Professional Documents
Culture Documents
1-#4 TOP AND BOTTOM, TYPICAL REFER TO SCHEDULE 2" TYPICAL CONSTRUCTION JOINT EQUAL A NOTES: 1. WHERE CLEAR SPACING BETWEEN ADJACENT SLEEVES IS LESS THAN 3", THE SLEEVE GROUP SHALL BE TREATED AS AN EQUIVALENT RECTANGULAR OPENING WITH LENGTH "L" AND WIDTH "W" AS SHOWN. 2. WHERE CLEAR SPACING BETWEEN ADJACENT SLEEVES IS GREATER THAN OR EQUAL TO 3", SCHEDULED SLAB BAR REINFORCEMENT SHALL BE OFFSET AS REQUIRED TO MISS SLEEVES. 3. REINFORCEMENT SHOWN IS IN ADDITION TO SCHEDULED SLAB REINFORCEMENT. 4. SCHEDULED SLAB MESH REINFORCEMENT MAY BE CUT AS REQUIRED TO MISS PIPE SLEEVES. 5. REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR LOCATION AND SIZE OF SLEEVES. 6. ISOLATED PIPE SLEEVES THAT ARE SMALLER THAN 5" AND DO NOT INTERRUPT REINFORCEMENT DO NOT REQUIRE THE USE OF THIS DETAIL. 7. THIS DETAIL SHOULD NOT BE USED FOR OPENING GROUPS WITH DIAMETERS LARGER THAN 12". CONSULT STRUCTURAL ENGINEER FOR FRAMING OF SUCH CONDITIONS. 8. PROVIDE HALF OF INTERRUPTED REINFORCEMENT PLUS ONE ADDITIONAL BAR OF SAME SIZE ON EACH SIDE OF EQUIVALENT RECTANGULAR OPENING. PROVIDE A MINIMUM OF 1-#4 TOP AND BOTTOM EACH SIDE OF OPENING. ADDITIONAL REINFORCEMENT, REFER TO SCHEDULE BELOW EQUAL SCHEDULED SLAB REINFORCEMENT CONTINUOUS THROUGH JOINT T/2 T/2 P1 h1 SLAB SURFACE PROFILE
10'-0" (120") P2
REFER TO NOTE 1 1-#4 CONTINUOUS AT PERIMETER WITH 1-#4x4'-0" AT EXTERIOR CORNERS AND 1-#4x4'-0" DIAGONAL AT RE-ENTRANT CORNERS 2'-0" 2'-0"
4' -0 "
TOP REINFORCEMENT, REFER TO SCHEDULE BOTTOM REINFORCEMENT, WHERE SCHEDULED 3/4" CHAMFER, TYPICAL
2'-0"
SLAB-ON-GRADE, REFER TO PLAN FOR THICKNESS AND REINFORCEMENT AND REFER TO SPECIFICATIONS FOR CURING METHOD VAPOR RETARDER DIRECTLY BELOW SLAB
DATUM
12"
0
P1 d2 h2
0
EXTERIOR CORNERS
RE-ENTRANT CORNERS
2'-0"
0
h1
0
z = MEAN VALUE OF ALL x FLOOR READINGS Sz = STANDARD DEVIATION OF ALL z FLOOR READINGS q = MEAN VALUE OF ALL q FLOOR READINGS Sq = STANDARD DEVIATION OF ALL q FLOOR READINGS
NOTES: 1. CONSTRUCTION JOINTS SHOULD BE LOCATED ON THE MIDDLE THIRD OF THE SLAB SPAN. 2. CONCRETE SURFACE AT CONSTRUCTION JOINT SHALL BE CLEAN AND FREE OF LAITANCE. 3. DO NOT USE FOR POST-TENSIONED SLABS.
3. 4.
