You are on page 1of 141

PCI

MANUAL FOR THE DESIGN


OF
HOLLOW CORE SLABS

SECOND EDITION

by

Donald R. Buettner and Roger J. Becker


Computerized Structural Design, S.C.

Prepared for the


PCI Hollow Core Slab Producers
Committee

John E. Saccoman, Chairperson

James Beerbower Ernest Markle


Kevin Boyle James Markle
Jeffrey Butler Milo J. Nimmer
Loris Collavino William C. Richardson, Jr.
Edward J. Gregory Klaus Rosenstern
Pat Hynes Wes Schrooten
Paul Kourajian Larry Stigler

PRECAST / PRESTRESSED CONCRETE INSTITUTE


175 WEST JACKSON BOULEVARD
CHICAGO, ILLINOIS 60604

312 786--0300 FAX 312 786--0353


Copyright 1998
By Precast/Prestressed Concrete Institute

First edition, 1985


Second edition, 1998

All rights reserved. This book or any part thereof may not be
reproduced in any form without the written permission of the
Precast/Prestressed Concrete Institute.

ISBN 0--937040--57--6

Printed in U.S.A.
INTRODUCTION

Purpose of Manual

The application and design of precast, prestressed hollow core slabs is similar to that of other pre-
stressed members. However, there are situations which are unique to hollow core slabs either be-
cause of the way the slabs are produced or because of the application of the slabs.
For special situations, hollow core producers have developed design criteria and conducted in-
house testing to verify that their approaches are valid. In fact, there is consistency between the many
types of hollow core slabs available. The purpose of this manual is to bring together those things that
are common, that are verified by test and that can be universally applied to hollow core slabs. Be-
cause there are differences, some topics covered will also point to the differences where closer coor-
dination with the local producer is required.
This manual was prepared by Computerized Structural Design, S.C., Milwaukee, Wisconsin with
input and direction from the PCI Hollow Core Slab Producers Committee. Additionally, the fire and
acoustical sections were prepared by Armand Gustaferro of The Consulting Engineers Group, Inc.,
Mt. Prospect, Illinois and Allen H. Shiner of Shiner and Associates, Inc., Skokie, Illinois, respective-
ly. All reasonable care has been used to verify the accuracy of material contained in this manual.
However, the manual should be used only by those experienced in structural design and should not
replace good structural engineering judgment.

Scope of Manual

This document is intended to cover the primary design requirements for hollow core floor and
roof systems. In instances where the design is no different than for other prestressed members, the
PCI Design Handbook and the ACI Building Code should be consulted for more in-depth discussion.
For the architect or consulting engineer, this manual is intended as a guideline for working with
hollow core slabs, a guide for the use and application of hollow core slabs and an indication of some
of the limitations of hollow core slabs. For the plant engineer, the manual will hopefully present
some backup and reference material for dealing with everyday design problems.
TABLE OF CONTENTS
Introduction

Notation

Chapter 1 -- Hollow Core Slab Systems


1.1 Methods of Manufacturing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--1
1.2 Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--1
1.3 Advantages of Hollow Core Slabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
1.4 Framing Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
1.5 Wall Panel Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--4
1.6 Design Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--5
1.7 Cross-Sections and Load Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--5
1.8 Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--6

Chapter 2 -- Design of Hollow Core Slabs


2.1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--1
2.2 Flexural Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--1
2.2.1 ACI Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--1
2.2.2 Stresses at Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--2
2.2.3 Prestress Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--3
2.2.4 Service Load Stresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--5
2.2.5 Design Flexural Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--6
2.3 Shear Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--9
2.3.1 ACI Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--9
2.4 Camber and Deflection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--11
2.4.1 Camber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--12
2.4.2 Deflections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--14
2.5 Composite Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--15
2.6 Strand Development . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--19
2.6.1 ACI Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--19

Chapter 3 -- Special Design Considerations


3.1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1
3.2 Load Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1
3.2.1 Load Distribution Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--1
3.2.2 Design Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--2
3.3 Effect of Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--8
3.4 Continuity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--10
3.5 Cantilevers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--10
3.6 Horizontal Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--12

Chapter 4 -- Diaphragm Action with Hollow Core Slabs


4.1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--1
4.2 Design Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--1
4.3 Distribution of Lateral Forces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--3
4.4 Structural Integrity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4
4.5 Elements of a Diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4
4.6 Diaphragm Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--6
4.6.1 Longitudinal Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--6
4.6.2 Transverse Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--8
4.7 Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--8
4.8 Topped vs. Untopped Diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--9
4.9 Design Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--9

Chapter 5 -- Connections in Hollow Core Slabs


5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--1
5.2 Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--1
5.3 Typical Details with Concrete Beams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--2
5.4 Typical Details with Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--9
5.5 Typical Details with Steel Beams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--15
5.6 Typical Cantilever Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--20
5.7 Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--23

Chapter 6 -- Fire Resistance of Assemblies made with Hollow Core Slabs


6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--1
6.2 Heat Transmission through Floors or Roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--1
6.2.1 Equivalent Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--1
6.2.2 Toppings, Undercoatings, or Roof Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . 6--2
6.2.3 Ceilings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--4
6.3 Structural Fire Endurance of Floor or Roof Assemblies . . . . . . . . . . . . . . . . . . . . . . . . 6--4
6.3.1 Simply Supported Slabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--5
6.3.2 Effect of Spray Applied Coatings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--9
6.3.3 Structurally Continuous Slabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--9
6.3.4 Detailing Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--11
6.4 Restraint to Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--12

Chapter 7 -- Acoustical Properties of Hollow Core Slabs


7.1 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--1
7.2 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--1
7.3 Approaching the Design Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--2
7.3.1 Dealing with Sound Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--2
7.4 Sound Transmission Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--2
7.5 Impact Noise Reduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--3
7.6 Absorption of Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--5
7.7 Acceptable Noise Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--5
7.8 Establishment of Noise Insulation Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--8
7.9 Leaks and Flanking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--8
7.10 Human Response to Building Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--9
7.11 Vibration Isolation for Mechanical Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--10

Chapter 8 -- Guide Specification for Precast, Prestressed Hollow Core Slabs . . . . . . . . . . 8--1

References

Index
NOTATION

A = Cross-sectional area fd = Stress at extreme tension fiber due to


a = Depth of equivalent compression stress unfactored member self weight
block Fi = Portion of base shear applied at level i
aθ = Depth of equivalent compression stress fpc = Compressive stress in concrete at the
block under fire conditions centroid of the section due to effective
Acr = Area of crack face prestress for non-composite sections or
Ae = Net effective slab bearing area due to effective prestress and moments
Aps = Area of prestressed reinforcement resisted by the precast section alone for
Avf = Area of shear friction reinforcement composite sections
b = Width of compression face fpe = Compressive stress in concrete at extreme
bw = Net web width of hollow core slab fiber where external loads cause tension
C = Confinement factor due to the effective prestress only
C = Compressive force fps = Stress in prestressed reinforcement at
C = Seismic factor dependent on site and nominal strength
structure fundamental period fpsθ = Stress in prestressed reinforcement at fire
C = Factor for calculating steel relaxation strength
losses as given in Table 2.2.3.2 f′ps = Maximum steel stress in partially
c = Distance from extreme compression developed strand
fiber to neutral axis fpu = Specified tensile strength of
CR = Prestress loss due to concrete creep prestressing steel
Cs = Seismic coefficient fpuθ = Tensile strength of prestressing steel at
D = Dead load elevated temperatures
d = Distance from extreme compression fiber Fpx = Force applied to diaphragm at level under
to centroid of non-prestressed consideration
tension reinforcement fse = Effective stress in prestressing steel after
db = Nominal diameter of reinforcement all losses
dp = Distance from extreme compression fiber fsi = Stress in prestressing steel at initial
to centroid of prestressed prestress
reinforcement Ft = Additional portion of base shear applied at
DW = Distribution width top level
e = Distance from neutral axis to centroid of fu = Usable grout strength in a horizontal joint
prestressed reinforcement fy = Steel yield strength
Ec = Modulus of elasticity of concrete h = Overall member depth
Eci = Modulus of elasticity of concrete at the hn = Net height of grout in keyway between
time of initial prestress slab units
ES = Prestress loss due to elastic shortening of I = Occupancy importance factor
concrete I = Cross-sectional moment of inertia
Es = Modulus of elasticity of steel J = Factor for calculating steel relaxation
reinforcement losses as given in Table 2.2.3.1
f′c = Specified design compressive strength of k = Fraction of total load in a horizontal joint
concrete in a grout column
f′ci = Compressive strength of concrete at the Kcir = Factor for calculating elastic shortening
time of initial prestress prestress losses
fcir = Net compressive stress in concrete at Kcr = Factor for calculating prestress losses due
centroid of prestressed reinforcement at to concrete creep
time of initial prestress Kes = Factor for calculating prestress losses due
fcds = Stress in concrete at centroid of to elastic shortening
prestressed reinforcement due to Kre = Factor for calculating prestress losses due
superimposed dead load to steel relaxation as given in Table 2.2.3.1
Ksh = Factor for calculating prestress losses due Vi = Factored shear force due to externally
to concrete shrinkage applied loads occurring simultaneously
K′u = Factor from PCI Handbook Fig. 4.12.2 for with Mmax
calculating flexural design strength = Vu -- Vd
L = Live load Vn = Nominal shear strength of a member
ℓ = Span length Vs = Nominal shear strength provided by shear
ℓd = Reinforcement development length reinforcement
Vu = Design shear force
ℓe = Strand embedment length from member
V/S = Volume to surface ratio
end to point of maximum stress
w = Uniformly distributed load
ℓf = Flexural bond length w = Bearing area length
ℓt = Strand transfer length W = Total dead load plus other applicable
M = Service load moment loads for seismic design
Mcr = Cracking moment wi = Portion of W at level i
Md = Unfactored dead load moment wpx = Portion of W at level under
Mg = Unfactored self-weight moment consideration
Mn = Nominal flexural strength yb = Distance from neutral axis to extreme
Mnθ = Flexural strength under fire conditions bottom fiber
Mmax = Maximum factored moment due to yt = Used as either distance to top fiber or
externally applied loads tension fiber from neutral axis
= Mu -- Md Z = Seismic zone factor
Msd = Unfactored moment due to β1 = Factor defined in ACI 318-95, Section
superimposed dead load 10.2.7.3
Mu = Factored design moment γp = Factor for type of prestressing strand
Mθ = Applied fire moment δall = Limiting free end slip
P = Effective force in prestressing steel after δs = Actual free end slip
all losses εps = Strain in prestressed reinforcement at
Po = Effective prestress force at release prior to nominal flexural strength
long term losses εs = Strain in prestressed reinforcement
Pi = Initial prestress force after seating losses εse = Strain in prestressed reinforcement after
Q = First moment of area losses
R = Fire endurance rating µ = Shear friction coefficient
RE = Prestress loss due to steel relaxation µe = Effective shear friction coefficient
Re = Reduction factor for load eccentricity in ρp = Ratio of prestressed reinforcement
horizontal joints ρ′ = Ratio of compression reinforcement
RH = Ambient relative humidity φ = ACI strength reduction factor
Rw = Seismic coefficient dependent on ω = ρfy/f′c
structural system type ω′ = ρ′fy/f′c
S = Section modulus ωp = ρpfps/f′c
SH = Prestress loss due to concrete shrinkage ωw = Reinforcement index for flanged sections
T = Tensile force ω′w = Reinforcement index for flanged sections
tg = Width of grout column in horizontal joint ωpw = Reinforcement index for flanged sections
V = Seismic base shear ωpu = ρp fpu/f′c
Vc = Nominal shear strength of concrete θ = Subscript denoting fire conditions
Vci = Nominal shear strength of concrete in a
shear-flexure failure mode
Vcw = Nominal shear strength of concrete in a
web shear failure mode
Vd = Shear due to unfactored self weight
Vh = Horizontal beam shear
CHAPTER 1

HOLLOW CORE SLAB SYSTEMS

1.1 Methods of Manufacturing long. Slabs are then sawcut to the appropriate
A hollow core slab is a precast, prestressed con- length for the intended project.
crete member with continuous voids provided to The economy of the generalized hollow core
reduce weight and, therefore, cost and, as a side system is in the quantity of slabs that can be pro-
benefit, to use for concealed electrical or mechan- duced at a given time with a minimum of labor re-
ical runs. Primarily used as floor or roof deck sys- quired. Each slab on a given casting line will have
tems, hollow core slabs also have applications as the same number of prestressing strands. There-
wall panels, spandrel members and bridge deck fore, the greatest production efficiency is obtained
units. by mixing slabs with the same reinforcing re-
An understanding of the methods used to quirements from several projects on a single pro-
manufacture hollow core slabs will aid in the spe- duction line. This implies that best efficiency for a
cial considerations sometimes required in the use single project is obtained if slab requirements are
of hollow core slabs. Hollow core slabs are cast repetitive.
using various methods in the seven major systems 1.2 Materials
available today. Because each production system As stated previously, hollow core slabs are pro-
is patented, producers are usually set up on a fran- duced with two basic concrete mixes; low slump
chise or license basis using the background, and normal slump concrete. For the low slump
knowledge and expertise provided with the ma- concretes, water content is limited to slightly
chine development. Each producer then has the more than that required for cement hydration.
technical support of a large network of associated Water-cement ratios are typically about 0.3. Mix-
producers. ing is critical because the limited water available
Two basic manufacturing methods are current- must be well dispersed in the mix. Water reducing
ly in use for the production of hollow core slabs. admixtures can be used to optimize a mix by re-
One is a dry cast or extrusion system where a very ducing cement and water requirements while still
low slump concrete is forced through the ma- retaining adequate workability for proper com-
chine. The cores are formed with augers or tubes paction of the concrete by the machine. Air en-
with the concrete being compacted around the trainment admixtures are not effective in the dry
cores. The second system uses a higher slump mix concrete. With the low water-cement ratios
concrete. Sides are formed either with stationary, and compaction placing method, air is difficult to
fixed forms or with forms attached to the machine disperse well and maintain.
with the sides being slip formed. The cores in the
Table 1.1 Hollow Core Systems
normal slump, or wet cast, systems are formed
with either lightweight aggregate fed through Manufac- Machine Concrete Core Form
tubes attached to the casting machine, pneumatic turer Type Type/Slump
tubes anchored in a fixed form or long tubes at- Dy-Core Extruder Dry/Low Tubes
tached to the casting machine which slip form the Dynaspan Slip Form Wet/Normal Tubes
cores. Elematic Extruder Dry/Low Auger/Tube
Table 1.1 lists the seven major hollow core sys- Flexicore Fixed Form Wet/Normal Pneumatic
tems available today along with the basic in- Tubes
formation on the casting technique. Various Spancrete Slip Form Dry/Low Tubes
names may be used by local licensees to describe SpanDeck Slip Form Wet/Normal Filler
the same products. In most cases, the slabs are aggregate
cast on long line beds, normally 300 ft to 600 ft Ultra-Span Extruder Dry/Low Augers

1--1
The wet cast products (those cast with normal
slump concrete), have water-cement ratios in the
range of 0.4 to 0.45. Depending on the slip form-
ing system used, slumps of 2 to 5 inches (50 - 130
mm) are used. The mix design and use of admix-
tures is dependent on achieving a mix that will
hold its shape consistent with the forming tech-
nique used.
Aggregates vary in the various manufacturing
processes depending on what type is locally avail-
able. Maximum aggregate size larger than pea
gravel is rarely used because of the confined areas
Latex feathering ready for direct carpet application
into which concrete must be placed. Light weight
aggregates are occasionally used to reduce the
weight of the sections and to achieve a significant
reduction in required equivalent thickness in a fire
rated application. Concrete unit weights ranging
from 110 to 150 pcf (1760 - 2400 kg/m3) are used
in the industry.
Strand use in hollow core slabs includes about
every size and type of strand produced depending
on what is available to a particular producer. The
trend is toward primary use of the larger 1/2 in (13
mm) diameter, low relaxation strand. The philos-
ophy of strand use varies from using many strand
sizes to optimize cost for a given project to using
only one or two strand sizes for simplicity of in-
ventory and production.
Except for special situations, keyway grout is
normally a sand and Portland cement mixture in
proportions of about 3:1. The amount of water
used is a function of the method used to place the
grout but will generally result in a wet mix so key-
Acoustical spray on exposed slab ceiling
ways may be easily filled. Shrinkage cracks may
occur in the keyways, but configuration of the key
is such that vertical load transfer can still occur
with the presence of a shrinkage crack. Rarely is
grout strength required in excess of 2000 psi (13.8
MPa) for vertical load transfer.
Although it is discouraged, non-shrink, non-
staining grout is occasionally specified for use in
keyways. In evaluating the potential benefits of
non-shrink grout, the volume of grout must be
compared to the overall volume of concrete in the
slabs and support materials. Because the size of
the keyway is small in relation to a floor or roof as-
sembly of slabs, total shrinkage will be affected
Electrical and HVAC application only to a minor degree. Shrinkage cracks can still

1--2
occur in the keyways and there is little benefit to acteristics associated with concrete. The Sound
be gained in comparison with the additional cost. Transmission Class rating ranges from about 47 to
57 without topping and the Impact Insulation
1.3 Advantages of Hollow Core Slabs Class rating starts at about 23 for a plain slab and
Hollow core slabs are most widely known for may be increased to over 70 with the addition of
providing economical, efficient floor and roof carpeting and padding. Detailed information on
systems. The top surface can be prepared for the the acoustical properties of hollow core slabs is
installation of a floor covering by feathering the presented in Chapter 7.
joints with a latex cement, installing non-structur-
al fill concretes ranging from 1/2 in to 2 in (13 - 51 1.4 Framing Concepts
mm) thick depending on the material used, or by The primary consideration in developing a
casting a composite structural concrete topping. framing scheme using hollow core slabs is the
The underside can be used as a finished ceiling as span length. For a given loading and fire endur-
installed, by painting, or by applying an acoustical ance rating, span length and slab thickness may be
spray. optimized by consulting a producer’s published
When properly coordinated for alignment, the load tables. Section 1.7 presents sample load
voids in a hollow core slab may be used for electri- tables and instructions for the use of the tables.
cal or mechanical runs. For example, routing of a The PCI Design Handbook1 recommends limits
lighting circuit through the cores can allow fix- on span-depth ratios for the hollow core slabs. For
tures in an exposed slab ceiling without unsightly roof slabs, a span-depth ratio limit of 50 is sug-
surface mounted conduit. Slabs used as the heated gested and for floor slabs, a limit of 40 is sug-
mass in a passive solar application can be detailed gested. In practice, a span-depth ratio of 45 is
to distribute the heated air through the cores. common for floors and roofs when fire endurance,
Structurally, a hollow core slab provides the ef- openings, or heavy or sustained live loads do not
ficiency of a prestressed member for load capac- control a design.
ity, span range, and deflection control. In addi- Consideration must be given to factors which
tion, a basic diaphragm is provided for resisting affect slab thickness selection for a given span.
lateral loads by the grouted slab assembly pro- Heavy superimposed loads, as required by the
vided proper connections and details exist. A de- function of a system, would require a lower span-
tailed discussion of diaphragm capabilities is depth ratio. Similarly, heavy partitions or a large
presented in Chapter 4. number of openings will result in higher load ca-
Excellent fire resistance is another attribute of pacity requirements. The fire resistance rating re-
the hollow core slab. Depending on thickness and quired for the application will also affect the load
strand cover, ratings up to a 4 hour endurance can capacity of a slab. As the code required fire rating
be achieved. A fire rating is dependent on equiva- increases, prestressing strands can be raised for
lent thickness for heat transmission, concrete cov- more protection from the heat. The smaller effec-
er over the prestressing strands for strength in a tive strand depth will result in a lower load capac-
high temperature condition, and end restraint. ity. Alternatively, a rational design procedure can
Underwriters Laboratories publishes fire ratings be used to consider the elevated strand tempera-
for various assemblies. However, many building tures during a fire. This fire design condition may
codes allow a rational design procedure for control a slab design and, again, result in a lower
strength in a fire. This procedure, described in de- load capacity.
tail in Chapter 6, considers strand temperature in Once slab thicknesses and spans are selected,
calculating strength. Required fire ratings should the economics of layout become important.
be clearly specified in the contract documents. While ends cut at an angle can be designed and
Also, the fire rating should be considered in deter- supplied, it is most efficient to have the bearing
mining the slab thickness to be used in prelimi- perpendicular to the span so square cut ends can
nary design. be used.
Used as floor-ceiling assemblies, hollow core It is also desirable to have the plan dimensions
slabs have the excellent sound transmission char- fit the slab module. This is dependent upon the

1--3
slab systems available in the project area. ture of the slabs. At the other extreme, if a “flat”
Non-module plan dimensions can be accommo- floor is required in a structure consisting of multi-
dated using partial width slabs. Some producers ple bays of varying length and change in slab
intentionally cast narrow widths as filler pieces direction, the highest point will determine the top
while others use a section split from a full slab. elevation of the topping. A greater amount of top-
Such a split section might be created by a longitu- ping will then be required in “low” areas. These
dinal sawcut or a break if the edge will not be ex- considerations must be dealt with in the planning
posed to view. stages to both control costs and minimize ques-
Construction tolerances must be accounted for tions and potential for “extras” during construc-
in developing a plan layout. Tolerance on slab tion.
length may be taken up by allowing a gap at the Camber, camber growth, and deflections must
slab ends in the bearing detail. On the non-bearing be considered when slabs run parallel to a stiff ver-
sides, clearance may be provided by using a detail tical element such as a wall (e.g. slabs running
where the slabs lap over a wall or beam. If the slab parallel to the front wall of an elevator). The door
edge butts a wall or beam, a gap should be pro- rough opening should allow for camber to pro-
vided. Refer to local producers’ information for duce proper door installation. Alternatively, the
recommendations of proper tolerances. slab span might be rearranged so the front wall is a
When a hollow core slab deck is exposed to bearing wall. Then door problems would be alle-
weather for a long period of time during construc- viated.
tion, water can accumulate in the cores. The pri- Camber, camber growth, and deflections must
mary source of water infiltration is at the butt be taken into account in roofing details. Where
joints. In cold weather, this water can freeze and changes in relative slab position can occur, coun-
expand causing localized damage. One remedy terflashings are suggested to accommodate such
for this situation is to drill weep holes at the slab changes.
ends under each core. The need for such weep
holes is generally known only after a construction 1.5 Wall Panel Applications
schedule is established. The specifier and the slab Some hollow core slab systems can also pro-
supplier are not usually in a position to know of vide slabs to be used as walls. Long line manufac-
such a need in advance. turing can result in economical cladding or load
Hollow core members will be cambered as with bearing panels used in manufacturing or commer-
any other prestressed flexural member. In the cial applications. The hollow core wall panels are
planning stages, consideration should be given to prestressed with two layers of strands for accom-
the causes of differential camber. For two slabs of modating handling, structural loadings and bow-
identical length and prestressing, the camber may ing considerations. Some manufacturers can add
be different because of concrete and curing varia- 2 in to 4 in (51 - 102 mm) of insulation to the hol-
tions. This factor is independent of a framing low core section with a 1 1/2 in thick to 3 in (38 - 76
scheme. However, joints between slabs of un- mm) thick concrete facing to create an insulated
equal spans or joints at which a change in the span sandwich panel.
direction occurs, will cause a potential differential A variety of architectural finishes are available
camber problem. This must be recognized and with hollow core wall panels. While the finishes
dealt with in the design layout. Wall locations can be very good, the variety of finishes available
may hide such a joint, but the door swing might be is different from those typically available with
directed to the least variable side. true architectural precast concrete panels. In
Camber must also be accommodated when a judging the quality of finish on hollow core wall
topping is to be provided. The quantity of topping panels, consideration must be given to the
required must consider the amount of camber and manufacturing process.
the function of the floor. In occupancies where
flat floors are not a requirement, a constant top-
ping thickness may be used to follow the curva-

1--4
1.6 Design Responsibilities Producer load tables define the allowable live
It is customary in the hollow core industry for load that a given slab can safely support in addi-
the producer to perform the final engineering for tion to the slab self weight. The load capacity will
the product to be supplied to the job. This would be a function of the slab thickness, the amount of
include design for vertical loads and lateral loads prestressing provided, and the location of the pre-
specified by the Engineer of Record, embedded stressing strands. Fire rated slabs may require
items for specified connection forces, and han- additional concrete cover below the strands which
dling and shipping. However, the Engineer of Re- will affect the load capacity.
cord plays a very important role in the design pro- The design criteria used to develop these load
cess. Prior to selection of the hollow core produc- tables is defined by the ACI Building Code2 as
er, enough preliminary planning should be done to outlined in Chapter 2. Depending on the design
insure that the specified floor and roof system is criteria controlling a slab’s load capacity, some
achievable. That is, the project should be one that advantage may be gained by understanding that in
can be engineered without requiring changes from most applications, superimposed loads will con-
the contract documents. sist of both dead and live loads. Where ultimate
The contract documents must clearly indicate strength controls, an equivalent live load can be
design criteria to which hollow core slabs will used to enter a load table. It is calculated as:
have to conform. This is especially important
when the hollow core slabs must interface with w equivalent = 1.4 superimposed Dead load
1.7
other construction materials. When connections + Live load
are required, the forces to be transmitted through However, if bottom fiber tensile stresses con-
the connections must be specified in the contract trol, no adjustment in superimposed loads may be
documents. The producer is best able to deter- used.
mine the most efficient connection element to be Similarly, many loading conditions consist of
embedded in the slab. However, the balance of a loads other than uniform loads. For preliminary
connection which interfaces with another materi- design only, an equivalent uniform load may be
al should be detailed in the contract documents. calculated from the maximum moment caused by
The Engineer of Record also has a responsibil- the actual loads.
ity in the review and approval of erection draw-
8 M superimposed
ings prepared by the precast producer. Review of w equivalent =
these drawings is the last opportunity to assure ℓ 2

that the producer’s understanding of the project Shear will not be properly addressed in this sit-
coincides with the intent of design. Erection uation. Thus, the final design must consider the
drawings should be checked for proper design actual load pattern.
loads, proper details and bearing conditions, con- Because of the uniqueness of each hollow core
formance with specified fire ratings, and the loca- slab system and the many possibilities of strand
tion of openings. patterns available from various producers, a ge-
neric hollow core slab has been developed to dem-
onstrate design procedures. Figure 1.7.1 depicts
the slab section and properties and illustrates a
1.7 Cross-Sections and Load Tables typical form for a producer’s load tables.
Each of the major hollow core slab systems has Throughout this manual, this section will be used
a standard set of cross-sections that can be pro- to demonstrate various calculation procedures
duced by their equipment. Available in thick- where any one of the proprietary cross-sections
nesses ranging from 4 in to 15 in (102 - 380 mm), could be substituted. It must be emphasized that
core configurations make each system unique. this cross-section is not available for use and
Each individual producer has additional produc- should not be specified.
tion practices which may affect the capabilities of Figures 1.7.2 through 1.7.8 present the propri-
their product. Therefore, most producers prepare etary slab cross-sections currently available. The
and distribute load tables in their market area. section properties are as provided by the manufac-

1--5
turers, but weights are based on 150 pcf (2400 For final design use the methods of Chapter 2
kg/m3) concrete. The actual weights may vary particularly to check shear.
slightly from those given. The availability of any
particular section in a given area must be verified 1.8 Tolerances3
with the local producers. Figures 1.7.9 present Figure 1.8.1 shows the dimensional tolerances
charts of the general range of load capacities for precast hollow core slabs. These tolerances
available in a given slab thickness. As with any are guidelines only and each project must be con-
chart of this nature, the chart should be carefully sidered individually to ensure that the tolerances
approached and verified with local producer load shown are applicable.
tables, especially for the longest and shortest and Figure 1.8.2 shows erection tolerances for hol-
lightest and heaviest conditions. Special care is low core slabs. When establishing tolerances, the
also required when fire rated slabs must be used function of the slabs should be considered. For
on a project. (See Chapter 6) example, slabs covered by finish materials may
The following examples demonstrate the ways not need the close tolerances required for exposed
in which load tables may be used. slabs.
Example 1.7.1 Equivalent Uniform Load
From the load table in Figure 1.7.1 select a
strand pattern to carry a uniform superimposed
dead load of 20 psf and a uniform live load of 60
psf on a 24 foot span.
wtotal = 20 + 60 = 80 psf
4-7/16 in dia. strands required: capacity = 118 psf
flexural strength controls

w equivalent = 1.4 20 + 60 = 77 psf


1.7
Use 4-3/8 in dia. strands: capacity = 79 psf
flexural strength controls.
Example 1.7.2 Non-Uniform Loads
From the load table in Figure 1.7.1 select a
strand pattern to carry a superimposed uniform
load of 20 psf dead plus 40 psf live and a continu-
ous wall load of 600 plf located perpendicular to
the span and at midspan. The design span is 25
feet.
For preliminary design
2
M superimposed = 25 20 + 40 + 25 600
8 4
= 8438 ft-#/ft
88438
w equivalent =
25 2
= 108 psf
Try 6-3/8 in dia. strands - capacity = 120 psf

1--6
Fig. 1.7.1 Generic hollow core slab

36" Section Properties


1 1/2" 5 1/4" 1 1/4" A = 154 in2
I = 1224.5 in4
bw = 10.5 in
yb = 3.89 in

8"
Sb = 314.8 in3
St = 297.9 in3

1"
1 1/2" 1 1/2" wt = 53.5 psf
4 1/4"

SAMPLE LOAD TABLE3

Allowable Superimposed Live Loads, psf

Spans, ft
Strands, 270LR φMn, ft-k 14 15 16 17 18 19 20 21 22 23
4-3/8″ 45.1 317 270 232 200 174 152 133 116 102 90
6-3/8″ 65.4 356 311 272 240 212 188 168 150
4-7/16″ 59.4 320 278 243 214 189 167 148 132
6-7/16″ 85.0 3431 3111 2831 258 231 208
4-1/2″ 76.7 327 289 257 229 204 183
6-1/2″ 105.3 3171 2901 2671 2471
Strands, 270LR φMn, ft-k 24 25 26 27 28 29 30
4-3/8″ 45.1 79 79 69 61 53 46
6-3/8″ 65.4 134 120 108 97 87 78 70
4-7/16″ 59.4 118 105 94 84 75 67 59
6-7/16″ 85.0 187 169 153 139 126 114 104
4-1/2″ 76.7 165 148 134 121 109 99 90
6-1/2″ 105.3 2271 2101 1952 1782 1632 1492 1372
1 - Values are governed by shear strength.
2 - Values are governed by allowable tension
3 - Table based on 5000 psi concrete with 6 f′ c allowable tension. Unless noted, values are
governed by strength design.

