System Voltage ( P-P ) System Voltage ( P-N ) Future Load Expansion Average Intermittent Use of Equipment Sr.

N o

415

Volt

Linear Load:

General Equipments, Heater

Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com

Equipment Reefers HVAC Area Lighting Office Loads

UPS,Invertor,Ballast,VFD Non-Linear Load: 230 Volt 20% % 1.2 (0.7 To 1.0) 0.8 0.8 Total Connected Load on Diesel Generator Set Load Starting Running Diversity Load Type Supply Qty P.F P.F Factor Load Kw/Hp Motor Motor Non-Linear Linear 3Ph 3Ph 1Ph 3Ph 180 193 1 1 0.8 3 196 109 Kw Kw Kw Kw 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.5 0.5 0.5 0.6

Starting Condition Motor Starter Dol Dol Auto.Tra. Starting Amp 1252 5035 852 114 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Starting Kva 540 2171 196 82 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Starting Kw 432 1737 157 65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Running Condition Full Full Full Load Load Load Kva Kw Amp 90 362 196 82 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 72 290 157 65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 125 503 533 114 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

RESULTS
Starting Kva Starting Kw Starting Amp Running Kva Running Kw Running Amp Alternator Details Voltage (P-N) Efficiency Engine Overload Capacity 2989 2391 7253 730 584 1275 230 80% 130%

(Appro 130% To 150%)

Required Generator Rating

Generator KVA Engine KW

2869 607

(Select D.G near This Value)

Calculate D.G Set Efficiency & Unit Rate of Power D.G Size ( Kva ) D.G P.F D.G Running Hours Diesel Consumption (Liter) KWH Reading of Meter M.F of KWH Meter Diesel Rate /Liter (Rs) Efficiency of D.G KWH/Liter (Unit Per Liter) Unit Rate of Power (Rs) 1000 1 20 1000 10000 1 40 63% 10 4.0

Calculate Approximate Fuel Consumption D.G Size (Kva) D.G P.F D.G Operation 115 0.8 Full Load

Required Diesel Liter/Hour 23.11