Abstract
Section 300 covers design for concrete and steel structures such as pipeways, pipe supports, equipment support, stairs, ladders, walkways, platforms, guyed stacks, pipeway crossings, and roadway bridges. This section does not cover buildings and offshore structural platforms, although most of the components can be used on offshore production facilities. The guidelines in this section are written for inexperienced engineers or engineers working outside their discipline or area of expertise.

Contents
310 311 312 313 320 321 322 323 324 330 331 332 333 334 340 341 342 343 Introduction Background Information People and Organizations Industry Codes and Practices Piping Support Design ConsiderationsElevated Pipeways Design Guidelines Low-Level Pipeways and Sleepers Secondary Pipe Supports, Springs, and Hangers Equipment Supports Design Requirements Design Loads Structural Analysis and Design Design Considerations for a Corrosive Environment Stairs, Ladders, Walkways, Platforms, and Handrails General Design Loads Grating and Floor Plate Design and Selection

Page
300-3

300-6

300-29

300-32

ChevronTexaco Energy Technology Co.

300-1

April 2004

300 Industrial Structures

Civil and Structural Manual

344 350 351 352 353 354 360 361 362 363 364 365 370 371 380 381 382 383 390

Ladders, Cages, and Guards Guyed Stacks Use and Layout Design Installation Maintenance Pipeway Crossings and Roadway Bridges General Considerations Buried Lines Corrugated Pipe Arches Overhead Pipeway Crossings Bridges for Pipeline Crossings Computer Programs For Designers STAAD III Model Specification, Standard Drawings, and Engineering Forms Model Specification Standard Drawings Engineering Forms References 300-66 300-65 300-62 300-52 300-45

April 2004

300-2

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

310 Introduction
As used in this section, the term industrial structure refers primarily to structures used to support piping and equipment. In addition, the section addresses guying of stacks and the design of stairs, ladders and other means for accessing these structures. Information included here will be useful for both novice engineers and engineers working outside their discipline. While this information will help you develop preliminary designs and make informed decisions, it is not a substitute for review and sign-off by a registered civil or structural engineer. To enhance the utility of this section, some major subsections have their own references. A comprehensive list of primary references can be found in Section 390.

311 Background Information


Industrial structures are required to perform a specific function, and a complete understanding of this function is critical. But, in addition to meeting functional requirements, there are other important objectives that a designer should strive to meet. These objectives include: Select a framing system and structural elements appropriate for the type of loads involved. Meet all safety requirements, including those in the Safety in Designs Manual (SID). Provide a structure that can be economically fabricated and installed. Select materials appropriate for the environmental conditions. Give particular attention to the detailing of structural connections. Structural problems are frequently traced to inadequate or inappropriate connection details. Provide a structure that performs satisfactorily over its intended useful life, without requiring extensive maintenance. Provide a structure that creates minimum interferences to the normal activities of the operators. Provide a structure with the access, clearances, work and laydown areas necessary for maintenance. Present a balanced appearance consistent with the facilities being supported. Give consideration to aesthetics whenever the structure is highly visible. Provide space and structural capacity for changes and future loads.

ChevronTexaco Energy Technology Co.

300-3

April 2004

300 Industrial Structures

Civil and Structural Manual

Keep structural details as simple as possible to fit up and weld. Review of structural steel details should take into account the accessibility for welders to perform their work. Eliminate areas which will collect and hold moisture and other foreign material. Such areas will be subject to accelerated corrosion.

There are many standard structural details illustrated in Company Standard Drawings and Forms, and other structural design references. For many simple structures, these details will reduce design time and provide proven solutions. A list of these drawings and forms is included in Section 380. The Company primarily uses either structural steel or reinforced concrete structures. The choice is most often an economic decision based on lowest installed cost. However, the importance of maintenance costs and flexibility for future modifications and additions may also be considerations.

Design Documentation
Structural designers are responsible for documenting the design basis for structures. This documentation should assist designers involved in future additions, modifications, or corrective actions. The following items should be included on design drawings where applicable: Design Codes (Including Date or Edition) Company Design Standards (Wind and Earthquake) Design Operating Loads Design Loads and Moments for Foundations Soil Bearing Pressures Pile Design Loads Unusual Design Conditions

312 People and Organizations


Be familiar with the people, organizations, regulations and requirements that provide input to your designs, or have a review and/or approval function. Here are a few of the most important:

Government Agencies
The extent of local governmental review is closely tied to existing regulations. Where no regulations exist, follow local management perception of need and anticipation of future requirements. Identify applicable regulations, required permits, and government agencies with jurisdiction over the work. Determine if there are requirements that civil/structural drawings be stamped by a Professional Civil Engineer and/or Structural Engineer. Since 1986, the State of California requires that ....all final civil engineering plans, specifications, reports, or documents shall bear the seal or stamp of the registrant, and the expiration date of the certificate or authority.

April 2004

300-4

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Two examples of how local codes have influenced designs are: At one location, the applicable building code was based on an earlier edition of the Uniform Building Code. Subsequent changes to the UBC were not recognized by the local authorities. Another locality enforced their own limitation on the allowable openings between rails on a handrail. This required the addition of a second midrail for all railings.

Safety Engineer
The local Company safety engineer is an important contact to establish at the early stages of design. For example, the number, location, and types of egress are critical items that should be addressed early. Periodic discussions with the safety engineer are encouraged to review required clearances, to consider special situations, and to clarify or interpret Company requirements and practices. Final review by the safety engineer occurs when the structure is complete. Items found to be in nonconformance at that time can prove to be costly to correct.

Fire Protection Engineer


The fire prevention specialists in CRTCs Health, Environment, and Safety Group must be consulted to establish fireproofing requirements. Early agreement to define the vertical and horizontal fireproofing limits for specific structures or locations is desirable.

Facility Operators
The local operators will normally have four primary concerns relating to structures. These include: functional aspects of the structure, operator access, clearances, and servicing/maintenance requirements. They will influence size of platforms and number and types of access.

Drafting and Engineering


Division of work between engineers and designer/draftsmen will depend on established practices at a location, level of experience for designer/draftsmen, and complexity of intended structure. Contact with other engineering disciplines is frequently required to define intended function, anticipated loads, space limitations, access and clearances required for operations and maintenance work.

313 Industry Codes and Practices


This section lists the applicable codes used for design of steel and concrete structures.

ChevronTexaco Energy Technology Co.

300-5

April 2004

300 Industrial Structures

Civil and Structural Manual

Steel Construction
Manual of Steel Construction - American Institute of Steel Construction (AISC). Includes: AISC Specification for the Design, Fabrication and Erection of Structural Steel for Buildings Structural Welding Code - AWS D1.1, American Welding Society (AWS) ASTM Standards in Building Codes Specifications, Test Methods, Definitions Volume 1 Metal Bar Grating Manual - The National Association of Architectural Metal Manufacturers (NAAMM)

Concrete Construction
Building Code Requirements for Reinforced Concrete, American Concrete Institute (ACI 318) ASTM Standards in Building Codes Specifications, Test Methods, Definitions Volume 1 Safety In Designs Manual Uniform Building Code. International Conference of Building Officials. Covers the fire, life and structural safety aspects of all buildings and related structures. The UBC is commonly accepted in whole or in part by municipalities, so that review and approval of designs is frequently based on meeting UBC requirements. A separate volume, Uniform Building Code Standards, presents test, material, and special design standards which are referenced in the UBC. Guidelines for the Seismic Evaluation and Design of Petrochemical Facilities [20] is an excellent resource as it provides commentary and guidance on how to apply the Uniform Building Code, which is mainly intended for buildings, to structures typically found in petrochemical facilities. Standard Welding Symbols. A copy of the AWS Standard Welding Symbols is included at the end of this section (Figure 300-30). Incorrect or incomplete weld symbols on drawings can lead to inadequate welded connections, or to increased fabrication costs because of claimed extras by the fabricator. An example occurred when an engineer designed some critical connections as full penetration welds. However, the basic welding symbol used on the drawings could also be interpreted as a partial penetration weld. Since the notation CP (for complete penetration) was left off the drawing, and the specification did not call for full penetration welds, the fabricator made a claim for a sizable extra to the contract. Note Figure 300-30, Standard Welding Symbols, is a foldout at the end of this section.

320 Piping Support


This subsection on piping support discusses design considerations and applicability of three types of support: stanchions for elevated pipeways, grade-level pipeways and sleepers, and secondary supports, springs and hangers.

April 2004

300-6

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Stanchion supports (Figure 300-1) are commonly used in refineries and other plants where piping runs might interfere with vehicle and personnel movement. They are considerably more expensive than grade-level supports. In many instances, stanchions remain a constant size while the piping loads and configurations they bear often change. With this in mind, it is important to ensure that stanchion design reflects potential future loadings. In addition to carrying process lines and utility/service headers, the pipeway stanchions carry electrical and instrument distribution systems along with mechanical and safety equipment. Another issue in stanchion design is fire protection. Generally, on-plot stanchions are either fireproofed or constructed of fireproof material, while off-plot stanchions are not. The exception will be stanchions located in near-off-plot pipeways, i.e., pipeways adjacent to or between process plants.

321 Design ConsiderationsElevated Pipeways


This section discusses 10 major considerations used to determine pipeway design parameters. These include:

1. Pipeway Capacity
Pipeway capacity, the amount of the available space to carry piping, is the critical element affecting stanchion design. The width of pipeway, number of levels, and stanchion geometry are all dependent on establishing the pipeway capacity. Requirements for pipeway space are determined from planning studies by the piping engineers and designers and input from operations, and are based on estimated current space requirements plus an allowance for future lines.

2. Stanchion Geometry
After determination of design pipeway capacity, studies can begin on stanchion geometry alternatives. These studies will establish: Overall pipeway width Number of pipeway levels Column spacing Elevation of crossbeams Extension of support beams outside the column lines Requirements for other supports at plot limit manifolds

Factors considered in these studies include: Vehicle access Plant space limitations Proposed piping layouts at plot limit waterfalls Location of utility stations Electrical/instrument conduits Access during construction and maintenance considerations

ChevronTexaco Energy Technology Co.

300-7

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-1

Pipeway Stanchion

Individuals responsible for the stanchion structural design will often get involved in these studies as the constructability and economics of various design concepts are considered.

April 2004

300-8

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

3. Stanchion Spacing
The horizontal distance between stanchions is normally determined from plant layout studies and is influenced by the size of lines to be supported. For acceptable piping/conduit spans, stanchion spacing between 20 to 30 feet is generally used. Smaller stanchion spacings to accommodate the small allowable span of small diameter piping and conduit are typically not used, since small lines can be supported by unistrut between two larger lines or by intermediate crossbeams. See Figure 300-2 for an illustration of intermediate crossbeams. For information on recommended spans for individual line sizes, refer to Section 324.

4. Clearances
Vertical and horizontal clearances must be determined by the operating requirements of the facility. At times there may be a need for an operating or maintenance roadway underneath the pipeway. If the roadway runs longitudinally directly below the pipeway, side clearance for the stanchion columns must be sufficient for vehicle access plus an allowance for manifolds or other equipment mounted on or adjacent to the stanchion columns.
Fig. 300-2 Pipeway Isometric Illustration of Terms

The vertical clearance above the roadway must be sufficient to allow passage of fire protection vehicles and a hydraulic maintenance crane. A frequently used minimum vertical clearance from high point of grade to the lowest projection on the pipeway is 12 feet-6 inches, but specific plants may require a different clearance.

ChevronTexaco Energy Technology Co.

300-9

April 2004

300 Industrial Structures

Civil and Structural Manual

For multi-level stanchions, the clear vertical distance between levels will vary depending on the average and maximum line sizes to be installed. Adequate clearance is necessary for lines to enter the pipeway and for reasonable accessibility for completing field welds, insulation, and painting. For the average case a clearance of 2 feet-6 inches is suggested, from top of lower support beam to underside of the beam above. Where small lines (4-inch maximum) are involved, the spacing may be reduced to about 2 feet. A clearance of 3 feet or more may be required if a number of large lines are proposed. For example, if there are a number of 12-inch lines in the pipeway, a 4-foot clearance might be desired so that two elbows can be used for a 90 degree jumpover of other lines in the pipeway. See Figure 300-3.
Fig. 300-3 Clearances for Piping

When there are only a few large lines in a pipeway, it may be desirable to consider using 45 degree jumpovers instead of 90 degrees for lines entering the pipeway. This will reduce the required clearance between pipeway levels. Structural bracing can be a head-knocker. In areas where people walk, the lower ends of braces should intersect columns high enough to keep a 7-foot clearance above grade. However, in Seismic Zones 3 and 4, braces must extend down to grade (See Figure 300-2). A barrier should be used to prevent accidents. In Seismic Zone 2, the 7-foot clearance is acceptable, provided certain design requirements are met. See Chapters 2211 and 2212 of the 1994 UBC for details.