Note: This slab is for illustration purposes only. Do not specify this slab for a project.

1--7
Fig. 1.7.2

Trade name: Dy-Core


Equipment Manufacturer: Mixer Systems, Inc., Pewaukee, Wisconsin

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
4′-0″ x 6″ 142 3.05 661 37 4.45 1475 62
4′-0″ x 8″ 193 3.97 1581 50 5.43 3017 75
4′-0″ x 10″ 215 5.40 2783 56 6.89 4614 81
4′-0″ x 12″ 264 6.37 4773 69 7.89 7313 94
4′-0″ x 15″ 289 7.37 8604 76 9.21 13225 101

Note: All sections not available from all producers. Check availability with local manufacturers.

Fig. 1.7.3

Trade name: Dynaspan


Equipment Manufacturer: Dynamold Corporation, Salina, Kansas

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
4′-0″ x 4″ 133 2.00 235 35 3.08 689 60
4′-0″ x 6″ 165 3.02 706 43 4.25 1543 68
4′-0″ x 8″ 233 3.93 1731 61 5.16 3205 86
4′-0″ x 10″ 260 4.91 3145 68 6.26 5314 93
8′-0″ x 6″ 338 3.05 1445 44 4.26 3106 69
8′-0″ x 8″ 470 3.96 3525 61 5.17 6444 86
8′-0″ x 10″ 532 4.96 6422 69 6.28 10712 94
8′-0″ x 12″ 615 5.95 10505 80 7.32 16507 105

Note: All sections not available from all producers. Check availability with local manufacturers.

1--8
Fig. 1.7.4

Trade name: Elematic


Equipment Manufacturer: Mixer Systems, Inc., Pewaukee, Wisconsin

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
4′-0″ x 6″ 157 3.00 694 41 4.33 1557 66
4′-0″ x 8″ 196 3.97 1580 51 5.41 3024 76
4′-0″ x 10″(5) 238 5.00 3042 62 6.49 5190 87
4′-0″ x 10″(6) 249 5.00 3108 65 6.44 5280 90
4′-0″ x 12″ 274 6.00 5121 71 7.56 8134 96

Note: Elematic is also availble in 96″ width. All sections not available from all producers. Check availability with local manufacturers.

Fig. 1.7.5

Trade name: Flexicore


Licensing Organization: The Flexicore Co. Inc., Dayton, Ohio

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
1′-4″ x 6″ 55 3.00 243 43 4.23 523 68
2′-0″ x 6″ 86 3.00 366 45 4.20 793 70
1′-4″ x 8″ 73 4.00 560 57 5.26 1028 82
2′-0″ x 8″ 110 4.00 843 57 5.26 1547 82
1′-8″ x 10″ 98 5.00 1254 61 6.43 2109 86
2′-0″ x 10″ 138 5.00 1587 72 6.27 2651 97
2′-0″ x 12″ 141 6.00 2595 73 7.46 4049 98

Note: All sections not available from all producers. Check availability with local manufacturers.

1--9
Fig. 1.7.6

Trade name: Spancrete


Licensing Organization: Spancrete Machinery Corp., Milwaukee, Wisconsin

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
4′-0″ x 4″ 138 2.00 238 34 3.14 739 59
4′-0″ x 6″ 189 2.93 762 46 4.19 1760 71
4′-0″ x 8″ 258 3.98 1806 63 5.22 3443 88
Ultralight Spancrete 4′-0″ x 10″ 312 5.16 3484 76 6.41 5787 101
4′-0″ x 12″ 355 6.28 5784 86 7.58 8904 111
4′-0″ x 15″ 370 7.87 9765 90 9.39 14351 115

4′-0″ x 8″ 246 4.17 1730 60 5.41 3230 85


4′-0″ x 10″ 277 5.22 3178 67 6.58 5376 92
4′-0″ x 12″ 316 6.22 5311 77 7.66 8410 102

Note: Spancrete is also available in 40″ and 96″ widths. All sections are not available from all producers. Check availability with
local manufacturer.

Fig. 1.7.7

Trade name: SpanDeck


Licensing Organization: Fabcon, Incorporated, Savage, Minnesota

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
4′-0″ x 8″ 246 3.75 1615 62 5.55 2791 87
4′-0″ x 12″ 298 5.87 5452 75 8.01 7856 100
8′-0″ x 8″ 477 3.73 3236 60 5.53 5643 85
8′-0″ x 12″ 578 5.86 10909 72 7.98 15709 97

Note: All sections not available from all producers. Check availability with local manufacturers.

1--10
Fig. 1.7.8

Trade name: Ultra-Span


Licensing Organization: Ultra-Span Technologies, Inc., Winnipeg, Manitoba, Canada

Section Untopped with 2″ topping


width
x A yb I wt yb I wt
depth in2 in in4 psf in in4 psf
4′-0″ x 4″ 154 2.00 247 40 2.98 723 65
4′-0″ x 6″ 188 3.00 764 49 4.13 1641 74
4′-0″ x 8″ 214 4.00 1666 56 5.29 3070 81
4′-0″ x 10″ 259 5.00 3223 67 6.34 5328 92
4′-0″ x 12″ 289 6.00 5272 75 7.43 8195 100

Note: All sections are not available from all producers. Check availability with local manufacturers.

Fig. 1.7.9(a) Slab load ranges

300
6" Hollow Core Slab
3/4" Concrete Cover
250
~ = 45
h
Superimposed Live Load, psf

200
6" + 2" Topping

150
6"

100

50

10 20 30 40

Span, ft

1--11
Fig. 1.7.9 (b) Slab load ranges

300
8" Hollow Core Slab
3/4" Concrete Cover
250

~ = 45
Superimposed Live Load, psf

h
200

8" + 2" Topping


150

8"
100

50

10 20 30 40

Span, ft

Fig. 1.7.9(c) Slab load ranges

300
10" Hollow Core Slab
3/4" Concrete Cover
250

10" + 2" Topping


Superimposed Live Load, psf

200
~ = 45
h

150
10"

100

50

10 20 30 40

Span, ft

1--12
Fig. 1.7.9 (d) Slab load ranges

300
12" Hollow Core Slab
3/4" Concrete Cover
250
12" + 2" Topping
Superimposed Live Load, psf

200
~ = 45
h
12"
150

100

50

10 20 30 40

Span, ft

Fig. 1.7.9(e) Slab load ranges

200
15" Hollow Core Slab
3/4" Concrete Cover
175
15" + 2 1/2" Topping
Superimposed Live Load, psf

15"
150
~ = 45
h

125

100

75

50
10 20 30 40 50 60

Span, ft

1--13
Fig. 1.8.1 Product tolerances -- hollow core slabs
a = Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1/2 in j = Center of gravity of strand group
b = Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1/4 in The CG of the strand group relative to the top of the plank
c = Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1/4 in shall be within ±1/4 in of the nominal strand group CG. The
dt = Top flange thickness position of any individual strand shall be within ±1/2 in of
Top flange area defined by the actual measured values of nominal vertical position and ±3/4 in of nominal horizontal
average dt x b shall not be less than 85% of the nominal area position and shall have a minimum cover of 3/4 in.
calculated by dt nominal x b nominal. k = Position of plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±2 in
db = Bottom flange thickness l = Tipping and flushness of plates . . . . . . . . . . . . . . . . ±1/4 in
Bottom flange area defined by the actual measured values m = Local smoothness . . . . . . . . . . . . . . . . . . . . . ±1/4 in in 10 ft
of average db x b shall not be less than 85% of the nominal
(does not apply to top deck surface left rough to receive a
area calculated by db nominal x b nominal.
topping or to visually concealed surfaces)
e = Web thickness
The total cumulative web thickness defined by the actual Plank weight
measured value Σe shall not be less than 85% of the nominal Excess concrete material in the plank internal features is
cumulative width calculated by Σe nominal. within tolerance as long as the measured weight of the
f = Blockout location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±2 in individual plank does not exceed 110% of the nominal
g = Flange angle . . . . . . . . . . . . . . 1/8 in per 12 in, 1/2 in max. published unit weight used in the load capacity calculation.
h = Variation from specified end squareness n = Applications requiring close control of differential camber
or skew . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1/2 in between adjacent members of the same design should be
i = Sweep (variation from straight line parallel to centerline of discussed in detail with the producer to determine applicable
member) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±3/8 in tolerances.

b
dt

e
c

CGS
db

l
CROSS SECTION

n
h
g
10 ft k ELEVATION
m

f
i

PLAN

1--14
Fig. 1.8.2 Erection tolerances - hollow core floor and roof members
a = Plan location from building grid datum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 in
a1 = Plan location from centerline of steel* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 in
b = Top elevation from nominal top elevation at member ends
Covered with topping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 3/4 in
Untopped floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1/4 in
Untopped roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 3/4 in
c = Maximum jog in alignment of matching edges
(both topped and untopped construction) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 in
d = Joint width
0 to 40 ft member length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1/2 in
41 to 60 ft member length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 3/4 in
61 ft plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 in
e = Differential top elevation as erected
Covered with topping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4 in
Untopped floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4 in
Untopped roof** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4 in
f = Bearing length*** (span direction) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 3/4 in
g = Differential bottom elevation of exposed hollow-core slabs**** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4 in

* For precast concrete erected on a steel frame building, this tolerance takes precedence over tolerance on dimension “a”.
** It may be necessary to feather the edges to ± 1/4 in to properly apply some roof membranes.
*** This is a setting tolerance and should not be confused with structural performance requirements set by the architect/engineer.
**** Untopped installation will require a larger tolerance here.

a bldg. Y grid datum

bldg. Y grid datum


a
bldg. X grid datum

a bldg. X grid datum


a
f

d
d
c

hollow core
c floor or roof member hollow core
centerline of floor or roof member
PLAN steel structure
PLAN
a1
clearance
centerline of e
steel structure
e

f
g
f hollow core g b
b floor or roof member
precast or cast in place
concrete support member
bldg. elevation datum bldg. elevation datum
ELEVATION

Precast element to precast or ELEVATION


cast-in-place concrete or masonry Precast element to structural steel

1--15
CHAPTER 2

DESIGN OF HOLLOW CORE SLABS


2.1 General b) Extreme fiber stress in tension except
The design of hollow core slabs is governed by as permitted in (c) . . . . . . . . . 3 f′ ci
the ACI (318-95) Building Code Requirements
c) Extreme fiber stress in tension at ends
for Structural Concrete.2 As with prestressed con-
of simply supported members . . . . . .
crete members in general, hollow core slabs are
checked for prestress transfer stresses, handling . . . . . . . . . . . . . . . . . . . . . . . . 6 f′ ci
stresses, service load stresses, deflections and de-
2.2.1.2 Permissible stresses at service
sign (ultimate) strength in shear and bending. For
uniform load cases, the manufacturer’s load tables loads (Section 18.4)
will take into account these various design consid- a) Extreme fiber stress in compression
erations and print a load capacity based on the due to prestress plus sustained loads
governing criteria. For loading conditions other . . . . . . . . . . . . . . . . . . . . . . . . 0.45 f′c
than uniform, or for the development of load b) Extreme fiber stress in compression
tables, the design steps presented in this section due to prestress plus total load
are used. . . . . . . . . . . . . . . . . . . . . . . . . 0.60 f′c
An excellent reference for prestressed member c) Extreme fiber stress in tension in pre-
design exists in the PCI Design Handbook.1 compressed tensile zone . . . . . 6 f′ c
Charts and tables provide design aids to shorten d) Extreme fiber stress in tension in pre-
the calculation procedures. Another excellent compressed tensile zone where deflec-
source for design information is the PCI Standard tions are calculated considering bili-
Design Practice4 which reflects design practices near moment-deflection relationships
in the industry. . . . . . . . . . . . . . . . . . . . . . . . . 12 f′ c
The generic slab presented in Section 1.7 will
be used for the calculations presented in this sec- 2.2.1.3 Loss of prestress (Section 18.6)
tion. The cross-section was selected to provide a Calculation of losses shall consider:
means of demonstrating calculation procedures a) Seating loss
and does not represent any slab currently in use. b) Elastic shortening of concrete
Therefore, this generic slab should never be speci- c) Creep of concrete
fied for use on a project. See Section 1.7 for the d) Shrinkage of concrete
slabs currently available. e) Steel relaxation
2.2.1.4 Design (ultimate) strength
2.2 Flexural Design a) Load Factors (Section 9.2)
U = 1.4D + 1.7L
b) Strength Reduction Factors (Section
2.2.1 ACI Requirements 9.3)
Chapter 18 of ACI (318-95) presents provi- Flexure φ = 0.9
sions for the flexural design of prestressed con- c) Flexural Strength (Section 18.7)
crete members. The applicable limits from ACI
are paraphrased as follows: Mu ≤ φMn = ÔA psf ps d p − a
2
 
A psf ps
2.2.1.1 Permissible stresses at transfer a =
(Section 18.4). 0.85f′ cb
a) Extreme fiber stress in compression fps = value calculated by strain
. . . . . . . . . . . . . . . . . . . . . . . . 0.6 f′ci compatibility

2--1
or moment 25 in from slab end


fps = f pu 1 −
γ p f pu
ρ  Md = 30.5
2
2.08 − 2.08 0.05353′
2
2

β 1 p f′ c
= 4.74 ft-k
Mn > 1.2 Mcr 4.7412
Md
=
2.2.2 Stresses at Transfer
S

279.9
314.8
When the prestressing strands are cut to apply
the prestressing force to the concrete, only the slab = +0.191 ksi top fiber
self weight is present to counteract the effects of = --0.181 ksi bottom fiber
eccentric prestress. A check of stresses is required
Net concrete stress at transfer point
at this point to determine the concrete strength re-
quired to preclude cracking on the tension side or = --0.162 ksi top fiber
crushing on the compression side. The concrete = +1.542 ksi bottom fiber
strength at the time of transfer may be only 50% to Self weight at midspan
60% of the 28 day design strength.
2
Md = 30.5 (0.0535)(3′) = 18.66 ft-k
8
Example 2.2.2.1 - Transfer Stresses
Md 18.6612
Using the generic hollow core cross-section =
defined in Section 1.7, check stresses at transfer of
prestress using the following criteria:
S

279.9
314.8

Prestressing steel: 4 - 1/2″ dia. 270 ksi, low relax- = +0.752 ksi top fiber
ation strands. = --0.711 ksi bottom fiber
Aps = 4(0.153) = 0.612 in2 Net concrete stress at midspan
assume 5% initial loss = +0.399 ksi top fiber
dp = 7″ = +1.012 ksi bottom fiber
ℓ = 30′-6″ Allowable stresses:
initial stress = 70% fpu tension at end = 6 f′ ci

 
Solution: 2

Stresses will be checked at the transfer point f′ci = − 162 = 729 psi
6
and at midspan
tension at midspan = 3 f′ ci
At release prestress force
does not control
Po = (0.70)(0.95)(0.612)(270) = 109.9k
Prestress effect compression = 0.6 f′ci
P
= o  Po e f′ci = 1542 = 2570 psi
A S 0.6
Concrete strength required at release
109.92.89
= 109.9  = 2570 psi
154
297.9
314.8 Note that if tension or compression in the end
region exceeds allowables based on a reasonable
= --0.353 ksi top fiber concrete release strength, strands may be de-
= +1.723 ksi bottom fiber bonded in some manufacturing systems or, for
tension, top mild reinforcement may be used in
Self weight at transfer point
some manufacturing systems to resist the total
ℓt = 50db = 50(1/2) = 25 in tension force.

2--2
If tension in the midspan region controls, either 1) Elastic Shortening
a high release strength must be used or mild rein- Es
forcement must be added to resist the total tension ES = Kes f
E ci cir
force. Mild reinforcement should only be used in
the wet cast manufacturing system. Kes = 1.0 for pretensioned members

2.2.3 Prestress Losses


The calculation of prestress losses affects the fcir = Kcir  A I

P i P ie 2
+ −
M ge
I
service load behavior of a slab. The accuracy of
any calculation method is dependent on the pre- Kcir = 0.9 for pretensioned members
ciseness of concrete and prestressing steel materi-
al properties as well as external factors such as hu-
midity used in the calculation procedure. The 2) Concrete Creep
accuracy of loss calculations has little effect on Es
the ultimate strength of a member. CR = Kcr (f -- f )
E c cir cds
Prestress loss calculations are required for pre-
diction of camber and for service load stress cal- Kcr = 2.0 for normal weight pretensioned
culations. Since the success of a project is judged members
on service load performance rather than ultimate
strength, it behooves any slab producer to use a = 1.6 for sand lightweight pretensioned
loss calculation procedure which best predicts the members
behavior of the product as produced.
M sde
For low relaxation strand and for special cases fcds =
(e.g., long spans or special loadings) using stress I
relieved strand, the 1995 ACI Code references 3) Shrinkage of Concrete
several sources for prestress loss calculations.
The method presented here was developed by Zia,

SH = 8.2 x 10-6KshEs 1 − 0.06 V
S

et al.5 and considers the following parameters: x (100 -- RH)

Fig. 2.2.3.1 Ambient relative humidity

80
70

70
80

70
70
60 75 75
70

50
40
80 30
70
70
60 40 40
50 60
70
75

2--3
Table 2.2.3.1 Table 2.2.3.2 Values of C
Type of tendon Kre psi J Stress- Stress-relieved
270 Grade stress-re- relieved bar or
lieved strand or wire 20,000 0.15 fsi/fpu strand or low-relaxation
250 Grade stress-re- wire strand or wire
lieved strand or wire 18,500 0.14 0.80 1.28
0.79 1.22
240 or 235 Grade stress-
17,600 0.13 0.78 1.16
relieved wire
0.77 1.11
270 Grade low-relax- 0.76 1.05
ation strand 5000 0.040
0.75 1.45 1.00
250 Grade low-relax- 0.74 1.36 0.95
ation wire 4630 0.037 0.73 1.27 0.90
240 or 235 Grade low-re- 0.72 1.18 0.85
laxation wire 4400 0.035 0.71 1.09 0.80
145 or 160 Grade stress- 0.70 1.00 0.75
relieved bar 6000 0.05 0.69 0.94 0.70
0.68 0.89 0.66
Ksh = 1.0 for pretensioned members 0.67 0.83 0.61
0.66 0.78 0.57
RH = Ambient relative humidity from Fig- 0.65 0.73 0.53
ure 2.2.3.1 0.64 0.68 0.49
4) Steel Relaxation 0.63 0.63 0.45
0.62 0.58 0.41
RE = [Kre -- J (SH + CR + ES)]C 0.61 0.53 0.37
0.60 0.49 0.33
Kre, J, C = factors from Tables 2.2.3.1
and 2.2.3.2 Solution:
5) Total Loss = ES + CR + SH + RE 1) Elastic Shortening
Pi = 0.7(4)(41.3k) = 115.6k
Observations and experience in a plant may
2
provide modifications to loss calculations to bet- Mg = 30.5 (0.0535)(3′)
8
ter predict slab performance.
= 18.66 ft-k
= 224 in-k
Example 2.2.3.1 Loss of Prestress
Using the generic hollow core cross-section
defined in Section 1.7, calculate the loss of pre-
stress based on the following information:

fcir = 0.9 115.6 +
154
115.6(2.89)
1224.5
2

Prestressing steel: 4-1/2″ dia. 270 ksi, low re- 2242.89
laxation strands --
1224.5
Apsfpu = 0.153(270) = 41.3k/strand = 0.857 ksi
dp = 7″ using Es = 28,500 ksi and Eci = 3250 ksi
initial stress = 70% fpu Es
ES = Kes f
E ci cir
ℓ = 30′-6″
Superimposed dead load = 20 psf = (1.0) 28500 (0.857)
3250

2--4
= 7.52 ksi % = 25.6 (100) = 13.5%
0.7270
2) Concrete Creep
M e
fcds = sd 2.2.4 Service Load Stresses
I
Service load concrete stresses are calculated as
30.5
8
0.023122.89
2
a measure of performance or serviceability. For
= the in-service state when deflections must be cal-
1224.5 culated, a stress check must first be made to deter-
= 0.198 ksi mine whether gross section properties or cracked-
using Ec = 4300 ksi and normal weight concrete transformed section properties are to be used.
In-service stresses are checked assuming that
E
CR = Kcr s (fcir -- fcds) all prestress losses have occurred. The calculated
Ec
stresses are compared to the permissible stresses
= (2.0) 28500 (0.857 -- 0.198) noted in Section 2.2.1. Hollow core slabs are nor-
4300 mally designed to be uncracked under full service
= 8.74 ksi loads. Tensile stress limits of between 6 f′ c and
3) Shrinkage of Concrete 7.5 f′ c are commonly used. In special circum-
V = Area = 154 = 1.75 stances where deflections will not be a problem
S Perimeter 236 + 8 and where cracking will not be of concern, the up-
use RH = 70% per limit of 12 f′ c can be used.


SH = 8.2 x 10-6KshEs 1 − 0.06 V
S
 Example 2.2.4.1 Service Load Stresses
Using the generic hollow core cross-section
x (100 -- RH) defined in Section 1.7, calculate the service load
stresses given the following criteria:
= 8.2 x 10-6(1.0)28500
Prestressing steel:
x (1 -- 0.06 x 1.75)(100 -- 70)
4-1/2″ dia. 270 ksi, low relaxation strands
= 6.27 ksi
Apsfpu = 0.153(270) = 41.3k/strand
4) Steel Relaxation
dp = 7″
From Table 2.2.3.1
Initial stress = 70% fpu
Kre = 5000, J = 0.04
f′c = 5000 psi
From Table 2.2.3.2
ℓ = 30′-6″
C = 0.75 for fsi/fpu = 0.7
Clear Span = 30′-0″
RE = [Kre -- J(SH + CR + ES)]C Superimposed Dead Load = 20 psf
Live Load = 50 psf
= [ 5000
1000
− 0.04x
Solution:
2
Msustained = 30 (0.0535 + 0.020)
]
(6.27 + 8.74 + 7.52) 0.75 8
= 8.27 ft-k/ft = 99.2 in-k/ft
= 3.07 ksi
2
5) Total Loss at Midspan Mservice = 30 (0.0535 + 0.020 + 0.050)
8
= 7.52 + 8.74 + 6.27 + 3.07 = 13.89 ft-k/ft = 167 in-k/ft
= 25.6 ksi With losses = 13.5% from Example 2.2.3.1

2--5
Apsfse = (0.7)(4)(41.3)(1 -- 0.135)
= 100.0k
Mcr 
= yI P + Pe + 7.5 f′ c
b A Sb

Top fiber compression with sustained loads This ensures that when the concrete develops
flexural cracks, the prestressing steel will not have
100.02.89) 99.23 reached its full design stress. Violation of this cri-
ftop = 100.0 − + teria might result in strand fractures at the point of
154 297.9 297.9
= 0.649 -- 0.970 + 0.999 flexural cracking with a resulting brittle failure.
However, ACI (318-95) Section 18.8.3 allows
= + 0.679 ksi violation of this requirement for flexural members
Permissible compression with shear and flexural strength at least twice that
required.
= 0.45f′c The upper limit of reinforcing requires that,
= 0.45(5000) ωp or,
= 2.25 ksi > 0.679 ksi OK
Top fiber compression with total load
ω + dd ω − ω′ or
p
p

ftop = 100.0 −
100.02.89) 1673
+
ω + dd ω − ω′ 
pw
p
w w
154 297.9 297.9
be not greater than 0.36β1
= 0.649 -- 0.970 + 1.679
The need for an upper limit on reinforcing is re-
= 1.358 ksi lated to the assumptions of ultimate concrete com-
Permissible compression pressive strain. Using a uniform compression
stress block forces more concrete to reach ulti-
= 0.60f′c mate strain as reinforcing ratios increase. There-
= 0.60(5000) fore when the upper reinforcing limit is exceeded,
the moment capacity must be based on the com-
= 3.00 ksi > 1.358 ksi OK
pression block. For this condition,
Bottom fiber tension
φMn = φ f′ cbd 2p0.36β 1 − 0.08β 21
fbottom = 0.649 + (0.970 -- 1.679) 297.9
314.8 for rectangular sections or for flanged sections
= --0.022 ksi (tension) with the neutral axis within the flange.
The stress in the prestressing steel at ultimate
Permissible tension may be calculated in several ways. The ACI equa-
= 7.5 f′ c tion (18-3) may be used as an approximation,
charts and tables from the PCI Design Handbook
= 7.5 5000 may be used, or a strain compatibility analysis
may be made.
= 0.530 ksi > 0.022 ksi OK
Example 2.2.5.1 Design Flexural Strength
2.2.5 Design Flexural Strength
Using the generic hollow core slab defined in
The moment capacity of a prestressed member Section 1.7, check the design flexural strength
is a function of the ultimate stress developed in the given the following criteria:
prestressing strands. As with non-prestressed
Prestressing steel: 4-1/2″ dia., 270 ksi, low re-
concrete, upper and lower limits are placed on the laxation strands
amount of reinforcing to ensure that the stress in
dp = 7″
the strands is compatible with concrete stresses
for ductile behavior. initial stress = 70% fpu
The lower limit of reinforcing requires that: f′c = 5000 psi
φMn ≥ 1.2 Mcr ℓ = 30′-6″

2--6
Clear span = 30′-0″ φMn ≥ 1.2 Mcr
Superimposed Dead Load = 20 psf From Example 2.2.3.1
Live Load = 50 psf Loss = 13.5%
Solution: Apsfse = 0.7(4)(41.3)(1 -- 0.135)
METHOD 1: ACI Equation (18-3)
= 100.0 k
φMn = φApsfps(dp -- a/2) Bottom compression

fps = f pu 1−
γp
β1
 
ρp
f pu
f′ c
= 100.0 +
154
100.02.89
314.8
= 1.567 ksi
Use γp = 0.28 for low relaxation strands


β1 = 0.85 -- 5000 − 4000 0.05  3.89

Mcr = 1224.5 1.567 +
7.5 5000
1000

1000
= 660 in-k/slab
= 0.80
ÔM n
= 920 = 1.39 > 1.2 OK
A ps 40.153 M cr 660
ρp = = = 0.0024
bd p 367
METHOD 2: PCI Design Handbook
 
fps = 270 1 − 0.28 0.0024 270
0.80 5
 Using Figure 4.12.2 from the 5th Edition Hand-
book.
A ps f pu
= 257.7 ksi ωpu =
bd p f′ c
ρpf ps 0.0024257.7 441.3
ωp = = =
3675
f′ c 5
= 0.124 < 0.36 β1 = 0.288 OK = 0.131
K′u = 538
A psf ps 40.153257.7
a = = bd 2p
0.85f′ cb 0.85536
φMn = K′u
12000

 
= 1.03 in 2
36(7)
Note: If “a” exceeds the top flange thickness, the = 538
12000
compression block will encroach on the core area.
For this situation, multiple compression forces are = 79.0 ft-k/slab
used for the internal couple as is done with other
flanged members. METHOD 3: Strain Compatibility

φMn = 0.9(4)(0.153)(257.7) 7 − 1.03
2
 The stress-strain diagram from Figure 11.2.5 of
the PCI Design Handbook, shown in Fig. 2.2.5.1,
= 920 in-k/slab = 76.7 ft-k/slab will be used for this example. However, the actual
stress-strain curves received with strand mill re-
wu = 1.4(0.0535 + 0.02) + 1.7(0.05) ports should be used when available.
= 0.188 ksf The concrete ultimate strain is assumed to be
2 0.003 in/in. The method involves a trial and error
Mu = 30 (0.188) procedure to obtain equilibrium within the section
8
where the force in the compression block equals
= 21.14 ft-k/ft
the tensile force in the steel. The equations are de-
= 63.4 ft-k/slab < 76.7 OK veloped from the strain diagram shown.
Check minimum reinforcement a = β1c

2--7
Fig. 2.2.5.1 Stress-strain curves, prestressing strand

270
270 ksi strand
MINIMUM YIELD STRENGTH AT
Es = 28,500 ksi 1% ELONGATION FOR 270 ksi
250 (ASTM A416)

250 ksi strand

230
MINIMUM YIELD STRENGTH AT
1% ELONGATION FOR 250 ksi
Stress - fps (ksi)

(ASTM A416)

210

190

170

150
0 0.005 0.010 0.015 0.020 0.025 0.030

Strain- ps (in./in.)