FL AND F F SHALL BE STATISTICALLY DETERMINED ACCORDING TO ASTM E 1155 "STANDARD TEST METHOD FOR DETERMINING FLOOR FLATNESS AND LEVELNESS USING THE F-NUMBER SYSTEM." REFER TO CONCRETE SPECIFICATIONS FOR REQUIRED FL AND F F VALUES
NOTES: 1. REFER TO ARCHITECTURAL, STRUCTURAL, OR MEP DRAWINGS FOR HOUSEKEEPING PAD PLAN DIMENSIONS AND THICKNESS (4" MINIMUM THICKNESS). 2. CONTRACTOR SHALL COORDINATE DIMENSIONS AND OTHER SPECIAL REQUIREMENTS WITH EQUIPMENT MANUFACTURERS AND PROVIDE WHERE REQUIRED WHETHER SHOWN ON STRUCTURAL DRAWINGS OR NOT.
2
6"
PER
REFER TO PLAN TOP OF CAP SCHEDULED BEAM TOP AND BOTTOM REINFORCEMENT. DO NOT DISCONTINUE AT CONSTRUCTION JOINT 1" CLEAR CONSTRUCTION JOINT LOCATION FORMED SHEAR KEY (HORIZONTAL) 2" 3" 2" 3" 2'-6 "
EQUAL
B/2 + Ld
" -6 2'
TURN GRADE BM DOWN TO TOP OF PILE CAP WHERE TOP OF PILE CAP IS BELOW BOT OF GRADE BM #4 DOWELS @12" CENTERED IN GRADE BM
3"
BEAM
0"
AT NEW PILE CAP PROVIDE CORNER BARS TOP AND BOTTOM. PROVIDE CORNER BARS FOR EACH LAYER OF BEAM REINFORCING SPECIFIED REFER TO PLAN TOP OF SLAB 6" PER SCHED
0
REFER TO PLAN TOP OF SLAB REFER TO PLAN TOP OF GRADE BEAM SCHEDULED STIRRUPS SCHEDULED REINFORCING
1 1/2" CLEAR
0"
30 <= A <= 150 PROVIDE STANDARD 90 END HOOKS FOR TOP STEEL INSIDE TOP STEEL OF SUPPORT BEAMS
0
ADDITIONAL DOWELS, USE 2-#5x4'-0" TOP AND BOTTOM UNLESS REQUIRED OTHERWISE BY NOTE 3 OR 4
PROVIDE (1) ADDITIONAL BEAM STIRRUP EACH SIDE OF CONSTRUCTION JOINT AND EACH END OF ADDITIONAL DOWELS (NOT SCHEDULED)
A SLAB REINFORCEMENT, TYPICAL NOTES: 1. GENERAL CONTRACTOR SHALL SUBMIT DESIRED CONSTRUCTION JOINT LAYOUT AS A SHOP DRAWING FOR APPROVAL A MINIMUM OF TWO WEEK PRIOR TO POUR. 2. CONSTRUCTION JOINT LOCATIONS SHALL BE COORDINATED WITH REINFORCING STEEL SUPPLIER AND ERECTOR. 3. ACCEPTABLE JOINT LOCATIONS ARE AS FOLLOWS: a. FOR BEAMS NOT SUPPORTING INTERSECTING BEAMS: PLACE JOINT MIDDLE THIRD OF SPAN. b. FOR BEAMS SUPPORTING INTERSECTING BEAMS, CHECK WITH STRUCTURAL ENGINEER. 4. FOR JOINT LOCATIONS OTHER THAN WITHIN MIDDLE THIRD OF SPAN, CONTRACTOR SHALL COORDINATE REQUIRED ADDITIONAL REINFORCEMENT WITH THE ENGINEER ON THE SHOP DRAWINGS. TURN GRADE BM DOWN TO TOP OF PILE CAP WHERE TOP OF PILE CAP IS BELOW BOT OF GRADE BM NOTES: 1. GRADE BEAMS SHALL BE POURED MONOLITHICALLY AROUND CORNERS. REFER TO TYPICAL GRADE BEAM CONSTRUCTION JOINT DETAIL FOR ACCEPTABLE CONSTRUCTION JOINT LOCATIONS. NOTES: 1. GRADE BEAMS SHALL BE POURED MONOLITHICALLY AT INTERSECTIONS. REFER TO TYPICAL GRADE BEAM CONSTRUCTION JOINT DETAIL FOR ACCEPTABLE CONSTRUCTION JOINT LOCATIONS. #4 DOWELS @12" CENTERED ON GRADE BM DRILL AND EPOXY 8" INTO EXIST PILE CAP WITH HILTI HIT RE 500-SD ADHESIVE AT EXISTING PILE CAP