5. Fireproofing Requirements
Structural steel pipeway stanchions can be covered with special materials or concrete to protect them from fire. Precast or cast-in-place concrete pipeway stanchions usually do not require special fire protection consideration. Fireproofing materials and requirements are discussed in the Insulation and Refractory Manual, Section 400. Generally, fireproofing principal members of a pipeway structure is warranted if exposure to fire could result in failure of these members and cause loss or serious damage to critical piping, or supported equipment such as air-cooled exchangers.

April 2004

300-10

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

On-plot pipeway stanchions are generally fireproofed up to and including the first main horizontal member, but not less than 20 feet above grade. Knee braces for support beam extensions outside the stanchion columns are generally fireproofed when located less than 20 feet above grade. Braces provided for wind and seismic loading need not be fireproofed, as long as the structure is stable without them for gravity loading conditions. In high risk areas (equipment operating pressure over 1000 psig), fireproofing may be required for the second and higher levels of pipeway supports. Structural members supporting air coolers handling liquid hydrocarbons above pipeways in process areas should be fireproofed up to the point of applied load. For off-plot stanchions the only fireproofing generally required is at plot limit manifolds areas, and at other locations deemed to be fire hazard areas. If fireproofing is warranted for such areas, it would be limited in scope, such as: Pipeway columns within 25 feet of manifolds or fire hazardous areas. Horizontal members that support piping coming from manifolds.

Fireproofing would normally not be required for off-plot pipeway diagonal bracing or for longitudinal struts between stanchions. Installation Fireproofing is provided for structural steel members by using either regular portland cement concrete, gunite, or special insulating materials. Refer to the Insulation and Refractory Manual Section 400 for a discussion of surface preparation, priming, top coats, and fireproofing materials. Following are the ratings for various thickness of concrete fireproofing over steel:
Minimum Thickness(1)
2-1/2 inch 2 inch 1-1/2 inch

Fire Rating (Hours)


4 3 2

(1) On the face of steel member. Thickness at edge of structural member may be 1/2 inch less. Thickness requirements are illustrated in Figure 300-4 for beams. The top flange face of beams does not require fireproofing. The flange faces for columns require full thickness coverage.

For main support members that require fireproofing, it is customary to provide a 4-hour fire rating as shown on Drawing GA-N33336 (in the Fire Protection Manual). Concrete having a minimum compressive strength of 2500 psi is recommended for fireproofing. Corrosion under fireproofing can be a serious problem. Flashing or caulking may be required to prevent entry of water between the fireproofing and steel. Acceptable sealants should be specified. Two products that have been used are Dow Corning No. 732 Silicone elastomeric sealer, and H.B. Fuller, Foster Products Division No. 94-95 Butyl Caulking.

ChevronTexaco Energy Technology Co.

300-11

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-4

Fire Proofing Cover

6. Steel vs. Concrete


For a new installation, the preferred stanchion materials are either steel or concrete. Some factors that influence the final choice are: Stanchion Geometry Structural steel is usually the economic choice for complex pipeway stanchions (multi-level, cantilever beams, larger spans). These are difficult and costly to construct with precast or cast-in-place concrete. Moreover, steel structures have the additional advantage of being more adaptable for future modifications. Reinforced concrete is generally limited to simple structures that require fireproofing. A combination of materials may also be used, such as reinforced concrete for the lower portion that requires fireproofing, and structural steel above. Fireproofing The economics of steel vs. concrete depend on the fireproofing requirements. Structural steel is generally the economic choice if concrete encasement is not required. However, for installations that require fireproofing, the added costs to encase the structural steel reduces the cost differential between steel and reinforced concrete. Other Considerations Other factors should be considered in the evaluation of steel vs. concrete. Some of these may require input from installation contractors. Items that might be evaluated for specific installations include: Relative impacts of steel vs. concrete on project construction schedule.

April 2004

300-12

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Differences in weather impacts. For example, steel might be preferred over concrete in a freeze/thaw environment. Impact on other construction activities performed concurrently in the area. Does stanchion geometry lend itself to precasting and use of reusable forms? Ability to precast on-site or in contractors yard.

7. Foundations
Spread Footings Since the axial loading imposed by pipeway columns is relatively light, spread footings are an option if the soils have adequate bearing capacity. Spread footings are generally designed on the basis that the column-to-footing connection is hinged. The reasons include: Soil conditions may preclude imposing large moments on the footing without substantially increasing the footing dimensions. Fixed column-to-footing connections are more difficult to achieve and may be more costly.

Pile-Supported Footings Pile-supported footings can be designed to take combined axial loads and longitudinal and/or transverse moments from stanchion columns. A column-to-footing connection using a base plate and anchor bolts requires careful design to assure complete moment transfer. An alternative is to extend the column into the pile cap by grouting into a prepared pocket. Typical column-to-footing connections are shown in Figure 300-5.
Fig. 300-5 Typical Column-to-Footing Connections

ChevronTexaco Energy Technology Co.

300-13

April 2004

300 Industrial Structures

Civil and Structural Manual

8. Longitudinal Struts or Tiebeams


Longitudinal loads on stanchions result primarily from the friction forces developed by thermal expansion of the supported lines, along with possible loads from anchored lines. It is a common practice in stanchion design to tie individual stanchions together longitudinally with structural strut members. Braced stanchions are provided at appropriate locations, every fifth to tenth stanchion along the pipeway, to resist the total longitudinal forces developed. These are strategically located to resist longitudinal pipeway loading and minimize restrictions to vehicle and personnel access. Diagonal bracing can be used to anchor a single stanchion, or multiple stanchions can be braced as shown in Figure 300-2. For some pipeways, the tiebeams act as struts only, and do not carry external loads. Often, there are vertical loads imposed. These occur where: Tiebeams serve as support for steam loops or lines that branch from the main pipeway. Small pipeway lines or conduit are directly supported by the tiebeams between stanchions. Intermediate crossbeams are provided between stanchions for support of small lines and electrical/instrumentation conduit. Intermediate crossbeams in turn receive their support by the longitudinal tiebeams.

9. Future Expansion
A space allowance for future lines is normally included in the determination of pipeway capacity. This allowance is frequently based on a percentage of the space proposed to meet current requirements. For example, an arbitrary 25% allowance might be chosen, to be adjusted upward or downward depending on the expectations for future lines. Another factor to consider is the ease or difficulty to add pipeway capacity in the future. On-plot stanchions frequently present great difficulties with regard to expansion, and increased spare capacity in the initial installation is warranted. If you choose to make provisions for modifications and expansion of the pipeway in the future, member sizes and details should be designed to support an additional level to the pipeway, the addition of cantilever crossbeam extensions, or an increase in the pipeway width by adding another row of columns and extending the cross beams.

10. Loadings
Following the conceptual development studies for the pipeway and structures, develop a consistent and realistic set of design loads. Loadings to be considered on stanchions are: Dead loads from pipeway structure Pipe gravity loads including fluids Electrical and control conduit loads

April 2004

300-14

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Thermal expansion loads from piping including anchor forces Earthquake and wind loads Loads from equipment and associated platforms

Pipe Gravity Loads Pipe gravity loads may be treated as uniform loading of 35 pounds per square foot of contributory area of loading, per pipeway level for columns and transverse beams. This is equivalent to the loading from water- filled 6-inch lines (0.250-inch wall) at standard 10-inch spacing between lines. The above loading is appropriate for the typical pipeway, but a more refined determination may be justified if the majority of lines will be either less than or will exceed 6-inch diameter. Piping plans should be checked to avoid special loading situations that may exert high concentrated loads. Longitudinal Tiebeams Tiebeams that will also support lines at pipeway intersections should be designed for the full unit loading of 35 pounds per square foot of contributing area. Tiebeams at other locations should be designed for anticipated current and future loads. It is common practice to apply the same design loads to a continuous string of tiebeams to provide uniformity in design and give maximum flexibility for adding future loads. Thermal Loads Thermal loads result from expansion or contraction of piping from changes in both ambient temperatures and operating line temperatures. The static coefficient of friction for individual lines is usually estimated at 0.3 to 0.5 (steel against steel), with the value 0.42 used for 1 or 2 pipes and 0.3 for 3 or more pipes. The horizontal force due to friction is: Ff = fW
(Eq. 300-1)

where: Ff = friction force (lbs) f = coefficient of friction W = weight of piping and contents supported by structure Thermal loads are usually considered internal and self-compensating for stanchions with longitudinal tiebeams. That is, if a group of stanchions are interconnected and anchored to resist longitudinal movement, thermal loads on individual stanchions can be disregarded. Even for stanchions that do not have longitudinal tiebeams there will be some selfcompensation of thermal loads. The friction forces developed by individual hot lines will tend to be offset by resisting forces from other lines in the pipeway not

ChevronTexaco Energy Technology Co.

300-15

April 2004

300 Industrial Structures

Civil and Structural Manual

expanding at the same time. By carefully considering the load contribution from hot lines, the designer can select total thermal forces for stanchion design that are adequate but not overly conservative. Thermal loads on pipeway stanchions should be considered at changes in pipeway direction, where expansion loops or bellows are used, or where pipes may be restrained external to the pipeway, such as where connected to vessels or equipment. In a long, rigidly-connected pipeway, consideration should be given to thermal stresses induced into the stanchions due to expansion of structural members. These stresses can be mitigated by subdividing the length of the pipeway into groups of individual stanchions tied together with longitudinal tiebeams. Each group is individually anchored, with no tiebeams between groups. Earthquake Earthquake forces (transverse and longitudinal) can be determined using procedures given in Section 100, Wind and Earthquake Design Standards. Seismic loading in the transverse direction is usually of greater concern than in the longitudinal direction, as supports are restrained longitudinally by the lines themselves. Transverse seismic loading is resisted by rigid frame design of the stanchions or diagonal bracing in the transverse plane. Wind Wind loading transverse to the pipeway is calculated using the projected area of the largest pipe at each pipeway level, plus the area of the support columns. Rigid frame design or diagonal bracing is the usual choice for resisting lateral wind loading. The wind force longitudinal to the pipeway is usually neglected. For wind forces refer to Section 100, Wind and Earthquake Design Standards. Other Loads Pipeway stanchions may also be used to support operating equipment such as air coolers and miscellaneous vessels. Loads should be determined from the operating weight of equipment, platforms, and supporting structures.

322 Design Guidelines


The purpose of this section is to review accepted design practices for stanchions, and direct the reader to references on this subject.

Design Reference
Included in the References subsection is a document entitled Pipe Support Design (Reference [16]). Individuals not familiar with designs for pipeway structures may wish to obtain a copy of this manual through Chevron Research and Technology Company. In using this document the following cautions apply: Refer to Section 100 of this manual to determine design loadings for wind and earthquake.

April 2004

300-16

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

In developing designs use good judgment when following the procedures given in Reference [16]. Take a critical approach to determine if unusual loadings or other conditions require modifications to the design steps.

Construction Details for Earthquake Resistance


Details for earthquake-resistant design should give the structure the ability to absorb energy. The following general comments apply: Reinforced Concrete Structures. Design all moment-resisting space frames as ductile frames (for seismic zones 2,3 and 4) in accordance with Section 1921 of the 1994 Uniform Building Code, and to ACI 318, Chapter 21, Special Provisions for Seismic Design. Steel Structures. Pay special attention to connections. Ultimate strength of connections should exceed the yield strength of connected members. At connections and other points of high stress in rigid frame structures, follow the requirements of the AISC Specification for plastic design regarding width-thickness ratios, lateral bracing, web stiffening, and fabrication. Design in accordance with Sections 2211 and 2212 of the 1994 Uniform Building Code.

Column Orientation (Structural Steel)


Selection of column orientation is unique to each design. It is influenced by: The geometry of the structure Relative magnitudes of transverse and longitudinal forces Limitations on the use of bracing Connection details for cross beams Moment transfer at the base of columns

To provide maximum access under on-plot pipeways, stanchions are frequently designed as rigid frame structures to take transverse pipeway loading. The strong axis of the columns is oriented accordingly as shown in Figure 300-6. For off-plot pipeways, where transverse bracing between columns is acceptable, orientation of the strong axis to take longitudinal pipeway loading is a common practice.

Attachments and Inserts for Concrete Supports


It is relatively easy to add miscellaneous small lines and/or equipment to bare structural steel pipe support structures. However, for reinforced concrete, or concrete encased steel, it is important to establish what attachments are required to be embedded in the concrete. Examples include unistrut to support conduit or small piping and lifting inserts for handling or installation of precast reinforced concrete sections. For all reinforced concrete crossbeams supporting piping, a slide plate is required as detailed on CIV-EF-588. For all stanchions, stop plates must be provided at the ends of support beams to prevent piping from moving off the supports.

ChevronTexaco Energy Technology Co.

300-17

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-6

Column Orientation for Rigid Frame

Standard Form CIV-EF-588 (A&B)


Provides standard details for connections, attachments, and reinforcing for both double column and T-type precast concrete stanchions.