These curves can be approximated by the following equations:

250 ksi strand 270 ksi strand


εps ≤ 0.0076: fps = 28,500 εps (ksi) εps ≤ 0.0086: fps = 28,500 εps (ksi)

εps > 0.0076: fps = 250− 0.04 (ksi) εps > 0.0086: fps = 270 − 0.04 (ksi)
Á ps − 0.0064 Á ps − 0.007

Using 13.5% loss from Example 2.2.3.1


fse = 0.7(270)(1 -- 0.135) = 163.4 ksi
0.003 0.85 f c’
f se
εse = = 163.4 = 0.0057
c a C E s 28500
dp
Assume c = 1″ then a = 0.80(1) = 0.8″
T
dp
s εs = c (0.003) -- 0.003

= 7 (0.003) -- 0.003 = 0.018


1

2--8
εps = εse + εs = 0.0107 in/in
= 0.0057 + 0.018 = 0.0237 εps = 0.0057 + 0.0107
= 0.0164 in/in
From stress-strain curve
fps = 266 ksi
fps = 268 ksi
for bars
T = 4(0.153)(268) = 163.8
εs = 5.5 (0.003) − 0.003
C = 0.85(5)(0.8)(36) 1.53
= 0.0078 in/in
= 122.4k < 163.8k
yield strain = 60 = 0.002 in/in
Try c = 1.3″ then a = 0.80(1.3) = 1.04″ 29000
7 (0.003) -- 0.003 T = 4(0.153)(266) + 2(0.2)(60)
εs =
1.30 = 162.8 + 24
= 0.0131 = 186.8k
εps = 0.0131 + 0.0057 = 0.0188 C = 0.85(5)(1.22)(36)
= 186.7k ≅ 186.8k ok
From stress-strain curve
fps = 267 ksi   2
 
φMn = 0.9 162.8 7 − 1.22 + 24 5.5 − 1.22
2

T = 4(0.153)(267) = 163 = 1042 in-k
C = 0.85(5)(1.04)(36) = 86.8 ft-k

= 159k ≈ 163k 2.3 Shear Design



φMn = 0.9(4)(0.153)(267) 7 − 1.04
2
 2.3.1 ACI Requirements
Hollow core slabs are designed for shear ac-
= 952 in-k/slab = 79.3 ft-k/slab cording to the same ACI Code provisions used in
On occasion, conventional reinforcement is general for prestressed members. In dry cast sys-
added to a hollow core slab to locally provide add- tems, the normal practice is to not provide stirrups
ed flexural strength. When required, the bars are when the applied shear exceeds shear capacity be-
placed in cores right after the slab is cast and con- cause of the difficulty encountered placing stir-
crete is added to fill the cores with the bars. The rups in most production processes. The place-
following example illustrates the flexural strength ment of stirrups in a wet cast system is certainly
calculation. easier than in a dry cast extruded system and is a
viable shear enhancement method. An alternative
Example 2.2.5.2 Flexural Strength with Bars used to increase shear capacity is to reduce the
Repeat Example 2.2.5.1 but add 2 - #4 bars in number of cores used in a given slab. This may be
cores. done by either leaving out a core for the entire
Solution: length of a slab or by locally breaking into the
cores and filling them solid while the concrete is
Use strain compatibility for strength calculation still in a somewhat plastic state.
with an effective depth of 5.5 in for the #4 bars. The provisions for shear are found in Chapter
Assume c = 1.53 in. 11 of ACI 318-95. With some paraphrasing, the
then a = 0.80(1.53) = 1.22 in requirements are:
Vu ≤ φVn
for strands
φ = 0.85 for shear
εs = 7 (0.003) − 0.003
1.53 Vn = Vc + Vs

2--9
For the purpose of this discussion, Vs, the con- Using the generic hollow core cross-section
tribution of shear reinforcement, will be taken as defined in Section 1.7, check the slab for shear
zero. The nominal concrete shear strength may be given the following information:
found using equation (11-9), Prestressing steel: 4-1/2″ dia., 270 ksi, low


Vc = 0.6 f′ c + 700
V ud
Mu w

b d (11-9)
relaxation strands.
Initial stress = 70% fpu loss = 15%
when the effective prestress force is not less than f′c = 5000 psi
40 percent of the tensile strength of the flexural re- ℓ = 25′-6″
inforcement. The term Vud/Mu shall not exceed Clear span = 25′-0″
1.0. The minimum value for Vc may be used as
Superimposed Dead Load = 20 psf
2 f′ c bwd and the maximum value is the lesser of Live Load = 50 psf
5 f′ c bwd or the value obtained from Equation Masonry dead load = 800 plf at 3′
(11-12) considering reduced effective prestress in from one support
the transfer zone. Solution:
Alternatively more refined shear calculations
Uniform load: wu = 1.4(0.0535 + 0.020)
can be made according to the lesser of Equations
+ 1.7(0.05)
(11-10) or (11-12).
= 0.188 ksf = 0.564 klf
V M cr
Vci = 0.6 f′ c b wd + V d + i (11-10) Line Load: Pu = 1.4(0.800) = 1.12k/ft
M max
= (3′)(1.12) = 3.36k
Vcw = (3.5 f′ c + 0.3fpc) bwd (11-12)
Load, shear and moment diagrams for 3′ slab
Equation (11-10) predicts shear strength for an width:
inclined shear failure mode. For Equation
(11-10), the following relationships are used: 1.12 x 3’= 3.36 k

Mcr = yI (6 f′c + fpe -- fd) (11-11) 3’ 0.188 x 3’= 0.564 k
ft

25’
Vd = Unfactored self weight shear for k
non-composite sections 10 k
8.31
Vi = Vu -- Vd 4.95
k
Vu
Mmax = Mu -- Md
Md = Unfactored self weight moment for
non-composite sections k
7.45
The minimum value for Vci need not be less
than 1.7 f′ c bwd or 2 f′ c bwd when the effective
Mu

prestress force is not less than 40% of the tensile 27.48 ft-k
strength of the flexural reinforcement. For equa-
49.25 ft-k
tions (11-10), (11-11) and (11-12), the reduction
in prestressing force at the member end due to Using the more refined approach according to
transfer must be considered. The ACI Code al- ACI Equations (11-10) or (11-12), φVc is:
lows an assumption that prestressing force in- φVcw = 0.85 3.5 5000 + 0.3f pc
creases linearly from zero at the member end to 1000
full effective prestress in a length equal to 50 x (10.5)(7) (11-12)
strand diameters. = 15.46 + 0.0187fpc
fpc is calculated as a function of the transfer of pre-
Example 2.3.1.1 Shear Design stress into the section along the span.

2--10
transfer length = 50 db = 50(1/2) = 25″ = 11.130 + 26.233fpe -- 2.01x + 0.8x2
with bearing length = 3″ Mmax = Moment due to factored
full prestress transfer is achieved 22″ from loads minus Md
the face of support
Apsfse = 4(41,300)(0.70)(1 - 0.150) Based on these definitions, φVcw, φVci, and Vu are

x x + 3 to x = 22″
25
 calculated at intervals across the span. A summa-
ry is presented in Table 2.3.1.1. Figure 2.3.1.1
presents the results graphically.
fpc =
A psf se 98294 x + 3
A
=
154 25
  Table 2.3.1.1 Allowable Shear
φVcw φVci
15.46 + 0.0187 98294 x + 3
x Vu
φVcw = h/2 = 0.333′ 9.82k 18.81k 59.40k
154 25
0.5′ 9.72 19.76 45.74
= 15.46 + 11.96 x + 3 to x = 22″ 1.0′ 9.44 22.64 31.92
25
1.5′ 9.16 25.51 27.15
φVci =  0.6
5000
1000
VM
10.57 + V d + i cr
M max
 2.0′
2.5′
8.88
8.59
27.42
27.42
23.34
18.93
x 0.85 (11-10) 3.0′ 8.31 27.42 15.98
3.0′ 4.95 27.42 10.02
Vd = Shear due to unfactored self weight
3.5′ 4.67 27.42 9.11
(for non-composite section)
4.0′ 4.39 27.42 8.34

= 3(0.0535) 25 − x = 2.01 -- 0.16x
2

Alternatively, the simplified equation (11-9)
Vi = Shear due to factored loads minus Vd might be used.
 
Mcr = yI 6 f′ c + f pe − f d
b 
φVc = 0.85 0.6 5000 + 700 MV 7
u
u

A
ey
fpe = Apsfse 1 + b
I
  x
10.57
1000
fpe = 98.294 x Vu
1541 + 3.89 − 13.89
1224.5
 x +25 3 = 2.65 + 306.1
Mu u
(M in in-k).
The results of this equation are also shown on Fig-
ure 2.3.1.1.

= 1.541 x + 3 ≤ 1.541 ksi
25
 At all points, Vu < φVc so shear strength is ade-
quate and stirrups are not required.
fd = flexural stress due to load used for Vd
Md 2.4 Camber and Deflection
= Camber is the upward deflection of a pre-
S
stressed member and results from the prestressing
30.0535x force being eccentric from the center of gravity of
25 − x
= 2 the cross-section. Since both prestressing force
314.8 and eccentricity are established by the required
design load and span length, camber is a result of
= 2.01x − 0.08x
2
314.8 the design rather than a design parameter. There-
fore, camber requirements should not be speci-
Mcr = 314.8 x
12 fied.


0.424 + f pe −
2.01x − 0.08x 2
314.8
12  Deflections are also affected by the amount of
prestressing only because prestressing establishes
the load at which a member will crack. If tensile

2--11
Fig. 2.3.1.1 Shear for Example 2.3.1.1

25

5 f’c bw d

20

Eq. (11-10)

Eq. (11-12)

15 Eq. (11-9)

10 2 f’c bw d
Shear, kips

Vu
5

0
0 1 2 3 4

Distance into Span, ft

stresses are kept below cracking, deflections will tions are not predictable with any degree of accu-
be independent of the prestress level. racy and any calculation of long term movements
Cambers and deflections will change with time must be considered to be only estimates.
due to concrete creep, prestress loss and other fac- This section presents calculation procedures
tors. The sustained compression due to the pre- for determining long term deflections. From the
stressing will cause camber growth. Balancing producer’s standpoint, history and experience
this is the effect of creep on deflections due to self must be used to modify the procedures to fit the lo-
weight and other sustained loads. It is this time cal product. From the specifier’s standpoint, these
dependent movement which, in addition to instan- procedures will allow only approximate estimates
taneous deflections, must be considered in the de- of long term effects and should be complemented
velopment of framing schemes and detailing. with discussions with local producers.
Instantaneous cambers and deflections are pre-
dictable as long as the material properties are
known. The time dependent cambers and deflec- 2.4.1 Camber

2--12
Table 2.4.1 Long term multipliers6
Without With
Condition Composite Composite
Topping Topping
At Erection:
1. Deflection (downward) component - apply to the elastic
deflection due to the member weight at release of prestress 1.85 1.85
2. Camber (upward) component - apply to the elastic camber
due to the prestress at the time of release of prestress 1.80 1.80
Final:
3. Deflection (downward) component - apply to the elastic
deflection due to the member weight at release of prestress 2.70 2.40
4. Camber (upward) component - apply to the elastic camber
due to prestress at the time of release of prestress 2.45 2.20
5. Deflection (downward) - apply to elastic deflection due to
superimposed dead load only 3.00 3.00
6. Deflection (downward) - apply to elastic deflection caused
by the composite topping ------ 2.30

Hollow core slabs are produced with straight Solution:


strand patterns rather than using draped or de- Estimate initial losses at 5% and use Eci = 3250
pressed strands. Using (+) to indicate upward ksi
movement and (--) to indicate downward move- Po = 0.95(0.7)(4)(41.3) = 109.9k
ment, net camber can be calculated as:
2
109.93.89 − 1[30.5(12)]
camber = Peℓ − 5wℓ
2 4
camber =
8EI 384EI 832501224.5
4
To determine initial camber, the appropriate 530.0535(30.5) 1728
values for prestress force and modulus of elastic- --
38432501224.5
ity of the concrete must be used. When ultimate
moment rather than tensile stresses govern a de- = 1.34 -- 0.79
sign, the initial strand stress may be reduced to = 0.55″ Say 1/2″ to 3/4″ initial camber
modify the anticipated camber. Additionally, slab Estimating long term effects is complicated be-
camber is sensitive to support point locations dur- cause, as time passes, the prestressing force de-
ing storage. Camber will increase as these support creases due to losses and the modulus of elasticity
points move in from the slab ends. of the concrete increases with concrete strength
Example 2.4.1 Initial Camber gain. Traditionally, a creep factor of 2.0 has been
Using the generic hollow core slab defined in applied to instantaneous deflections to estimate
section 1.7, calculate the initial camber given the the additional deflection due to creep. This has
following: been modified by Martin6 for prestressed con-
Prestressing steel: 4-1/2″ dia., 270 ksi, low re- crete. Table 2.4.1 presents suggested multipliers
laxation strands to determine both long term final deflections and
position at erection. It should be noted that in us-
Apsfpu = 0.153(270) = 41.3k/strand ing these multipliers, a total deflection is calcu-
Initial stress: 70% fpu lated rather than the additional increment due to
dp = 7″ long term effects.
ℓ = 30′-6″ Example 2.4.2 Long Term Camber

2--13
For the slab of Example 2.4.1, determine the
net camber at erection and the final camber.
Table 2.4.2 Maximum Permissible Computed Deflections1
Type of member Deflection to be considered Deflection limitation
Flat roofs not supporting or attached to non- Immediate deflection due to live load L
structural elements likely to be damaged by ℓ*
large deflections 180
Floors not supporting or attached to non- Immediate deflection due to live load L
structural elements likely to be damaged by ℓ
large deflections 360
Roof or floor construction supporting or That part of the total deflection occurring after
attached to nonstructural elements likely to attachment of nonstructural elements (sum of ℓ ***
be damaged by large deflections the long-term deflection due to all sustained 480
loads and the immediate deflection due to any
Roof or floor construction supporting or at- additional live load)**
tached to nonstructural elements not likely to ℓ ****
be damaged by large deflections 240
* Limit not intended to safeguard against ponding. Ponding should be checked by suitable calculations of deflection, including added deflections due to ponded
water, and considering long-term effects of all sustained loads, camber, construction tolerances, and reliability of provisions for drainage.
** Long-term deflection shall be determined in accordance with 9.5.2.5 or 9.5.4.2, but may be reduced by amount of deflection calculated to occur before attach-
ment of nonstructural elements. This amount shall be determined on basis of accepted engineering data relating to time-deflection characteristics of members
similar to those being considered.
*** Limit may be exceeded if adequate measures are taken to prevent damage to supported or attached elements.
**** But not greater than tolerance provided for nonstructural elements. Limit may be exceeded if camber is provided so that total deflection minus camber does
not exceed limit.

Solution: the effective moment of inertia of the section.


At erection, Calculations using bilinear moment-deflection
initial camber = 1.34 -- 0.79 relationships are required when tension exceeds
6 f′ c and are covered extensively in references 1
= 0.55″ from Example 2.4.1 and 2. By definition, cracking occurs at a tensile
Erection camber = 1.34(1.80) -- 0.79(1.85) stress of 7.5 f′ c. While the ACI Code requires
= 0.95″ such bilinear calculations when 6 f′ c tension is
Say 1″ erection camber exceeded, in effect bilinear behavior is meaning-
less up to a tension of 7.5 f′ c. Since hollow core
Final camber = 1.34(2.45) -- 0.79(2.70)
slabs are normally designed to be uncracked un-
= 1.15″ der service loads, the effects of cracking will not
Say approximately 1 1/4″ final camber be considered here.
Table 2.4.1 includes multipliers for determin-
ing the long term effects for superimposed loads.
2.4.2 Deflections
Again, use of the multipliers gives an estimate of
As with camber, concrete creep will also affect
total deflection rather than an increment for the
deflections due to sustained superimposed loads.
additional long term deflection.
These long term effects must be considered for
comparison with Table 9.5(b) of the ACI Code to
determine acceptability. This table is reproduced Example 2.4.3
here as Table 2.4.2. Engineering judgement For the slab of Examples 2.4.1 and 2.4.2, deter-
should be used in comparing calculated deflec- mine the total deflection due to a superimposed
tions to the ACI Code limits. Many building code load of 20 psf dead and 50 psf live on a clear span
specified live loads exceed the actual loads in a of 30′-0″ including long term effects. Use Ec =
structure. While it may be implied that the full 4300 ksi.
live load be used for comparison to Table 9.5(b), Solution:
situations may arise where it is more reasonable to From Example 2.4.2
use actual anticipated live loads for deflection
comparisons. A further complication for super- Final camber = 1.15″
imposed loads is that flexural cracking will reduce superimposed dead load instantaneous deflection:

2--14
4 4
50.023(30) 1728 50.023(30) 1728
= = 0.208″ =
38443001224.5 38443002307
= 0.11″
Final deflection = 0.208 (3.0) = 0.62″ (Note: 2307 in.4 = composite moment of inertia
Instantaneous live load deflection: using a 3000 psi topping on a 5000 psi slab.)
4 Long term dead load deflection
50.053(30) 1728
= = 0.52″ = 0.11(3.0) = 0.33″
38443001224.5
Instantaneous live load deflection:
Final position
= 50 (0.11) = 0.28″
final camber = + 1.15″ 20
sustained dead load = -- 0.62 Final Position = +1.05 -- 0.60 -- 0.33 -- 0.26 =
net camber + 0.53″ --0.14″ including instantaneous live load.
live load increment = -- 0.52 Calculate increment due to differential shrinkage
+ 0.01″ assuming shrinkage strain of 500 × 10--6 in/in in
both the topping and slab:
For comparison to the provisions of Chapter 9
If total shrinkage = 500 × 10-6
of the ACI Code, when non-structural elements
and erection shrinkage = 250 × 10-6
are attached to the slabs, the portion of deflection
differential shrinkage = 250 × 10-6
after erection may be used for comparison.
The differential shrinkage can be thought of as
Change in camber = 1.15″ -- 0.95″ = + 0.20″ a prestress force from the topping where
Sustained dead load = -- 0.62″
Instantaneous live loads = -- 0.52″ P = Atopping (strain)(modulus)
-- 0.94″ = 36″(2″)(0.00025)(3320)
When a composite topping is used, it will be = 59.8k
cast after a portion of the slab shrinkage has oc-
The effect is lessened by concrete creep and,
curred. There will then be differential shrinkage using a factor of 2.30 from Table 2.4.1, reduces to:
between the topping and slab. This differential
can cause additional deflection and bottom tensile P = 59.8/2.30 = 26k
stress. These effects will generally be negligible. The eccentricity of this force is:
e = 9″ -- 3.89″
Example 2.4.4 Composite Slab
= 5.11″
Given the slab of Example 2.4.3, add a 2″ com-
posite topping and recalculate deflections includ- M = Pe = 26 x 5.11 = 133 in-k
ing the affects of differential shrinkage.
downward deflection = Mℓ
2
Solution: 8EI
Final camber = 1.34 x 2.20 -- 0.79 x 2.40 2
133(30x12)
=
= 1.05″ 843002307
Instantaneous topping weight deflection: = 0.22″ ≅ 1/4″
)4
50.0253(30 1728 Considering the span used in this example and
= the accuracy of the other camber and deflection
38443001224.5
calculations, it can be easily seen that differential
= 0.26″ shrinkage will generally not be significant.
Long term deflection due to topping weight
2.5 Composite Design
= 0.26″ (2.30) = 0.60″ A composite, structural concrete topping is
Superimposed dead load deflection: commonly used in floor construction with hollow

2--15
core slabs. The composite action is desirable to Since the composite topping and hollow core
add stiffness and strength for gravity loads and slabs interact to create the final structural element,
may also be required for load transfer within a dia- it is imperative that the topping bond well with the
phragm. When a composite topping is used, con- slabs. While the building designer may only be in-
sideration must be given to its strength, detailing terested in the final product, the process of achiev-
and quality assurance. ing a well bonded, composite topping is very im-
The required compressive strength of the top- portant. The hollow core producer is dependent
ping may be determined from the hollow core slab on a properly bonded topping, yet is not involved
design requirements. Load tables provided by lo- in specifying, designing or installing the topping.
cal producers will normally indicate that either a The hollow core producer is responsible for sup-
3000 psi (20.7 MPa) or 4000 psi (27.6 MPa) con- plying a slab that is capable of bonding with a top-
crete is required. Diaphragm requirements may ping. The installer of the topping is responsible
necessitate a higher strength topping concrete. for surface preparation, topping concrete mix de-
From a detailing standpoint, the primary con- sign and curing to assure proper bond.
sideration is that hollow core slabs will have cam- At a minimum, the slab surface must be clean
ber. If the topping is finished as a level surface, the and damp at the time of topping installation. It is
camber will reduce the topping thickness in the recommended that the surface be thoroughly satu-
midspan region which will affect the load capacity rated prior to topping placement, but all standing
of the slabs. With significant topping thickness water must be removed. ACI 301-967 specifies
reduction, the integrity of the topping concrete that a sand and cement grout be scrubbed into the
may also be compromised. A preliminary slab de- slab surface ahead of topping placement. If this
sign can provide an estimate of camber and the procedure is used, it is imperative that initial set
minimum topping thickness necessary to support not be allowed prior to topping placement. If ini-
the design loads. The first option is to provide the tial set occurs, the grout can become a bond break-
minimum thickness topping at midspan and allow er. Similarly, bonding agents, which are rarely
the thickness to increase at the slab ends to main- specified, will also act as a bond breaker if any ini-
tain a flat floor. Finish and bearing elevations can tial set occurs prior to topping placement.
then be set to this criteria. The topping concrete mix and curing tech-
A second option to minimize topping concrete niques will also affect bond of a composite top-
volume is to allow the minimum topping thick- ping. Curling at topping edges or joints will cause
ness to follow the curvature of the slabs. This will local delamination. Curling is a result of differen-
result in a finished floor with camber which may tial shrinkage between the top and bottom sur-
be acceptable in some occupancies. In this option, faces of the topping. Generally, water is lost more
it is important that all trades be made aware of the quickly from the top surface causing additional
final camber as it may affect their work. Parti- drying shrinkage. This can be minimized by prop-
tions, doorways and stairs will be particularly af- er curing techniques and low shrinkage concrete.
fected in this option. Design of hollow core slabs for composite ac-
When control joints are used in a structural top- tion is usually limited to a horizontal shear
ping, they should be located over the joints in the strength of 80 psi (0.5 MPa) according to section
precast units below where cracks would most nat- 17.5.2.1 of ACI 318-95. Through limited pub-
urally occur in the topping. At the ends of slabs, lished8 and unpublished testing, the machine fin-
where movement will occur due to camber ished surface has been found to meet the require-
changes, deflections, creep, shrinkage or elastic ments of that section. The horizontal shear check
shortening, control joints are desirable. should be based on the shear diagram rather than
Reinforcing of a topping may be required for using an average horizontal shear over the dis-
structural design. If not, consideration should be tance from zero moment to maximum moment
given to using minimum shrinkage reinforcement when checking compliance with the 80 psi limit.
for crack control. Composite ties are not normally provided giv-
en the difficulty and expense of installing the ties

2--16
in a machine casting operation. When the horizon- I = 1224.5 + 154(5.24 -- 3.89)2
tal shear exceeds 80 psi (0.5 MPa) and composite 3
ties are not used, the topping is considered to be + 2 (27.7) + 2(27.7)(9 -- 5.24)2
12
superimposed dead load on a non-composite slab. = 2307 in4
In a wet cast system, horizontal shear ties with 1/4
in amplitude roughening may be used to take ad- Calculate prestress losses:
vantage of the higher stresses allowed by ACI. From Example 2.2.3.1
Design of a composite section is similar to that ES = 7.52 ksi
presented in Sections 2.2 and 2.3. The following
example demonstrates the additional consider- Concrete creep
ations with a composite section. 2
Msd = 30 (0.025 + 0.020)(3)
8
Example 2.5.1 Composite Design = 15.19 ft-k
Using the generic hollow core cross-section de-
fined in Section 1.7, add a 2 in structural topping 15.19(12)(2.89)
fcds =
and check for the following conditions: 1224.5
Prestressing steel: 4-1/2″ dia., 270 ksi low relax- = 0.430 ksi
ation strands CR = (2.0) 28500 (0.857 -- 0.430)
4300
Initial stress: 70% fpu
= 5.66 ksi
dp: 7 in
SH = 6.27 ksi
Slab: f′c = 5000 psi
Eci = 3250 ksi

