You are on page 1of 7

Dimensional drawings Installation of cable termination

Minimum air gap


Max voltage kV 10 12 24 36 Phase to earth A 90 120 220 320 Indoor Phase to phase B 90 120 250 370 Phase to phase C 10 10 30 50 Outdoor Phase to earth A 130 160 270 380 Phase to phase B 130 160 270 380

Minimum air gap between cores* in parallel


10 kV C 10 mm 12 kV 10 mm 24 kV 30 mm 36 kV 50 mm

* The cable terminations must be placed in the same height.

Cable accessories for XLPE-insulated cables 12-42 kV | Kabeldon cable accessories 1420 kV |

3/4

Premolded cable termination, indoors SOT 7.2 kV

Use Premolded cable termination for XLPE- and EPR-insulated cables 1- or 3-core with Al or Cu conductor for 6.6/7.2 kV, indoors. It can also be installed in an indoor humid environment*.

3
Standards Meets the requirements of: CENELEC, HD 629.1 S1 Design Premolded cable termination made of silicone rubber with integrated field control. The length of the termination is approximate 145 mm which also makes it suitable for installations in narrow spaces. The termination is supplied in kits for 3 single-core cables. Note: Cable lugs are to be ordered separately. Branch seal TSH for 3-core cable is to be ordered separately.

145

Always select products by Insulation diameter.


* For the best watertightness in an indoor humid environment, order branch seal kit TSH. See page 3/46.

Insulation diameter mm 3-core / three 1-core 10.515 12.925.8 21.434.9

Conductor cross section mm 1035 50185 185500

Designation

Conductor cross section mm

Weight kg/kit 0.2 0.2 0.2

SOT 1013 SOT 102-3 SOT 103-3

1035 50185 185500

3/5 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 12-42 kV

Min

200

Premolded cable termination, indoors and outdoors, complete SOT SCL 1236 kV

Use Premolded cable termination for XLPE- and EPR-insulated 1- or 3-core cable with Al- or Cu- conductor for 1236 kV. The indoor termination can also be installed in a humid indoor environment*.

3
Standard Fulfills requirements of: SS 424 14 45 edition 1 IEEE 48 1996 CENELEC HD 629.1 Design Premolded cable termination made of silicone rubber with integrated field control and top sealing. The outdoor type is provided with permanent sheds for extended creepage distance. The cable termination is supplied in kits for 1- or 3-core cables. The kits include: Bi-metalic shear-off cable lugs SCL-B for Al- and Cuconductor. The cable lug has bolts which breaks off once the correct torque is reached. Branch seal and protective heat-shrink hoses in kits for outdoor, 3-core cables.
* For the best watertightness in an indoor humid environment, order branch seal kit TSH. See page 3/46.

SOT 1- and 3-core outdoor.

SOT 1- and 3-core indoor.

Always select products by Insulation diameter.

Insulation diameter mm 1115 1526 2439 2439 3854 1115 1524 2233 3140 2639 1524 2233 3140 3854 2639 3854

Conductor cross section 12 kV 24 kV mm 1035 50150 185300 400500 630 1035 50150 185300 400630 1035 50150 185300 400630 1016 2595 120300 400 500630 1016 2595 120300 400630 1016 2595 120300 400630 70300 70300 400630 36 kV

Designation

weight kg/kit

Designation

weight kg/kit

3-core / 3 x 1-core indoor SOT 241 A-3 SCL2 SOT 2413 SCL3 SOT 242-3 SCL5 SOT 242-3 SCL6 SOT 242 B-3 SCL6 3-core outdoor SOT 243 A-3 SCL2 SOT 243-3 SCL3 SOT 244-3 SCL5 SOT 245-3 SCL6 3-core indoor/outdoor SOT 3613 SCL5 3 x 1-core outdoor SOT 243 A-31 SCL2 1.10 SOT 243-31 SCL3 1.65 SOT 244-31 SCL5 2.15 SOT 245-31 SCL6 4.20 3 x 1-core indoor/outdoor SOT 36131 SCL5 SOT 362-31 SCL6 2.45 4.30 0.90 1.35 1.80 3.40 3.60 2.20 2.55 3.05 5.20 3.10

1-core indoor SOT 241 A SCL2 SOT 241 SCL3 SOT 242 SCL5 SOT 242 SCL6 SOT 242 B SCL6 1-core outdoor SOT SOT SOT SOT 243 243 244 245 A SCL2 SCL3 SCL5 SCL6 1-core indoor/outdoor SOT 361 SCL5 SOT 362 SCL6 0.30 0.45 0.60 1.15 1.20 0.40 0.55 0.70 1.40 0.82 1.45

Cable accessories for XLPE-insulated cables 12-42 kV | Kabeldon cable accessories 1420 kV |

3/6

Premolded cable termination, indoors and outdoors SOT 1236 kV

Use Premolded cable termination for XLPE- and EPR-insulated cables 1- or 3-core with Al or Cu conductors for 1236 kV. The indoor termination can also be installed in a humid indoor environment*.