323 Low-Level Pipeways and Sleepers


To minimize the cost of structural supports, pipeways outside of process areas are frequently installed at or near grade level. Sleeper supports are used to keep the lines clear of the ground. This helps protect pipes from corrosion, and allows the grade under the pipeway to be drained and maintained. A minimum ground clearance of 12 inches is suggested but additional clearance allows easier maintenance. Figure 300-7 illustrates the types of piers commonly used for supporting low level pipeways. Pipe, new or used, is commonly used for construction of low level pipeways and sleepers. Reasons include: availability, cost, easier painting and maintenance of pipe versus beams, appearance, and pipe provides an ideal shape for the horizontal member supporting piping.

April 2004

300-18

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-7

Types of Piers for Supporting Low Level Pipeways

Routing
In general, pipeway routing is selected to minimize the length of piping runs. However, consideration must be given to pipeway, plant, and tankfield expansion. Cross country routing of individual lines must be avoided. New pipeways planned for older facilities should be routed and sized so that existing lines can be placed on them as part of a future program of line and pipeway consolidation.

Pipeway Crossings
Low-level pipeways require special treatment at intersections with refinery roads, highways, and railroads. The method selected for the pipeway crossing will have to be based on economics, piping considerations, vehicle accessibility, and the clearances and restrictions imposed by plant operators, or by a railroad company or highway department if outside Company-owned facilities. Refer to Section 360 for a discussion on alternative pipeline crossings.

Sleeper Design
Loads. Develop vertical loading requirements either using the unit pipeway loading of 35 pounds per square foot of contributory area of loading as discussed in

ChevronTexaco Energy Technology Co.

300-19

April 2004

300 Industrial Structures

Civil and Structural Manual

Section 321 (stanchions), or by calculating the actual weight of proposed lines. For recommended maximum spans between supports for various line sizes refer to Section 324. Low-level sleepers are usually self-supporting and must be designed to resist overturning forces developed by thermal expansion of lines. Section 321 discusses calculation of thermal load friction forces.

Foundation Type
Select sleeper and pier foundation type appropriate to the local site conditions and calculated overturning forces. Many sleeper design situations can be accommodated by the standard support details shown on Drawing GF-M-99874. Typical details and member sizes are given for single pier supports up to 3 feet in width, and double pier supports up to 6 feet in width, with height of pipe supports 3 feet or less. These same details can be adapted for wider pipeways by using multiple supports. When sleeper requirements are outside the range of load capacity and height limitations given, it will be necessary to proceed with detailed designs. Selection of sleeper foundation type depends on soil conditions and applied loads. Spread footings may be appropriate in many places if the soil offers good support and economic footing sizes can be achieved. For guidance in sizing and design of spread footings and pile-supported footings, refer to Section 200. Occasionally, because of induced moments to the foundation, a pole-type footing is the economic choice. The Uniform Building Code (Reference [5]) provides the formula given in Equation 300-2. This equation, along with Figure 300-8, can be used in determining the embedment requirements for pole footings in various soil conditions. Where piled footings are required, refer to Section 200.
Fig. 300-8 Allowable Foundation Pressure Reproduced from the 1994 edition of the Uniform Building Code 1994, with the permission of the International Conference of Building Officials Allowable Foundation Pressure (lbs/sq ft)
4000 2000 2000 1500

Class of Materials
1. Massive crystalline bedrock 2. Sedimentary and foliated rock 3. Sandy gravel and/or gravel (GW and GP) 4. Sand, silty sand, clayey sand, silty gravel and clayey gravel (SW, SP, SM, SC, GM and GC) 5. Clay, sandy clay, silty clay and clayey silt (CL, ML, MH and CH)

Lateral Bearing (lbs/sq ft/ft of depth below lowest point of ground adjacent to foundation)
1200 400 200 150

1000

100

April 2004

300-20

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Design Criteria Nonconstrained


The following equation may be used in determining the depth of embedment required to resist lateral loads where no constraint is provided at the ground surface, such as rigid floor or rigid ground surface pavement. A - 1 + 1 + 4.36h ------------- d = --2 A
(Eq. 300-2)

where: A = 2.34 P / S1 b P = Applied lateral force in pounds. S1 = Allowable lateral soil-bearing pressure in lb/ft2 set forth in Fig. 300-8 based on a depth of one third the depth of embedment. b = Diameter of round post or footing or diagonal dimension of square post or footing (feet). h = Distance in feet from ground surface to point of application of P. d = Depth of embedment in earth in feet but not over 12 feet for purpose of computing lateral pressure. Anchors. Where pipe anchors are required, special attention must be given to the associated lateral forces on the sleeper. Drawing GB-M99653 (in Piping Manual) provides details for pipe shoe anchors suitable for anchor supports on structural steel, pipe, or reinforced concrete stanchions.

324 Secondary Pipe Supports, Springs, and Hangers


Secondary supports include all pipe supports other than stanchions and sleepers. These supports may be for individual lines or for multiple lines.

Vertical Design Loads


Vertical design loads are computed on the basis of actual weights of pipe, fluids, insulation, valves, and fittings. As a general rule, the length of pipe supported at a given point is taken as half the sum of the adjacent spans. Where the support is close to a vertical run, it is assumed that the support carries the entire load of the vertical section. Where horizontal bends exist, a judgment is made on the contributory loads to individual supports.

ChevronTexaco Energy Technology Co.

300-21

April 2004

300 Industrial Structures

Civil and Structural Manual

Horizontal Design Loads


Thermal. For supports that carry only one or two lines, the longitudinal friction loads due to thermal expansion and steel-on-steel sliding is generally computed with a static friction coefficient of 0.42. Section 321 discusses calculation of friction forces. In cases where several lines are carried by a support, a judgment is made as to the combined contribution of thermal loads. A common practice is to use the longitudinal force developed by the largest line(s) and assume that no restraint or load contribution is provided by other lines. Because of the size of the line and operating temperature for some situations, it may be desirable to consider the use of teflon pipe slides as a means for reducing thermal loads. With teflon the coefficient of friction can be reduced to about 0.1. The actual coefficient is a function of the load pressure against the teflon slide, decreasing as the unit loading on the teflon increases. However, as a practical consideration, the weight of most piping is not sufficient to achieve the lowest coefficients attainable with teflon. Wind. Transverse wind forms should be determined by the procedures given in Section 100. The projected horizontal area is based on the diameter of the largest line supported. Earthquake. Refer to Section 100 for determination of earthquake forces.

Other Loads
If guides or anchors are provided on supports, any lateral loads imposed by piping must be considered. Combining loads from piping flexibility studies and wind or earthquake may be necessary.

Support Spacing
Spacing of supports is a function of allowable stresses and deflections in the pipe. Longitudinal flexural stresses in the pipe can generally be considered independent of circumferential stresses caused by fluid pressure. The temperature of the pipe must be taken into account, with respect to the modulus of elasticity and allowable flexural stresses. The limiting consideration for deflections is usually the requirement that significant amounts of liquid not be trapped after draining the lines, or visually the lines do not appear to be sagging. Figure 300-9 may be used as a guide for commonly recommended spans. Spans and recommended deflections given are for uninsulated water-filled schedule 40 pipes. For the cases shown, flexural stresses are all below 20,000 psi.

April 2004

300-22

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-9

Recommended Spans and Deflection

Recommended Nominal Pipe Size (in.) Recommended Span (ft.) Maximum Deflection (in.)
3/4 1 1-1/2 2 3 4 6-12 10 15 20 20 30 35 40 1/4 1/4 1/4 1/4 3/8 1/2 1/2

Actual deflection for any line in a continuous horizontal run with uniform spans may be determined from the following equation: Deflection = 5.88 w L4 / E I
(Eq. 300-3)

where: w = Wgt. of line, fluid, insulation lb/ft L = Span in feet E = Modulus of Elasticity (psi) I = Moment of Inertia (in4) Vertical runs of piping should be guided as well as supported. The spacings of guides depends upon the rigidity of the piping and the wind pressures acting on the system. The following table (Figure 300-10) may be used to obtain maximum spacing of guides for various pipe sizes. Horizontal runs of piping may require guides near expansion loops. Guide requirements should be reviewed with the engineer or designer responsible for pipe flexibility studies.

Hangers
In general, resting-type supports are preferred over hanging supports. However, to maintain maximum access for personnel under piping, smaller lines may be supported by hanging one pipe from another or from an overhead structural member. Ensure that excessive vertical and lateral loads are not imposed on any supporting pipe, and the operating temperature of such supporting pipes should not exceed 150F. Hanger details are shown on GF-M-99874 (Sheet 2) and CIV-EF799C. Commercial hanger units are readily available.

Adjustable Pipe Supports


Adjustable supports are used where design loads must remain fully supported. This generally occurs at the piping connection support closest to equipment such as at

ChevronTexaco Energy Technology Co.

300-23

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-10 Recommended Guide Spacing Nominal Pipe Size (in.)


1 1-1/2 2 2-1/2 3 4 6 8 10 12 14 16 18 20 24

Maximum Spacing of Guides (ft.)


22 23 24 25 27 29 33 37 41 45 47 50 53 56 60

pumps and compressors. Adjustable supports are also used for alignment of equipment piping. Adjustable supports are not appropriate for accommodating differential settlement at pumps or compressors. Supports for this equipment should be anchored to the pump or compressor foundation and not to an independent foundation. Included on Standard Drawing GF-M-99874 are details and member sizes for adjustable pipe supports:

Support Design Considerations


The following drawings provide standard details that may be used for secondary pipe supports: CIV-EF-799 (6 sheets A through F) Pipe Support Details GF-M-99874 (2 sheets) Guide Sheet for Pipe Supports GB-M-99653 Standard Pipe Shoe & Pipe Shoe Anchors (in Piping Manual)

Drawing GF-M-99874 provides typical details and member sizes for single post supports up to 3 feet in width, and double post supports up to 6 feet in width, with the height of pipe supports 3 feet or less. Support requirements outside the load capacity and height limitations given in GF-M-99874 will require detailed design. Wherever practical, designers should standardize the sizes of members used for field fabricated supports. This will help to minimize the stock of material required in the field, and maintain a uniform appearance. The size selected for support

April 2004

300-24

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

members should present a balanced appearance consistent with the size of pipes being supported. If the width of pipe supports is sufficient for lines to be added in the future, make certain that this is considered in the design loads. If open space is left on a pipe support it is natural for someone in the future to assume that the supports are adequate for line additions. If in doubt use a uniform loading of 35 psf of pipeway for such design loading.

Spring Supports
Vertical thermal expansion can cause unacceptable loads on connected equipment. This problem can be overcome by providing flexible pipe supports which apply supporting force throughout the expansion and contraction cycle of the system. The most important consideration in the design of a spring support is defining the necessary characteristics of the unit. These are rarely set by the thermal stresses in the supported pipe, but usually are governed by permissible stresses on connected mechanical equipment specified by the manufacturer, to avoid failure or undesirable distortions in the equipment. Spring supports should be provided with means to prevent misalignment, buckling, eccentric loading of the springs, or unintentional disengagement of the load. Materials, design, and manufacture of spring supports are covered in ANSI/MSS SP-58 (Reference [19]). There are three basic types of spring units: Spring Cushion Supports Variable Spring Supports Constant Support

Figure 300-11 illustrates the use of these support types and the principles of their operation. Spring Cushion Supports. This class of spring is characterized by having 2 inches or less total deflection. As the name implies it is used to reduce localized stresses in the line and dampen line vibration. Variable Spring Supports. Variable spring hangers are used to support piping subject to vertical movement where the more costly constant supports are not required. The inherent characteristic of a variable spring is such that its supporting force varies with spring deflection and spring scale. Therefore, vertical expansion of the piping causes a corresponding extension or compression of the spring and will cause a change in the actual supporting effect of the hanger. Since the pipe weight is the same during any condition, cold or operating, the variation in supporting force results in pipe weight transfer to equipment or adjacent hangers, and consequently develops additional stresses in the piping system. When variable spring hangers are used, the effect of this variation must be considered. Constant Support. Constant support hangers provide constant supporting force for piping throughout its full range of vertical expansion and contraction. This is accomplished through the use of a helical coil spring working in conjunction with a bell crank lever in such a way that the spring force times its distance to the lever pivot is always equal to the pipe load times its distance to the lever pivot. The

ChevronTexaco Energy Technology Co.

300-25

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-11 Spring Supports Courtesy Anvil International, Inc.

constant support hanger is used where it is desirable to minimize any pipe weight load transfer to connected equipment or adjacent hangers.