RE = 5000 − 0.04(6.27 + 5.66 + 7.52) 0.75
1000

Ec = 4300 ksi = 3.17 ksi
Topping: f′c = 3000 psi Loss = 7.52 + 5.66 + 6.27 + 3.17
Ec = 3320 ksi = 22.62 ksi = 12%
Slab length: 30′-6″ Calculate service load stresses:
Slab span: 30′-0″ Apsfse = 0.7(4)(41.3)(1 -- 0.12)
Loads: topping = 25 psf = 101.8k
dead load = 20 psf 2
Mnon--comp = 30 (0.0535 + 0.025)
live load = 50 psf 8
Calculate section properties: = 8.83 ft-k/ft = 106 in-k/ft
2
Base section A = 154 in2 Mcomp = 30 (0.020 + 0.050)
I = 1224.5 in4 8
yb = 3.89 in = 7.88 ft-k/ft = 94.5 in-k/ft
Topping At top of topping
n = 3320/4300 = 0.77 94.5(3)(10 − 5.24)
ftop = (0.77)
2307
use width = 0.77(36)
= 0.450 ksi
= 27.7 in
At top of slab
Composite
101.8(2.89)(4.11)
A = 154 + 2(27.7) = 209.4 in2 ftop = 101.8 −
154 1224.5
154(3.89) + 2(27.7)(9) 106(3)(4.11) 94.5(3)(8 − 5.24)
yb = + +
209.4 1224.5 2307
= 5.24 in. = 1.080 ksi

2--17
At bottom of slab
101.8(2.89)(3.89)
Vu = 302 − 2(12)
10 (0.223)(3)
fbottom = 101.8 +
154 1224.5 = 9.8 k < 22 k ok
106(3)(3.89) 94.5(3)(5.24) Section is composite
− −
1224.5 2307
Check web shear at h/2:
= --0.058 ksi
transfer length = 50(0.5) = 25 in
Calculate flexural strength
at h/2 plus 3 in bearing
wu = 1.4(0.0535 + 0.025 + 0.020)
+ 1.7(0.050) Apsfse = 101.8 258  = 32.6 k
= 0.223 ksf
for composite section, fpc is calculated at centroid
2
Mu = 30 (0.223)(3) of composite section
8
32.6(2.89)(5.24 − 3.89)
= 75.26 ft-k fpc = 32.6 −
154 1224.5
Using ACI Eq. (18-3)
= 0.108 ksi
4(0.153)
ρp =
36(9)
= 0.0019
φVcw = 0.85  3.5 5000
1000

+ 0.3(0.108) (10.5)(9)
fps  0.85

= 270 1 − 0.28 0.0019 270
3

= 22.5k > 9.8 k ok
= 254.8 ksi Check inclined shear at 4 ft
a =
4(0.153)(254.8)
0.85(3)(36)
2

Vu = 30 − 4 (0.223)(3)
= 1.7 in = 7.36k

φMn 
= 0.9(4)(0.153)(254.8) 9 − 1.7
2
  
Vd = 30 − 4 (0.0535 + 0.025 + 0.020)(3)
2
= 1144 in-k = 95.3 ft-k = 3.25k
Check 1.2 Mcr Vi = 7.36 -- 3.25 = 4.11k

fbottom = 101.8 +
154
101.8(2.89)(3.89)
1224.5
 
Mu = 0.223(3)(4) 30 − 4 = 34.8 ft-k
2 2
= 1.596 ksi

Md = (0.0535 + 0.025 + 0.020)(3)(4) 30 − 4 
Mcr 
= 2307 1.596 +
5.24
7.5 5000
1000
 = 12.25 + 3.12 = 15.37 ft-k
2 2

Mmax = 34.8 -- 15.37 = 19.43 ft-k


= 936 in-k 101.8(2.89)(3.89)
fpe = 101.8 +
ÔM n 154 1224.5
= 1144 = 1.22 > 1.2 ok
M cr 936 = 1.596 ksi
Check horizontal shear: 12.25(12)(3.89) 3.12(12)(5.24)
fd = +
φVnh = φ80bvd 1224.5 2307
= 0.85(80)(36)(9) = 0.552 ksi
= 22030 lb
= 22 k
Mcr = 2307
5.24

6 5000
1000
+ 1.596 − 0.552 
at h/2 = 646 in-k = 53.9 ft-k

2--18
φVci = 0.85 
0.6 5000
1000
(10.5)(9) 

+ 0.85 3.25 +
4.11(53.9)
19.43

= 15.86k > 7.36k ok

2--19
Fig. 2.6.1.1 Fig. 2.6.1.2

fps
Steel Stress

fse

t f fps
d fps req’d.
Length into span greater than
fps available
Strand Development
d

Section 12.9.2 of the ACI Code limits inves-


2.6 Strand Development tigation of development length to the section near-
est the end of the member where full design
strength is required. In conventionally reinforced
2.6.1 ACI Requirements concrete, the rate of moment increase must be
Section 12.9 of the ACI Code covers develop- considered in selecting reinforcing bar sizes. This
ment length for prestressing strands. While the consideration is also valid in prestressed concrete
topic has received considerable discussion9-16, members. As shown in Figure 2.6.1.2, with a
the ACI Code expression currently remains: steep rate of moment increase, critical sections
ℓd = (fps -- 2/3fse)db may occur in the strand development length at less
than maximum moment.
A further requirement is that the development Demand on strand strength above fse does not
length shall be doubled when bonding of a strand occur until after flexural cracking occurs. If flex-
does not extend to the end of the member and the ural cracking occurs in the transfer length, the
precompressed tensile zone is allowed to be in strand cannot accept additional stress so bond fail-
tension at service loads. ure occurs. Therefore, the limit on member flexu-
The ACI Code expression for development ral strength in the strand transfer length is the
length describes two bond mechanisms. The first cracking moment.
is the transfer length which is the bond length re- In the flexural bond length, strand stress can in-
quired to transfer the effective prestress after crease above fse, but not to full fps. Therefore,
losses, fse, to the concrete. This portion of the de- there is additional flexural strength above the
velopment length is: cracking moment, but less than full nominal
strength. If flexural cracking occurs at factored
ℓ t = f se d b load in the flexural bond length, the maximum
3
With fse equal to 150 ksi (1034 MPa), the trans- value for fps can be calculated as:
fer length becomes 50db, the length used for shear x − ℓt
calculations. f′ps = fse + (fps -- fse)
The second mechanism is for bond length after ℓf
the steel stress increases above fse. To develop the where x = the distance from the end of the
full design strength of the strand, fps, a bond length member to the section of interest
in addition to the transfer length is required. The
flexural bond length is expressed as:
The nominal moment capacity is then calculated
ℓ f = (fps -- fse)db on the basis of this maximum strand stress.
Figure 2.6.1.1 depicts the increase in steel Martin and Korkosz17 suggest that with partial-
stress along the development length of the strand. ly developed strand, the full concrete compressive

2--20
failure strain will not be achieved. A strain com- Hollow core slab systems are often required to
patibility analysis can be performed to determine carry concentrated or wall loads which may affect
the concrete strain that would be consistent with the rate of moment increase near the member end.
f′ps and nominal strength can then be calculated While not required by ACI, it is suggested that the
using that strain. transfer length and flexural bond length regions
When debonded strands are mixed with fully be investigated for reduced capacity when the mo-
bonded strands, a similar strain compatibility ment gradient is high.
analysis may be required in the flexural bond The development length equations in the ACI
length for the debonded strands. In this case, Code are based on testing conducted with mem-
nominal strength can be calculated in two ways: bers cast with concrete having normal water-ce-
1. Analyze section with all strands at the f′ps for ment ratios. As noted in the Commentary to the
the debonded strands. ACI Code, no slump concrete requires extra pre-
cautions. Hollow core slabs produced with the ex-
2. Analyze section with only fully bonded strands trusion process fall into this category. As original-
at their fps and ignore the debonded strands. ly presented by Anderson and Anderson10 and
The greater of the two results would predict the reinforced by Brooks, Gerstle and Logan18, a
nominal strength of the section. measure of satisfactory bond is the free end slip of
For hollow core slabs, the strain compatibility a member after it is cut to length. A limit on free
analysis for partially developed strand will yield end slip expressed as:
variable results as compared to a traditional ap- f sef si
proach where f′ps is used with a full concrete strain δall = d
6E s b
of 0.003 in/in. If f′ps is close to fse, the strain com-
has been suggested as a maximum free end strand
patibility analysis will predict moment capacity of
slip for using the ACI Code development lengths.
about 85% of the traditional analysis. When f′ps is
This expression approximates the strand shorten-
10% greater than fse, the difference reduces to 5%
ing that would have to occur over the transfer
or less. The additional complexity of the strain
length. For a 1/2″ (12.7 mm) dia. strand stressed
compatibility analysis would only seem war-
initially to 189 ksi (1300 MPa), the free end slip
ranted when flexural cracking is expected near the
should not exceed about 3/32″ (2.4 mm) if the ACI
transfer point or when debonded strands are used.
Code transfer and development lengths are to be
There are several aspects of a bond length dis-
used.
cussion that are significant to hollow core slab de-
When free end slip exceeds δall, the transfer
sign. In many framing schemes, there will be a re-
length and the flexural bond length will increase.
quirement to use very short slabs to fill in an area.
Shear strength in the transfer length and moment
With fully developed strands, these slabs will nor-
capacity in the flexural bond length will be de-
mally have very large load capacities. However,
creased and the length into the span where full
capacity may be reduced because the strands
moment capacity is provided will be increased.
might only be partially developed. For example,
If the free end strand slip is known from quality
for a slab prestressed with 1/2″ (12.7 mm) φ, 270
control measurements, the member capacity can
ksi (1860 MPa) strands with fse = 150 ksi (1034
be evaluated with consideration of extended
MPa) and fps = 260 ksi (1790 MPa):
transfer and flexural bond lengths. As a function
ℓ d = f ps − 2 f sed b of measured end slip, the transfer length and flex-
3 ural bond length can be calculated for each strand

= 260 − 2 150 0.5
3
 as follows:
ℓ t = 2δsEs/fsi
= 80″ = 6′-8″ (2030 mm)
This slab would have to be two development ℓ f = 6δsEs(fps -- fse)/(fsifse)
lengths, or 13′-4″ (4.1 m) long in order to develop Shear strength can be evaluated by substituting
its full design strength. A shorter slab would have the extended transfer length for 50 db in evaluat-
reduced capacity. ing the rate of increase of prestress. Flexural

2--21
Fig. 2.6.1.3 Effect of End Slip

80.00
Moment (ft-k)

60.00
Moment Capacity
with 5/32" End Slip
40.00
Moment Capacity
20.00 Uniform Load
with Normal End Slip
Moment Diagram
0.00
0.0 5.0 10.0 15.0 20.0 25.0 30.0

Distance Along Member Length (ft)


(a)

80.00
Moment (ft-k)

60.00
Moment Capacity
with 5/32" End Slip
40.00
Moment Capacity
20.00 Uniform Load
with Normal End Slip
Moment Diagram
0.00
0.0 5.0 10.0 15.0 20.0 25.0

Distance Along Member Length (ft)


(b)

strength calculations are affected only by the ex- The following example demonstrates the use of
tension of the strand development length and po- the Martin and Korkosz strain compatibility anal-
tential reduction of f′ps. The strain compatibility ysis for partially developed strand and the use of
analysis suggested by Martin and Korkosz for free end slip for evaluating strength. The proce-
sections with partially developed strand becomes dure illustrated is also valid with normal end slip
more complex as there can be variation in devel- by using the appropriate transfer and bond
opment lengths within a given member. lengths.
Figure 2.6.1.3 illustrates the change in moment
Example 2.6.1.1 Initial Strand Slip
capacity for the generic slab of Section 1.7 from
Given the generic hollow core slab defined in
normal slip to 5/32 in (4 mm) slip on all strands. In
Section 1.7, calculate the design flexural strength
(a), the span length is 30 ft (9.1 m) and there would
given the following:
be no change in slab capacity for uniform load. In
(b), the span is reduced to 25 ft (7.6 m) and it is Prestressing steel: 4-1/2″ dia., 270 ksi low
clear that the extended development length would relaxation strands.
result in reduced capacity even with uniform load. Es = 28500 ksi
End slip in excess of normal slip has a more signif- dp = 7″
icant effect in shorter slabs. f′c = 5000 psi

2--22
fsi = 185 ksi T = C
fse = 163.4 ksi Find
fps = 267 ksi c = 2.18″
δs = 3/16 in. all strands
εc = 0.000929 in/in
Solution:
Concrete stress at top
ℓ t = 2(3/16)(28500)/185
= 4300(0.000929)
= 57.8″
= 3.995 ksi
ℓ f = 6(3/16)(28500)(267 -- 163.4)/185/163.4
= 109.9″ Concrete stress at top of core
2.18 − 1.25
ℓ d = 57.8 + 109.9 = (3.995) = 1.704 ksi
2.18
= 167.7″
3.984 + 1.704
The minimum slab length required to achieve C1 = (1.25)(36)
full flexural capacity is 2(167.7)/12 or 28 ft. Cal- 2
culate flexural capacity at 10 ft. = 128k
10x12 − 57.8 C2 = 1.704 (10.5)(2.18 -- 1.25)
f′ps = 163.4 + (267 -- 163.4) 2
109.9
= 222 ksi = 8.3k
Apsf′ps = 4(0.153)(222) Mn = (135.9(7 -- 0.54) -- 8.3(1.56 -- 0.54))/12
= 135.9k = 72.45 ft-k
Traditional analysis
a = 135.9 = 0.89 in.
.85536
Mn = 135.9(7 -- 0.89/2)/12
= 74.24 ft-k
Strain compatibility analysis
Ec c
c C1
C2
dp
T = Apsf’ps
s

εps = εse + εs
εse = 163.4/28500
= 0.00573 in/in
εps = 222/28500
= 0.00779 in/in
εs = 0.00779 -- 0.00573
= 0.00206 in/in
Using trial and error for

2--23
CHAPTER 3

SPECIAL DESIGN CONSIDERATIONS


3.1 General Information slabs will contribute in carrying a given load in a
The application of hollow core slabs as roof given location. This section presents a design
and floor deck members creates several situations method that may be used when the slabs do actual-
for consideration in design which are either not ly have to support non-uniform loads.
completely covered by ACI Code provisions or
which involve consideration of production pro- 3.2.1 Load Distribution Mechanisms
cesses. This section presents information which As load is applied to one slab in a system, the
may be used as a guideline for the situations de- response of the slab system is to deflect and also
scribed but not as hard and fast rules. The criteria twist if the load is not on the longitudinal center-
presented represent conservative practices and line of the system. As the loaded slab edges try to
should be verified with local producers. Pub- move down, the interlock of the grout in the joints
lished data relative to each situation is referenced. with the keyways formed in the slab edges forces
However, extensive in plant testing has been con- adjacent slabs to deflect a similar amount. The
ducted by hollow core producers which may al- flexural and torsional stiffness of the adjacent
low less conservative criteria to be used because slabs reduce the deflection of the loaded slab from
of the unique characteristics of a particular slab. what might be expected if the slab were alone.
Shear forces are developed along the keyways and
3.2 Load Distribution the loaded slab then gets some support from the
As demonstrated in Chapter 2 of this manual, adjacent slabs. As this effect trickles through the
hollow core slabs are designed as individual, one system, the keyways between slabs force equal
way, simple span slabs. When the slabs are deflections for slab edges at any given keyway.
installed and grouted together at the keyways, the Many times shrinkage cracks will occur in the
individual slabs become a system that behaves grouted joints at the interface between the grout
similarly to a monolithic slab. A major benefit of and slab edge. This cracking does not impair the
the slabs acting together is the ability to transfer mechanism described above because the configu-
forces from one slab to another. In most hollow ration of the keyways in the slab edges still pro-
core slab deck applications, non-uniform loading vides mechanical interlock even with the presence
occurs in the form of line loads, concentrated of a crack.
loads, or load concentrations at openings. The Shear forces transferred along keyways cause
ability of individual slabs to interact allows these two sets of forces that are normally not considered
load concentrations to be shared by several slabs. in hollow core slab design. The first is torsion
The ability to distribute loads among several slabs which develops because the shear on one edge of a
has been demonstrated in several published tests given slab is different in magnitude from the shear
19-25 and many unpublished tests. on the opposite edge. As depicted in Figure 3.2.1,
In many cases, load concentrations do not have the keyway shears reduce as the distance from the
to be carried by the slabs. For example, a header at load increases. These torsions cause shear stress
a large opening may be supported directly to a in the slabs in addition to the direct shear stress.
foundation or vertical support element; a beam The second set of forces is induced because the
might be installed to directly carry a heavy con- system is tending to behave as a two way slab.
centrated load; or a heavy wall parallel to a slab Transverse bending moments occur because of
span might be designed to carry its own weight or the edge support provided by adjacent slabs. The
any load superimposed on the wall as a deep beam result is transverse tensile stress developed in the
spanning between vertical supports. However, bottom of the slab and compressive stress in the
when such loads must be supported by the slab top. Hollow core slabs are not provided with
system, a method is required to decide how many transverse reinforcement. Transverse tensile

3--1
Fig. 3.2.1

V1 V1 V2 V2 V3

V1 > V2 > V3

stresses must then be resisted by plain concrete. The two basic design parameters considered
The magnitude of load concentration causing the for hollow core slabs are flexure and shear. De-
transverse tension must be limited to preclude a sign for flexure is straightforward with the effec-
splitting failure. See Section 3.2.2. tive load resisting width being a function of the
Several factors affect the ability of a slab sys- span length. Conversely, shear design is compli-
tem to distribute loads to adjacent slabs. As the cated by torsions developed in the system. If tor-
width of an assembly of slabs gets narrower than sion is not to be used as a design parameter, direct
the span length, a reduction in the number of slabs shear must then be modified to reflect the increase
contributing to the support of a concentration of in shear stress from the torsion.
load occurs. This occurs because the freedom of Figure 3.2.2 depicts a method of establishing
the free edges of the system to deflect and twist be- an effective resisting section for any type of load
comes more significant. A second factor is the to be distributed between slabs. In the midspan re-
spacing of the slab joints. With slabs available in gions, the effective width is defined as a function
widths ranging from 2 feet to 8 feet (0.6 to 2.4 m), of span length. At the supports, the effective
some differences in load distribution behavior can width is defined as an absolute width. The width
be expected. Finally, the span length affects the at the support is restricted to account for shear
number of contributing slabs. As span length stresses due to torsion. Use of these resisting sec-
changes for a wide system, the interaction of flex- tions will result in prediction of peak values of
ural and torsional stiffnesses changes. For longer moment and shear. That is, the effective width
spans, flexural stiffness reduces relative to tor- concept is simply a mechanism used to determine
sional stiffness. This results in relatively less slab the maximum design moments and shears rather
rotation and less transverse curvature. The result than a depiction of the actual load path through the
is that more slabs can contribute to distribution on system.
longer spans as long as the system is wide relative The performance of slab systems indicates that
to its length. shear and moment might affect additional slabs.
For example, for a load located some distance
from a free edge, the peak moment due to that load
3.2.2 Design Guidelines can be predicted by assuming the load is resisted
ACI 318-95 recognizes the load transfer capa- by a width equal to 0.50ℓ. In reality, in flexure, a
bilities of hollow core slabs in Section 16.3.1. total width equal to 85% to 90% of the span length
That section specifies that distribution of forces might have some moment attributable to that load.
be established by analysis or test. The guidelines In shear, the 1′-0″ (0.3m) effective section at the
presented here were based on extensive, full scale support at a free edge may be used to predict the
testing of a specific slab system. Additionally, a peak shear but, because of torsion, the total reac-
comparison of these guidelines to an analytical tion due to an edge load will not actually be con-
study has been done. Therefore, the guidelines centrated in the 1′-0″ (0.3m).
presented here should satisfy the requirement of Several limitations should be recognized for
ACI (318-95) 16.3.1. Figure 3.2.2.

3--2
Fig. 3.2.2 Effective resisting width of slab for load anywhere along span

0.25
0.50
0.25
4’-0" 1’-0"

Interpolate

Interpolate
0.50 0.25

1) As the width of the system becomes narrow- tablished by test for each slab system. Ref-
er than the span length, the effective resist- erence 23 provides guidance for edge loads.
ing widths will become narrower.
The concept of using an effective resisting sec-
2) For extremely high span-depth ratios (in ex- tion is subtlely different from the traditional con-
cess of approximately 50), the effective sec- cept of load distribution width. Traditionally,
tion at midspan may be reduced by 10 to 20 loads have been divided by distribution widths for
percent. design. Using an effective resisting section means
that a given load is resisted by a varying width de-
3) For spans less than about 10 ft, the effective pending on the location of the section being inves-
width at the support may become narrower. tigated in the span. This is best illustrated by ex-
ample.
4) Local load concentrations can cause longi-
tudinal splitting failures due to transverse Example 3.2.1 General Case
bending in the system. Punching shear type Given an untopped hollow core system using
failures can also occur. The magnitude of 36″ wide slabs as shown in Figure 3.2.3, deter-
concentrated loads must be limited to pre- mine the slab design loads. Slab weight = 53.5 psf
clude such failures. These limits are best es-

3--3
Fig. 3.2.3.

5 ’-6 "
P1

9 ’-6 "
w1
P2
25’-0"

6 ’-0" P2
w1
P1
9 ’-6 "

5 ’-6 "

DL = 10 psf w1D = 650 #/ft P1D = 500 # P2D = 1000 #


LL = 40 psf w1L = 1040 #/ft P1L = 1000 # P2L = 3000 #

Solution DW = 0.5ℓ = 0.5(25) = 12.5 ft


Step 1: Evaluate the shear and moment diagrams
Between x = 0 and x = 6.25 ft
for the non-distributable loads.
DW = 4 + x (12.5 -- 4)
wu = 1.4(53.5 + 10) + 1.7(40) = 157 psf 6.25
= 4 + 1.36x
Vx = w (ℓ/2 -- x) = 0.157(25/2 -- x) See Table 3.2.1
Step 4: Divide the shears and moments from Step
Mx = w x (ℓ − x) = 0.157x (25 − x)
2 2 2 by the effective width from Step 3 and
See Table 3.2.1 add to the shears and moments in Step 1.
Step 2: Evaluate the shear and moment diagrams See Table 3.2.1
for the distributable loads. Step 5: Design the slabs for the web shear, in-
wu = 1.4(650) + 1.7(1040) = 2678#/ft clined shear, and moments obtained from
Step 4.
Pu = 1.4(500) + 1.7(1000) = 2400#
The solution for the general case where the
Pu = 1.4(1000) + 1.7(3000) = 6500# shears and moments are calculated at intervals
See Table 3.2.1 along the span is best suited for use with a comput-
er. The information could then also be used to cal-
Step 3: Evaluate the effective width along the culate shear strength at the same time.
span. For many cases, a general solution is not neces-
At support sary. Simplifying shortcuts can be used to shorten
DW = 4.0 ft the design process. Consider the case where shear
At 0.25ℓ = 0.25(25) = 6.25 ft is known not to be a problem.

3--4
Table 3.2.1 Shears and Moments for Example 3.2.1
Non-distributed Distributable Effective Final
Loads Loads Width
x Vux Mux Vux Mux DWx Vu(k/ft) Mu(ft-k/ft)
0 1.96 0 34.34 0 4.0 10.55 0
h/2 1.91 0.65 33.45 11.28 4.45 9.43 3.18
1 1.81 1.88 31.66 33.0 5.36 7.72 8.04
2 1.65 3.61 28.98 63.32 6.72 5.96 13.03
3 1.49 5.18 26.31 90.98 8.08 4.75 16.44
4 1.33 6.59 23.63 115.94 9.44 3.83 18.87
5 1.18 7.85 20.95 138.23 10.80 3.12 20.65
6 1.02 8.95 15.87 156.64 12.16 2.32 21.83
7 0.86 9.89 13.19 171.17 12.5 1.92 23.58
10 0.39 11.78 0 195.78 12.5 0.39 27.44
11 0.24 12.09 0 195.78 12.5 0.24 27.75
12.5 0 12.27 0 195.78 12.5 0 27.93

Example 3.2.2 Example 3.2.3

D = 250 plf D = 250 plf


L = 200 plf
25’-0 "

25’-0 "
D = 10 psf D = 10 psf
L = 40 psf L = 40 psf

Slab wt. = 53.5 psf Slab wt. = 53.5 psf


Effective width Effective width

Given the system shown, determine the design Given the system shown select a generic slab
load. from Figure 1.7.1 to support the loads shown.
Solution: Solution:
Make preliminary selection based on flexure:
Shear is judged to be not critical
From Figure 3.2.2 the effective width resisting 250 + 200
Superimposed w = 10 + 40 +
the line load is 0.50ℓ = 0.50(25) = 12.5 ft 0.5025
= 86 psf
Determine the design superimposed load:
Select 4 - 7/16″, 270 ksi low relaxation strands
w = 40 + 10 + 250/12.5 from Figure 1.7.1
First shear check
= 70 psf
effective width at support = 4′-0″ = DW
Using the generic slab load table in Figure 1.7.1 wu = 1.4(10 + 53.5) + 1.7(40)
select an 8″ slab with 4 - 7/16″ diameter strands. + (1.4 x 250 + 1.7 x 200)/DW
If it is not known whether shear is critical, sim- = 157 + 690/DW
ple iterative checks may be made.
Using DW = 4.0

3--5
Example 3.2.4

10’ 10’

9’-6"

25’-0"
6’-0"
9’-6"
Typ. wall load Effective
width Typ. point load
D = 300 plf
D = 1800#
L = 400 plf
L = 2880#
Uniform loads: slab wt = 53.5 psf
D = 10 psf
L = 40 psf

wu = 157 + 690/4.0 = 330 psf Therefore, shear check is complete and slab is ad-
equate.
Check shear based on this load and find
@ h/2 Vu = 4.02 k/ft and φVcw = 6.04 k OK To summarize the steps taken to check shear in
Example 3.2.3, distributable loads were divided
@ 3.0 ft Vu = 3.13 k/ft and φVci = 3.05 k NG by the effective width at the support to make a
conservative shear check. If shear along the span
Second Shear Check is found to be satisfactory, no further steps are re-
Inclined shear did not check at 3.0 ft so deter- quired and the shear check is complete. If shear in
mine effective width at 3.0 ft, recalculate distrib- the span at some point is found to be inadequate,
uted load and recheck shear. the effective width at that point is used to calcu-
lated a new load which will then be conservative
At ℓ/4, DW = 0.5ℓ = 0.5(25) = 12.5 ft for points further into the span. Shear is re-
At support, DW = 4.0 ft checked. This iterative approach is used until all
points further into the span check for shear. If
Interpolate at 3 ft, DW = 3 (12.5 -- 4) + 4 shear works for a given situation, generally no
25∕4 more than three cycles will be required.
= 8.08 ft A combination of loads will be used to further
wu = 157 + 690/DW demonstrate this method in the following exam-
ple.
= 157 + 690/8.08
= 242 psf
Example 3.2.4
Given the center bay of an apartment building
Again check shear at 3.0 ft and beyond and find as shown, design for the applied loads using the
φVci > Vu at all points. generic slab shown in Figure 1.7.1

3--6
Solution: x h/2 1.09′ 1.85′ 2.61′ 3.37′
Select preliminary slab based on flexure: Vu k/ft 7.11 6.93 6.45 6.12 5.79
Use DW = 0.50ℓ = 0.5(25) = 12.5 ft φVn k/ft 6.30 7.79 8.44 6.09 4.79
Because wall and point loads are spaced closer
than 12.5 ft, conservatively use spacing of loads as
Note that web shear at h/2 does not work. No
DW.
further modifications can be made to adjust the
At design strip:
shear calculation. Shear enhancement is required
in the form of stirrups, solid cores, higher concrete
468# 468# strength or using a deeper section.
Proceed to check inclined shear which was not
adequate at 2.61 ft.
70 70 Recalculate effective width at 2.61 ft as:
50 = 2.61 0.5ℓ − 4 + 4
0.25ℓ
= 2.61 (12.5 -- 4) + 4 = 7.54′
6.25
1758# 1758#
wu = 157 + 1100/7.54 = 303 psf
Pu = 7416/7.54 = 984 plf
1800 + 2880
Point loads = = 468 plf Obtain the following results:
10
300 + 400 x 2.61 3.37 4.14 4.90 5.66
Parallel walls = = 70 psf
10 Vu k/ft 3.97 3.74 3.51 3.28 3.05
Uniform load = 10 + 40 = 50 psf φVn k/ft 6.07 4.77 3.94 3.36 2.94
M = 11,511 ft-#/ft
equivalent uniform load = 8 x 11511/252 Inclined shear is now adequate to a distance of
= 147 psf 5.66 ft into the span. Recalculate the effective
width at 5.66 ft.
Select 4-1/2″, 270 ksi, low relaxation strands
capacity = 148 psf at 25 ft. 5.66 0.5ℓ − 4 + 4
Check shear 0.25ℓ
For design strip = 11.7 ft
including slab wt.
wu = 1.4(10 + 53.5)) + 1.7(40) Note that loads are located only 10 ft apart
+ (1.4 x 300 + 1.7 x 400)/DW which means that design strips would start to
overlap. For this case, the maximum effective
= 157 + 1100/DW
width might be used as the distance between
Pu = (1.4 x 1800 + 1.7 x 2880)/DW loads, or 10 feet, rather than 0.5 ℓ.
= 7416/DW wu = 157 + 1100/10 = 267 psf

Start at support where effective width = 4.0 ft Pu = 7416/10 = 742 plf


wu = 157 + 1100/4 = 432 psf With these loads, it is found that Vu < φVn for
Pu = 7416/4 = 1854 plf the balance of the span. Therefore, the slab se-
lected is adequate except for the shear enhance-
Obtain the following results: ment required for web shear as previously noted.

