Professional Documents
Culture Documents
Description Application TITANEX flexible cable is intended for installations with moving equipment, electric appliances and for building sites. The cable may be rated 0,6/1 kV where the installation has built-in protection and for motors in lifting appliances - machine tools - etc. This cable can be used in refrigerating installations. Installation This cable can be installed in open air or be buried but with extra mechanical protection. Conductors laid up Assembled conductors. Marking USE <HAR> N (x ou G) S TITANEX N = number of cores G = with Green-Yellow x = without Green-Yellow S = section in mm Nota Max continuous operating conductor temperature in normal use : +60C ( in every case of mobile installation) +85C ( fixed protected installation ) +200C ( in short circuit ) Permissible current rating is measured for an ambient temperature of 30C and a maximum operating and conductor temperature of 85C . For other temperature please refer to correction factors .
Page 1 / 6
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Page 2 / 6
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Special cross-linked elastomer Black Special cross-linked elastomer Bare copper Yes Very good Flexible Accidental Good 200 C -25 .. 55 C 60 C
New cores identification Core identification in accordance with HD 308 S2 (October 2001)Identification of cores in cables and flexible cords. HD 308 S2 since january 2004 G (earth core) X (without earth core) 1 Black (preferential) Black (preferential) 2 Blue + Brown Blue + Brown 3* Green - Yellow + Blue + Brown Brown + Black + Grey 3** Blue + Brown + Black 4 Green - Yellow + Brown + Black + Grey Blue + Brown + Black + Grey 5 Green - Yellow + Blue + Brown + Black + Grey Blue + Brown + Black + Grey + Black > 5 White printed numbers + 1 Green - Yellow White printed numbers * For the cables without Green/Yellow with a cross-section >4mm ** For the cables without Green/Yellow with a cross-section of 1,5mm & 2,5mm Number of cores
Voltage drop, single phase V/A.km 23.3 14.0 8.7 5.9 3.4
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Voltage drop, single phase V/A.km 39.4 27.0 10.1 6.7 3.8 2.5 1.68
Max. outer diam. mm 10.0 11.0 15.1 16.8 22.6 25.7 30.7
Min. outer diam. mm 7.7 8.5 11.8 13.1 17.7 20.2 24.3
Perm. current rating open air A 18 23 23 32 32 56 77 102 136 168 203 262 320 373 432 495
Voltage drop, single phase V/A.km 39.4 27.0 27.0 16.2 16.2 7.0 4.0 2.5 1.7 1.21 0.87 0.64 0.5 0.4 0.35 0.3
Max. outer diam. mm 10.7 11.9 11.9 14.0 14.0 18.0 24.2 27.6 33.0 37.1 42.9 48.3 54.0 60.0 66.0 72.0
Min. outer diam. mm 8.3 9.2 9.2 10.9 10.9 14.1 19.1 21.8 26.1 29.3 34.1 38.4 43.3 47.4 52.0 57.0
Approx. weight kg/km 117 134 134 195 195 346 663 924 1345 1760 2390 3110 4170 5080 6220 7730
Page 4 / 6
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Perm. current rating open air A 16 21 21 29 38 50 68 92 122 150 182 232 281 325 373 425 500
Voltage drop, single phase V/A.km 34.08 23.3 23.3 14.0 8.71 5.84 3.42 2.2 1.44 1.04 0.75 0.56 0.44 0.36 0.31 0.28 0.23
Max. outer diam. mm 12.0 13.1 13.1 15.5 18.0 20.0 26.5 30.1 36.6 41.1 47.5 54.0 61.0 66.0 73.0 80.0 91.0
Min. outer diam. mm 9.6 10.2 10.2 12.5 14.0 15.7 20.8 23.8 28.9 32.5 37.7 42.7 48.4 53.0 58.0 64.0 72.0
Approx. weight kg/km 144 165 165 245 357 443 818 1150 1700 2180 3030 3990 5360 6500 7990 9910 13120
Voltage drop, single phase V/A.km 34.1 23.6 14.0 8.72 5.84 3.43 2.2 1.44
Max. outer diam. mm 14.0 14.4 17.0 19.9 22.2 29.1 33.3 40.4
Min. outer diam. mm 10.9 11.2 13.3 15.6 17.5 22.9 26.4 32.0
Approx. weight kg/km 180 238 297 453 557 1001 1430 2096
Page 5 / 6
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Eighteen cores Cross Perm. current rating section open air mm A 1.5 9 2.5
twenty four cores Cross section Perm. current rating open air mm A 1.5 8 thirty six cores Cross section mm 1.5 2.5
Page 6 / 6
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.