Selection of Spring Supports


Selection of springs is usually made by piping or structural designers working with the design data given in manufacturers catalogs. Requirements for springs are generally developed from the results of a computer-generated piping stress analysis. The type of spring support unit is determined by such considerations as the amount

April 2004

300-26

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

of head room, support above the spring or below the spring, and geometry of the support mechanism. The size of spring unit is based on operating loads, movement from cold to hot position, and direction of movement from cold to hot position. Using the example table in Figure 300-12, you can work through the following example for selecting a variable spring support. This table has been excerpted from a more comprehensive table in the Grinnell catalogue. All spring support manufacturers have similar tables. Example: Thermal expansion downward is 2-1/4 inches. Total operating pipe load 4700 pounds Steps: 1. Enter hanger selection chart looking for a load of approximately 4700 pounds (maximum load). In this example, you will find 4700 pounds under Hanger Size 14. Read deflection for a figure type that allows for a full range of deflection. In this example, the deflection of the spring in the hot condition is 5-3/4 inches. Check range of deflection. Hot deflection - cold deflection = 5-3/4 inches - 2-1/4 inches = 3-1/2 inches Read corresponding cold load by checking chosen hanger size at cold deflection = 3800 pounds (Size 14 hangar, 3-1/2 inches deflection) Difference in pipe loads 4,700 hot (3,800) cold 900 pounds Hot and cold loads both within Working Range of Size 14 Figure 98 unit. Order this support preset to 3-1/2 inch deflection.

2. 3. 4. 5.

6. 7.

Note The 900 pounds difference in loading will impose an equal but opposite loading at other supports on equipment. There may be instances where moment forces require even less deflection. In these instances, upsize your hangar selection.
Fig. 300-12 Example Load Table in Pounds for Selection of Hanger Size Courtesy of Anvil International, Inc. (1 of 2) Working Range (in.) 13
1800 1875 1950 2025

Hanger Size 14
2400 2500 2600 2700

Spring Deflection (in.) 15


3240 3375 3510 3645 0

ChevronTexaco Energy Technology Co.

300-27

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-12 Example Load Table in Pounds for Selection of Hanger Size Courtesy of Anvil International, Inc. (2 of 2) Working Range (in.)
0 2100 2175 2250 2325 1 2400 2475 2550 2625 2 2700 2775 2850 2925 3 3000 3075 3150 3225 4 3300 3375 3450 3525 5 3600 3675 3750 3825 3900 Spring Size - lb. per in. 300

Hanger Size
2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 400 3780 3915 4050 4185 4320 4455 4590 4725 4860 4995 5130 5265 5400 5535 5670 5805 5940 6075 6210 6345 6480 6615 6750 6885 7020 540

Spring Deflection (in.)


1

Ordering Description
Information that must be provided when ordering spring supports may vary between manufacturers, but the following data are normally required: Support Type and Figure No. (from manufacturers catalog) Size Desired supporting force in operating position Calculated amount and direction of pipe movements from installed to operating position

April 2004

300-28

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Customers identification number Desired factory spring preset

Spring Support Installation and Maintenance


After installation, and in preparation for startup, field engineers should inspect the springs and remove chocks, if any. Generally, spring supports do not require extensive preventive maintenance, except for inspection and repainting as required to control corrosion. Manufacturers state that spring units are low maintenance items and that periodic checking of operational loads and deflections is generally a more important consideration than physical inspection and maintenance of the unit itself. A frequent problem is that actual pipe loads exceed design loads, and the support bottoms out. This could result in higher concentrated piping stresses. Replacement or readjustment of the spring support is required if this condition is encountered.

330 Equipment Supports


This section of the guidelines discusses the design of elevated equipment support structures. Examples of equipment requiring support include air coolers, exchangers, horizontal vessels, catalyst handling equipment, conveyors, etc. This section is limited in scope to the following situations: To assist engineers reviewing design work by consultants. To provide design guidelines for relatively simple structural supports.

For more complex structures and unusual loading situations, the design work should generally be undertaken by an experienced Company or contractor civil/structural engineer.

331 Design Requirements


Obtain certified vendor prints to define dry and operating weights, critical physical dimensions, foot print of support points, details of equipment supports, and location of appurtenances. A complete understanding is required of the function of the equipment to be supported. The following items need to be addressed: Access stairs, platforms, and ladders required by operators Requirements for routine maintenance Crane access or permanent lifting equipment, (davit or monorails) required for handling equipment or parts which cannot be manually handled by two persons. (Limited to approximately 100 pounds in easy-to-reach location.) Testing plans (hydrotest), weights and sequence

ChevronTexaco Energy Technology Co.

300-29

April 2004

300 Industrial Structures

Civil and Structural Manual

Incremental platform space required as laydown area for equipment to be cleaned or repaired Special equipment loading conditions; for example, vibration or impact loads, or earthquake or wind loads Additional equipment and piping to be supported from the structure Extent of fireproofing required Limitations on vertical or lateral deflections because of closely interconnected piping or equipment Requirements for equipment and piping insulation. It frequently happens that the thickness of insulation is overlooked when determining structural and personnel clearances.

332 Design Loads


All equipment, piping, and electrical loads must be accounted for. Fluids, catalyst or other operating loads must be included. Consider special loading conditions imposed on the structure: thermal expansion, hydrotest, upset conditions, impact loads, tube bundle pulling, etc. For wind and earthquake loading, refer to Section 100.

333 Structural Analysis and Design


Two-dimensional or three-dimensional analysis of the structure is most easily done with a structural computer program. Not all designers, however, will have access to a suitable program, and hand calculations will be necessary. If the designer has limited experience in structural design, the Pipe Support Design Manual (Reference [16]) may serve as a guide for analysis of small support structures using hand calculations for relatively simple, braced frame structures. In the analysis and design of structures, the following important requirements are occasionally overlooked: 1. 2. 3. 4. Proper application of vertical and horizontal loads (bending about both principal axes) to get the most severe combined axial and bending forces. Code check of combined axial compression and bending stresses for structural steel columns. (Refer to AISC Specification.) Consideration of biaxial bending and compression in the design of concrete columns. Appropriate adjustments to allowable stresses (structural steel) for seismic or wind loading, or to factored loads (reinforced concrete).

April 2004

300-30

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

The engineers should verify that these factors have been included in the analysis, if appropriate.

Deflections
The following deflection limits are suggested: Total deflection of beams should generally not exceed 1/250 of the span. For beams supporting closely interconnected equipment, total deflection should not exceed 1/500 of the span. Sideways deflection of structures due to wind/earthquake loads should not exceed 1/100 of the height.

Connections
Shop connections are generally welded. Field connections are generally bolted. For most applications, including onshore coastal areas, no special coating is required for structural bolts. Bolted connections for main structural steel should generally be friction-type connections made with minimum 3/4-inch diameter high strength bolts. Bolted connections for secondary structural steel should be minimum 3/4 inch diameter unfinished bolts, except bolts for stair bracing and handrails may be 1/2 inch diameter, and for stair treads 3/8 inch diameter. Beveled washers should be specified for connections where an outer face of the bolted parts has a slope greater than 1:20. Connections should be designed to provide the full strength of connected members in seismic zones. This allows for absorption of a large amount of energy during an earthquake.

334 Design Considerations for a Corrosive Environment


If the expected atmosphere is corrosive or maintenance will be difficult, this fact should be taken into account when designing steel structures. For example: For primary steel members maintain a minimum thickness for angles and flanges of beams and tees (e.g., 3/8 inch). For secondary members and webs a suggested minimum thickness of 1/4 inch may be appropriate. Double-angle members back to back should be avoided. All welds should be continuous. Provide coatings for bolts.

Where corrosion protection coatings are used for bolts, these coatings should be specified on the drawings or fabrication specifications. Following are comments on the more common types of protective coatings used for corrosive atmospheres, or for marine/coastal areas:

ChevronTexaco Energy Technology Co.

300-31

April 2004

300 Industrial Structures

Civil and Structural Manual

Galvanized. Good corrosion protection. May give some difficulty during removal in the future, as nut may jam in the bolt threads. Cadmium Plated. Good corrosion protection. Can suffer hydrogen cracking in high strength bolts (UTS over 125 ksi) due to hydrogen charging during plating. Controlled by baking out hydrogen after plating. Teflon Coated. Good corrosion protection. Excellent for connections where a future make & break requirement is anticipated. Quality varies, the problem being the presence of holidays. Overtorqued nuts will damage threads. Double nuts are commonly used to avoid loosening. This coating is used extensively in sub-sea applications.

340 Stairs, Ladders, Walkways, Platforms, and Handrails


341 General
It is important that individuals involved in layout or design of stairs, ladders, walkways, and platforms review the appropriate sections in the Safety in Designs Manual (SID) (Reference 15). The Safety in Designs Manual provides a summary reference of safety requirements and recommendations for Company facilities. New facilities or modifications must meet the safety requirements of the Safety in Designs Manual. Company standard drawings referenced herein conform to the requirements of the Safety in Designs Manual and have been checked thoroughly for compliance with the Occupational Safety and Health Act. Company standards are considered more complete than minimum legal requirements and, according to the Compliance Policy, must be followed. Engineering discretion may be used to comply with the Safety in Designs Manual or standard drawing contents, but deviations or omissions from established criteria are acceptable only when documented and specifically authorized by appropriate Engineering supervision or management. Particular attention should be paid to required overhead and side design clearances, details of construction, and to the specific locations where each of the following safety features is required: Railings Toeboards Hoop guards, ladder safety guards and drop bars Ladder cages Landing areas for stairs, ladders and stiles Intermediate landings for stairs and ladders

Compliance with Regulations


The contents of the Safety in Designs Manual are in compliance with OSHA requirements. The 1996 version was generated after extensive review of Federal and California OSHA standards, the Uniform Building Code, the Uniform Fire Code and National Fire Protection Association Standards.

April 2004

300-32

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

There may be local requirements which exceed OSHA or are more restrictive and would therefore supersede the Safety in Designs Manual contents. Engineers, construction reps, or inspectors must be reminded of this fact and encouraged to discuss local requirements with knowledgeable local Company personnel. Note that handrails and guardrails in our refineries must comply with OSHA guidelines and not the Uniform Building Code. Often UBC requirements are not applicable to refinery structures because refineries are not accessible to the public. An example of this is that handrailings for platforms and stairways at locations subject to UBC requirements should have an intermediate rail. UBC requires guardrails such that a 12-inch sphere cannot pass through. However, this requirement is not applicable to most of our facilities. Contract language should require compliance with current Company standards and applicable laws. Existing facilities need not be modified if they meet legal requirements and adequate safety is provided.

Standard Drawings
Wherever possible use the Companys standard drawings for stairs, ladders, and handrails. These drawings meet the requirements of the Safety in Designs Manual, are based on the design loads specified herein, and provide uniformity in designs. A list of standard drawings is in Section 382; the drawings are also included in the List of Standard Drawings and Forms.

Design Uniformity
In all cases the design of walkways, ladders, and stairs should be uniform within any operating area. For additions or modifications to existing facilities, the requirements of the Safety in Designs Manual should normally be followed. However, to achieve uniformity within a specific operating area it may be desirable at times to follow some existing practices. An example would be using tread run and riser heights to match existing stairs. If legal requirements are not met or adequate safety is not provided by following the existing practices in a given facility, then new or modified facilities should comply with the Safety in Designs Manual requirements.

342 Design Loads


The Companys standard drawings and forms are based on the design loads given in this section. There is no need for detailed design unless anticipated loads and conditions differ from these standards.

Stairs
Suggested design load for stair stringers is 100 psf, but the load should not be less than a 1000 lb. concentrated load on the horizontal projected area of the stairs. Stair treads are normally selected from manufacturers standard sizes for a range of tread widths and spans. Manufacturers commonly use a 300-pound design load plus an additional 1/3 impact load for their calculation of recommended spans. This load is

ChevronTexaco Energy Technology Co.

300-33

April 2004

300 Industrial Structures

Civil and Structural Manual

applied at the centerline of the span, and is distributed over the trea nosing and 4 bearing bars.

Platforms/Walkways
Minimum design load for walkways is 75 psf live load. Minimum design loads for maintenance platforms should be 75 psf live load, or 2000-pound, concentrated load placed upon any space 2'-6" x 2'-6". However, such platforms should be designed for the maximum probable loads imposed by the intended use, for example, equipment loads which can be set down on platforms by fixed davits or monorails. Exchanger platforms should be designed to carry exchanger channel and shell covers, but not tube bundles. Ladders. Designed for anticipated usage, but not less than a single concentrated load of 200 pounds. Companys Standard Drawing GF-M88575, Standard Ladders and Guards, has rungs, stringers, and support details that are adequate for loads far in excess of 200 pounds. Railings. Anticipated loads but not less than 200 pounds at any point in any direction on the top rail.

343 Grating and Floor Plate Design and Selection


Grating
Serrated steel grating should be used in the following situations: For platforms where there is a need to see through, such as furnace firing platforms and plot limit block valve manifolds For stair treads (with a distinctive, cast-abrasive, non-skid nosing) For platforms where operating conditions make steel plate with non-skid coating ineffective, such as areas where liquid spillage is expected In wet and cold climates where snow and ice commonly create walkway hazards

At one time, steel plate with non-skid coating was the recommended surface for platforms and walkways above 6 feet from grade. Currently, serrated steel grating is an acceptable option to steel plate. The disadvantages of grating include: On elevated structures some individuals may find serrated steel grating stressful because of the see through aspect. Small objects and tools can drop through to walkways or surfaces below. It is more difficult to work on, and is hard on the knees when kneeling.