3--7
3.3 Effect of Openings Fig. 3.3.1 Effects of openings
Openings may be provided in hollow core sys-
tems by saw cutting after a deck is installed and
grouted, by shoring and saw cutting, by forming
or sawing the openings in the plant or by installing > 3/8 0.25 0.25
short slabs with steel headers. Some typical head-
er configurations are shown in Section 5.7. In lay-
ing out openings for a project, the least structural
effect will be obtained by orienting the longest di- > 3/8
mension of an opening parallel to a span, or by
coring small holes to cut the fewest prestressing (a)
strands, or when several openings must be pro-
vided, aligning the openings parallel to the span to
again cut the least number of prestressing strands.
For slab design, openings cause load con-
centrations which may be distributed over the slab < 3/8 0.25
system as discussed in Section 3.2. As with non-
uniform loads, openings cause torsion in the slabs.
Therefore, the method of determining shear ade- 0.25 0.25
quacy must also consider the effects of torsion on
the shear stresses. In flexure, the primary consid-
< 3/8 0.25
erations are the length of the opening parallel to
the span and the length of strand embedment
1’-0 " 1’-0 "
available from the end of an opening to the point
(b)
of maximum moment.
Figure 3.3.1 shows some general opening loca-
tions with suggested interpretations of the effec-
tive resisting slab width described in Section 3.2.
Local slab producers may have information which
would allow different design approaches for their 0.5
particular slab.
Figure 3.3.1(a) depicts a relatively small open-
ing located at midspan. In flexure, the load from
the short slabs can be resisted by slabs within 0.25
0.25 ℓ on each side of the opening. As a guideline,
if an end of the opening shown is not closer to the 1’-0 " 1’-0 "
support than 3/8 ℓ, there will be no special consid- (c)

erations for shear design with only uniform loads.


When non-uniform loads are superimposed near
slabs. The resulting torsion on the adjacent slabs
the opening, the effective resisting section shown
requires that a reduced effective width at the sup-
in Figure 3.2.2 would then be used for those non-
port be used if torsional shear stresses are not di-
uniform loads.
rectly calculated.
Figure 3.3.1(b) shows a similar condition
Figure 3.3.1(c) depicts the extreme where an
where an opening is located with an end closer to
opening is located right at the end of a span.
the support than 3/8 ℓ. In this case, shear is con- Again, the reduced shear width adjacent to the
sidered as though the opening created a free edge. opening is required to reflect torsional shear
That is, load from the short slabs or opening will stresses. An end opening extending less than the
be transmitted as an edge load to the adjacent
lesser of 0.125 ℓ or 4 ft (1.2m) into the span may be

3--8
neglected when considering flexure. However,
some capacity reduction might be required for the

6’
D = 10 psf
slab with the opening when strand embedment L = 40 psf

25’-0"
length is less than full required development.

19’
When non-uniform loads are superimposed in the
area of an end opening, these loads should be con-
sidered as being at a free edge for shear calcula- Slab wt = 53.5 psf
3’
tions.

Example 3.3.1 Solution:

The ends of the opening are closer than 3/8 ℓ to


11’-6 " 2’ 11’-6 "

D = 10 psf the support on both ends. Therefore, consider the


opening as though it were a free edge.
25’-0 "
L = 40 psf

2’
load on strip with opening
Slab wt = 53.5 psf
w = 3(10 + 40 + 53.5)
= 311 plf
Given the slab system shown, select a generic for flexure and preliminary slab selection use ef-
slab from Figure 1.7.1 to carry the loads given fective width = 0.25 ℓ to each side
considering the opening. 311∕2
w = 10 + 40 +
0.2525
Solution:
= 75 psf
Check proximity of opening to support
3/8 ℓ = 0.375(25) = 9.38′ Try 4 - 7/16″ dia., 270 ksi, low relaxation strands
11.5′ > 9.38′ no special shear Check Shear
considerations effective width at support = 1′-0″ each side
Distribute load from strip with opening: wu = 1.4(10 + 53.5) + 1.7(40) +
superimposed w = 10 + 40 = 50 psf 3[1.4(10 + 53.5) + 1.740)]∕2
load on strip with opening =
DW
2(10 + 40 + 53.5) = 207 plf
= 157 + 235/DW
distributing 1/2 of strip load each side
where DW = effective width on each side
207∕2 wu = 157 + 235/1 = 392 psf
w = 50 +
0.25ℓ
Using this load, obtain:
= 50 + 104
0.2525 x h/2 1.1 1.85 2.61 3.37 4.14
= 67 psf Vu k/ft 4.77 4.47 4.17 3.87 3.58 3.28
φVn k/ft 6.08 7.29 6.62 4.80 3.80 3.15
Select, from Figure 1.7.1, 4 - 3/8″ dia., 270 ksi,
Shear is adequate to 4.14 ft into span.
low relaxation strands
Modify effective width at 4.14 ft
Example 3.3.2 DW = 4.14 (0.25ℓ − 1) + 1
0.25ℓ
Given the floor system shown, select a generic
slab from Figure 1.7.1 to carry the loads given. = 4.14 (6.25 -- 1) + 1
6.25

3--9
= 4.48 ft duced. A detailed discussion of this is presented
in Section 6.3.3.
wu = 157 + 235/DW
= 157 + 235/4.48 3.5 Cantilevers
Cantilever design in hollow core slabs differs
= 209 psf from design with conventional precast members
because of the production procedures used for
Find shear is adequate at 4.14 ft and all points fur-
hollow core slabs. Guidelines noted here are con-
ther into span. Use 4 - 7/16″ dia., 270 ksi, low re-
servative and may be exceeded depending on the
laxation strands.
specific product used.
Because long line beds are used for the produc-
3.4 Continuity tion of hollow core slabs, top prestressing strands
Hollow core slabs are normally designed as may be economical only when full bed capacity is
part of a simple span system. However, continuity utilized. Even then, substantial amounts of pre-
over supports can be achieved by placing rein- stressing strand may be used inefficiently because
forcing steel in the grouted keyways, in a compos- of debonding requirements. The economics of us-
ite structural topping, or by concreting bars into ing top strand must, therefore, be determined by
cores. Within limits, the result will be better con- the local producer.
trol of superimposed load deflections and a lower When top strands are used, the length of the
requirement for positive moment capacity. cantilever is usually not sufficient to fully develop
With reinforcing steel in either a composite a strand. A reduced value for fps is required and
topping or in cores, elastic moments with allow- the design procedures given in Section 2.6 should
ance for negative moment redistribution deter- be used. In dry cast systems, the bond of top
mine the amount of reinforcing required. Because strands may be less than desired so a further re-
of the relative efficiencies of positive prestressing duction in fps is required. This reduction may be
steel and negative mild reinforcing, it is difficult substantial and each producer should be consulted
to economically justify a continuous system de- on top strand bond performance.
sign. When top strands are not economical,
When reinforcing is required at supports for non-prestressed reinforcement may be placed in
reasons such as structural integrity ties or dia- the cores or directly in the unit in the case of a wet
phragm connections, the reinforcing ratios are cast product. This is generally done while the slab
generally quite low, and therefore, develop little concrete is still plastic so bond of the fill concrete
moment capacity. While this reinforcing may be with the slab may be achieved. The reinforcement
considered in calculating service load deflections, is selected based on conventional design with due
it is recommended that full simple span positive consideration given to bar development length.
moment capacity be provided for strength design With either top strands or reinforcing bars, it
unless moment-curvature relationships existing at may be necessary to debond portions of the bot-
the supports at ultimate loads are known. tom prestressing strand in the cantilever zone to
One situation that seems reasonable for consid- help minimize the top tension under service loads.
ering a reduction in the positive moment require- Not all producers have the ability to debond bot-
ments is where the slabs are required to have a fire tom strands which could potentially limit cantile-
rating developed using the rational design proce- ver length or load capacity.
dure. In this case, a limit analysis approach would It is desirable to limit service level tensions in
be reasonable. cantilevers so that uncracked section properties
The negative moment reinforcing, which is un- may be used to more accurately predict deflec-
affected by fire loads, can develop full yield mo- tions. The tensile stress limit may vary for differ-
ment potential and effectively provide a plastic ent systems used. For example, the practice with
hinge at the support. As a result, the positive mo- some dry cast systems is to limit tensile stresses to
ment at midspan may be correspondingly re- 100 psi (0.7 MPa). In other dry cast systems and in

3--10
wet cast systems, the limit may be raised to 6 f′ c. = --0.491 ksi (tension)
The tension limit will basically be a function of a Net tension with fully bonded bottom strands:
producer’s past experience.
ft = --0.176 + 0.463 -- 0.491
As a rule of thumb, cantilever lengths falling in
the range of 6 to 12 times the slab thickness will be = --0.204 ksi
workable depending on the superimposed load
and individual producer’s capabilities. Allow 6 5000 = 0.424 ksi OK
Note that some of the bottom strands could
Example 3.5.1 Cantilever Design have been debonded for the length of the cantile-
Using the generic hollow core slab section de- ver if top tensile stresses had exceeded a desirable
fined in Section 1.7, design for the following level.
conditions shown in Figure 3.5.1.
Stresses in backspan:
Fig. 3.5.1
200 plf D.L.
Because the backspan is long in this example,
stresses will not be critical in the backspan. When
40 psf L.L. the backspan is short relative to the cantilever
15 psf D.L.
length, stresses may require a check in the back-
26’ 7’ span to determine the length of bonding of the top
4.06 ft-k/ft strands.
D.L. + L.L.
2.87’ Ultimate Strength
7.25 ft-k/ft
5.98 ft-k/ft At the cantilever, strain compatibility will gen-
Full (D.L. + L.L.) u erally show that the bottom strands may be ig-
2.82’
nored in determining the nominal moment capac-
11.02 ft-k/ft
5.98 ft-k/ft ity. When the bottom prestress is very heavy or
D.L.u on backspan the bottom strands are high in the slab, a strain
4.79’ (D.L. + L.L.) on
5.39 ft-k/ft
u compatibility analysis should be performed con-
cantilever
sidering both strand layers.
Solution: For this example, assume the bottom strands
may be ignored.
From the load table in Figure 1.7.1, select 4 -
3/ ″
8 dia., 270 ksi strands as the primary reinforce-
ment. Try 2 - 3/8″ dia., 270 ksi, low relaxation

fps = 270 1 − 0.28
0.8
 2(0.085)(270)
(36)(7)(5)

strands as cantilever reinforcement. Assume 15%
losses and 70% initial stress. = 265 ksi

Check stresses at cantilever: 2(0.085)(265)


a = = 0.294 in
(0.85)(5)(36)
Bottom strands:
154
1 − 2.89 × 4.11 φMn
12

= 0.9 (2)(0.085)(265) 7 − 0.294
2

ftop = 0.7(0.85)(4)(23)
1224.5
= 23.15 ft-k/slab
= --0.176 ksi (tension)
Mu = 3(5.98) = 17.94 ft-k/slab
Top strands:
ftop = 0.7(0.85)(2)(23) 154
1 − 3.11 × 4.11
1224.5

Mcr = 1224.5 0.463 − 0.176 +
4.11
7.5 5000 1
1000 12

= + 0.463 ksi = 20.29 ft-k/slab
ÔM n
Applied moment: = 23.15 = 1.14 < 1.2 NG
4.063(12)(4.11) M cr 20.29
ftop = -- Add 1 - #4 bar top per slab.
1224.5

3--11
Design summary

2- 38" strands bonded 13’-5" at cantilever end


Debond 1- #4 x 12’-5" at cantilever end

4-38" strands bonded full length

Check length of top strand to be bonded: 3.6 Horizontal Joints


lavailable = 7(12) = 84 in Figure 3.6.1 depicts three conditions typically
used in a multistory wall bearing building where
ℓd = (fps -- 2/3fse)db hollow core slabs are used in a platform detail.
Several expressions 27-31 have been proposed to
= (265 -- 2(0.7)(0.85)(270)/3)(0.375) describe the transfer of axial load through this hor-
= 59.2 in < 84 in izontal joint.
With hollow core slabs used for floors, the most
Therefore, the strand is fully effective in the canti-
efficient detail is to build the slab ends into the
lever. The moment capacity would have to be re-
wall. Depending on the butt joint size, the
calculated by the procedures of Section 2.6 if the
strength of the joint for transfer of vertical loads
development length were found to be greater than
can be enhanced with the addition of grout in the
the length available.
butt joint, Fig. 3.6.1(b), and in both the joint and
Bond of the top strands in the backspan must be
cores, Fig. 3.6.1(c). Grout fill in the cores in-
long enough to develop the fps required in the can-
tilever design. The top strands should also be creases the net slab width and provides confine-
bonded for a distance of one transfer length (50 di- ment for a grout column.
ameters) past the inflection point under the worst The strength of the joint for vertical load trans-
load condition. For this example a bonded length fer can be predicted using Eq. 3.6.1 for an un-
of 77 in. would be required. grouted joint, Fig. 3.6.1(a). For a grouted joint,
Fig. 3.6.1(b) or (c), the greater of Eq. 3.6.1 and Eq.
Alternate Design 3.6.2 can be used. Both grouted and ungrouted
Provide mild reinforcement in lieu of top pre- joints can have the slab cores either filled or not
stressing strands filled. Both equations include a capacity reduc-
Try 2 - #5 Gr 60 bars at d = 7″ tion term for load eccentric from the centerline of
2(0.31)(60) the joint. With single story walls braced at the top
a = = 0.243″ and bottom, this eccentricity will be negligible.
(0.85)(5)(36)
φPn = φ0.85Aef′cRe (Eq. 3.6.1)
φMn
12

= 0.9 (2)(0.31)(60) 7 − 0.243
2
 φPn = φtg ℓfuCRe/k (Eq. 3.6.2)
where
= 19.19 ft-k/slab
Pn = nominal strength of the joint
= 6.4 ft-k/ft > 5.98 OK Ae = effective bearing area of slab in joint = 2wbw
Top stress = --0.176 -- 0.491 w = bearing strip width
= --0.667 ksi with fully bonded bw = net web width of slab when cores are not
bottom strands filled
= unit width as solid slab when cores are filled
Note that a cracked section must be considered f′c = design compressive strength of slab con-
in calculating cantilever deflections because the crete or grout whichever is less
top stress exceeds a tension of 6 f′ c. tg = grout column thickness

3--12
Fig. 3.6.1 Common platform details

w w w tg w

(a) (b)

w tg w

(c)

ℓ = width of slab being considered φ = 0.7


fu = design compressive strength of wall or grout Where bearing strips with a modulus of elastic-
whichever is less when walls are reinforced ity other than 50,000 psi (345 MPa) are used, the
against splitting and slab cores are filled amount of force in the grout column will be al-
tered. A theoretical approach presented in Refer-
= 80% of design compressive strength of wall ence 30 considers pad stiffness, grout column
or design compressive strength of grout, strength as compared to grout strength, and con-
whichever is less when walls are not rein- finement of the grout column. A comparison of
forced against splitting or slab cores are not this theoretical procedure with the Johal proce-
filled dure indicates that conservative capacity will be
C = 1.0 when cores are not filled predicted by substituting the actual pad modulus
of elasticity for 50,000 when calculating k.
= 1.4 2500∕f′ c(grout) ≥ 1.0 when cores are The bearing strips need to also be checked
filled against manufacturer’s recommended stress lim-
k = 0.65 + (f′c(grout) -- 2500)/50,000 its. Figure 3.6.2 summarizes the forces in the
Re = reduction factor for eccentricity of load joint and the recommended effective bearing
strip width.
= 1 -- 2e/h
Another set of forces acting on the horizontal
e = eccentricity of applied load measured from joint develop from the negative moments induced
joint centerline in the floor slabs due to the clamping effect of a
h = wall thickness bearing wall on the slab ends. Two consequences

3--13
Fig. 3.6.2. Force distribution in horizontal joint Solution:
Loads
Roof: wu = 28 (1.4(53.5+15)+1.7(30))
= 4.ll klf
Pu Floors: wu = 28 (1.4(53.5+10)+1.7(40))
= 4.39 klf
V1 V2 Walls: wu = 1.4(800)
= 1.12 klf/story
Accumulate loads above floor noted
Floor wu Σwu
18 4.11 + 1.12 5.23
17 4.39 + 1.12 10.74
1-k Pu + V1 1-k Pu + V2
2 kPu 2 16 5.51 16.25
2/3w 15 5.51 21.76
2/3w
14 5.51 27.27
13 5.51 32.78
result. The splitting strength of the bearing wall is 12 5.51 38.29
reduced when the normal force restraining slab 11 5.51 43.80
end rotation is considered. Secondly, the joint or
slab may crack to relieve the frictional restraint. 10 5.51 49.31
This condition is undesirable from either the 9 5.51 54.82
standpoint of joint or slab integrity. Reinforcing 8 5.51 60.33
normal to the slab butt joint is most efficient for
controlling this condition. To date, there are no 7 5.51 65.84
published studies to evaluate effects of this rota- 6 5.51 71.35
tional restraint. No adverse effects have been 5 5.51 76.86
cited when nominal diaphragm or structural integ-
rity reinforcement has been provided across the 4 5.51 82.37
joint. 3 5.51 87.88
2 5.51 93.39
Example 3.6.1
Using the generic hollow core slab section de- a) Evaluate capacity of ungrouted joint (Fig.
fined in Section 1.7, determine the grouting re- 3.6.1(a))
quirements for an interior butt joint as depicted in bw = 10.5″ for generic slab = 3.5 in/ft of
Figure 3.6.1(a) given the following criteria: width
Slab span: 28 feet f′c (slab) = 5000 psi
18 story building with:
3 in bearing strips
8″ concrete bearing walls
f′c wall = 5000 psi φPn = φ0.85 Ae f′c Re (Eq. 3.6.1)
Loads: Roof -- DL = 15 psf LL = 30 psf
Floors -- DL = 10 psf LL = 40 psf

φPn = 0.7(0.85)(2)(3)(3.5)(5) 1 −
2(0)
8

Walls -- DL = 800 plf/story = 62.48 k/ft
LL Reduction: None for example Adequate for Floors 8 through roof

3--14
b) Evaluate strength of grouted joint using Use 1/2 in butt joint with cores filled below 8th
3000 psi grout for floor.
1) 2 in butt joint with no filled cores (Fig.
3.6.1(b)) It should be noted that this example may over-
state the height of building that can be supported
φPn = φ 0.85Aef′cRe (Eq. 3.6.1)
on an ungrouted joint. Concentrated loads due to

= 0.7(0.85)(2)(3)(3.5)(5) 1 −
2(0)
8
 corridor lintels, wall openings, or exterior span-
drels must also be considered in most buildings re-
= 62.48 k/ft sulting in an increase in load to be transferred
or through the horizontal joint.

φPn = φtg ℓfuCRe/k (Eq. 3.6.2)


fu = 3000 psi
C = 1.0
k = 0.65 + (3000 -- 2500)/5000
= 0.66
φPn = 0.7(2)(12)(3)(1.0)
x 1− 2(0)
8

∕0.66

= 76.36 k/ft > 62.48


Therefore φPn = 76.36 k/ft
2) 1/2 in butt joint with cores filled (Fig.
3.6.1(c))
φPn = φ 0.85Aef′cRe (Eq. 3.6.1)


= 0.7(0.85)(2)(3)(12)(3) 1 −
2(0)
8

= 128.5 k/ft
or
φPn = φtg ℓfuCRe/k (Eq. 3.6.2)
fu = 3000 psi
C = 1.4 2500∕3000 = 1.28
k = 0.65 + (3000 -- 2500)/50,000 = 0.66
φPn = 0.7(0.5)(12)(3)(1.28)
x 1−  2(0)
8

∕0.66

= 24.4 k/ft < 128.5


Therefore φPn = 128.5 k/ft

3--15
CHAPTER 4

DIAPHRAGM ACTION WITH HOLLOW CORE SLABS

4.1 General Information satisfy Section 7.13 in precast concrete structures.


When hollow core slabs are used as floor or For large panel bearing wall structures, minimum
roof decks to support vertical loads, the natural forces are specified to provide ties throughout the
extension is to use the slabs as a diaphragm to re- structure. For other types of precast structures,
sist and transmit lateral loads. Lateral loads will only general detailing philosophies are specified.
be applied to building structures in the form of lat- In either case, the fundamental requirement is to
eral earth pressures, wind loads or seismic loads. provide a complete load path from any point in a
The function of a diaphragm is to receive these structure to the foundation. Clearly, a diaphragm
loads from the building elements to which they is a significant element in this load path. A tie sys-
have been applied and transmit the loads to the lat- tem that satisfies the strength and force transfer
eral-resisting elements which carry the lateral demands on a diaphragm will generally satisfy the
loads to the foundation. The design issues in a detailing requirements for structural integrity.
hollow core diaphragm are the design of connec-
tions to get loads into the diaphragm, the strength 4.2 Design Loads
and ductility of the slab system to transmit these Lateral loads imposed on hollow core dia-
loads to the lateral-resisting elements and the de- phragms can include lateral earth pressures, wind
sign of the connections required to unload the lat- loads or seismic loads. Lateral earth pressures
eral forces from the diaphragm to the lateral-res- will be established by the characteristics of the
isting elements. soil being retained. Wind and seismic loads will
Clear communication is required between the be dictated by the applicable building code for the
building designer and the hollow core slab suppli- structure. Soil and wind loads are forces actually
er when the hollow core system is to be used as a applied to the structure. Seismic forces are gener-
diaphragm. Some elements of the diaphragm de- ated from within the structure as inertial forces
sign may be delegated to the hollow core slab sup- due to lateral displacement from ground motions.
plier. However, only the building designer is in While soil and wind loads can be safely treated as
the position to know all the parameters involved in static loads, seismic loads must be considered as
generating the applied lateral loads. Because of dynamic loads. In all cases, the same elements
many design issues, only the building designer will comprise a complete diaphragm, but the duc-
can determine the location and relative stiffnesses tility demands on a seismic resistant system are
of the lateral-resisting elements. These parame- significantly more important.
ters dictate the distribution of forces in the dia- The balance of the discussion in this chapter
phragm. If any design responsibility will be dele- will be concerned with lateral loads from wind
gated to the hollow core supplier, the location and and seismic. This is not intended to slight the im-
magnitude of the lateral loads applied to the dia- portance of considering unbalanced soil pressures
phragm and the location and magnitude of forces which can commonly be a significant consider-
to be transmitted to lateral-resisting elements ation in many projects using hollow core slabs.
must be specified. Where hollow core slabs must The basic principles of hollow core diaphragms
connect to other building materials, or where de- which will be discussed are equally applicable to
mands on connections go beyond simple strength lateral soil pressures.
demands, the connection details should be shown There are many documents which cover design
in the contract documents. for wind and seismic loads. The references used
An additional consideration in detailing dia- for this chapter are the 1994 UBC code32 and the
phragms is the need for structural integrity. ACI 1996 BOCA code33. For wind load, both codes
Section 16.5 provides minimum requirements to are similar in that a basic wind speed is selected

4--1
based on the building location, an exposure cate- wpx = portion of W at level under consideration
gory is selected based on the surrounding terrain, The magnitude of Fpx need not exceed
an importance factor is selected based on the oc- 0.75ZIwpx but shall not be less than 0.35 ZIwpx.
cupancy of the building, modifying factors are de- Many other requirements are included in the UBC
termined for the geometry of the building and the code which are not restated in this summary.
design positive and negative wind pressures are The BOCA code prescribes a seismic design
calculated. procedure. A very important note is that the
For seismic loads, the two codes take different BOCA provisions result in forces that are already
approaches. The UBC code allows an equivalent factored and are intended to be used with ultimate
static load approach for many building types. For strength design methods with no additional load
others, where certain heights or irregularities are factors. The base shear is calculated as:
present, a dynamic lateral force procedure is re- V = CsW (Eq. 4.2.3.)
quired. The static force procedure allows design
for a base shear of: where
V = ZIC W (Eq. 4.2.1) Cs = coefficient related to peak velocity-related
Rw acceleration, soil profile, structural system
where type and building fundamental period
Z = seismic zone factor W = total dead load plus other applicable loads
I = importance factor The base shear is distributed over the height of
C = factor dependent on site and structure fun- the building in proportion to the distribution of the
damental period building mass with consideration of the building
period. A minimum eccentricity of 5% of the per-
Rw = coefficient dependent on structural system pendicular building dimension is also required by
type BOCA when distributing forces to the lateral-re-
W = total dead load plus other applicable loads sisting elements. For Seismic Performance Cate-
This base shear is then distributed over the gories B and greater, each floor or roof diaphragm
height of the structure in proportion to the dis- shall be designed for a minimum load equal to
tribution of weights over the height. Additionally, 50% of the effective peak velocity-related accel-
a minimum eccentricity of 5% of the building di- eration times the weight attributable to the level
mension perpendicular to the direction being con- under consideration. The peak velocity-related
sidered shall be included when determining the acceleration is determined by the project location.
distribution of forces to the lateral-resisting ele- Again, there are many provisions in the BOCA
ments when the diaphragm is not flexible. Specif- code which are not covered in this summary.
ic to diaphragms, for Zones 2, 3, and 4, the UBC In light of the performance of some diaphragms
requires that a floor or roof diaphragm resist a in recent earthquakes, the seismic demand on dia-
force equal to: phragms is an area of new focus. Preliminary in-
n dications are that diaphragms should remain elas-
Ft + Σ Fi tic during a seismic event to ensure that post-elas-
i=x
Fpx = n w px (Eq. 4.2.2) tic behavior can be achieved in the
Σ wi lateral-resisting elements. By designing a dia-
i=x
phragm to remain elastic, several things are ac-
where complished. Diaphragm flexibility, discussed in
Fpx = force applied to diaphragm at level under Section 4.3 will be less significant. The ductility
consideration requirements for connection details will be of less
Ft = additional portion of base shear applied at concern. The horizontal distribution of forces to
top level lateral-resisting elements can be maintained.
The building code provisions summarized
Fi = portion of base shear applied at level i above are based on achieving post-elastic perfor-
wi = portion of W at level i mance. To keep a diaphragm compatible with