3
Standard Meets the requirements of: CENELEC, HD 629.1 S1 IEEE 48 1996 Design Premolded cable termination made of silicone rubber with integrated field control and top sealing. The outdoor type is provided with permanent sheds for extended creepage distance. The termination is supplied in kits for 1- or 3-core cables. 3-phase kits for outdoor use include branch seal and protective heat-shrink hoses.
* For the best watertightness in an indoor humid environment, order branch seal kit TSH. See page 3/46.

SOT 1- and 3-core outdoor.

SOT 1- and 3-core indoor.

Note: Cable lugs are to be ordered separately. Always select products by Insulation diameter.

Insulation diameter mm 1115 1526 1526 2439 1115 1526 2439 3854 1115 1524 2233 3140

Conductor cross section 12 kV 24 kV mm 1035 5095 120185 185400 1035 50185 185500 630** 1035 50150 150300 400500 1016 2550 70120 150400 1016 25120 150400 500630** 1016 2570 95240 300400 2570 95240 300400 500630* 70300 400630* 36 kV

Designation

Weight

Designation

Weight kg/kit

1524 2233 3140 3854 2639 3854

50150 150300 400500 500630**

kg/kit Indoor termination incl. branch seal for 3-core SOT 241A-3C 0.9 SOT 2413C 0.9 SOT 2413D 1.3 SOT 242-3D 1.4 Indoor termination 3-core / 3 x 1-core SOT 241 A-3 0.60 SOT 2413 0.60 SOT 242-3 0.70 SOT 242 B-3 0.90 Outdoor termination incl. branch seal for 3-core SOT 243 A-3 1.90 SOT 243-3 1.80 SOT 244-3 2.00 SOT 245-3 2.50 Indoor/outdoor termination 3-core SOT 3613 Outdoor termination 3 x 1-core SOT 243-31 0.80 SOT 244-31 0.90 SOT 245-31 1.11 SOT 246-31 1.50 Indoor/outdoor termination 3 x 1-core SOT 36131 1.40 SOT 362-31 1.60

Indoor termination 1-phase kit SOT 241 A 0.20 SOT 241 0.19 SOT 242 0.23 SOT 242 B 0.30 Outdoor termination 1-phase kit SOT 243 A 0.31 Indoor/outdoor termination 1-phase kit Outdoor termination 1-phase kit SOT 243 0.27 SOT 244 0.30 SOT 245 0.38 SOT 246 0.51 Indoor/outdoor termination 1-phase kit SOT 361 0.42 SOT 362 0.52

* Can be mounted on cables with 800 and 1000 mm by using silicone rubber tape IA 2342 (1 per kit) as top seal, see page 5/3.

3/7 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 12-42 kV

Premolded cable termination for cables with Cu-tape screen SOT 7.236 kV

Use Premolded cable termination for XLPE- and EPR-insulated 1-core cables with Al or Cu conductors and Cu-tape screen for 7.236 kV. The indoor termination can also be installed in a humid indoor environment*.

3
Standard Meets the requirements of: CENELEC HD 629.1 S1 IEEE 48 1996 Design Premolded cable termination made of silicone rubber with integrated field control and top sealing. The outdoor type is provided with permanent sheds for extended creepage distance. The indoor termination can also be installed in a humid indoor environment. The kits includes copper braids and constant force springs for connection of the Cu-tape screen to earth. One kit includes material for three single core terminations.
* For the best watertightness in an indoor humid environment, order branch seal kit TSH. See page 3/46.

Note: Cable lugs are to be ordered separately.

Always select products by Insulation diameter.