Choice between grating and checkered plate is usually based on plant practice. Cost of grating is approximately 33% less expensive and approximately 20% lighter than checker plate.

April 2004

300-34

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

In general, grating should not be used on working platforms because bolts, nuts, and tools can drop through openings. Grating for coastal areas is normally ordered with galvanized coating. Galvanizing permits an extended period of use before first maintenance, as compared to painted grating. New galvanized grating is not normally painted. For inland areas (noncorrosive climates), grating which is painted instead of galvanized may be used if maintenance painting is not anticipated for five years. Maintenance painting of grating has proven to be time consuming and costly. Fertilizer plants and other areas may warrant special coatings or the use of aluminum or fiberglass-reinforced plastic grating. Check with Fire Protection before specifying these materials. Coating or galvanizing should be done after fabrication and attachment of banding. Acceptable manufacturers and types of bar grating for walkways are listed in Specification CIV-EG-398. The type of grating acceptable to the Company is designated as W-19-4, a designation that is universally accepted by the bar grating manufacturers. It has bearing bars on 1-3/16 inch centers, with cross bars at 4-inch centers, and is welded steel. Standards for grating are given in the Metal Bar Grating Manual published by National Association of Architectural Metal Manufacturers (NAAMM). Acceptable grating and serrated surfaces are illustrated in Figures 300-13 and 300-14.
Fig. 300-13 W-19-4 Grating Reprinted with permission of the National Association of Architectural Metal Manufacturers (NAAMM), Chicago, IL

Expanded metal gratings and mechanical locked gratings are not recommended. The only type of expanded metal grating that is acceptable to the Company is Grip Strut Safety Grating. Because of the higher cost over bar grating, Grip Strut is used only in special applications.

ChevronTexaco Energy Technology Co.

300-35

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-14 Serrations Reprinted with permission of the National Association of Architectural Metal Manufacturers (NAAMM), Chicago, IL

Grating used in areas exposed to weather should have bearing bars with 3/16 inch minimum thickness. Grating with 1/8 inch thick bearing bars may be used only in areas protected from weather or corrosion. For most installations, the preferred minimum bearing bar depth is 1-1/4 inch. Bearing bars with 1-inch depth should be limited to stair treads, and short spans, such as over trenches, not subject to vehicle loads. Acceptable spans (the distance between supports in the direction bearing bars run) for grating are based on manufacturers safe load tables, and with a unit stress of 18,000 psi. Figure 300-15 provides recommended maximum spans, safe loads, and deflections for a range of spans and bearing bar sizes. Tables prepared by grating manufacturers are based on the NAAMM table. The tables are designed to provide safe live loads, and the weight of the grating does not have to be taken into account. Safe load tables are based on plain bearing bar grating, and an adjustment must be made for serrated grating to account for reduction in bar depth. This may be accomplished by applying the reduction factors listed in Figure 300-16 to the tabulated safe loads.

Bearing Bar Direction


Grating is generally manufactured in panel sections 3 feet wide with lengths up to 24 feet. Bearing bars run the length of the panels. Layout and framing of walkways and platforms, and the specified direction of bearing bars, should take into account the orientation of the manufactured panels.

April 2004

300-36

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-15 Load TableSteel Grating Courtesy Gary Grating

ChevronTexaco Energy Technology Co.

300-37

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-16 Reduction Factors for Serrated Grating Bar Depth (inches)
1 1-1/4 1-1/2 1-3/4

Multiply by
0.82 0.86 0.88 0.90

To a great extent it is a matter of personal preference as to the direction of run for the bearing bars. Primary considerations are to simplify fabrication, make economic use of material, and provide a consistent layout for a given area. The one exception is that at locations where there is a need to see through, the bearing bars should be oriented for maximum visibility. It is good design practice in the selection of spans for deck grating to limit deflections to 1/4 inch to avoid discomfort to pedestrians from too much flexing of the walking surface.

Fastenings
Normal fastening of platform grating is with 3/16 inch fillet weld 1-1/2 inches long, spaced at intervals not exceeding 18 inches at edge supports, with a minimum of four welds per panel. Grating should be tack welded at 18 inch centers over intermediate supports. For removable grating, such as for access to equipment, use galvanized steel saddle clips to fasten grating to support members as shown in Figure 300-17. Clips are normally secured using Nelson studs welded to the structural supports. Clips may also be secured with self-tapping screws, subject to approval by the operators. Using clips for securing grating is recommended only in locations where panels must be removable. The clips have a tendency to work loose, causing the grating to become uneven, and creating a tripping hazard. Some installations have used Ram set studs for fastening clips. Experience has been mixed: Sometimes they dont properly set. They easily break. They may locally overstress members.

Stair Treads
Stairs serving platforms with grating walking surfaces should be furnished with treads fabricated from the same type grating as the platform. Typical bar size for treads with serrated bars is 1-inch x 3/16 inch, which is suitable for spans up to 2'-6". For stairs wider than 2'-6" the bar size must be increased to 1-1/4 inch or 1-1/2 inch. Each tread should be furnished with a distinctive, non-skid, cast abrasive nosing, which provides protection against slipping. The edge of the platform at descending stairs should also be provided with cast abrasive nosing. Note that actual tread width must equal or exceed the specified tread run. Available stan-

April 2004

300-38

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-17 Steel Saddle Clips Courtesy NAAMM

dard tread widths of 9-3/4 inches, 11 inches, or 12 inches are therefore required to conform with Companys stair requirements. Refer to stair tread illustration shown in Figure 300-18.
Fig. 300-18 Stair Tread Details

Stair treads are generally bolted to the stair stringers. This allows easy change out of damaged or corroded treads without hot work.

ChevronTexaco Energy Technology Co.

300-39

April 2004

300 Industrial Structures

Civil and Structural Manual

Banding
Banding is the welding of a flat bar to a side or end of a grating panel, or along the line of a cutout. The band does not extend above or below the bearing bars, except when it serves as a toe plate. Load-Carrying Band. A band used in a cutout to transfer the load from unsupported bearing bars in the cutout to the supported bearing bars. The band should be welded to one side of each bearing bar with a 1/8 inch fillet weld. Trim Band. A band which carries no load, but is used chiefly to improve appearance or eliminate a safety hazard. In this case, weld the band to every 4th or 5th bar. However, in locations where corrosion is a problem, for example coastal areas, it may be desirable to weld all bars to the band.

Steel Plate with Non-skid Coating


Plain steel plate with a non-skid coating is specified for platforms that do not require grating. Non-skid coatings contain small, hard grit particles that give an abrasive surface, and should be selected on the basis of severity of intended service. For guidelines on the selection of the appropriate coating refer to the Quick Reference Guide in the Coatings Manual. Checkered floor plate is not recommended for platforms and walkways, and its use as stair treads is not permitted. The disadvantages of checkered plates are poor nonskid qualities, difficulty in maintaining paint, and higher cost, which is more than for plain steel plate. Steel plating for platforms is generally fastened to supporting members with intermittent fillet welding or plug welds at intervals not exceeding 18 inches. Where removable plates are required, plate should be fastened with 3/8-inch diameter cadmium plated steel flat head bolts which are countersunk at intervals not exceeding 18 inches. For some installations it may be necessary to specify complete seal welding to provide for liquid containment or because of environmental conditions. Continuous welding of steel plate should be made with 1/8 inch welds to minimize plate warpage. Unless fluid containment is a requirement, a minimum of one 1/2 inch diameter drain hole is generally provided near the center of each panel of platform floor plate, to minimize collection of rainwater. The thickness generally used for steel plate platform surfaces is 1/4 inch. A general rule of thumb in using this size plate is to limit the product of the width and length dimensions to around 24 square feet (example, 4 feet by 6 feet) when supported on four sides. Much larger plate support dimensions could be used that would adequately support a 40 psf live load; however, this would introduce excessive deflection or bounce in the deck when walked upon. Longer support spans also tend to accentuate ponding problems. For these reasons, the short span of the plate is generally limited to a maximum of 4 feet-0 inches with supports at about 6-foot spacing in the long span direction. For short spans, 3 feet-0 inches or less, the long span is not limited. Where joining of plates occurs between framing members, an

April 2004

300-40

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

angle 1-1/2 by 1-1/2 by 1/4 inch should be used under the joint. Gaps between floor plates resting on a supporting member should be limited to about 1/4 inch.

Openings in Platforms
Attention must be given to openings through floorplate or grating required for piping, conduit, or equipment, to avoid the hazard of dropping tools or parts, or creating a tripping hazard. The following general guidelines apply. See the Safety in Designs Manual for specifics. If possible, keep gaps between the floor surface and equipment or piping less than 1 inch. The larger the gap, the more likely a bolt or tool will fall through the gap. Platforms on a horizontal vessel must be extended under the vessels curvature. If gap opening exceeds 1 inch, a toeboard must be provided. Platforms on vertical vessels should not have a space exceeding 1 inch between platform and vessel or surface of insulation for an insulated vessel. If the gap opening exceeds 1 inch, a toeboard must be provided. If the gap is 3 inches or more, guard railing is also required. Platforms bounded by vertical pipes should extend to the centerline of the pipes with cutouts around the pipes not exceeding 1 inch. If the spacing of the vertical pipes exceeds 9 inches, then a guard railing is required. Floor plate openings. Openings should have maximum 1 inch clearance between floor plate and pipe, duct, or equipment. Circular openings 12 inches in diameter and larger, and rectangular openings 12 inches and larger in the smaller dimension should be banded with a toe plate if the opening between the plate and the pipe, duct or equipment exceeds 1 inch. A toe plate increases the maximum acceptable opening to 3 inches. If the gap is 3 inches or more, guard railing is also required. Floor grating openings. Openings in grating with a maximum diameter or side dimension of 12 inches need not be banded, but should have a 1 inch maximum clearance from the equipment. Circular openings 12 inches in diameter and larger, and rectangular openings 12 inches and larger in the smaller dimension should be banded with bearing bars, and should have a maximum clearance between the equipment of 1 inch. A toe plate may be substituted for a bearing bar, in which case the acceptable clearance is increased to 3 inches. If the gap is 3 inches or more, guard railing is required. All openings for pipe should be round.

Stairs
Stair access and platforms are required for: Points which require access for servicing or operating during each 8 hour shift Locations of mechanical equipment Location at which samples are to be taken

ChevronTexaco Energy Technology Co.

300-41

April 2004

300 Industrial Structures

Civil and Structural Manual

Locations for servicing, maintaining, or operating equipment handling H2S Plot limit manifolds

Stair Design
The exact number and locations of stairs will need to be reviewed and accepted by Operations and Safety. For platforms served by stairs, it is convenient to set the elevation above grade, or between platforms, at even multiples of 7-3/4 inches. This will facilitate the use of the Companys recommended standard riser and tread dimensions. Riser = 7-3/4 inches Tread = 9-3/4 inches Where a stairway cannot meet the above requirements, the riser heights and tread run dimensions may be varied provided: Tread run plus riser height dimension equals 17-1/2 inches. Stair slope is between 30 degrees and 40 degrees. All riser heights in any one structure or platform are the same. To the greatest extent possible, all riser heights in a general area are the same.

For stairways starting at grade, where paving is concrete, the stair stringer should be bolted to the concrete. If necessary to maintain riser height, the paving at the bottom of the stair may be raised in height 2 inches to 3 inches and sloped gradually (1:10 max) down to the adjoining paving. If the stair ends on asphaltic concrete, a concrete pad 2 feet-6 inches by 3 feet or larger, should be installed. If necessary, feather the paving up to meet the pad. For unpaved areas with gravel or crushed rock surface, a concrete pad with a minimum landing area of 2 feet-6 inches square or larger, should be provided. The height of this pad should be flush with the surrounding grade, or be set at 3 inches above grade. Refer to Figure 300-19. The top flanges of the channel stair stringers at the base of the stair should be cut off at an angle of 45 degrees, ground smooth, and stringers cut off vertically to match front edge of first tread to avoid creating a tripping hazard. Handrails and midrails should be provided on both sides of stairs serving walks or platforms requiring guardrails and midrails. Midrails should be omitted on the wall side of stairways adjoining walls. In spite of careful planning and effort, it is difficult to make stair stringers at the bottom of a flight of stairs terminate at the as built concrete slab elevation. The reasons for this include: Frequently because of sloping slabs, the exact final grade elevation at the stair location is not known at the time the stair design is executed. Working to normal construction tolerances contributes to dimensional problems in final fit-up of stairs.

April 2004

300-42

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-19 Stair Landings

ChevronTexaco Energy Technology Co.

300-43

April 2004

300 Industrial Structures

Civil and Structural Manual

Slabs adjacent to pile-supported foundations may settle with respect to the structure. This can be a continuing problem during the life of the installation. If this problem is expected to occur, it may be desirable to support the bottom of the stair off the foundation, or a pile-supported landing pad might be considered.

The normal remedy for correcting elevations at the bottom of stairs is to build up the slab, and to slope up the paving around it as illustrated in the Safety in Designs Manual. The 2 feet-6 inches by 2 feet-6 inches minimum flat landing area dimension must be maintained.