A/2 + Ld
PROVIDE HALF OF INTERRUPTED REINFORCEMENT PLUS ONE ADDITIONAL BAR OF SAME SIZE ON EACH SIDE OF OPENING
NOTES: 1. WHERE GRADE BEAMS OF UNEQUAL DEPTH FRAME TO THE SAME SUPPORT, TOP OF SUPPORT SHALL BE AT THE BOTTOM OF THE DEEPEST GRADE BEAM. 2. REFER TO GENERAL NOTES FOR CLEAR COVER AT SIDES, TOP AND BOTTOM OF BEAM.
12
11
10
CL COLUMN AND CAP, UNLESS NOTED OTHERWISE 1 ADDITIONAL SET OF TIES AT EACH END OF LAP SPLICE 2'-0" TYPICAL 4" MINIMUM CLEAR REFER TO PLAN TOP OF SLAB VERTICAL SLEEVES COMPACTED SUBGRADE OVER CAP B/3 4" MINIMUM FACE OF COLUMN ADDITIONAL REINFORCEMENT, REFER TO SECTION SCHEDULED BEAM REINFORCEMENT NOTES: 1. GENERAL CONTRACTOR SHALL COORDINATE REQUIRED BEAM SLEEVES WITH MECHANICAL, ELECTRICAL, AND PLUMBING CONTRACTORS. REQUIRED SLEEVES MAY OR MAY NOT BE SHOWN ON THE STRUCTURAL DRAWINGS. GENERAL CONTRACTOR SHALL SUBMIT PLAN SHOWING LAYOUT OF ALL SLEEVES WITH FORMWORK SHOP DRAWING SUBMITTAL. 2. SLEEVES SHALL BE LOCATED WITHIN THE MIDDLE THIRD OF THE SCHEDULED BEAM WIDTH. 3. CONTINUOUS BEAM REINFORCEMENT MAY BE SLIGHTLY DISPLACED (3" MAXIMUM) OR ADJACENT BARS BUNDLED (2 BAR BUNDLES MAXIMUM) TO FACILITATE SLEEVE INSTALLATION. DO NOT CUT, OFFSET, OR BEND REINFORCEMENT. 4. SLEEVES OCCURRING ON OPPOSITE SIDES OF A COLUMN MUST BE IN LINE. 5. THE OUTSIDE DIAMETER OF A SLEEVE MAY NOT EXCEED 15% OF THE SCHEDULED WIDTH OF THE BEAM THROUGH WHICH IT MUST PASS. 6. THE CONTRACTOR SHALL CONTACT THE ENGINEER OF RECORD WHEN A SLEEVE SIZE OR LOCATION DOES NOT MEET THE ABOVE CONDITIONS. 7. SCHEDULED BEAM STIRRUPS NOT SHOWN FOR CLARITY. PENETRATION HEIGHT D/3 D/3 MINIMUM MINIMUM NOTES: 1. GENERAL CONTRACTOR SHALL COORDINATE LOCATION, SIZE, AND ELEVATION AND INCLUDE IN HIS CONTRACT PRICE ALL REQUIRED HORIZONTAL PENETRATIONS THROUGH CONCRETE BEAMS WHETHER SHOWN ON STRUCTURAL DRAWINGS OR NOT. 2. WHERE BEAM PENETRATIONS ARE REQUIRED BUT ARE NOT SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS, CONTRACTOR SHALL SUBMIT DRAWINGS SHOWING DIMENSIONS AND LOCATIONS OF ALL REQUIRED PENETRATIONS FOR REVIEW AND APPROVAL. 