4--2
Fig. 4.3.1 Diaphragm bending moments
w w

M-
Moment Moment

M+ M+
M+ M+
Flexible diaphram on Rigid diaphram on
Rigid supports flexible supports
(a) (b)

post-elastic performance in the lateral-resisting to be considered as a flexible diaphragm. Analy-


system system, an analysis can be done to evaluate sis considering flexible diaphragms is much more
the total potential post-elastic capacity of the lat- complex than for rigid diaphragms and should be
eral-resisting elements. Providing a diaphragm considered in light of the project complexity and
with strength beyond this capacity will achieve seismicity for the project location. For most low
compatibility, but will involve significant analy- and mid-rise structures in low seismic risk areas,
sis. Alternatively, the diaphragm design forces an assumption of a rigid diaphragm will be rea-
prescribed by the building codes can be increased sonable.
by a factor of 2R/5 to keep the diaphragm elastic The difference in behavior of flexible and rigid
and minimize required analysis. Whether build- diaphragms is illustrated in Figure 4.3.1. In (a),
ing code provisions are based on service or fac- the flexible diaphragm with rigid supports be-
tored load levels, use of 2R/5 loads will result in haves as a continuous beam. Shears and moments
factored loads for design. in the diaphragm are a function of the plan geome-
try. In (b), the deflections of the flexible supports
4.3 Distribution of Lateral Forces must be the same because of the rigid diaphragm.
Once the lateral forces to be applied to the dia- The diaphragm shears and moments will be a
phragm have been determined, the next problem function of the relative stiffnesses of the supports.
is to determine the distribution of those lateral The differences between (a) and (b) can be consid-
forces to the lateral-resisting elements which will erable. Actual behavior will fall between the two
carry the forces to the foundation. This problem is cases tending toward one or the other as a function
usually structurally indeterminate which means of the diaphragm stiffness.
that deformation compatibilities must be consid- In seismic areas, the topic of diaphragm flexi-
ered for establishing equilibrium. The stiffnesses bility has become a more significant issue. UBC
to be considered are those of the diaphragm and requires consideration of the diaphragm flexibil-
the lateral-resisting elements. Concrete dia- ity for the horizontal distribution of forces. A
phragms are normally considered to be rigid when flexible diaphragm is defined by the UBC as one
compared to the lateral-resisting elements. De- having a maximum lateral deformation more than
pending on the type and magnitude of lateral twice the average story drift for the level under
forces applied, a hollow core diaphragm may need consideration. It may be inferred from UBC Sec-

4--3
tion 1631.1 that this consideration would only ap- Fig. 4.4.1 Tie forces in bearing wall buildings
ply in seismic zones 2, 3, and 4. The BOCA code
simply states that the horizontal distribution of
forces consider the relative stiffnesses of the later-
1
al-resisting system and the diaphragm. This pro-
vision would apply to Seismic Performance Cate- b T2
gories B and greater. By code then, diaphragm 2

flexibility need not be considered when designing T1


3

for wind or for seismic loads in Zones 0 and 1 un- T3


der the UBC or Seismic Performance Category A T1
under BOCA. T3
When diaphragm flexibility must be consid- T2
ered, a cracked moment of inertia calculation is
suggested in Reference 34 and a Virendeel truss T2
model in suggested in Reference 35. Since the
analysis of a structure with a flexible diaphragm is
dependent on so many factors beyond the dia-
phragm itself, such analysis is beyond the scope of For seismic loading, it is preferable to use con-
this manual. ventional reinforcing steel for these types of ties to
limit the elongations and deformations. When
structural integrity requirements control in non-
4.4 Structural Integrity seismic areas, untensioned prestressing strands
As noted in the introduction to this chapter, the may be used to satisfy the strength requirements.
ACI code requires consideration of structural in-
tegrity for all precast concrete structures. While
4.5 Elements of a Diaphragm
proper detailing for lateral loads will satisfy the
Figure 4.5.1 illustrates the various elements
complete load path philosophy of structural integ-
which comprise a complete diaphragm. The fol-
rity, there are some minimum provisions in ACI
lowing definitions will be used to describe the var-
Section 16.5 which must be met. With specific re-
ious elements:
gard to diaphragms, provisions to be aware of in-
Boundary Element:Edge member around the pe-
clude:
rimeter of a diaphragm or
1. For buildings other than large panel bearing the perimeter of an opening
wall buildings, the connection to the dia- in a diaphragm which ties
phragm of members being laterally braced by the diaphragm together. The
the diaphragm shall have a minimum nominal boundary element may func-
tensile strength of 300 lb per lin ft (4.4KN/m). tion as a chord or a drag
strut.
2. For large panel bearing wall structures, a sum- Collector: Elements which transfer
mary of the tie forces is given in Figure 4.4.1 shear from the diaphragm to
and are required to have the following mini- a lateral-resisting element.
mum nominal strengths: Chord: Tension or compression ele-
ment creating a flange for
T1 = nominal strength of 1500 lb per lin ft the diaphragm to develop
(21.9 KN/m) of floor or roof span flexural integrity in the dia-
T2 = nominal strength of 16,000 lb (71 KN) phragm.
Drag Strut: Element used to “drag” lat-
T3 = nominal strength of 1500 lb per lin ft eral loads into the lateral-re-
(21.9 KN/m) of wall sisting elements and to dis-
These minimum strengths shall not control if tribute shears over a greater
the actual forces in the diaphragm are greater. length of the diaphragm

4--4
web. (Also called dia- ing element as an axial tension or compression.
phragm strut.) Drag struts are not required for structural integrity
Longitudinal joint: Joint oriented parallel to the as long as the diaphragm is connected directly to
slab span. the lateral-resisting elements. Drag struts simply
Transverse joint: Joint oriented perpendicular spread out shears that might otherwise be highly
to the slab span. localized. Under the UBC code, it is implied that
To satisfy structural integrity, all diaphragms drag struts are required elements in Zones 2, 3,
should have boundary elements of some type. and 4. The BOCA code is silent on the use of drag
The boundary elements are essential to ensure that struts, but it can be implied that they are required
a diaphragm will have the strength to transfer lat- for Seismic Performance Categories B and great-
eral loads to the lateral-resisting system. As a er.
chord, tension reinforcement is placed in the When a bonded structural topping is used with
boundary element to allow the diaphragm to act as a hollow core slab diaphragm, these elements can
a deep horizontal beam or tied arch. This rein- be provided directly by reinforcement in the top-
forcement can also provide shear friction steel for ping. When no topping is provided, these ele-
shear transfer along the longitudinal joints. ments are developed as grouted or concrete ele-
Collectors are required in all diaphragms to ments external to the hollow core slabs. As a sim-
transfer forces from the diaphragm to the lateral- ple example, Figure 4.5.2 depicts two common
resisting elements. Such connectors are also re- boundary conditions. In (a), the boundary rein-
quired for structural integrity to provide a com- forcement is placed in a masonry bond beam and
plete load path for lateral forces to the foundation. the collector reinforcement is placed in the key-
Collectors may also function to get forces into a ways between slabs. In (b), the boundary rein-
diaphragm. forcement is placed in a grouted or concrete filled
Drag struts act to engage a longer length of dia- space at the end of the slabs. The collector rein-
phragm web for transferring diaphragm shears forcement is again placed in the keyways between
into the lateral-resisting elements. A drag strut is slabs. The primary difference between the details
parallel to the applied load, receives load from the is that the boundary reinforcement in (a) is eccen-
diaphragm and transfers load to the lateral-resist- tric from the diaphragm web while it is concentric

Fig. 4.5.1 Diaphragm elements

Lateral - Resisting
Element
Boundary Element
Drag
(chord)
Strut

Drag Strut

Lateral
Resisting
Element

Transverse
Joint

Collector

Load
Lateral - Resisting Boundary Element Longitudinal
Element (chord) Joint

4--5
Fig. 4.5.2 Boundary elements

(a) (b)

in (b). The concentric boundary element will ex- Fig. 4.6.1 Shear friction steel in butt joint
hibit better performance in a seismic situation and
should be used in Zones 3 and 4 under the UBC or
Seismic Performance Categories C, D and E un-
der the BOCA code.

4.6 Diaphragm Strength


The diaphragm must have the strength to trans-
fer imposed lateral loads from the point of ap-
plication to the point of resistance. The dia-
phragm spans between lateral-resisting elements
as a deep beam or tied arch. Shears and tensions
will develop and must be resisted in the dia-
phragm to have a complete system.

4.6.1 Longitudinal Joints When the grout strength is exceeded or ductile


The grouted keyways between slabs do have behavior is required, shear friction principles may
capacity to transfer longitudinal shear from one be used to design reinforcement to be placed per-
slab to the next. Using a shear stress of 80 psi pendicular to the longitudinal joints.36 This rein-
(0.55 MPa), the useable ultimate strength for lon- forcement may be placed in the transverse joints at
gitudinal shear is: the slab ends rather than being distributed along
the length of the joints. Placed as shown in Figure
φVn = φ(0.08)hn ℓ (Eq. 4.6.1)
4.6.1, the area of steel is calculated as:
where V
Avf = u (Eq. 4.6.2)
ℓ = length of joint under consideration (in) Ôf yμ
hn = net height of grout key (in) where
φ = 0.85 Vu = factored applied shear

4--6
Fig. 4.6.2 Alternate longitudinal shear Fig. 4.6.3 Collector detail
connections

Bar Spacing
by Design
Intermittent slab
cut-outs

Reinforcement across Welded connection


grout keyway
(a) (b)
Boundary
µ = 1.0 for shear parallel to longitudinal joints Reinforcement
= 1.4 for shear parallel to transverse joints
where concrete can flow into cores
φ = 0.85
While the detail shown in Figure 4.6.1 is the
most economical means of providing a mechani-
cal connection across the longitudinal joints, al- Fig. 4.6.4 Potential effects of rigid lap
ternate connections are available which may be connection
desirable in certain circumstances. Figure
Vertically rigid
4.6.2(a) shows reinforcing steel placed across the connection
longitudinal joint and grouted into the cores. This
detail might be considered when the amount of re-
inforcement required in the transverse joints is
great enough to cause congestion. Figure 4.6.2(b) Potential joint
shows weld anchors in the slabs and a loose plate cracking and
grinding
welded across the longitudinal joint. Use of this
detail should be carefully coordinated with the
hollow core slab supplier to ensure that proper an-
chorage of the weld plates in the slabs can be ac-
complished. deflection to occur without distress at the connec-
Where the diaphragm must unload shear into a tion. Figure 4.6.4 shows potential damage at the
lateral-resisting element, boundary element or in- first interior longitudinal joint when a vertically
terior drag strut, a condition similar to the longitu- rigid connection is used. The potential for distress
dinal joint exists. For longitudinal shear, again is dependent on the slab span and the real applied
shear friction can be used to design reinforcement loads. Short, lightly loaded spans may experience
as the collector to cross potential crack planes and no problems.
transfer the shear. Figure 4.6.3 depicts an exam- The effect of different vertical stiffnesses may
ple of such a collector detail. While drag struts be accounted for by:
and boundary elements may have a vertical stiff-
ness similar to the slab deck, the lateral-resisting 1. Determining that distress will not affect the
elements will usually have a significantly higher strength or performance of the system,
vertical stiffness. The collectors connecting di-
rectly to the lateral-resisting elements will tend to 2. Locating vertically rigid connections near the
be rigid vertically. While strength and toughness slab supports where vertical movement is
at such collectors is certainly important, it is minimized, or
equally important to consider every day perfor-
mance of the structure. At rigid vertical elements, 3. Providing allowance for vertical movement in
it may be desirable to allow slab camber growth or the connection detail.

4--7
4.6.2 Transverse Joints Mu
Vh = (Eq. 4.6.5)
The transverse joints serve many functions. As jh
described in Section 4.6.1, reinforcement in the In the first case, a unit shear is calculated and shear
transverse joints may provide the shear friction re- friction reinforcement is distributed according to
inforcement for shear in the longitudinal joints. the shear diagram. In the second case, the total
The transverse joint may also have to act as a drag shear is calculated as the tension or compression
strut with axial tension or compression to carry di- of the internal couple. In this case, shear friction
aphragm loads to the lateral-resisting elements. A reinforcement is uniformly distributed over the
transverse joint may also be the chord member length between zero moment and maximum mo-
where flexural tension is resisted. Finally, an inte- ment. It is suggested that the shear friction rein-
rior transverse joint disrupts the web of the hori- forcement be distributed according to the shear
zontal beam where horizontal shear would have to diagram in UBC zones 3 and 4 and BOCA Seis-
be transferred to maintain the composite depth of mic Performance Categories C, D and E to mini-
the diaphragm. mize the force redistribution required with a uni-
The design of shear friction reinforcement for form spacing.
longitudinal joint shear is covered in Section Because of the orientation of the joints and the
4.6.1. Drag strut reinforcement is calculated sim- loading directions considered, the reinforcement
ply as: in the transverse joint discussed above is not all
T additive. Typically, the chord tension and longitu-
As = u (Eq. 4.6.3) dinal joint shear will be concurrent. The drag strut
Ôf y
tension will typically occur with loads applied in
Chord tension is resisted by reinforcement to pro- the perpendicular direction.
vide flexural strength to the diaphragm. It is sug-
gested that the effective depth of the reinforce- 4.7 Collectors
ment from the compression side of the diaphragm Collectors function as connections to transfer
be limited to 0.8 times the depth of the diaphragm. forces into diaphragms and from diaphragms to
Hence, the chord reinforcement is calculated as: boundary elements, drag struts or lateral-resisting
Mu elements. The preceding discussion has indicated
As = (Eq. 4.6.4)
Ô0.8hf y that reinforcing bars may be used as collectors us-
ing shear friction design procedures. As shear
where friction reinforcement, the steel is used in tension
h = depth of the diaphragm to resist a shear force. In detailing the steel, a
crack plane is defined and the bars must be an-
φ = 0.9 chored for full strength on each side of the crack
Because diaphragms tend to act as tied arches plane. For anchorage at a transverse boundary
rather than beams, tension in the chord reinforce- element, the bars may be grouted into the keyways
ment does not go to zero at the ends of the dia- or into slab cores where the top of the core is cut
phragm. The chord reinforcement must be an- away. Concrete is then used to fill the cores for the
chored at the ends of the diaphragm where a stan- length of the bar embedment. Based on a review
dard hook at the corner will suffice. For of the literature, it is not clear when anchorage of
horizontal shear in the web of the diaphragm, a collector bars in keyways is sufficient and when
shear parallel to the transverse joint is developed. the collector bars should be placed in slab cores.
Shear friction reinforcement perpendicular to the There is a concern that as the boundary element
transverse joint and embedded in the slab key- and keyway crack, anchorage for a collector bar in
ways can be used to reinforce for this shear. The a keyway may be lost. Deformations and revers-
applied shear can be calculated as: ible loading in a seismic event would suggest that
anchoring collector bars in slab cores would be
V Q
Vh = u preferable in more intense seismic areas. In keep-
I ing with code philosophy, it is suggested that bars
or be anchored in slab cores in UBC zones 3 and 4

4--8
Fig. 4.9.1 Example Problem

8 @ 25’-0"= 200’-0"

30’
20’

80’
30’

30’
30’

and BOCA Seismic Performance Categories C design forces. It is suggested that a topping be
and greater. considered in high seismic zones in buildings with
In non-seismic and low seismic design situa- plan irregularities or large diaphragm span to
tions, the collectors need not be reinforcing bars. depth ratios.
Particularly for direct connections to lateral-re- Untopped hollow core diaphragms are sug-
sisting elements, welded and bolted connections gested when the diaphragm force system is
will suffice for the collector connections when straightforward and the in-plane diaphragm
they are compatible with the slab system used. deflections are acceptable. An example at the end
of this chapter illustrates a procedure for deter-
4.8 Topped vs. Untopped Diaphragms mining diaphragm deflections. In high seismic
When a composite structural topping is pro- areas, local codes may limit the use of untopped,
vided, it should have a minimum thickness of 2 to hollow core diaphragms.
2 1/2 in (50-65 mm). The topping can then be de-
signed as the diaphragm without consideration of
the hollow core slabs. When the topping provides 4.9 Design Example
the strength and stiffness for the diaphragm but Given the building plan shown in Figure 4.9.1,
the connections are made in the hollow core slabs, design and detail the untopped hollow core dia-
shear stresses will be present at the interface of the phragm assuming:
topping and the hollow core slabs. These stresses
will generally be well distributed throughout the a. wind design per UBC
interface, but may be more highly localized near b. Zone 2A seismic per UBC.
the connections. As discussed in Chapter 2, hori-
zontal shear stresses should be kept below a nomi- Building data
nal strength of 80 psi (0.55 MPa). 6 stories
The primary benefits of a composite structural 14 ft floor to floor
topping are to increase stiffness and to allow easi- 8 in hollow core floors wt = 53.5 psf
er continuous ties in plans with irregular shapes or partitions & mechanical wt = 20 psf
large openings. However, in seismic areas, the precast framing system wt = 32 psf
additional topping weight increases the seismic exterior wall system (avg.) wt = 35 psf

4--9
Solutions: Mu = 1.3(1739) = 2261 ft-k
a. Seismic Zone 0; Basic wind speed 80 mph • Chord Forces:
Use Exposure C
Using the perimeter beams as chords:
Design wind pressure = P = CeCqqsIw
Mu
where Tu =
Ô0.8h
Ce = 1.53
= 2261 = 39.3k
Cq = +0.8, -- 0.5 0.9(0.8)(80)
qs = 16.4
Connect beams through columns for this force
Iw = 1.0 plus forces due to volume change and gravity
P = 1.53(0.8)(16.4)(1.0) = 20.1 loads. (Fig. 4.9.2 Det. C)
= 1.53(0.5)(16.4)(1.0) = 12.5
The chord must continue through the center
32.6 psf
wall.
Wind to diaphragm = w = 14(0.0326) = 0.46k/ft
T
As = u (φ was included in Tu)
• Consider load applied parallel to the slabs fy

Total V = 200(0.46) = 92k = 39.3


60
Assuming a rigid diaphragm, the shear dis- = 0.66 in2
tribution to the walls based on their flexural stiff-
ness is: Use 2 - #6 (Fig. 4.9.2 Det. F)
• Connect diaphragm web to chords
30 ft walls: V = 40k
Mu
20 ft wall: V = 12k Vuh =
jh
The diaphragm equilibrium is: j ≅ 0.8
0.46 k/ft Vuh = 2261
0.8(80)
= 35.3k

40 k 12 k 40 k
Distribute over length from zero moment to
maximum moment
40
6 Vuh = 35.3 = 0.41k/ft
87
V
87ft
6
Additionally, this connection must resist the
40 negative wind pressure from the exterior wall
system.
M
wu = 1.3(0.0125)(14)

1739 ft-k
= 0.23k/ft
Use 300 lb/ft for structural integrity

The factored design forces are then: (Fig. 4.9.2 Det. A)


The same forces must be resisted at the trans-
Vu30 = 1.3(40) = 52k
verse joints. Use shear friction for the shear
Vu20 = 1.3(6) = 7.8k with bars placed in the keyways perpendicular

4--10
to the transverse joint. With keyways at 3 ft on Using shear friction reinforcement
center:
Avf = 1.02 in2 (from above) or
3(0.3) 3(0.41)
As = + 6
0.9(60) 0.85(60)(1.4) As = = 0.11 in2 does not control
0.9(60)
= 0.034 in2/keyway
Use 4 - #5 located near slab ends
Use #3 at every 2nd keyway
(Fig. 4.9.2 Det. D)
(Fig. 4.9.2 Det. B)
Alternatively, mechanical connections of slab
• Longitudinal shear to wall could be used to transfer the same
forces.
The maximum longitudinal joint shear is at the
first slab joint from the 30 ft shear wall. Since con- • Shear at center 20 ft wall:
nections will be made directly from the center bay With the rigid diaphragm assumption:
to the shear wall, only the center bay joint length
should be considered. Vu = 7.8k on each side of wall
Vu = 52k Avf = 7.8
0.85(60)(1.0)
φVn = φ(0.08)hn ℓ
= 0.15 in2
= 0.85(0.08)(8 -- 2)(20 x 12)
Use 2 - #4 located near slab ends or use
= 97.9k mechanical connections
With concerns for shrinkage cracking in joints, (Fig. 4.9.2 Det. E)
transverse shear friction reinforcement can be • Consider load applied perpendicular to the
provided in the transverse joints at each end of the slabs
center bay.
Total V = 80(0.46) = 36.8k
Vu
Avf =
Ôf yμ Distribution to walls is:

52 V = 36.8/2
=
0.85(60)(1.0)
= 18.4k
= 1.02 in2 / 2 transverse joints
The diaphragm equilibrium is:
= 0.51 in2 per joint
0.46 k/ft
Use 1 - #7 in transverse joint
(Fig. 4.9.2 Det. B)
• Shear connection to 30 ft wall 18.4 k 18.4 k

Vu = 52k 18.4

Additionally, negative wind pressure must be V


resisted across this joint, but would not be con- 18.4
current with shear. Structural integrity ties will
control for this case. M
Tu = (0.3)(20)
= 6k for bay 368 ft-k

4--11
The factored design forces are then: #3 at every 2nd keyway will be adequate
Vu = 1.3(18.4) = 23.9k (Fig. 4.9.2 Det. B)

Mu = 1.3(368) = 478 ft-k b. Seismic Zone 2A


The building weight attributable to each floor
• Chord force: is:
Mu wi = 80(200)(0.0535 + 0.020 + 0.032)
Tu =
Ô0.8h +14(0.035)(200 + 80)(2)

= 478 = 1962k
0.9(0.8)(200)
then
= 3.3k W = 6(1962)
As = 3.3 = 0.06 in2 = 11772k
60
• Base shear
The #3 bars across the transverse joints will be
adequate for the chord force. (Fig. 4.9.2 Det. B) V = ZIC W
Rw
Longitudinal shear
Z = 0.15
Mu
Vuh = I = 1.0
jh
C = 2.75
≅ 478
0.8(200) Rw = 8
= 3.0k will not control 0.15(1.0)(2.75)
V = (11772)
8
• Shear connection to walls
= 607k
Using shear friction reinforcement • Vertical Distribution
Vu = 23.9k/30 ft wall Ft = 0.07TV
= 0.8k/ft controls over parallel wind with a site coefficient of 1.2 and C = 2.75
With bars in keyways at 3 ft on center T = 0.4 sec < 0.7 sec
3(0.8) Ft = 0
Avf =
0.85(60)(1.4) (V − F t)w xh x
Fx = n
= 0.034 in2 per keyway Σ w ih i
i=1
Use #3 in every 2nd keyway
wi hi wxhx Fx
(Fig. 4.9.2 Det. F)
1962 84 164808 173
• Shear in transverse joint 1962 70 137340 145
Vu = 1.3(18.4 -- 0.46 × 30) 1962 56 109872 116
= 6k 1962 42 82404 87
1962 28 54936 58
Avf = 6
0.85(60)(1.0) 1962 14 27468 29
= 0.12 in2 576828

4--12
Fig. 4.9.2 Wind design summary

8 @ 25’-0"= 200’-0"

C F
A

30’
E
30’

20’

80’
D

30’
B

30’

#4 near each
end of wall
0.3k/ft
0.41k/ft

39.3k
Chord Force

Intermittent slab
cut-outs

A C
E

#3 @ every
2nd keyway
#7 cont. 2-#5 near each
#3 every
end of bay
2nd keyway

2-#6
Intermittent slab
cut-outs

B D F

4--13
• Diaphragm load The diaphragm equilibrium is:
n
Ft + Σ Fi 2.77 k/ft
i=x
Fpx = n w px
Σ wi
i=x

wpx Ft + ΣFi Σwi Fpx 241 k 72 k 241 k

1962 173 1962 173 241


36
1962 318 3924 159
V
1962 434 5886 145 87ft
36
241
1962 521 7848 130
1962 579 9810 116 M
1962 607 11772 102
10483 ft-k
Minimum diaphragm load
Fpx = 0.35ZIwpx • Chord forces:
= 0.35(0.15)(1.0)(1962) Using reinforcement in a perimeter boundary
= 103k element
Mu
Maximum diaphragm load As =
Ô0.8hf y
Fpx = 0.75ZIwpx 10483
=
0.9(0.8)(80)(60)
= 0.75(0.15)(1.0)(1962)
= 3.0 in2
= 221k
Use 4 - #8
To keep diaphragm in the elastic range, multi-
(Fig. 4.9.3 Det. A)
ply the diaphragm loads by 2R/5. At the roof
Fpxu = 173(2)(8)/5 • Connect diaphragm web to chord

= 554k Mu
Vuh =
jd
The factored roof diaphragm load by code pro-
visions is ≅ 10483
0.8(80)
Fpxu = (1.1)(1.3)(173)
= 164k
= 248k
Distribute over length from zero moment to
Design roof diaphragm for a factored load of maximum moment
554k to keep in elastic range. Vuh = 164 = 1.89k/ft
87
• For shear parallel to slabs
Additionally, this connection must resist the
Using a rigid diaphragm, the shear distribution outward force from the exterior wall system.
to the walls is: Conservatively, this force will be:
30 ft walls: V = 241k T = 0.75ZIww
20 ft wall: V = 72k = 0.75(0.15)(1.0)(14 × 0.035)

4--14
= 0.055k/ft Avf = 269
0.85(60)(1.0)
Tu = 0.055(2)(8)/5
= 5.27 in2 / 4 joints
= 0.176k/ft
= 1.32 in2 per joint
Tu V
As = + u In boundary elements, add chord requirement
Ôf y Ôf yμ
At first joint
= 0.176 + 1.89
0.9(60) 0.85(60)(1.4) Mu = 241(3) -- 32(2.77)/2

= 0.033 in2/ft = 711 ft-k

As = 1.32 + 711
Use #3 at 3 ft on center grouted into cores 0.9(0.8)(80)(60)
(Fig. 4.9.3 Det. A) = 1.53 in2
At the transverse joint, the same shear parallel 4 - #8 ok
to the transverse joint as at the chord must be
transferred. However, the tension should con- (Fig. 4.9.3 Det. A)
sider the inertial force from the weight of the
In transverse joints
exterior bay. Conservatively
As = 1.32 in2
T = 0.75ZIwp
Use 2 - #8
wp = 14(0.035) + 30(0.0535 + 0.020 + 0.032)
(Fig. 4.9.3 Det. B)
= 3.66k/ft
• Shear connection to 30 ft wall:
T = 0.75(0.15)(1.0)(3.66)
Transfer shear to wall and drag strut
= 0.41k/ft
Tu = 0.41(2)(8)/5 Vu = 253
80
= 1.31k/ft = 3.16k/ft

As = 1.89 + 1.31 Avf = 3.16


0.85(60)(1.4)) 0.9(60) 0.85(60)(1.0)
= 0.051 in2/ft = 0.062 in2/ft
Use #4 at 3 ft on center in keyways Use #4 hairpins at 3 ft on center
(Fig. 4.9.3 Det. B) (Fig. 4.9.3 Det. D)
• Longitudinal shear Drag strut reinforcement

The maximum longitudinal shear is at the first (80 − 30)


Tu = (3.16)
slab joint from the 30 ft wall. Provide shear 2
friction reinforcement in the two transverse = 79k
joints and the two boundary elements for shear
As = 79
resistance. Conservatively consider 5% mini- 0.9(60)
mum eccentricity being resisted only in end
walls. = 1.46 in2
Vu = 241 + (0.05 x 200)(554)/200 Use 2 - #8
= 269k (Fig. 4.9.3 Det. C)

4--15
• Shear connection at 20 ft wall nAs = 6.74(3.16)
Vu = 36k
= 21.3 in2
over building width
Vu = 36 = 0.45k/ft 57(x -- 4) + 4.3(x -- 8)2/2 = 21.3(956 -- x)
80
Avf = 0.45
0.85(60)(1.0) find x = 87.9 in
= 0.009 in2/ft
Use #4 dowels at 8 ft on center Icr = 57(87.9 -- 4)2 + 4.3(87.9 -- 8)3/3
+ 21.3(956 -- 87.9)2
(Fig. 4.9.3 Det. F)
Drag strut reinforcement = 17,184,000 in4
(80 − 20)
Tu = (0.45)(2)
2
= 829 ft4
= 27k

As = 27
0.9(60) As a rigid diaphragm, the factored load deflec-
tion between end shear walls is:
= 0.5 in2
(2.77)(200) 4 72(200) 3
Use 2 - #5 ∆ = 5 −
384 (4300)(829)(12) 48(4300)(829)(12)
(Fig. 4.9.3 Det. E)
• In-plane deflection of diaphragm = 1.07 in (ignoring shear deflections)
Idealize the diaphragm section as
As a flexible diaphragm with rigid supports the
deflection will be substantially smaller. The
4.3" nA s
8" diaphragm deflection plus the deflection of the
8" lateral-resisting system is used to evaluate the
gravity load support members for integrity
x
when deformed.
956"
• Consider load applied perpendicular to the
with 4000 psi concrete in chord slabs
Ec = 3835
with 5000 psi concrete in slab Total Vu = 554k
Ec = 4300
normalize on slab concrete Distribution to walls is
nchord = 0.89
ATchord = 0.89(64)
Vu = 554/2
= 57 in2
nsteel = 6.74 = 277k

4--16
The diaphragm equilibrium is: Drag strut reinforcement
(200 − 30)
Tu = (1.52)
6.93 k/ft 2
= 129.2k

As = 129.2 = 2.39 in2


277 k 277 k 0.9(60)
Chord reinforcement from load parallel to
277 slabs controls.
Vu • Shear in transverse joint
277
In center bay
Mu
wp = 20(200)(0.0535 + 0.020 + 0.032)
+ 20(14)(0.035)(2)
5544 ft-k
= 442k

• Chord force Conservatively use

Mu V = 0.75ZIw
Tu =
Ô0.8h = 0.75(0.15)(1.0)(442)
= 5544
0.9(0.8)(200) = 49.7k

= 38.5k Vu = 49.7(0.55)(2)(8)/5
= 87.5k per joint including
As = 38.5 = 0.64 in2
60 5% eccentricity
The #4 bars across the transverse joints at 3 ft Load parallel to slabs will control
on center will be adequate. (Fig. 4.9.3 Det. B)
See Figure 4.9.3 for summary
Longitudinal shear
Mu
Vuh =
jd

≅ 5544
0.80(200)
= 34.7k will not control
• Shear connection to walls
With 5% eccentricity
Vu = 1.1(277) = 304.7k
Transfer shear to wall and drag strut
Vu = 304.7/200 ft
= 1.52k/ft
Loading parallel to slabs controls

4--17
Fig. 4.9.3 Seismic design summary

8 @ 25’-0"= 200’-0"

G
A

30’
E

F
30’

20’

80’
D

30’
B

30’

#3 @ 3ft. o.c. 2-#8 cont. #3 @3ft o.c.