344 Ladders, Cages, and Guards


Platforms for which ladder access must be provided include: Locations which require access for operating equipment such as valves and motors, when access is required less frequently than once per 8-hour shift. Locations requiring access for maintenance only of appurtenances such as manholes, column or vessel nozzle flanges, relief valves, removable heads or covers, for example. Platforms need not be provided for services less than 15 feet above grade when access is required only for maintenance, if they can be reached from temporary tubular scaffolding without interfering with operating or emergency access to equipment.

For platforms served by ladders it is generally desirable to set the elevation above grade, or between platforms at even multiples of 1 foot-0 inches. Inclined ladders are undesirable. If used, because clearance problems require the ladder to be sloped, the incline forward shall not be greater than 15 degrees from the vertical. Side access ladders are preferred to front access ladders, as entry at the top of the ladder is easier and safer. Ladders should be arranged so the user faces toward equipment or structures rather than facing open space. Ladder rungs must be positioned so that the centerline of the rung at the top platform is at the same elevation as the top of the platform walking surface. Where more than one platform is served by a ladder, intermediate platforms should be located so that the top of each platform lines up with the centerline of a ladder rung. The spacing between ladder rungs should be maintained at 12 inches and the bottom rung should be 6 inches to 18 inches above the platform or finished pavement. The space around a ladder that must be kept free from obstructions is the same as the space required for a standard ladder cage, whether a ladder cage is provided or not. The minimum clearance behind ladders is 7 inches measured from the centerline of the ladder. Common problems are conduits, stiffening rings, foundations, field routed small piping, or insulation that reduce the 7 inch clearance. Minimum side clearance is 15 inches from centerline of ladder with minimum 30 inches clearance in front of ladder. This 30 inch by 30 inch clearance envelope includes the

April 2004

300-44

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

bottom landing area of the ladder and extends upward for the full length. Ladder stringers and rungs must be kept free of attachments other than those required to support the ladder. Ladders which could be climbed inadvertently on the back side must have a barrier installed per Drawing GF-M88575. The maximum vertical run of ladder must be 30 feet. Ladders attached to equipment subject to thermal expansion must be provided with slotted support clips at the ladder feet. Cages must be provided on all ladders serving platforms 20 feet or higher above grade. Drop bars must be provided on all ladders serving platforms which are 2 feet-6 inches or higher above grade. Hoop guards must be provided on all ladders serving platforms 10 feet or higher above grade.

350 Guyed Stacks


This subsection discusses the use, design, and installation of guys for stack support. Discussion of other structural topics, such as vortex shedding, foundations, or deadmen, is not included.

351 Use and Layout


Guys are required to provide structural stability for furnace stacks and flare stacks that cannot be designed as self-supporting. Layout of guys is dependent on space availability, height of stack, number of guys required, obstructions, clearances over roads, and layout of roads and other facilities in the area. The primary objective must be to provide: A safe design for structural support of the stack under all conditions Physical protection of the guys themselves from moving vehicles or construction equipment

Except where there is no alternative, guys should be oriented to avoid crossing roads. Where guys cross roads, the minimum clearances given in the Safety in Designs Manual (Reference [15]) should be maintained. Deadmen should be located as far from roads as possible, but a minimum of 25 feet outside of road shoulder is recommended. If guys and deadmen could be exposed to vehicle damage, or if there is a hazard to personnel, suitable guy protectors should be provided. The most efficient angle of inclination from the horizontal for guys is 45 degrees. In practice this is not always possible due to layout requirements, and frequently guys attached at multi-levels to the stack will be anchored at the same deadman.

ChevronTexaco Energy Technology Co.

300-45

April 2004

300 Industrial Structures

Civil and Structural Manual

Guys with angles of inclination less than 30 degrees are not as efficient because the corresponding sags and cable elongation are greater than for guys with steeper inclination. The effect is greater stack deflection under design loading conditions. Guys with inclination angles over 60 degrees are subject to greater axial tension, and the vertical component of the guys increases axial loads to the stack.

352 Design
The maximum working loads for guys are determined from the following parameters: Geometry of guys Number of guys at each level Number of guy levels Wind/seismic loading Weight of guy itself Ambient temperature changes Stack temperature changes Initial guy tension Coefficient of thermal expansion (guys and stack) Modulus of elasticity for guys

The calculation of maximum working loads usually requires consideration of a number of loading cases for the various environmental loads and operating temperatures. Because of the inelastic properties of guy systems, analysis can be done more quickly and accurately with computer programs. However, the relationships shown in Figure 300-20 will provide reasonable approximation of design guy loads.

Guyed Stack Design


Stresses in guyed stacks include: Compressive stresses from combined stack weight, lining, attached equipment and the vertical component from guy tension Bending moment stresses from wind or earthquake Shear stresses due to wind or earthquake

Local Buckling Stresses


Unstiffened cylindrical shells fabricated from carbon and low-alloy steels should be investigated for local buckling due to axial compression and bending when: D/t > 60 where: D = diameter (inches) t = shell thickness (inches)

April 2004

300-46

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-20 Uniformly Loaded Cables with Inclined Chords

For cylindrical shells not subject to internal or external pressure, the longitudinal tensile stress under loading conditions including wind or earthquake should not exceed 85% of the yield stress at the operating temperature at the section under consideration. The efficiency of full-penetration, butt-weld joints should be taken as 1.0. The compressive stress for carbon and low-alloy steel shells operating at atmospheric temperature should not exceed 2/3 of the minimum specified yield stress nor 2,320,000 t/R (psi) where t is the shell thickness and R is the radius, both in inches. The expression 2,320,000 t/R is based on modifying the classical buckling stress formula for a cylindrical shell given as CE t/R with C = 0.08 and E = 29,000,000 psi. For shells operating at high temperatures, and for other materials, the allowable compressive stress should not exceed the following: For cylindrical shells designed prior to the Summer of 1983 Addenda of the ASME Code: 1/3 greater than the allowable compressive stress permitted by the applicable edition of the ASME Code.

ChevronTexaco Energy Technology Co.

300-47

April 2004

300 Industrial Structures

Civil and Structural Manual

For cylindrical shells designed in accordance with the Summer 1983 Addenda or subsequent editions: the allowable compressive stress permitted by the ASME Code.

For structural analysis of the stack see References [11] and [13]. These references also address the analysis and design of ring girders and stiffeners at guy line supports to the stack. In structural analysis of stacks, it is important to establish the amount of corrosion allowance to be considered. For a discussion of vortex shedding for stacks, refer to Section 100, Wind and Earthquake Design Standards.

Initial Guy Tension


Initial tension, applied to the guys during erection, is between 5% and 12% of the minimum breaking strength. In selecting the amount of initial tension, the intent is to maintain some tension at all times on each of the guys regardless of the direction of the full design wind load. For the maximum operating condition (thermal expansion of the stack) the maximum working loads for guys is kept to about 20% of the minimum breaking strength. For combined operating conditions and wind or earthquake loading, the maximum guy loads are kept to 25% to 40% of the minimum breaking strength.

Maximum Design Loading Conditions


Steps for determining maximum design loading conditions on guys: 1. Select wind direction for maximum wind loads for any individual guys. Calculate wind loads on contributory area of stack, attachments, and guys. Refer to Section 100 for wind forces and shape factors. 2. Determine loads contributed by opposing guys under the design wind load conditions. This is an iterative process taking into account initial guy tensions and stack deflection. Determine added loads from thermal expansion or contraction of the stack and guys. Check for seismic loading on the stack.

3. 4.

Judgment will be required as to how these loads are combined. For many cases the maximum design wind loads and thermal loads are directly additive. In other cases the maximum wind loads (hurricane) would not be expected to occur concurrently with maximum operating thermal loads. In such cases it would be appropriate to establish a maximum operating wind load. For a detailed discussion of guyed stack design refer to Structural Engineering Handbook (Reference [11]).

April 2004

300-48

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Guy Wire Material


For most guys, it is recommended that structural strand (or Bridge Strand) be specified rather than wire rope.

Strand
The carrying capacity of a strand is greater than that of a rope of the same diameter. The outside surface of strand is smoother than that of wire rope. It is easier to protect with paint or other covering. Accessory fittings used with strands are smaller than those used with a comparable capacity wire rope because the strand diameter required for a given load is smaller. Strand has a higher modulus of elasticity than wire rope. Strand provides the minimum exposed surface area to the environment.

Wire Rope
Wire rope is easier to handle in the field than strand because it is more flexible. Because wire rope can be bent to a shorter radius than strand, smaller diameter ropes can be installed using thimbles and clips. This makes the fabrication of guys much easier in the field.

The following ASTM Specifications apply: A-475 Zinc-Coated Steel Wire Strand (for sizes up to 5/8 inch) A-586 Zinc-Coated Structural Strand (for sizes over 5/8 inch) A-603 Zinc-Coated Structural Wire Rope

Structural strand and wire rope are specified as 1 x (number of wires around the core combined in sets of 6); for example, 1 x 7, 1 x 19, 1 x 37, 1 x 61. The core recommended is an Independent Wire Rope Core (IWRC). The use of fiber core is not recommended because of reduced physical properties during the life of the guy.

Coatings
Three different zinc coating weights are available. Class A is the equivalent of double galvanized coating weight. Class B is twice the weight of A, and Class C is three times A. All conform to ASTM specifications. Structural strand or structural wire rope are available in A, B, and C coating weights. Combinations are also available with Class A for inner wires, and the heavier galvanizing, Class B or C, used for outer wires. The choice of coatings should be based on review of the environmental exposure, and experience with other galvanized surfaces at the same location. For most applications, Class A coating is appropriate. In locations where galvanized surfaces experience problems, then Class B or C would be justified.

ChevronTexaco Energy Technology Co.

300-49

April 2004

300 Industrial Structures

Civil and Structural Manual

Tables in ASTM A-586 and A-603 give minimum breaking strength for structural strand and structural wire rope respectively. These tables are based on 220,000 psi minimum ultimate tensile strength. The table for strand generally applies to guy material that is over 5/8 inch diameter. For strand 5/8 inch and smaller, the most readily available strand conforms to ASTM A-475. This strand comes in 4 grades: Common, Siemens-Martin, High Strength, and Extra High Strength. For general guy wire applications, the grade most readily available is Siemens-Martin.

Prestretching
Elongation of a steel cable results from a combination of elastic or recoverable stretch of the steel and inelastic or constructional stretch. Constructional stretch is a variable quantity governed by the size of equipment utilized in the manufacture of the cable, the arrangement of the steel wires within the cable, and the length of helical pitch of the cable components. To minimize the effect of the constructional stretch, the cable can be prestretched by applying a predetermined tension, generally not exceeding 55% of the rated breaking strength of the cable. Prestretching takes up slack in the cable construction (windings) without plastically deforming the wire. It leaves the cable with well defined and uniform elastic properties. A tolerance of 1 inch in 100 feet can be expected if proof loading and prestretching are performed at the manufacturing plant. Prestretching makes determination of lengths and fitting positions much easier in the field. The requirement for prestretching is based on the judgment of the designer. For long or large diameter guys, specify prestretching per ASTM A-586. For guys less than 1 inch in diameter and 250 feet long, prestretching will probably not be required, but manufacturers estimate of constructional stretch should be considered.

353 Installation
Guy Fittings
End terminations for structural strand are most often done with socket fittings, as shown on CIV-EF-336. Use Type 6 to avoid creating any bending in the strand. Sockets are designed to develop the full breaking strength of the strand, and are attached by brooming out the end of strand after it is installed through the socket and filling the socket cavity or basket with molten zinc or special epoxy designed for this application. Turnbuckles are commonly used for adjusting the guy length during installation and for tension adjustment in service. Turnbuckles should be specified with jaw or eye type terminations and not hook type. An alternative to turnbuckles is the bridge strand socket as illustrated in Figure 300-21. Bridge strand sockets are manufactured by Esco Ltd., Scarborough, Ontario. The advantages of the bridge strand socket are: Much greater takeup - up to 72 inches Easier to make the takeup - less torque required

April 2004

300-50

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Does not tend to twist the guy during tightening

Installation Planning
Before installing a guyed stack, a detailed procedure should be prepared. Items that should be included are: Ground assembly of stack or stack sections Lifting procedures for stack or section, supported by calculations to demonstrate that stresses during lifting or upending do not exceed allowables

Fig. 300-21 Bridge Strand Socket Courtesy ESCO

Temporary supports if required during installation Handling and attachment procedures for guys to the stack Detailed procedures outlining the equipment and the steps required to attach lower guy connection to deadman Procedures for tensioning and measurement of guy tension. These procedures should address the steps to be taken to assure that all guys connected to the same attachment level on the stack are tensioned uniformly throughout the procedure.