3. "D" DENOTES THE DEPTH OF BEAM. 4. CLEAR SPACING BETWEEN PENETRATIONS SHALL BE 24" MINIMUM UNLESS NOTED OTHERWISE BY THE STRUCTURAL ENGINEER. 5. PENETRATIONS SHALL BE LOCATED ACCORDING TO THE FOLLOWING CRITERIA: a. FOR BEAMS NOT SUPPORTING INTERSECTING BEAMS LOCATE PENETRATIONS WITHIN TWO FEET EITHER SIDE OF BEAM MIDSPAN. b. FOR BEAMS SUPPORTING INTERSECTING BEAMS CHECK WITH STRUCTURAL ENGINEER. 6. PENETRATION WIDTH MUST NOT EXCEED PENETRATION HEIGHT, UNLESS NOTED OTHERWISE ON THE STRUCTURAL DRAWINGS. 7. FOR LOCATIONS AND/OR SIZES OF PENETRATIONS NOT CONFORMING TO THE ABOVE CRITERIA AND NOT OTHERWISE DETAILED ON THE STRUCTURAL DRAWINGS, CONTRACTOR SHALL COORDINATE REQUIRED ADDITIONAL REINFORCEMENT WITH THE STRUCTURAL ENGINEER. 8. PROVIDE THE FOLLOWING REINFORCEMENT AT EACH SLEEVE, UNLESS NOTED OTHERWISE ON THE STRUCTURAL DRAWINGS: 1-#5 TOP AND BOTTOM AT BEAMS WITH WIDTHS LESS THAN 9". 2-#5 TOP AND BOTTOM AT BEAMS WITH 2-LEG STIRRUPS. 4-#5 TOP AND BOTTOM AT BEAMS WITH 4-LEG STIRRUPS. "N"-#5 TOP AND BOTTOM AT BEAMS WITH "N"-LEG STIRRUPS. 9. PROVIDE ADDITIONAL STIRRUPS ABOVE AND BELOW PENETRATIONS AT SPACING NOT TO EXCEED ONE THIRD OF THE SCHEDULED STIRRUP SPACING, UNLESS DETAILED OTHERWISE ON THE STRUCTURAL DRAWINGS. 10. SCHEDULED BEAM STIRRUPS NOT SHOWN FOR CLARITY.
3"
0"
3" MAXIMUM
PLAN
BEAM TOP AND BOTTOM REINFORCEMENT
PROVIDE (2) ADDITIONAL STIRRUPS EACH SIDE OF EACH PENETRATION TO MATCH SCHEDULED BEAM STIRRUPS REFER TO NOTE 9 MINIMUM PENETRATION HEIGHT SQUARE OR RECTANGULAR PENETRATION
CAP THICKNESS
SCHEDULED
REFER TO PLAN TOP OF CAP SCHEDULED CAP REINFORCEMENT, REFER TO TYPICAL CAP DETAIL
0"
B/3
VERTICAL SLEEVE
BEAM DEPTH, D
B/3
D/3
D/3
REFER TO TYPICAL CAP DETAIL COLUMN BELOW SCHEDULED COLUMN DOWELS WITH STANDARD HOOKS SUPPORTED ON CAP BOTTOM REINFORCEMENT CONCRETE PILES, REFER TO OTHER DETAILS FOR LAYOUT ADDITIONAL TIES AROUND DOWELS, TOP AND BOTTOM PROVIDE ONE SET OF ADDITIONAL STIRRUPS ON EACH SIDE OF SLEEVE (NOT SCHEDULED)
MINIMUM
D/3
D/3
PLAN
EDGE OF BEAM OR GIRDER BELOW
SECTION
PROVIDE ADDITIONAL 2-#5 ON EACH SIDE OF BEAM CENTERED ON SLEEVE, EXTEND 2'-0" MINIMUM EACH WAY PAST SLEEVE
D/3
17
B
2" TYPICAL 1 1/2" CLEAR 2'-0" MINIMUM TYPICAL PENETRATION WIDTH, REFER TO NOTE 6
ELEVATION
2" TYPICAL 1 1/2" CLEAR 2'-0" MINIMUM TYPICAL PENETRATION WIDTH, REFER TO NOTE 6
16
14