2-#5 cont. #4 @ 8ft. o.c.
grout in cores in cores
#4 @ 3ft. o.c.

4 - #8 4 - #8 cont.
cont. Intermittent slab
cut-outs

A C E G

#4 @ 3ft. o.c. #4 @8ft. o.c.


2 - #8 cont. #4 @ 3ft. o.c.
in keyways

2 - #8 cont.
Intermittent slab
2 - #5 cont.
cut-outs

B D F

4--18
CHAPTER 5

CONNECTIONS IN HOLLOW CORE SLABS

5.1 General 5.2 Details


Connections will be required in hollow core Common details are shown in Sections 5.3, 5.4,
slab systems for a wide variety of reasons. Chap- 5.5, and 5.6 to cover a number of conditions where
ter 4 described the connection requirements for a forces will probably exist that need to be trans-
hollow core diaphragm as an element for lateral mitted into or through a hollow core slab. The
stability. Most connection requirements will be conditions cover common detailing situations
for localized forces ranging from bracing a parti- when hollow core slabs are used and are intended
tion or beam to hanging a ceiling. to give the specifier an idea of the possibilities that
Connections are an expense to a project and, if exist. The commentary provided with each detail
used improperly, may have detrimental effects by is intended to give a better understanding of the
not accommodating volume change movements merits of each detail. The emphasis is that these
that occur in a precast structure. Connections may provide a guide which can be used as a basis for
develop forces as they restrain these movements. better discussions with local producers. The de-
In specifying connection requirements, the actual tails are only conceptual and would require de-
forces in the connection must be addressed. If no tailed information to be used on a project.
force can be shown to exist, the connection should Differences between wet cast and dry cast hol-
not be used. Again, cost is reduced and undesir- low core slabs will be evident in the embedded an-
able restraining forces will not be developed. chors that can be provided. Without forms to se-
When a connection is determined to be necessary, cure anchors to, dry cast systems may be limited
the force in the connection should be specified es- to shallow anchors that can be tied directly to
pecially when at an interface between a hollow strands or to inserts that can be placed after cast-
core slab and another material. The extent of de- ing. Wet cast systems can accommodate a wider
tailing to be left to the hollow core slab supplier variety of anchors placed directly in the form prior
should be those items that will be supplied with to casting. Therefore, anchor details in the hollow
the product. core slabs are not shown. Connection possibilities
need to be explored with the local producers.

5--1
5.3 Typical Details with Concrete Beams

Design Considerations:

• Can transfer internal diaphragm forces with headed


• Can be designed as structural integrity tie stud anchors
Plate with deformed With
bar grouted in returns
slab keyway Topping if
Fabrication Considerations:
required
• Advantageous to have no hardware in slab
• Beam embedments must line up with slab
joints
• Accommodates variations in slab length

Erection Considerations: Bearing strip

• Advantageous to have connection completed


by follow-up crew
• Difficult for welder to hold loose plate in P.C. or C.I.P.
position concrete
beam

Fig. 5.3.1

Design Considerations:

• Can transfer internal diaphragm forces Reinforcement


• Can be designed as structural integrity tie grouted in slab
keyway
Topping if
Grout required
Fabrication Considerations:

• May increase beam reinforcement for


shallower beam
• Layout must have opposing slab joints lined up

Bearing strip
Erection Considerations:

• Clean and simple


P.C. or C.I.P.
concrete
beam

Fig. 5.3.2

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--2
5.3 (Continued)

Design Considerations:

• With large factors of safety, friction may


transfer nominal forces
Topping if
• Additional structural integrity ties may be required
required

Fabrication Considerations:

• Clean and simple

Bearing strip
Erection Considerations:

• Clean and simple


P.C. or C.I.P.
concrete
beam

Fig. 5.3.3

Design Considerations:
Reinforcement draped
• Can transfer internal diaphragm forces over beam and grouted
• Can be designed as structural integrity tie in slab keyway
• Consider concrete cover on reinforcement Topping if
Grout
over beam required

Fabrication Considerations:

• Slab layout must have opposing joints lined up

Grout Bearing strip

Erection Considerations:

• Clean and simple P.C. or C.I.P.


concrete
beam

Fig. 5.3.4

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--3
5.3 (Continued)

Design Considerations:

• Can transfer internal diaphragm forces


• Will develop volume change restraint forces
that must be considered in design of Topping if
connections required

Fabrication Considerations:

• Slab manufacturing system must allow bottom


weld anchors
• Beam inserts must align with slab inserts
allowing fabrication tolerances Weld Plate
(alt. ends)

Bearing strip
Erection Considerations:
with
P.C. or C.I.P. headed
• Connections can be completed by follow-up concrete stud anchors
crew beam
• Access for welding may require ladders or
scaffold
• Spacer may be required to make weld

Fig. 5.3.5

Design Considerations:
Reinforcement
grouted in
• Can transfer internal diaphragm forces
slab keyway
• Can be designed as structural integrity tie
Reinforcement per
• Horizontal shear from beam cap must be design
Concrete
transferred Topping if
• Opposing slab joints must line up required

Fabrication Considerations:

• Clean and simple for slabs

Dam
Bearing strip
Erection Considerations: cores

• Beam may have to be shored until cap is


cured
• Horizontal shear reinforcement may present P.C. or C.I.P.
safety hazard for erector concrete
• Core dams must be placed beam

Fig. 5.3.6

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--4
5.3 (Continued)

Design Considerations:
Reinforcement
• Can transfer internal diaphragm forces grouted in
• Can be designed as structural integrity tie slab keyway
• Horizontal shear in composite beam must be
transferred Reinforcement per
• Opposing slab joints must line up design
Topping

Fabrication Considerations:

• Clean and simple for slabs

Erection Considerations: Dam


Bearing strip
cores
• Beam may have to be shored until topping is
cured
• Horizontal shear reinforcement may present
safety hazard for erector P.C. or C.I.P.
• Core dams must be placed concrete
beam

Fig. 5.3.7

Design Considerations: Plate as required


with headed
by design
stud anchors
• Can transfer diaphragm shear
or deformed bar
• Can provide lateral brace for beam
• Potential for negative moment in slabs
Topping if
required
Fabrication Considerations:

• Slab insert difficult to install. Because of


tolerance on sawcut ends, the insert should be
installed after slabs are cut to length
• Beam and slab inserts must align
with headed
stud anchors Bearing strip

Erection Considerations:

• If required for lateral beam stability, welding


may have to be completed as slabs are set
P.C. or C.I.P.
concrete
beam

Fig. 5.3.8

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--5
5.3 (Continued)

Design Considerations:
Plate with deformed bar
• Can transfer diaphragm shear
anchor grouted in
• Can provide lateral brace for beam
slab keyway
• Potential to develop negative moment in slabs
Topping if
required
Fabrication Considerations:

• Plates in beam must align with slab joints


allowing tolerance

Erection Considerations: Bearing


Plate with headed strip
• Connection can be completed with a follow-up stud anchors
crew
• Lateral bracing for beam will not be provided
until keyway grout cures P.C. or C.I.P.
concrete
beam

Fig. 5.3.9

Design Considerations:
Reinforcement grouted
in slab keyway
• Can transfer internal diaphragm forces
• Can be designed as structural integrity tie
Topping if
required

Fabrication Considerations:

• Clean and simple

Erection Considerations:
Bearing
• Clean and simple strip
• Keyway dimensions may limit the
reinforcement diameter
P.C. or C.I.P.
concrete
beam

Fig. 5.3.10

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--6
5.3 (Continued)

Design Considerations:
Reinforcement grouted
• Can transfer diaphragm shear in slab keyway
• Can be designed as structural integrity tie
Topping if
Longitudinal required
bar as req’d.
Fabrication Considerations:

• Clean and simple for both beam and slabs

Erection Considerations:
Bearing
• Reinforcement must be tied in place
strip
• Concrete must be cast around reinforcement
• Edge form is required for cast-in-place
concrete
• Dowels from beam may present safety hazard P.C. or C.I.P.
concrete
beam

Fig. 5.3.11

Design Considerations: Weld Plate (alt. ends)


• Can transfer internal diaphragm forces
• Will develop volume change restraint forces
that must be considered in design of Topping if
connection required

Fabrication Considerations:

• Slab manufacturing system must allow bottom


weld inserts
• Beam and slab inserts must align with
allowance for tolerance Bearing
strip

Erection Considerations:
with headed
• Connections can be completed by follow-up P.C. or C.I.P. stud anchor
crew concrete
• Access for welding may require ladders or beam
scaffold
• Spacer may be required to make weld
Fig. 5.3.12

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--7
5.3 (Continued)

Design Considerations:

• Can transfer diaphragm shear


• Torsional and lateral beam restraint can be Weld plate
provided
• Will develop volume change restraint forces Topping if
that must be considered in design of required
connection
Fabrication Considerations: Bearing
strip
• Slab manufacturing system must allow bottom
weld inserts
• Beam and slab weld anchors must align with
allowances for tolerance

Erection Considerations: with headed


P.C. or C.I.P.
concrete stud anchors
• Connections can be completed by follow-up beam
crew
• Access for welding may require ladders or
scaffold
• Spacer may be required to make weld
Fig. 5.3.13

Design Considerations:
Field bend
• This detail is not recommended because of into slab Topping
installation difficulties which may result in an keyway and if req’d.
unreliable connection grout

Fabrication Considerations:

• Great difficulty aligning bars with keyways

Bearing
Erection Considerations: strip
Longitudinal
• Potential difficulties in bending bars bar as req’d.
• Possible fracture of bent bars
• Second rebar bend may be required to align P.C. or C.I.P.
with slab joints concrete
• Cast-in-place concrete required around beam
reinforcement DO NOT USE
• Edge forming required
Fig. 5.3.14

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--8
5.4 Typical Details with Walls

Design Considerations:
Reinforcement
• Can transfer diaphragm shear grouted in Wall
• Can be designed as structural integrity tie slab keyway
• Can provide lateral brace for wall Grout
• Consider axial force path through slab ends
• Opposing slab joints must line up Topping if
required

Fabrication Considerations:

• Clean and simple for slabs


• Small tolerance for placement of bars in walls
• Tolerance on length of slabs to accommodate
bars in joint Bearing
Longitudinal
strip
bar as req’d

Erection Considerations:
Dowels as
P.C. or C.I.P.
• With longitudinal bar, have potential congestion required
concrete
• Slab erection must consider tight tolerance on wall
butt joint gap
• With precast walls, consider method of
installing vertical dowel
Fig. 5.4.1

Design Considerations:

• Can transfer diaphragm shear Reinforcement


grouted in Longitudinal
• Can be designed as structural integrity tie
slab keyway bar as req’d
• Can provide lateral brace for wall
• Opposing slab joints must line up
Topping if
required Grout
Fabrication Considerations:

• Clean and simple for slabs

Bearing
Erection Considerations: strip
• Clean and simple
• Wall is not braced until grout is placed and
P.C. or C.I.P.
cured Dowels as concrete
required wall

Fig. 5.4.2

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--9
5.4 (Continued)

Design Considerations:

• Can transfer diaphragm shear


• Can provide lateral brace for wall with proper Mortar bed
bar detailing to level
• Consideration should be given to forces block course
developed as slab ends rotate
Topping if
required
Fabrication Considerations:

• Clean and simple

Erection Considerations: Reinforcement


Bearing grouted in
• Simple for slab erection wall slab keyway
• The mason can set bars independent of the
slab joints Bearing
• Some block cutting may be required for bars Grouted strip
from keyways bearing
course

Fig. 5.4.3

Design Considerations:

• Can transfer diaphragm shear Mortar bed


• Can provide lateral brace for wall with proper to level
detailing block course
• Consideration should be given to forces Topping if
developed as slab ends rotate required

Fabrication Considerations:

• Clean and simple

Erection Considerations: Bearing Hooked bar


wall grouted in
• Simple for slab erection slab keyway
Bearing
• The mason can set bars independent of the
Solid strip
slab joints
• Grout at slab end may be difficult to place bearing Hooked bar
course in wall

Fig. 5.4.4

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--10
5.4 (Continued)

Bar to be field
Design Considerations: bent into slab
keyway or field
• This detail is not recommended because of drilled into wall
installation difficulties which may result in Topping
an unreliable connection if req’d

Fabrication Considerations:

Erection Considerations:
Bearing Bearing
• Mason will have great difficulty locating bars at wall strip
slab joints
• Potential difficulties to field bend bars including
fracture
• Second bend may be required to align bars
with joints
DO NOT USE

Fig. 5.4.5

Design Considerations:

• Wall will not be braced at this level

Topping
if req’d
Fabrication Considerations:

• Clean and simple

Clearance
Erection Considerations:
Non-bearing
wall
• Small tolerance in slab layout

Fig. 5.4.6

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--11
5.4 (Continued)

Design Considerations:

• Walls may not be laterally braced Clearance


• Consideration should be given to forces

for camber
developed from deflections or camber growth
• Drypack may be required under slab for axial

Allow
Topping
load transfer if req’d

Fabrication Considerations:

• Clean and simple

Wall
Erection Considerations:

• Allowance must be made for slab camber


• Wall will not be laterally braced at this level
• Small tolerance in slab layout

Fig. 5.4.7

Design Considerations:
Deformed bar
• Can transfer diaphragm shear or steel strap
• Can provide lateral brace for wall
• Consideration should be given to forces Grout
Topping
developed from deflection or camber growth if req’d
• Consider axial load path

Fabrication Considerations:

• If not done in field, slots and holes must be cut


for steel Wall Grout
• In stack casting system slots and holes might
not be practically cut in plant

Erection Considerations:

• Allowance must be made for slab camber


• If not done in plant, holes and slots must be
cut for steel
• Wall is not braced until steel is grouted Fig. 5.4.8

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--12
5.4 (Continued)

Design Considerations:

• Wall thrust from earth pressure can be resisted


• Can transfer diaphragm shear only with special

for camber
detailing of keyway and reinforcement

Allow
• For long spans consider effects of restraint of
vertical movement

Fabrication Considerations:

• Clean and simple

Erection Considerations:
P.C. or C.I.P.
• Edge joint must be grouted which may not concrete
be standard practice wall

Fig. 5.4.9

Design Considerations:

• Can transfer diaphragm shear


• Can provide lateral brace for wall
• Consideration should be given to forces Reinforcement
developed from deflections or camber growth grouted into
broken core

Topping
Fabrication Considerations: if req’d

• If not done in field, edge core must be cut Grout at


open bars
• In stack casting operation, holes might not be
practically cut in plant

Erection Considerations:
Wall
• If not done in plant, holes must be field cut into
edge core
• Mason may have to cut block to install
reinforcement

Fig. 5.4.10

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--13
5.4 (Continued)

Design Considerations:

• Can transfer diaphragm shear


• Can provide lateral brace for wall
• Connection capacity must be verified by test
Reinforcing Bar
Driven In Hole
Fabrication Considerations:
Field Drill
• Clean and simple

Bearing
Bond Strip
Erection Considerations: Beam

• Minimum edge distances must be maintained


• No interfacing tolerances

Fig. 5.4.11

Design Considerations:

• Can transfer diaphragm shear


• Can provide lateral brace for wall
• Consider effects of vertical restraint Reinforcing Bar
• Connection capacity must be verified by test Driven In Hole

Field Drill
Fabrication Considerations:

• Clean and simple Dry Pack


Bond
Beam
Erection Considerations:

• Minimum edge distances must be maintained


• No interfacing tolerances

Fig. 5.4.12

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--14
5.5 Typical Details with Steel Beams

Design Considerations:

• Top beam flange should be considered 1" Min. joint


unbraced

2" (Min.) topping


if required
Fabrication Considerations:

• Clean and simple for slabs


• Beam flange width must be sufficient for slab
bearing length

Erection Considerations:
5" Min. flange
• Unsymmetrical loading may cause beam 6" Recommended
flange
instability Steel beam
Note: Top flange is
unbraced

Fig. 5.5.1

Design Considerations:

• Can transfer internal diaphragm forces


• Provides lateral brace for steel beam 2" Joint

Grout
Fabrication Considerations: Reinforcement
grouted in
Topping
• Slab layout must align slab joints slab keyway
if req’d
• Stabilizer bars might be field or shop installed
depending on local regulations or agreements
• Beam flange width must be sufficient for
minimum slab bearing

Erection Considerations: Steel beam with


stabilizer bars
• Grouting of slabs must include the butt joint to brace top flange
• Steel erection may require that stabilizer bars
be field installed
• Steel beam will not be laterally braced until
grout cures
• Unsymmetrical loading may cause beam Fig. 5.5.2
instability
Many connection details shown perform similar functions. Consult the local PCI producer for information on relative economy and design
capabilities.

5--15
5.5 (Continued)

Design Considerations:

• Can transfer internal diaphragm forces


• Provides lateral brace for steel beam
• Will develop volume change restraint forces Grout
Weld plate
that must be considered in design of (weld at alternate
connection Topping ends of slabs)
if req’d

Fabrication Considerations:

• Slab manufacturing system must allow for


installation of bottom weld anchors

Erection Considerations: Steel beam

• Welding of slabs to beam should be done as


erection proceeds to laterally brace beams

Fig. 5.5.3

Design Considerations:

• Can transfer diaphragm shear 1" (Min.) past centerline


• Provides lateral brace for steel beam of beam
• Potential torsion on steel beam should be
considered Weld plate (weld at alternate ends)
• Will develop volume change restraint forces Topping
that must be considered in design of if req’d
connection

Fabrication Considerations:

• Slab manufacturing system must allow for


installation of bottom weld anchors

Steel beam
Erection Considerations:

• Welding of slabs to beam should be done as


erection proceeds to brace beam
• Spacer may be required to make weld
Fig. 5.5.4

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--16
5.5 (Continued)

Design Considerations:

• Can transfer diaphragm shear


• Provides lateral brace for steel beam
Deformed bar
grouted in
slab keyway
Fabrication Considerations:

• Clean and simple

Erection Considerations:
Steel beam
• Welding of bars must be coordinated with slab
erection for alignment
• Depending on forces to be transferred
concrete may have to be cast along edge
• Beam will not be braced until keyway grout
cures

Fig. 5.5.5

Design Considerations:
1" 1"
• Internal diaphragm forces can be Additional Clr. Clr.
transferred only through topping reinforcement
2" (Min.) topping
• Provides lateral brace for steel beam over steel
if required
• Consider potential torsion on beam during beam
slab erection

1/2" Clr.
Fabrication Considerations:

• Beam flange width must be sufficient for Notch slab


minimum slab bearing Steel Beam
(as required) 6" Min. flange
• Slab notching will require a hand operation in
field or, preferably, in plant 8" Recommended
flange
Note:
Difficult erection if
Erection Considerations: this detail occurs at
both ends of slab
• Slab erection will be very difficult with this
detail on both slab ends. Slabs must be slid
into beams possibly through access holes in
flanges
Fig. 5.5.6
• Beams will not be braced during slab erection

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--17
5.5 (Continued)

Design Considerations: Additional 1" 1"


reinforcement Clr. Clr.
• Internal diaphragm forces can be transferred over steel 2" (Min.) topping
only through topping beam if required
• Provides lateral brace for steel beam
• Consider potential torsion in beam during slab
erection

1/2" Clr.
Fabrication Considerations:
Optional
Continuous ’s
• Angle legs must be sufficient for minimum slab reinforcement
welded to steel
bearing grouted in
beam
• Beam depth must be sufficient for clearance slab keyway
Steel Beam
under top flange 3" Min. Leg
4" Recommended leg

Erection Considerations:
Note:
Difficult erection if
• Slab erection will be very difficult if this detail
this detail occurs at
occurs at both slab ends. Slabs will have to
both ends of slab
be slid into beams possibly through access
holes in flanges
• Beams will not be braced during slab erection
Fig. 5.5.7

Design Considerations:

• Torsion design must consider erection


tolerance
• Lintel must be securely anchored at span ends
• Connection to slab may be required to brace
lintel Topping
if req’d
Fabrication Considerations:
Wall
• Clean and simple

Erection Considerations:
Channel and
• Watch for stability of lintel prior to slab erection plate lintel

Fig. 5.5.8

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--18
5.5 (Continued)

Design Considerations:

• Butt joint must be grouted to brace vertical


angle legs
• Lintel must be securely anchored at span ends
Topping if
req’d

Fabrication Considerations:

• Clean and simple

Erection Considerations: Double angle (min. 4" leg)


or WF (min. 8" flange)
• Lintel must be securely anchored prior to lintel
setting slabs

Fig. 5.5.9

Design Considerations:

• Clearance must be allowed for slab camber


• Beam will not be braced until topping is cast
Topping

Fabrication Considerations:
for camber

• Camber must be monitored to stay within Additional


Allow

clearance reinforcement

Erection Considerations:

• Erection may be very difficult if slab support


beams are also raised

Fig. 5.5.10

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--19
5.6 Typical Cantilever Details

Design Considerations:

• Wall bracing or transmitting diaphragm shear Cores filled with


would only be accomplished by questionable insulation over
friction exterior wall
• Additional structural integrity ties may be
required

Fabrication Considerations:

• None other than top reinforcement required for Bearing


cantilever strip

Wall
Erection Considerations:

• Clean and simple

Fig. 5.6.1

Design Considerations:

• Can transfer diaphragm shear Insulation Dowel grouted in


• Provides lateral brace for wall slabs at keyway

Fabrication Considerations:

• If not field drilled, slots in keyways and


aligning holes in masonry are required Bearing
• If not field drilled, alignment will be difficult strip
Wall

Erection Considerations:

• If not preformed, holes must be drilled through


slabs into masonry
• Wall may not be braced until grout cures
• Grout placement may be difficult

Fig. 5.6.2

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--20
5.6 (Continued)

Design Considerations: Dowels field bent


and grouted in
• This detail is not recommended because of slab keyways
installation difficulties which may result in
an unreliable connection

Fabrication Considerations:
Bearing
strip

Wall
Erection Considerations:

•Mason will have great difficulty aligning


dowels with slab joints
• Most keyway configurations will require
notches for dowels
• Field bending of dowels into keyways will be
very difficult
DO NOT USE

Fig. 5.6.3

Design Considerations:
Verify max. dimension
• Wall will not be braced by slabs with slab supplier
• Depending on end support conditions wall may
have to support edge slab Keyway filled
• No thermal break provided between interior with grout
and exterior
Fabrication Considerations:

• Depending on bearing conditions the overhang


dimension may be limited by the producer’s
ability to install transverse reinforcement
Allow for camber

Bearing wall
Erection Considerations: beyond
Non-bearing
• None wall
Preferred end of
bearing wall

Fig. 5.6.4

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--21
5.6 (Continued)

Design Considerations:

• Wall will not be braced by slabs Verify max. dimension


• Depending on end support conditions wall may with slab supplier
have to support edge slab Steel strap (weld to
• No thermal break provided between interior top anchors or expansion
and exterior bolt to slabs)

Fabrication Considerations:

• When transverse reinforcement cannot be


installed, steel strap must serve as external
reinforcement

Allow for camber


• Anchorage of a steel strap to the slabs will Bearing wall
depend on the producer’s ability to install top beyond
weld anchors Non-bearing
wall

Erection Considerations: Preferred end of


bearing wall
• Depending on end support conditions
temporary shoring may be required until steel
strap is installed and keyways are grouted

Fig. 5.6.5

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--22
5.7 Miscellaneous Details

Bearing
Feather edge
Hollow core with latex, conceal
slab in wall, or
recess when
no topping

Header angles
"A"

SECTION "A-A"
"A"

PLAN

HEADER DETAIL

Fig. 5.7.1

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--23
5.7 (Continued)

Bearing
Hollow core
slab

"B" "B"

Header angles

SECTION "A-A"
"A"

"A"

Feather edge with latex,


conceal in wall, or
recess when
no topping
PLAN

SECTION "B-B"

HEADER DETAIL

Fig. 5.7.2

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--24
5.7 (Continued)

Hanger thru bolt;


Expansion bolt; Toggle bolt; for heavy loads
only with sufficient only for vertical
bottom thickness loads
Light straps;
for ceiling and
duct work

Fig. 5.7.3

Other connection details perform functions similar to those shown. Consult the local PCI producer for information on relative economy and
design capabilities.