Guy Tensioning
For guys over 5/8 inch, a separate tensioning device is frequently used for installation. This may be a hydraulically operated tensioner, in which case a direct measurement of tension can be calculated. With this procedure the turnbuckle or bridge strand socket is tightened only after the guy is tensioned to the full design initial tension. When it is noted that the load is fully transferred from the installation device by takeup of the turnbuckle or bridge strand socket, the desired guy tension has been reached. Another method of checking for guy tension during installation or in service is with a tension indicator. The measuring device is mounted directly on the guy. Instruments are available from Martin-Decke-Division Cooper Industries, Inc., for guys from 1/4 inch to 1-1/2 inches. The tension indicator operates by producing a slight

ChevronTexaco Energy Technology Co.

300-51

April 2004

300 Industrial Structures

Civil and Structural Manual

calibrated offset in the guy wire between two fixed points. The pressure to make this offset is a measure of the load on the line. The deflection is slight so that no permanent set or distortion takes place.

Guy Protectors
Where guys are located near roads, pathways, or structures requiring frequent attendance, attach protectors made of wood moulding of 4 inch boards painted yellow and black and extending at least 7 feet above the ground. Where vehicles may be a hazard to guys, install guard posts in accordance with Standard Drawing GA-S99975.

354 Maintenance
Provided guys are adequately protected from corrosion and have not suffered from physical damage, a long service life is expected. They should, however, be regularly checked visually for their condition, and for loss of tension. Changes in tension can frequently be observed visually by viewing the entire length of the guy from a point directly off to one side. Guys under design initial tension exhibit little or no observed sag (catenary) when viewed in this manner. If an increase in sag is observed, a program to make actual tension measurements should be initiated. Guys that are viewed along the length of the guy, from the deadman to the attachment of the stack, will exhibit some catenary regardless of the amount of tension. If for some reason it becomes necessary to replace a single guy or a group of guys, a carefully planned procedure to do this work must be developed. Temporary bracing should be provided to accommodate all loads normally taken by the guy(s) being replaced. When releasing the tension of any guy, all other guys connected to the same stack level shall be slackened at the same time to maintain balanced loads on the stack. Maintaining structural integrity of the support system is paramount. The connection of guys to the top of flare and furnace stacks should be checked regularly, probably not exceeding 5-year intervals. This area could be subject to corrosion because of the flue gas. Interior shell corrosion has also been found at the location of attachments either because of differential cooling, or because the area was affected by the welding. The thickness of the stack must also be checked on a regular basis. The guy/stack system depends upon the stack to provide some structural support. When the stack thins due to corrosion, the stack can be overstressed and buckle during a design wind or seismic event. The critical section of the stack is usually at the bottom, so that area should be checked more carefully.

360 Pipeway Crossings and Roadway Bridges


This section discusses the typical options available for pipeway crossings at roads and railroads. The topics discussed include: General Considerations Buried Lines Without Casings

April 2004

300-52

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Buried Lines with Casings Corrugated Pipe Arches Overhead Pipeway Crossings Bridges for Pipeway Crossings Design Considerations Design Loads Types of Bridge Construction

Design of pipeway crossings is normally done by civil engineers. To comply with local requirements it may be necessary to have drawings and specifications for crossings signed by a registered engineer. For additional guidance, consult the Companys Pipeline Manual (Reference [21]) and API RP1102 (Reference [14]).

361 General Considerations


The type of pipeway crossing for a particular installation must be determined after consideration of the following: For crossing outside of Company facilities the design requirements mandated by the local or state highway authorities, or railroad company, that have authority for review and approval of crossings Elevation of lines with respect to the roads or railroads to be crossed Traffic volume Requirements for rail, truck or crane loadings Number of lines in the pipeway. Expectations for future lines Possible obstructions, particularly underground Soil conditions, including requirements for piling Elevation changes to roads required to accommodate crossing (dictated by depth of bridge structure or minimum earthfill over lines) Requirements for removable deck rather than fixed deck for bridges Area drainage Leak detection requirements Future maintenance requirements Work space limitations Overhead power lines and other obstructions that could restrict construction equipment Acceptable interruptions to traffic flow Available detours for traffic

ChevronTexaco Energy Technology Co.

300-53

April 2004

300 Industrial Structures

Civil and Structural Manual

362 Buried Lines


Buried Lines Without Casing
Uncased lines in earthfill are the least expensive crossings to install. They are normally limited to crossings within Companys own facility or to rural roads with low traffic loads. Uncased crossings are commonly used when only one or a few lines are involved in the crossing, and the probability is low that future lines will be installed at the same crossing. Because of concerns for corrosion and physical damage to buried lines, and the consequences related to repairing or replacement at a road crossing, attention should be paid to pipe coatings, pipe wall thickness, and details of the installation. For information on acceptable coatings used on buried lines refer to the Companys Coatings Manual. The disadvantages of the uncased crossing include: future repair or replacement costs for the lines can be higher than other crossings; spacing between lines is greater than normal pipeway spacing; the addition of future lines or other work in the vicinity of the crossing will be made more difficult; and detection of leaks is difficult. Installation. Installation of uncased crossings can be made with an open trench when traffic can be diverted. At other times it may be necessary to install lines by jacking or drilling operations. The diameter of hole for bored or jacked installations should not exceed the pipe diameter (including coating) by more than 1 to 2 inches to avoid excessive settlement around the pipe. If the pipeline is installed within an open trench, care must be taken to ensure that the line is uniformly supported throughout its length and backfill is thoroughly compacted. For open trench installation, the width of the trenching should not exceed the nominal pipe diameter by more than 2 feet. For determination of pipe stress due to external loads, and combined internal and external loading stress, refer to API RP 1102, Recommended Practice for Liquid Petroleum Pipelines Crossing Railroads and Highways (Reference [14]), or the Companys Pipeline Manual (Reference [21]) Section 400 and Appendix I. Refinery piping may not be considered a pipeline, but the principles in this procedure are the same as for piping. Typical installations for the uncased crossing are illustrated in the sketches in Figure 300-22.

Buried Lines With Casing


Cased lines through earthfill are more expensive than uncased, but less than other types of crossings. They are the common requirement for crossing single lines or a few lines under highways or railroad rights-of-way. The counties or other local jurisdictions where these crossings are located, or the railroad involved, will have regulations governing the requirements for cased crossings. Each line should be placed in its own casing. Cased lines are less subject to physical damage and line integrity at the crossing is more easily monitored. For selection of coatings for the line and casing refer to the Companys Coatings Manual. The disadvantages of the uncased pipeway crossing with regard to additional pipeway width and future line installation applies equally to cased lines.

April 2004

300-54

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-22 Example of Uncased Crossing Installations Courtesy API

The major problem with cased lines is maintaining electrical isolation between the line and the casing. This is particularly true for lines that are continuously buried, that is, the ends of the casing do not daylight on both sides of the crossing. If the pipe shorts out against the casing, corrosion of the line will occur as it becomes anodic with respect to the casing, and a heavy drain on a cathodic protection system can result. Methods to limit problems include: Use cased line crossings only where required. Avoid, if possible, placing cased crossings where ground water is present. Take special care to avoid damage to coatings during installation.

ChevronTexaco Energy Technology Co.

300-55

April 2004

300 Industrial Structures

Civil and Structural Manual

Use care to design and install line support insulators and end seals to centralize and isolate line. Provide corrosion protection coating for casing. Provide a secondary seal over the end seal. This can be a vinyl sleeve fitted and clamped to the line and to the casing.

Installation. Installation methods for cased lines are similar to those used for uncased lines. For determination of wall thickness for the casing refer to API RP 1102 (Reference [14]). Refer to Figure 300-23 which illustrate cased rail and highway crossings showing the recommended cover given in API RP 1102 (Reference [14]). For additional details and construction notes refer to API RP 1102
Fig. 300-23 Example of Cased Crossing Installations Courtesy API

Railroad Crossing Minimum Cover Location Minimum Cover


Under track structure proper, except secondary and industry tracks Under track structure proper for secondary and industry tracks Under all other surfaces within the rightof-way from bottom of ditches For pipelines transporting HVL 5.5 feet (1.7 meters) 4.5 feet (1.4 meters) 3 feet (0.9 meters) 4 feet (1.2 meters)

April 2004

300-56

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Figure 300-24 shows details of end seals and concentric support insulators for cased pipe crossings. The end seals are designed to provide positive hydrostatic protection from water or soil entering between the pipeline and casing. The concentric support insulators center the pipe within the length of the casing, making it easier to install the end seals, and to electrically isolate the carrier pipe from the casing pipe. After installation, a resistance check must be made to confirm that the carrier pipe is isolated from the sleeve.
Fig. 300-24 Cased Crossing With Concentric Support Insulators (Lines Under 150F)

API Recommend Practice 1102 states that vents are not required for casings. However, this requirement should be determined for each individual installation, and may be mandatory for rail and highway crossings.

363 Corrugated Pipe Arches


The use of corrugated steel pipe arches to protect lines crossing under roads permits the installation of a number of lines within the same enclosure. Figure 300-25 illustrates the use of this type of structure for crossings. Corrugated pipe arches can be obtained in a variety of spans from 6 feet to 20 feet wide with rise dimensions from about 4 feet to 13 feet. Since the arches are fieldassembled of individual standard-sized corrugated sheets bolted together, there is no restriction on the overall length for arched enclosures. The corrugated sheets are available in a number of thicknesses to safely support various combinations of dead and live loads. Corrugated pipe arches offer these advantages: Permit normal pipe spacing to be continued through the crossing Allow personnel access to lines for inspection, leak detection, and maintenance Provide space for future lines

Disadvantages include the need to reroute traffic for a considerable period of time in order to excavate a large cut through the roadway to install the arched structure.

ChevronTexaco Energy Technology Co.

300-57

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-25 Corrugated Pipe Arch

Corrugated pipe arches are more expensive than cased and uncased lines. Depending on the relative elevations of the pipeway and road, it may be necessary to elevate the road at the crossing to adequately clear the arched pipe enclosure. Manufacturers catalogs for corrugated pipe arches provide loading tables for their product. Selection of appropriate thickness of corrugated plate is relatively straightforward, and is based on earth fill over the structure, vehicle live loads, and span dimensions.

364 Overhead Pipeway Crossings


The advantages of using overhead pipeway crossings include easy access for inspection and maintenance work on lines and the ability to add more lines in the future. Disadvantages may include building pockets in lines that trap fluid and other material, and greater exposure to physical damage. Costs associated with overhead pipeway crossings are probably midway between costs for buried crossings and for bridges. Overhead pipeway crossings over unrestricted roads or railroads should have a minimum clearance of 22 feet-6 inches for a width equal to the width of the approaching road including shoulders. For limited access roads a vertical clearance of 15 feet-0 inches should be maintained. In any event, the clearances provided will require approval by facility operators on Company property, and the designated authorities for highway or rail crossings. For design of overhead pipeway crossings, see Section 320, Piping Support.

April 2004

300-58

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

365 Bridges for Pipeline Crossings


This section discusses basic considerations for designing bridges for pipeway crossings. Design loadings and types of construction are discussed.

References:
Standard Specifications for Highway Bridges, adopted by the American Association of State Highway and Transportation Officials (AASHTO) PCI Design Handbook - Precast and Prestressed Concrete ACI Manual of Concrete Practice AISC Manual of Steel Construction ACI 318 Building Code Requirements for Reinforced Concrete

Design Considerations
Engineers designing bridges should be familiar with AASHTO Standard Specification for Highway Bridges. Good judgment should be exercised in using the design criteria set forth by AASHTO because of the following special conditions applicable to Company bridges: Better control of bridge loading of heavy construction equipment than heavy equipment loading on public highway structures Low volume of vehicle traffic Better control over physical inspections Vehicle speed control to reduce vehicle impact loads Better recorded history of extreme loading conditions Maximum vehicle loads may be considered individually and may not have to be combined with concurrent loading from other vehicles.

In addition to designing bridges, engineers frequently are called upon to provide load ratings for existing bridges. To assist in this effort, a Bridge Rating Procedure is included in an appendix to the AASHTO document.

Design Loads
Historically, bridges tend to be under-designed for the vehicle loads that occur during their lifetime. Bridges, however, have a long service life if properly maintained. Some Company facilities have operable and safe bridges that were constructed in the 1930s, but vehicle loads from cranes and heavy transport trucks have gone up dramatically over the past 40 years. Further escalation in loadings cannot be ruled out, and the possibility of future increases should be considered when load criteria are established for new bridges. Figures 300-26 and 300-27 define AASHTO H15, H20, HS15, and HS20 standard truck dimensions, and lane loading.

ChevronTexaco Energy Technology Co.

300-59

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-26 Lane Loading

The table in Figure 300-27 compares axle loads for AASHTO design loading with vehicles commonly used within Company facilities, in this case the Richmond Refinery.