Insulation diameter mm 10.515 12.925.8 21.534.9 1115 1526 1526 2439 2439 2639 2639 1115 1524 1524 2233 2233 3140 2639 2639 1650 70185 240400 500630 2550 70185 240400 500630 1635 50120 150185 185240 300630 1635 50150 185240 300400 500630 7.2 kV Conductor cross section 12 kV 17.5 kV mm 2595 120185 240500 25120 150185 240300 400500 35120 150400 3570 95120 150240 300400 70185 240300 70185 240300 SOT 1013 R SOT 102-3 R SOT 103-3 S SOT 241A-3 R SOT 241-3 R SOT 241-3 S SOT 242-3 S SOT 242-3 T SOT 361-3 T SOT 361-3 U SOT 243A-3 R SOT 243-3 R SOT 243-3 S SOT 244-3 S SOT 244-3 T SOT 245-3 T SOT 361-3 T SOT 361-3 U 24 kV 36 kV Designation Size of copper braid mm 10 10 22 10 10 22 22 22 22 35 10 10 22 22 22 22 22 35
3/8

Indoor termination for three 1-core cables with Cu-tape screen

Outdoor termination for three 1-core cables with Cu-tape screen

Cable accessories for XLPE-insulated cables 12-42 kV | Kabeldon cable accessories 1420 kV |

Premolded cable termination for cables with Cu-tape screen SOT 7.236 kV

Use Premolded cable termination for XLPE- and EPR-insulated cables 3-core with Al or Cu conductors and Cu-tape screen for 7.236 kV.

Standard Meets the requirements of: CENELEC HD 629.1 S1 IEEE 48 1996 Design Premolded cable termination made of silicone rubber with integrated field control and top sealing. The outdoor type is provided with permanent sheds for extended creepage distance. The indoor termination can also be installed in a humid indoor environment. The kits includes Cu-braids and constant force springs for connection of the Cu-tape screen to earth. The kits also include branch seal and protective hoses of heat-shrink type. Note: Cable lugs are to be ordered separately.

Always select products by Insulation diameter.


Insulation diameter mm 10.515 12.925.8 12.925.8 21.434.9 1115 1526 1526 1526 2439 2439 2639 2639 1115 1524 1524 1524 2233 2533 3140 2639 2639 1650 70 95185 240400 2550 70 95185 240400 1635 50 70120 150185 185240 300400 1635 50 70150 185240 300400 7.5 kV Conductor cross section 12 kV 17.5 kV mm 2535 5095 120150 185 240400 2535 50120 150185 240400 35120 150400 3570 95120 150400 300400 70185 240300 70185 240300 SOT 1013 RC SOT 102-3 RC SOT 102-3 RD SOT 103-3 SD SOT 241A-3 RC SOT 2413 RC SOT 2413 RD SOT 2413 SD SOT 242-3 SD SOT 242-3 TD SOT 3613 TB SOT 3613 UB SOT 243A-3 RA SOT 243-3 RA SOT 243-3 RB SOT 243-3 SB SOT 244-3 SB SOT 244-3 TB SOT 245-3 TB SOT 3613 TB SOT 3613 UB 24 kV 36 kV Designation Size of Cu-braid mm 3 x 10 3 x 10 3 x 22 3 x 22 3 x 10 3 x 10 3 x 10 3 x 22 3 x 22 3 x 22 3 x 22 3 x 35 3 x 10 3 x 10 3 x 10 3 x 22 3 x 22 3 x 22 3 x 22 3 x 22 3 x 35

Indoor termination for 3-core cables with Cu-tape screen

Outdoor termination for 3-core cables with Cu-tape screen

3/9 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 12-42 kV

Dimensional drawings and accessories Premolded cable termination, SOT 1236 kV

I I Creepage distance L L I I

SOT, indoor

SOT, outdoor

Designation SOT 241/242/242 B SOT 243/244/245 SOT 246/361/362

I 235 330 390

L mm min 300 min 430 min 500

D 70/75/80 80/85

Creepage distance min 520 min 725

Accessories, to be ordered separately

SCL-B

UKR

FK

TSH

PSSK

Designation SCL-B UKR JSA, JXT FK TSH PSSK

Description Cable lug Universal clamp for fastening cable to a pole, etc. Earthing kits when the cable does not have a Cu-wire screen Overhead line clamp Branch seal kit Screen separation kit (if needed for indoor)

See page 3/51 7/2 3/47 3/50 3/46 3/45


3/10

Cable accessories for XLPE-insulated cables 12-42 kV | Kabeldon cable accessories 1420 kV |

You might also like