS AT THE TOP ANDBOTTOM.
6. INSTALL A 10 FOOT COPPER GROUNDROD, ANDBONDTO PANEL ANDMAST PIPE
WITH GREEN INSULATEDNO.6 AWG CONDUCTOR.
7. CORE HOLE THRU WALL FOR TWO ONE INCH CONDUITS. ONE CONDUIT FOR
120VAC POWER, ANDONE CONDUIT FOR THE SHIELDEDCABLE.
8. WITHIN THE BUILDING, CONNECT TO SPARE 120VAC PANELBOARDFOR POWERING
PANEL. ASSUME 20 FEET OF [ INCH PLASTIC CONDUIT, WITH 3#12 WIRES. LABEL
PANELBOARDDIRECTORY FOR NEWPANEL.
9. WITHIN THE BUILDING, FURNISH ANDINSTALL ONE YOKOGAWA EJ A SERIES
PRESSURE TRANSMITTER RANGED0-150PSI. TRANSMITTER WETTEDPARTS AND
TO BE HASTELLOY C ANDMANIFOLDTO BE STAINLESS STEEL. FURNISH
MOUNTING BRACKET AS REOUIREDFOR TRANSMITTER. REMOVE EXISTING
TRANSMITTER, ANDREWORK EXISTING SENSING LINE. ASSUME FOR
INSTALLATION OF 5 FEET OF INCH COPPER TUBING. PROVIDE BRASS BALL
SHUTOFF VALVE AT TRANSMITTER.
10.INSTALL 15 FEET OF [ INCH PLASTIC CONDUIT WITH 2/C#18SH CABLE FROMTHE
TRANSMITTER TO THE NEWPROCESSOR PANEL.
11.SEAL HOLES IN WALL WITH NON-SHRINK GROUT.
12.CONDUIT AT THIS LOCATION TO BE PVC SCHEDULE 40.