April 2004

300-60

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-27 Axle LoadsCranes and Trucks Courtesy AASHTO

Axle Loads(1) Cranes


75 ST P & H (W/12K CWT + 105' Boom) 80 ST Grove (W/13K CWT + 114' Boom) 90 ST P & H (W/25K CWT +50' Boom) 140 ST P & H (W/30K CWT + No Boom) 40 ST Link Belt HSP-8040

Feet F4
38.5K 39.2K 40.1K 33.7K 0

F1
19.0K 20.3K 25.8K 37.0K 0

F2
19.0K 20.3K 25.8K 37.0K 41.3K

F3
38.5K 39.2K 40.1K 33.7K 38.4K

A
4.5 4.5 4.5 4.5 0

B
14.15 14.25 14.7 14.83 12.6

Axle Loads Trucks


AASHTO H-15 AASHTO HS-15 AASHTO H-20 AASHTO HS-20 LPG Truck40 ST Vacuum Truck40 ST Flat Bed40 SST Container40 ST Asphalt Truck40 ST Gasoline Tanker40 ST Flat Bed40 ST

Feet F4
0 24.0K 0 32.0K 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K

F1
6.0K 6.0K 8.0K 8.0K 8.0K 8.0K 8.0K 8.0K 8.0K 8.0K 8.0K

F2
24.0K 24.0K 32.0K 32.0K 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K

F3
0 0 0 0 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K

F5
0 0 0 0 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K 18.0K

A
14.0 14.0 14.0 14.0 15.0 15.0 15.0 15.0 18.0 18.0 18.0

B
0 0 0 0 5.0 5.0 5.0 5.0 4.0 4.0 4.0

C
0 14 TO 30 0 14 TO 30 28.0 28.0 28.0 28.0 19.0 19.0 19.0

D
0 0 0 0 4.0 4.0 4.0 4.0 19.0 19.0 19.0

(1) Axle loads for cranes are based on normal travel position with boom facing rear or forward for best distribution of loads.

ChevronTexaco Energy Technology Co.

300-61

April 2004

300 Industrial Structures

Civil and Structural Manual

For any new installation it will be necessary to consider present and future loading requirements with the facility operators. The AASHTO specification provides procedures for determining impact loads and longitudinal loads. Since Company-owned bridges are subject to restricted loading and use, as previously discussed, designers may find it appropriate to make adjustments to these loads. Lateral vehicle loading can generally be neglected.

Types of Bridges
Selection of the type of bridge construction to be used for a particular installation will depend on: Design vehicle live loads Requirements for removable deck panels Required number of spans Economics Construction schedule Underground obstructions or existing pipeway that will dictate location of bridge abutments and intermediate piers Working space between pipeway elevation and desired roadway elevation

Five types of bridge structures, based on the materials of construction, are: Reinforced concrete, cast-in-place with fixed deck Removable precast, prestressed deck slabs Removable precast reinforced concrete deck slabs, supported on steel beams Fixed composite deck of reinforced concrete slab and steel Removable steel deck grating supported on steel beams

The five types are illustrated in Figure 300-28 and a comparison of advantages and disadvantages is given in Figure 300-29.

370 Computer Programs For Designers


PC-based computer programs for the analysis and design of frame structures are available from outside vendors. The Civil & Structural (C&S) Technical Services Team supports such programs. Contact the C&S Team for assistance in accessing and using the programs. An example is STAAD III Analysis and Design of ThreeDimensional Structures, discussed below. Other examples include SAP 90, RISA, STARDYNE, and PCA.

April 2004

300-62

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Fig. 300-28 Typical Bridge Types

ChevronTexaco Energy Technology Co.

300-63

April 2004

300 Industrial Structures

Civil and Structural Manual

Fig. 300-29 Comparison of Bridges for Pipeline Crossings Advantages


Cast in Place Concrete Probably the lowest cost structure.

Disadvantages
Limits access to lines below.

Long service life expected with low main- Limited to shorter span lengths (8'-10') tenance. without intermediate piers. Low elevation of roadway above lines. Removable Prestressed, Precast Concrete Panels Deck is removable for access to lines. Long service life. Low elevation of roadway above lines. Makes future expansion more difficult. Limited to short span lengths for heavy loads without intermediate piers. Special equipment required in precast yard or in field for prestressing.

Cost may be lower than other removable Deck panels can be damaged during panels depending on availability of handling when removed. precast yards. Removable Concrete Deck Slabs on Steel Beams Long service life. Can be used for longer spans than prestress panels only. Deck is removable for access to lines and inspection of bridge structural members.

Total depth of bridge is greater than other bridge types, increasing the distance between the pipeway and roadway elevations. May require ramping up of road at crossing. Structural steel beams will limit access to lines for minor alterations. Structural steel is subject to corrosion.

Fixed Reinforced Composite The continuous concrete bridge deck Deck provides a near trouble-free surface. Can be used for longer spans without intermediate supports. Removable Steel Deck Grating Supported on Steel Beams Provides full access to the lines below. Can be used for a range of widths and span lengths.

Cost is high relative to other bridge types. No direct access to the lines in the pipeway under the bridge. Structural steel is subject to corrosion. Higher maintenance because of the exposed steel. Cost is relatively high. Lines below are not protected from falling debris. Surface does not provide as good traction as concrete in bad weather.

371 STAAD III


General Information
STAAD III performs analysis and design of three-dimensional steel, concrete, and timber structures subject to static or dynamic loading. Structure models may include beam, truss, and user defined elements. Models may be input using either a text file or a graphic input generator. The program will design steel, concrete, and timber structures to AISC (both ASD and LRFD), ACI, and AITC codes, respectively. The dynamic analysis module allows both response spectrum and time history analysis.

April 2004

300-64

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Output
Printed analysis results include the following: Support Reactions Member Forces Joint Displacements and Rotations Code Checking / Design Results

Plots of input geometry, applied loads, mode shapes, deformed shapes, and shear and moment diagrams can be generated and printed on either a printer or plotter.

380 Model Specification, Standard Drawings, and Engineering Forms


381 Model Specification
CIV-MS-398 Steel Fabrication is included in the Specification section of this manual. This Model Specification lists acceptable steel materials and welding processes, describes the minimum requirement for fabrication, surface preparation, painting, and marking, and includes inspection guidelines.

382 Standard Drawings


The following standard drawings either are included in the Standard Drawings and Forms section of this manual or are available in other manuals as indicated. GA-M1001 GB-M1002 GD-M13909 GD-M13966 GF-M88575 GF-D99639 GF-M99645 GB-M99653 GF-C99694 GF-M99874 GF-M99931 GD-M99971 GA-S99975 Standard Stile, Type 1 Standard Stile, Type 2 Standard Clips Standard Steel Stairs Standard Ladders and Guards Circumference Stair, Platform for Tanks (in Tank Manual) Standard Railing Standard Pipe Shoes and Pipe Shoe Anchors (in Piping Manual) Standard Details for Support Feet for Horizontal Vessels (in Pressure Vessels Manual) Guide Sheet for Pipe Supports (2 pages) Guide for Typical Details of Platforms for Vertical Vessels Design Guide for Cantilever Brackets for Vertical Vessel Platforms Standard Details for Removable and Stationary Guard Posts

ChevronTexaco Energy Technology Co.

300-65

April 2004

300 Industrial Structures

Civil and Structural Manual

383 Engineering Forms


The following Standard Engineering Forms relating to this section are included in the Standard Drawings and Forms section of this manual or are available in other manuals as indicated. CIV-EF-79 CIV-EF-336 CIV-EF-588A CIV-EF-588B PIM-EF-595 CIV-EF-632 PIM-EF-739 CIV-EF-799 A through F Details of Stanchions Details for Guys and Deadmen Precast Concrete Stanchions Precast Concrete Stanchions T Type Clips for Vertical Vessels (in Pressure Vessels Manual) Low Walks Clips for Horizontal Vessels (in Pressure Vessels Manual) Pipe Support Details

390 References
1. Manual of Steel Construction. American Institute of Steel Construction, Inc. Summary: Manual includes the dimensions and properties of standard structural members for design and detailing. Includes sections on beam, column, and connection designs. Includes AISC Specification for the Design, Fabrication & Erection of Structural Steel for Buildings. 2. Structural Welding Code AWS D1.1. American Welding Society. Summary: Covers welding requirements applicable to welded structures. Establishes qualification standards and testing requirements for weld procedures, tackers, and welders. Establishes standards for inspection and nondestructive testing of welds. 3. The Companys Welding Manual. Summary: This manual gives a good technical explanation of welding processes, equipment, inspection methods, and guide to weld inspection. 4. ACI Manual of Concrete Practice. American Concrete Institute Publication. Part 1 Part 2 Part 3 Part 4 Part 5 Materials and General Properties of Concrete Construction Practices and Inspection Design, Specifications, and Related Topics. (Includes ACI 318, Building Code Requirements for Reinforced Concrete.) Bridges, Substructures, Sanitary and Special Structures. Structural Properties. Masonry, Precast Concrete

April 2004

300-66

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Building Code Requirements for Reinforced Concrete (ACI Standard 318) provides the minimum requirements for any reinforced concrete design or construction that is regulated by a general building code. Includes: analysis and design, development of reinforcement, and reinforcement details. 5. Uniform Building Code. International Conference of Building Officials. Summary: A general building code that provides the minimum requirements for fire, life, and structural safety aspects for buildings and related structures. It includes engineering regulations on quality and design for steel, concrete, and other materials. Editions of this code are published at approximately three-year intervals. 6. ASTM Standards in Building Codes. American Society for Testing Materials. Summary: Provides standard specifications, test methods, and definitions for structural steel shapes and plates, cement, concrete, reinforcement, and other materials used for buildings and structures. 7. Standard Specifications for Highway Bridges. Adopted by The American Association of State Highway and Transportation Officials. Summary: Provides a standard specification for the design of highway bridges including standard vehicle loads, placement of loads for maximum moment, shears, and reactions. 8. Design Handbook in Accordance with the Strength Design Method of ACI 318. American Concrete Institute. ACI 340.1 R, 340.2 R Summary: A general handbook used for design of flexural members, stirrups, columns, and footings. Includes tables and diagrams and example calculations that will assist the designer to size structural members, determine reinforcement, and calculate stresses. 9. The Companys Coatings Manual. Summary: Provides technical information for the structural designer on types of coating materials, selection of coating systems, surface preparation, application, and inspection of coatings. Includes Companys color standards. 10. Metal Bar Grating Manual. The National Association of Architectural Metal Manufacturers (NAAMM). Summary: Provides industry standards for steel and aluminum grating including: standard grating designations (size and spacing of bearing bars) standard marking system, load tables, anchoring details, manufacturing tolerances and standards for stair treads. 11. Structural Engineering Handbook. Gaylord, Edwin H., Jr. and Gaylord, Charles N. (Editors). Summary: An all-inclusive handbook that includes information on structural analysis, steel and reinforced concrete design, bridges, and guyed towers.

ChevronTexaco Energy Technology Co.

300-67

April 2004

300 Industrial Structures

Civil and Structural Manual

12. Design of Welded Structures, Blodgett, Omer W., The James F. Lincoln Arc Welding Foundation. Summary: A dual purpose textbook and reference manual that discusses beam, column and girder design, welded connection design, and welded joint design. 13. Tubular Steel Structures - Theory and Design, Troitsky, M.S., The James F. Lincoln Arc Welding Foundation. Summary: Presents a guideline for the structural analysis and design of thinwalled, large diameter tubular steel structures, such as self-supporting and guyed stacks. 14. API RP 1102Recommended Practice for Liquid Petroleum Pipelines Crossing Railroads and Highways. American Petroleum Institute. Summary: Covers the design, installation, inspection, and testing required to ensure safe crossings of pipelines under railroads and highways. 15. The Companys Safety in Designs Manual. Summary: This manual highlights and supplements the safety requirements in local, state, and Federal regulations, and is in accordance with Company policies, standards, and practices. 16. Pipe Support Design, Chevron Research and Technology Company. Summary: This manual, developed for the Richmond Refinery, provides the techniques required to design pipe supports, check the adequacy of existing supports, or design modifications to existing supports to enable them to carry additional loads. Copies of this manual may be obtained through Chevron Research and Technology Company, Civil and Structural Technical Services Team. 17. PCI Design Handbook - Precast and Prestressed Concrete, Prestressed Concrete Institute. Summary: Provides for analysis and design, safe load tables for standard precast shapes, design of components, handling and erection, and design of connections. 18. American Society of Civil Engineers Minimum Design Loads for Buildings and Other Structures. ASCE 7-95. Summary: Provides requirements to govern assumptions for dead, live, and other loads in the design of structures. 19. Pipe Hangers and Supports - Materials, Design and Manufacture, ANSI/MSS SP-58. 20. Guidelines for the Seismic Evaluation and Design of Petrochemical Facilities, ASCE Task Committee on Seismic Evaluation and Design of Petrochemical Facilities, Draft Report.

April 2004

300-68

ChevronTexaco Energy Technology Co.

Civil and Structural Manual

300 Industrial Structures

Summary: Offers commentary and guidance in the design of petrochemical facilities. It provides interpretation of various design issues not explicitly addressed in the Building Codes. 21. Chevrons Pipeline Manual. Summary: Provides technical and design information for the various facets of pipeline assessment and design.