TOP OF PILE SLAB ON GRADE, REFER TO PLAN ds hs hwash hnut OVERRUN SLAB REINFORCING PER PLAN SLAB ON GRADE, REFER TO PLAN La da hnom hc dc 6" ds hs ds hs hs hwash hnut OVERRUN
hnom
La
da La hc dc
da hc dc hnom
8"
8"
EQ
EQ
8"
SLAB TURNDOWN AROUND EXIST PILE CAP/GRADE BM La > La,min = hnom + hs + hwash + hnut + OVERRUN EXPANSION AND UNDERCUT La > La,min = hnom + hs SCREW La > La,min = hnom + hs + hwash + hnut + OVERRUN ADHESIVE
6"
1'-0"
EQ
EQ
1'-0" PILE
2'-2" 2'-10"
da = dc = ds = La,min = La =
DIAMETER OF ANCHOR (IN) DIAMETER OF HOLE IN CONCRETE = DIAMETER OF DRILL BIT (IN) DIAMETER OF HOLE IN STEEL ATTACHMENT (IN) MINIMUM LENGTH OF ANCHOR (IN) ORDERED LENGTH OF ANCHOR (IN)
hnom = NOMINAL EMBEDMENT DEPTH (IN) hc = DEPTH OF HOLE IN CONCRETE (IN) hs = THICKNESS OF STEEL ATTACHMENT (IN) hwash = THICKNESS OF WASHER (IN) hnut = HEIGHT OF HEX NUT (IN) OVERRUN =1/4" UNLESS NOTED OTHERWISE
23
Printed on 30% Post-Consumer Recycled Content Paper
22
5
CONTRACTOR AND INSTALLER NOTES: 1. ONLY POST-INSTALLED ANCHOR PRODUCTS SPECIFIED IN THE CONTRACT DOCUMENTS SHALL BE USED WHERE SPECIFIED IN THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL PROVIDE SIGNED AND SEALED CALCULATIONS TO THE ENGINEER OF RECORD (EOR) FOR ANCHOR PRODUCTS SUBSTITUTED FOR THOSE INDICATED IN THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE EOR PRIOR TO USING POST-INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN ANCHORS AND REINFORCEMENT. 2. ANCHOR LENGTHS SPECIFIED IN THE CONTRACT DOCUMENTS INDICATE THE NOMINAL EMBEDMENT DEPTH . REFER TO THE ANCHOR TYPE FOR THE DEFINITION OF NOMINAL EMBEDMENT DEPTH 'hnom'. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE CORRECT ANCHOR LENGTH 'La' FOR ORDER BASED ON THE SPECIFIED NOMINAL EMBEDMENT DEPTH, ATTACHMENT THICKNESS AND OTHER ANCHOR CHARACTERISTICS NOTED. 3. MINIMUM ANCHOR LENGTH 'La,min' IS DETERMINED AS SHOWN FOR EACH ANCHOR. ORDER AND INSTALL AN ANCHOR LENGTH EQUAL TO OR GREATER THAN THIS VALUE. INSTALLED ANCHOR LENGTHS SHALL NOT HAVE NOMINAL EMBEDMENT DEPTHS THAT EXCEED THEIR CORRESPONDING MINIMUM CONCRETE THICKNESS LIMITS. REFER TO ANCHOR'S ICC-ES EVALUATION SERVICE REPORT (ESR). 4. REFER TO THE ANCHOR'S ICC-ES EVALUATION SERVICE REPORT (ESR) FOR DRILL BIT TYPE AND DIAMETER, AND DEPTH OF HOLE TO BE DRILLED IN THE CONCRETE. 5. FOLLOW THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII).
