You are on page 1of 1

DARCY FRICTION LOSS CALCULATOR FOR PIPES, FITTINGS & VALVES

Given Data Flow Rate (Q) Pipe Inside Diameter (D) Kinematic Viscosity () Specific Roughness () Pipe Length (L) Calculated Data Average Velocity - V (m/s) Reynolds Number Darcy Friction Factor Head Loss - Pipe (m) m3/hr mm cSt m m 190 0.05278 m3/s 154.02 0.15402 m 1 1.000E-06 m2/s 1.50E-06 300 INPUTS CALCULATED VALUES

2.83 436299 0.014 10.80

TOTAL HEAD LOSS, hf (m)

14.56

Calculated Head Loss in Fittings, Valves, Entrances & Exits K 5 0.05 0.6 2.3 0.4 0.6 0.9 7 0.9 0.2 10 1 0.5 1 1.8 0.6 3.76 Qty 0 0 0 1 0 0 6 0 0 0 0 0 1 1 0 0 Sub Total K 0 0 0 2.3 0 0 5.4 0 0 0 0 0 0.5 1 0 0 9.2

Angle Valve Ball Valve, Full Port Butterfly Valve Check Valve, Swing Type Elbow 45 Degrees Elbow 90 Degrees, Long Radius Elbow 90 Degrees, Standard Flow Meter, Turbine Type Foot Valve Gate Valve Globe Valve Pipe Entrance, Inward Projected Pipe Pipe Entrance, Sharp Edge Pipe Exit Tee, Standard, Flow Through Branch Tee, Standard, Flow Through Run Head Loss - Valves & Fittings (m)