COOLING WATER SYSTEM Sl. No.

Features CONDENSER COOLING WATER SYSTEM Description Remarks

CW PUMPS

The CW system envisaged for the plant is re-circulating type with cooling towers. Water from CW sump will be pumped out by 3x50% pumps through pipes up to the condenser and from condenser to the cooling tower. COC 1.5 Number of Pumps: 3x50% Capacity of Pump: Total Head: 26 MWC

Design water temperature: Maximum water temperature: Minimum water temperature : Hot water temperature : Discharge elbow/column pipe Bowl/suction bell Impeller Impeller shaft Line shaft and head shaft Shaft couplings Water velocity RUBBER EXPANSION JOINT

33 deg C 36 deg C. 15 deg C. 42 deg C at 33 deg C inlet SS Gr.316L with polyglass coat ASTM A995 Gr.CD4 MCuN ASTM A995 Gr.CD4 MCuN ASTM A276 UNS S31803 ASTM A276 type 410 SS410

at pump suction shall not exceed 1m/sec and at pump discharge shall be between 2 - 2.5m/sec. Quantity: 3 nos at pump discharge 4 nos at Condenser inlet & outlet 1 no at Cooling Tower end Type Restrained type with three (3) tie rods Pressure Vacuum (0.1 kg/cm2 (abs) and 5 kg/ cm2 (g) Design temperature 600C Bellow High grade natural rubber compound with neoprene compound outer and inner

Sl. No.

Features

Description

Remarks

MOTOR OPERATED BUTTERFLY VALVES

No. off : Type : Max Flow Rate : Valve Classification Code : Basic Design Code Body : Valve Disc : Stem :

Eight nos Butterfly type, motor / Hydraulic operated DIBF BS 5155 ASTM A 536 Gr. 65-45-12 ASTM A 536 Gr. 65-45-12 + Rubber lined ASTM A 276T420