6.
7. 8. 9.
PRIOR TO STEEL FABRICATION OR DRILLING OF EXISTING CONCRETE LOCATE EXISTING REINFORCING STEEL AND PRESTRESSING STRANDS (IF APPLICABLE) USING GROUND PENETRATING RADAR (GPR) OR EQUIVALENT NON-DESTRUCTIVE METHODS. COORDINATE HOLE LOCATIONS TO AVOID EXISTING REINFORCING STEEL. IF RESULTING ANCHOR OR REBAR PATTERN DIFFERS FROM THAT SHOWN ON THE CONTRACT DOCUMENTS, FORWARD EACH NEW PATTERN TO THE ENGINEER FOR REVIEW AND APPROVAL. AFTER APPROVAL, FABRICATE CONNECTIONS, ANGLES OR PLATES AFTER ANCHORS HAVE BEEN INSTALLED TO MATCH AS-BUILT ANCHOR PATTERN. CORING OF CONCRETE TO INSTALL ANCHORS OR REBAR IS NOT ALLOWED. HAMMER DRILLING IS THE ONLY APPROVED METHOD FOR INSTALLING ANCHORS OR REBAR INTO HARDENED CONCRETE. HOLES THAT HAVE BEEN DRILLED INTO EXISTING CONCRETE BUT ABANDONED SHALL BE FILLED WITH EPOXY PER SPECIFICATION 03 30 00. HOLES SHALL BE PREPARED PER MANUFACTURERS INSTRUCTIONS PRIOR TO EPOXY INJECTION. SEE SPECIFICATIONS 033000 AND 014529 FOR ADDITIONAL INFORMATION REGARDING POST-INSTALLED ANCHOR AND REBAR INSTALLATION AND REQUIRED INSPECTIONS.
21
4
2
2"
0
3
A
6
" -6 2'
PROJECT
NEW ORLEANS ARENA ENHANCEMENTS 2012 ARENA RENOVATION & EXPANSION LSED # NOA-ENH-2012-AFC35.4M
New Orleans Arena 1501 Girod Street New Orleans, LA 70113
CLIENT
LOUISIANA STADIUM AND EXPOSITION DISTRICT
1500 Girod Street New Orleans, LA 70112
ARCHITECTS
AECOM LOUISIANA, A PROFESSIONAL CORPORATION
2380 McGee Suite 200 Kansas City, Missouri 64108 816.561.4443 tel 816.561.2863 fax www.aecom.com
ESKEW+DUMEZ+RIPPLE
365 Canal Street Suite 3150 New Orleans, LA 70130 504.561.8686 tel 504.522.2253 fax www.eskewdumezripple.com
MANNING ARCHITECTS
650 Poydras Street Suite 1250 New Orleans, LA 70130 504.412.2000 tel 504.412.2001 fax www.manningarchitects.com
CONSULTANTS
CIVIL AECOM
232 Third Street, Suite 201 Baton Rogue, LA 70801 225.663.4309 tel www.aecom.com
CENTERLINE BEAM AND FOOTING TO COINCIDE UNLESS NOTED OTHERWISE POUR SLAB DOWN ONTO TOP OF GRADE BEAM
LANDSCAPE AECOM
1360 Peachtree Street NE Suite 500 Atlanta, GA 30309 404.965.9627 tel www.aecom.com
REGISTRATION
CONFORMED SET
ADDENDUM #7 DESCRIPTION
KEY PLAN
PROJECT NORTH
PROJECT NUMBER
60263613
SHEET TITLE
FOUNDATION TYPICAL DETAILS AND SCHEDULES
SHEET NUMBER
S0.00.10