5--25
CHAPTER 6

FIRE RESISTANCE OF ASSEMBLIES


MADE WITH HOLLOW CORE SLABS

6.1 Introduction building code requirements.


One of the attributes of hollow core slab
construction is excellent fire resistance. More 6.2 Heat Transmission Through Floors or
than 30 standard fire tests (ASTM E119) have Roofs
been conducted on hollow core floor assemblies. The standard fire test method, ASTM E119,
The January, 1994 issue of Underwriters Labora- limits the average temperature rise of the unex-
tories, Inc. “Fire Resistance Directory” includes posed surface, i.e., the surface of floor or roof not
more than 50 design numbers for hollow core exposed to fire, to 250 degrees F (120 degrees C)
slabs which qualify for ratings of 1, 2, 3, or 4 during a fire test. This criterion is often called the
hours. Constructions which conform to these de- heat transmission end point.
signs are assigned ratings by most U.S. building For solid concrete slabs, the temperature rise of
codes. the unexposed surfaces depends mainly on the
As an alternative to UL ratings, model codes slab thickness and aggregate type. Figure 6.2
now include prescriptive requirements which can shows the relationship between slab thickness and
be used to establish fire endurance ratings. For fire endurance as determined by the heat transmis-
each fire endurance rating, strand cover and sion end point criterion.
equivalent thickness provisions are given. Use of 6.2.1 Equivalent Thickness
such provisions eliminates the need for fire tests The information in Figure 6.2 is applicable to
or UL ratings. hollow core slabs by entering the graph with the
Most U.S. building codes will also assign rat- “equivalent thickness” of the unit instead of the
ings to hollow core assemblies which do not con- thickness. Equivalent thickness can be calculated
form with the UL designs if it can be shown by cal- by dividing the net area of the cross section of a
culations made in accordance with procedures hollow core unit by the width of the unit.
given in the PCI manual, “Design for Fire Resis-
tance of Precast, Prestressed Concrete” (PCI Fig. 6.2 Fire endurance (heat transmission) of
MNL 124-89)38 that they qualify for the required hollow core units
fire endurance. Readers can obtain more detailed 5
information from that manual on fire resistance of
hollow core slab assemblies as well as informa-
tion on fire resistance of concrete beams, walls, 4
cf)

and protection of connections.


Ag cf)
0p

ate
p

eg
(10

In Canada, The National Building Code of


15

gr
t (1
Fire Endurance, Hr

ht

Canada requires that fire resistance ratings be de-


eig

3
ate
igh
htw

on
e

termined either on the basis of results of tests con-


tw

te
rb
Lig

ga
igh
Ca

ducted in accordance with CAN/ULC-S101-M, e


gr
-L

g
nd

2 A
“Standard Methods of Fire Endurance Tests of s
Sa

e ou
Building Construction and Materials”, or on the lic
Si
basis of Appendix D, “Fire Performance Rat-
1
ings”. While the general principles set forth in this
Manual are fully valid in that they are based on
materials properties and structural engineering 0
procedures, users of the Manual are cautioned that 1-1/2 2 3 4 5 6 7
in Canada, fire resistance ratings should be deter- Equivalent Thickness, in.,
of Hollow Core Unit
mined strictly in accordance with applicable

6--1
In Figure 6.2, concrete aggregates are desig- for two hours or more. The addition of toppings,
nated as lightweight, sand-lightweight, carbon- undercoatings, fire resistive ceilings, roof insula-
ate, or siliceous. Lightweight aggregates include tion, or filling the cores with dry aggregates will
expanded clay, shale, slate, and slag which pro- increase the heat transmission fire endurance.
duce concretes having unit weights between about Figure 6.2.2.1 shows graphically the thickness of
95 and 105 pcf (1520 - 1680 kg/m3) without sand spray applied undercoating required for heat
replacement. Lightweight concretes in which transmission fire endurances of 2, 3 and 4 hours.
sand is used as part or all of the fine aggregate and Figure 6.2.2.2 shows the thickness of sand-light-
weigh less than about 120 pcf (1920 kg/m3) are weight concrete, insulating concrete and high
designated as sand-lightweight. For normal strength gypsum concrete overlays required for 2,
weight concrete, the type of coarse aggregate in- 3 and 4 hours. Figure 6.2.2.3 shows data for 2 and
fluences the fire endurance; the type of fine aggre- 3 hr. roofs with mineral board or glass fiber board
gate has only a minor effect. Carbonate aggre- insulation with 3-ply built-up roofing. Data
gates include limestone, dolomite, and limerock, shown in Figures 6.2.2.1, 6.2.2.2 and 6.2.2.3 ap-
i.e., those consisting mainly of calcium or magne- ply directly to hollow core slabs made with sili-
sium carbonate. Siliceous aggregates include ceous aggregates and are conservative for slabs
quartzite, granite, basalt, and most hard rocks oth- made with carbonate aggregates or with light-
er than limestone or dolomite. weight aggregates.

6.2.2 Toppings, Undercoatings, or Roof Example 6.2.1 Equivalent Thickness


Insulation Determine the thickness of topping required to
All 8 in (200 mm) deep hollow core units which provide a 3 hr. fire endurance (heat transmission)
are currently manufactured in North America for the generic hollow core slab shown in Figure
qualify for at least a one-hour fire endurance as 1.7.1. Both the slab and the topping are made with
determined by heat transmission and some qualify carbonate aggregate concrete.
Fig. 6.2.2.1 Hollow core units undercoated with spray applied materials
(Heat transmission fire endurance)

Hollow core slab made with


siliceous aggregate concrete

Sprayed mineral fiber or


vermiculite cementitous material

1.0

0.8
Thickness of SMF

4h
or VMC, in.

r
0.6
3h
r
0.4

0.2
2h
r

0
3.5 4.0 4.5 5.0 5.5
Equivalent Thickness, in.
of Hollow Core Unit

6--2
Fig. 6.2.2.2 Floors with overlays of sand-lightweight concrete (120 pcf maximum), insulating concrete
(35 pcf maximum), and high strength gypsum concrete

Overlay

Hollow Core slab made with


siliceous aggregate concrete

Sand-Lightweight Concrete Insulating Concrete


Overlay Overlay

2.5

4h
r
Overlay Thickness, in.

2.0

4h
r
1.5
3h
r 3h
r
1.0
2h 2h
r r
0.5

0
3.5 4.0 4.5 5.0 5.5 3.5 4.0 4.5 5.0 5.5
Equivalent Thickness, in., of Hollow Core Units

High Strength Gypsum Concrete


Overlay

y
Fire Endurance, Hr.

3 erla
. Ov
. C ay
.G verl
1 in .C . O
in. G
1/2
2

0
3.5 4.0 4.5 5.0 5.5
Equivalent Thickness, in., of
Hollow Core Units

6--3
Fig. 6.2.2.3 Roofs with insulation board and 3-ply built-up roofing
(Heat transmission fire endurance)

3-Ply built-up roofing

Mineral board or glass


fiber board insulation
Hollow core slab made with
siliceous aggregate concrete

0.75
Thickness, in., of Mineral Board
or Glass Fiber Board

0.50
3h
r
0.25 2h
r

0
3.5 4.0 4.5 5.0 5.5
Equivalent Thickness, in., of
Hollow Core Unit

Solution: the required thickness would be even less. Thus,


Equivalent thickness the roof qualifies for a fire endurance significantly
teq = Area/width longer than 2 hours.
= 154/36 6.2.3 Ceilings
= 4.28 in Gypsum wallboard used as ceilings increases
From Figure 6.2, the thickness of carbonate ag- the fire endurance of the assemblies. Very few fire
gregate concrete required for 3 hr. is 5.75 in. Thus, tests have been conducted utilizing concrete
the thickness of topping needed is: floors with gypsum wallboard ceilings, and no
5.75 -- 4.28 = 1.47 in such tests have been conducted utilizing hollow
core units. To be effective, gypsum wallboard
must remain in place throughout most of the fire
Example 6.2.2
endurance period. Because most hollow core
Determine if a hollow core slab roof will quali-
units by themselves have heat transmission fire
fy for a 2 hr. fire endurance (heat transmission) if
endurances of one hour to two hours and longer,
the slabs are made with carbonate aggregate con-
the wallboard must remain in place during fire ex-
crete, have an equivalent thickness of 4.28 in, and
posure for long periods of time. For a fire endur-
the roof insulation consists of a layer of 3/4 in thick
ance of 3 hours, a layer of 5/8 in (16 mm) Type X
mineral board. The roofing is a standard 3-ply
gypsum wallboard can be used. The wallboard
built-up roof.
should be installed as shown in Figure 6.2.3.
Solution:
From Figure 6.2.2.3 it can be seen that with an
equivalent thickness of 4.28 in, a layer of mineral 6.3 Structural Fire Endurance of Floor or Roof
board 0.16 in thick with 3-ply roofing qualifies for Assemblies
2 hours even if the slabs are made with siliceous During standard fire tests, specimens must sup-
aggregates. With carbonate aggregate concrete, port the anticipated superimposed loads through-

6--4
Fig. 6.2.3 Details of 3 hr. assembly consisting of hollow core slabs with a gypsum wall board
ceiling

4 3

5 Max. 4’

Restrained Unrestrained

3 1 1 6

7/8"

5/8" 3/4"
6 4
5 5
End Joint Side Joint
1. Precast concrete hollow core slabs - Minimum equivalent thickness = 2.75 in
2. Grout - (Not Shown) - Sand-cement grout along full length of joint.
3. Hanger Wire - No. 18 SWG galvanized steel wire. Hanger wire used to attached wallboard furring channels to precast concrete units.
Wire to be located at each intersection of furring channels and joints between hollow core slabs, but not to exceed 4 ft o.c.
4. Wallboard Furring Channels - No. 26 ga. galvanized steel, 7/8 in high, 2 3/4 in base width, 1 3/8 in face width and 12 ft long. Channels
to be installed perpendicular to hollow core slabs and spaced 24 in o.c., except at wallboard butt joints where they are spaced 6 1/2 in
o.c. Channels secured to concrete units with double strand of hanger wire looped through fasteners. At furring channel splices, chan-
nels to be overlapped 6 in and tied together with hanger wire at each end of splice.
5. Wallboard - 5/8 in thick, 4 ft wide, Type X, installed with long dimension perpendicular to furring channels. Over butt joints, a 3 in wide
piece of wallboard to be inserted with ends extending a minimum 6 in beyond board width.
6. Wallboard Fasteners - 1 in long, Type S, bugle head screws. Fasteners spaced 12 in on center along each furring channel except at
butt joints where fasteners spaced 8 in on center. At butt joints, fasteners located 3 1/4 in from board edge. Along side joints, fasten-
ers located 3/4 in from board edge.
7. Joint System - (Not Shown) - Paper tape embedded in cementitious compound over joints, and covered with two layers of cementi-
tious compound with edges feathered out. Wallboard fastener heads covered with two layers of cementitious compound.

out the fire endurance period. Failure to support the ultimate moment capacity is constant through-
the loads is called the structural end point. out the length:
The most important factor affecting the struc- φMn = φApsfps(dp -- a/2) (Eq. 6.3.1)
tural fire endurance of a floor or roof assembly is
See Chapter 2 for evaluating fps.
the method of support, i.e., whether the assembly
If the slab is uniformly loaded, the moment dia-
is simply supported and free to expand (“unre-
gram will be parabolic with a maximum value at
strained”) or if the assembly is continuous or ther-
midspan of:
mal expansion is restricted (“restrained”).
M = wℓ
2
6.3.1 Simply Supported Slabs (Eq. 6.3.2)
8
Figure 6.3.1.1 illustrates the behavior of a sim-
ply supported slab exposed to fire from beneath.
Because strands are parallel to the axis of the slab,

6--5
Fig. 6.3.1.1 Moment diagrams for simply sup- Where
ported beam or slab before and w = dead plus live load per unit of length,
during fire exposure
k/in
ℓ = span length, in
As the material strengths diminish with ele-
vated temperatures, the retained moment capacity
Fire becomes:
Mnθ = Apsfpsθ(dp -- aθ /2) (Eq. 6.3.3)
in which θ signifies the effects of high tempera-
@ 0 Hr
tures. Note that Aps and dp are not affected, but fps
is reduced. Similarly, a is reduced, but the con-
M = applied moment
crete strength at the top of the slab, f′c, is generally
not reduced significantly because of its lower
temperature.
Mn = moment capacity
@ 2 Hr

applied
M = moment

M n θ = reduced moment capacity

Fig. 6.3.1.2 Temperature-strength relationships for hot-rolled and cold-drawn steels

100
High strength
alloy steel bars
(tensile strength)
80

Hot-rolled steel
(yield strength)
Percent of Strength At 70 F

60
o

40
Cold-drawn
prestressing steel
250 or 270 ksi
(tensile strength)
20

0
70 200 400 600 800 1000 1200 1400
o
Temperature, F

6--6
Fig. 6.3.1.3 Temperatures within Fig. 6.3.1.4 Temperatures within
carbonate aggregate concrete siliceous aggregate concrete
slabs during fire tests slabs during fire tests

1600 1600
Siliceous Aggregate
Carbonate Aggregate Concrete
1500 1500
Concrete (Normal Weight) (Normal Weight)
1400 1400

1300 1300

.
n.

e
in

c
4i

rfa
4
1/

1/
e
fac

Su
.
1200

in
1200 r
in.

F
F

d
Su

se
1/
o
o

1/2 d

po
se
po

Ex
1100

Temperature,
1100
Temperature,

Ex

.
ro
om

in
Fr

.F

1
1000 n. n. 1000
1i

in
.
4i in

4
3/

3/
in. 1/
2
u=

=
900 1/2
900 1-

u
1-

.
in
800 n. 800

2
2i
700 700

.
in
n.
3i

3
600 600 .
n. in
4i 4
500 500
1/2 1 1-1/2 2 3 4 1/2 1 1-1/2 2 3 4
Fire Test Time, Hr Fire Test Time, Hr

Flexural failure can be assumed to occur when


Mnθ is reduced to M. From this expression, it can Fig. 6.3.1.5 Temperatures within sand-
lightweight concrete slabs
be seen that the fire endurance depends on the ap- during fire tests
plied loading and on the strength-temperature
characteristics of the steel. In turn, the duration of 1600
the fire before the “critical” steel temperature is Sand-Lightweight
1500 Concrete
reached depends upon the protection afforded to
the reinforcement. 1400
Test results have shown that the theory dis-
1300
cussed above is valid, not only for hollow core .
ce

in
rfa

4
floors, but also for roofs with insulation on top of 1200 1/
Su

.
in
F

the slabs. 2
1/
se
o

po

1100
Temperature,

Ex

Figure 6.3.1.2 shows the relationship between


m
ro

temperature and strength of various types of steel.


.F

1000 .
in

in
Figure 6.3.1.3, 6.3.1.4 and 6.3.1.5 show tempera- 1
4
3/
=

tures within concrete slabs during standard fire 900


u

.
in

tests. The data in those figures are applicable to


2
1/

800
1-

hollow core slabs. By using the equations given


.
in

above and the data in Figure 6.3.1.2 through 700


2

6.3.1.5, the moment capacity of slabs can be cal- 600


.

culated for various fire endurance periods, as il-


in
3

lustrated in the following example: 500


1/2 1 1-1/2 2 3 4
Fire Test Time, Hr

6--7
Example 6.3.1 wL = w -- wD = 170 -- 54 = 116 psf
Determine the maximum safe superimposed load
(d) Calculate maximum allowable wL at room
that can be supported by an 8 in deep hollow core
slab with a simply supported unrestrained span of temperature
25 ft and a fire endurance of 3 hr.
Given:
h = 8 in; u = 1.75 in; six 1/2 in 270 ksi strands;
 
fps = 270 1 − 0.28 0.918 270
0.80 366.25 5

Aps = 6(0.153) = 0.918 in2; b = 36 in; dp = 8 -- 1.75
= 249 ksi
= 6.25 in; wD = 54 psf; carbonate aggregate con-
crete; ℓ = 25 ft 0.918249
a = = 1.49 in
Solution: 0.85536
(a) Estimate strand temperature at 3 hr. from Fig- φMn = 0.9(0.918)(249)(6.25 -- 0.75)/12
ure 6.3.1.3, θs at 3 hr. at 1.75 in above fire-ex-
posed surface = 925 degrees F. = 94.3 ft-kips

(b) Determine fpuθ from Figure 6.3.1.2. For 894.31000


wu = = 402 psf
cold-drawn steel at 925 degrees F: (25) 23
fpuθ = 33% fpu = 89.1 ksi With load factors of 1.4 (dead load)
(c) Determine Mnθ and w + 1.7 (live load):

 
fpsθ = 89.1 1 − 0.28 0.918 89.1
0.80 366.25 5
 wL =
402 − 1.454
1.7
= 192 psf
Conclusion: wL = 116 < 192; 116 psf governs
= 86.8 ksi
Note: Fire endurance for heat transmission
0.91886.8 should also be checked
aθ = = 0.52in
0.85536
Table 6.3.1 shows values of u for simply sup-
Mnθ = 0.918(86.8)(6.25 -- 0.52/2)/12 ported unrestrained hollow core slabs for various
= 39.8 ft-kips moment ratios and fire endurance of 1, 2, and 3
hours. The values shown are based on
839.81000
w = = 170 psf Apsfpu/bdpf′c = 0.05 and can be reduced by 1/16 in
(25) 23 for Apsfpu/bdpf′c = 0.10.
Table 6.3.1 “u” inches, for simply supported unrestrained hollow core slabs*
Fire Aggregate Type
Endurance M/Mn Siliceous Carbonate Sand-Lightweight
(hr) (in) (mm) (in) (mm) (in) (mm)
1 0.50 1 1 /4 (32) 1 1/16 (27) 1 1/16 (27)
1 0.40 1 1/16 (27) 15/
16 (24) 15/
16 (24)
1 0.30 15/ (24) 13/ (21) 13/ (21)
16 16 16
2 0.50 15
1 /16 (49) 1 13/16 (46) 1 13/16 (46)
2 0.40 1 3 /4 (44) 1 9/16 (40) 1 9/16 (40)
2 0.30 1 9/16 (40) 1 5/16 (33) 1 5/16 (33)
3 0.50 2 1 /2 (64) 2 5/16 (59) 2 1 /8 (54)
3 0.40 2 3/16 (56) 2 (51) 1 15/16 (49)
3 0.30 1 15/16 (49) 1 11/16 (43) 1 11/16 (43)
*“u” is distance between center of strands and bottom of slab with all strands having same “u”. Based
on Apsfpu/bdpf′c = 0.05; conservative for values greater than 0.05.

6--8
Fig. 6.3.2 Equivalent concrete cover thickness for spray-applied coatings
5

4 )
Equivalent Concrete Cover Thickness, in. sla
bs
)(
M
( VC
rial
ate
3 sM bs
)
tiou ( sla
men F)
Ce SM
lite r(
be
icu Fi
rm ral
2 Ve ine
e dM
ray
Sp

0
0 1/4 1/2 3/4 1 1-1/4 1-1/2

Thickness of Spray-Applied Insulating Material, in.

6.3.2 Effect of Spray-Applied Coatings Fig. 6.3.3.1 Moment diagrams for continuous 2-
The fire endurance of hollow core slabs can be span beam before and during fire
increased by the addition of a spray-applied coat- exposure
ing of vermiculite cementitious material or
sprayed mineral fiber. Figure 6.3.2 shows the
relationship between thickness of spray-applied
coatings and equivalent concrete cover. Thus, if
strands are centered 3/4 in (19 mm) above the bot-
tom of a hollow core slab and if 1/4 in (6 mm) of
sprayed mineral fiber is applied, the u distance to Fire Fire

be used in Figures 6.3.1.3, 6.3.1.4 or 6.3.1.5 is 3/4


in (19 mm) plus the equivalent cover of 0.9 in (23 M -n

mm) obtained from Figure 6.3.2. -


M

6.3.3 Structurally Continuous Slabs


Continuous members undergo changes in M
+
stresses when subjected to fire, resulting from At 0 Hr
M +n
temperature gradients within the structural mem-
M -n θ
bers, or changes in strength of the materials at high
temperatures, or both. x0
Figure 6.3.3.1 shows a continuous beam whose -
underside is exposed to fire. The bottom of the M
beam becomes hotter than the top and tends to ex- +
At 3 Hr
pand more than the top. This differential tempera- M +n θ x1
ture causes the ends of the beam to tend to lift from
their supports thereby increasing the reaction at

6--9
Fig. 6.3.3.2 Uniformly loaded member Fig. 6.3.3.3 Symmetrical uniformly loaded mem-
continuous at one support ber continuous at both supports

M -n θ M -n θ M -n θ
w w

M -n θ

M -n θ
2
M+n θ

8
w
x1
x2 x0

M+n θ
x0 x2 x0

the interior support. This action results in a redis- simply supported at the other. Also shown is the
tribution of moments, i.e., the negative moment at redistributed applied moment diagram at failure.
the interior support increases while the positive Values for M +
nθ can be calculated by the proce-
moments decrease. dures given for “Simply Supported Slabs”.
During the course of a fire, the negative mo- Values for M −
nθ and xo can be calculated:


ment reinforcement (Figure 6.3.3.1) remains
wℓ 2  wℓ 2 2M +
cooler than the positive moment reinforcement M−
nθ =
n
(Eq. 6.3.4)
because it is better protected from the fire. Thus, 2 wℓ 2
the increase in negative moment can be accom- M− nθ
modated. Generally, the redistribution that occurs xo =2 (Eq. 6.3.5)
wℓ
is sufficient to cause yielding of the negative mo- In most cases, redistribution of moments oc-
ment reinforcement. The resulting decrease in curs early during the course of a fire before the
positive moment means that the positive moment negative moment capacity has been reduced by
reinforcement can be heated to a higher tempera- the effects of fire. In such cases, the length of xo is
ture before a failure will occur. Therefore, the fire increased, i.e., the inflection point moves toward
endurance of a continuous concrete beam is gen- the simple support. For such cases,
erally significantly longer than that of a simply 2M − n
supported beam having the same cover and loaded xo = (Eq. 6.3.6)
wℓ
to the same moment intensity. Figure 6.3.3.3 shows a symmetrical beam or
It is possible to design the reinforcement in a slab in which the end moments are equal. In that
continuous beam or slab for a particular fire en- case:
durance period. From Figure 6.3.3.1, the beam
M− nθ = wℓ ∕8 − M nθ
2 + (Eq. 6.3.7)
can be expected to collapse when the positive mo-
ment capacity, M + wx 22
nθ, is reduced to the value indi- and = M+ (Eq. 6.3.8)
8 nθ
cated by the dashed horizontal line, i.e., when the
redistributed moment at point x1, from the outer In negative moment regions, the compressive
support, M x1 = M + zone is directly exposed to fire, so calculations for
nθ.
dθ and aθ must be modified by (a) using f′cθ from
Figure 6.3.3.2 shows a uniformly loaded beam
Figure 6.3.3.4 and (b) neglecting concrete hotter
or slab continuous (or fixed) at one support and
than 1400 degrees F (760 degrees C).

6--10
Fig. 6.3.3.4 Compressive strength of concrete at high temperatures

70 200 400 600 800 1000 1200 1400


120 120

Carbonate
Percent of Original Compressive Strength 100 100

Sand-Lightweight
80 80

Siliceous

60 60

40 40

Original Strength = f’c


20 Average f’c = 3900 psi 20
Stressed to 0.4f’c during heating

0 0
70 200 400 600 800 1000 1200 1400
o
Temperature, F

6.3.4 Detailing Precautions Example 6.3.2


It should be noted that the amount of moment Determine the amount of negative moment re-
redistribution that can occur is dependent upon inforcement needed to provide a 3 hr. fire endur-
the amount of negative reinforcement. Tests have ance for sand-lightweight hollow core slabs, 8 in
clearly demonstrated that the negative moment re- deep, 5 ksi concrete, 48 in wide, with six 7/16 in 270
inforcement will yield, so the negative moment ksi strands and 2 in (4 ksi) composite topping.
capacity is reached early during a fire test, regard- Slabs span 25 ft of an exterior bay (no restraint to
less of the applied loading. The designer must ex- thermal expansion). Dead load = 65 psf, live load
ercise care to ensure that a secondary type of fail- = 100 psf. Strands are centered 1 3/4 in above bot-
ure will not occur. To avoid a compression failure tom of slab. The value for M + nθ can be calculated
in the negative moment region, the amount of neg- (by using the procedure discussed for simply sup-
ative moment reinforcement should be small ported slabs) to be 39.0 ft-kips. From Eq. 6.3.4
enough so that ωθ, i.e., Asfyθ /bθ dθ f′cθ, is less than (for use in Eq. 6.3.4):
0.30, before and after reductions in fy, b, d and f′c
w ℓ 2 = 4(65 + 100)(25)2/1000
are taken into account. Furthermore, the negative
moment bars or mesh must be long enough to ac- = 412.5 ft-kips
commodate the complete redistributed moment
and change in the inflection points. It should be M− nθ =
2

412.5 − 412.5 2 (39.0)
412.5
noted that the worst condition occurs when the ap- = 26.9 ft-kips
plied loading is smallest, such as dead load plus Determine As neglecting concrete above 1400 de-
partial or no live load. It is recommended that at grees F in negative moment region. From Figure
least 20% of the maximum negative moment rein- 6.3.1.5 neglect 3/4 in above bottom, and assume
forcement be extended throughout the span. steel centered in topping.
d = 10 -- 3/4 -- 1 = 8.25 in

6--11
Assume f′cθ in compressive zone = 0.8f′c = 4 ksi Fig. 6.4.1 Moment diagrams for axially
Assume d -- aθ/2 = 8.1 in restrained beam during fire exposure.
26.912 Note that at 2 hr. Mnθ is less than M
As = = 0.66 in2 and effects of axial restraint permit
608.1 beam to continue to support load.
0.6660 dT
check aθ = = 0.24 in
0.85448 T T
d -- aθ /2 = 8.25 -- 0.12 = 8.13 in ≅ 8.1 OK Fire
Use 6 x 6 - W2.1 x W2.1 WWF throughout plus #4
Grade 60 at 16 in in negative moment region.
As = 80.021 + 48 0.20 = 0.768 in2 @ 0 Hr, T=0
Mn
16 M
Calculate xo for dead load plus one-half live load.
@ 2 Hr.
M− 0.768 (26.9) = 31.3 ft-kips
nθ = M nθ
0.66 MT =
loading = 4(0.065 + 0.050) = 0.46 k/ft; T(d T - _a θ - ∆ )
2
Mn = 34.0 ft-kips (calculated for room tem-
(curved due to beam deflection)
peratures)

From Eq. 6.3.6 temperature rise of the unexposed surface rather


than by structural considerations, even though the
2M −n 2(34.0)
xo = = = 5.91 ft steel temperatures often exceed 1200 degrees F
wℓ 0.46(25)
(650 degrees C).
Half of #4 bars should extend 7 ft each side of inte- The effects of restraint to thermal expansion
rior support and half 5 ft. can be characterized as shown in Figure 6.4.1.
Use #4 Grade 60, 12 ft long at 16 in and stagger. The thermal thrust, T, acts in a manner similar to
an external prestressing force, which tends to in-
6.4 Restraint to Thermal Expansion crease the positive moment capacity.
If a fire occurs beneath a portion of a large floor Methods for calculating fire endurance of “re-
or roof, such as beneath a concrete floor slab in strained” floors or roofs are given in PCI MNL
one interior bay of a multi-bay building, the 124-89. It is seldom necessary to make such cal-
heated portion will expand and push against the culations, as noted below. The beneficial effects
surrounding unheated portion. In turn the un- of restraint are recognized in ASTM E119. The
heated portion exerts compressive forces on the standard presents a guide for determining condi-
heated portion. The compressive force, or thrust, tions of restraint. The guide includes Figure 6.4.2.
acts near the bottom of the slab when the fire In most cases, the interior bays of multi-bay floors
starts, but as the fire progresses, the line of thrust and roofs can be considered to be restrained and
rises and the thermal gradient diminishes and the the magnitude and location of the thrust are gener-
heated concrete undergoes a reduction in elastic ally of academic interest only. It should be noted
modulus. If the surrounding slab is thick and that Figure 6.4.2 indicates that adequate restraint
heavily reinforced, the thrust forces can be quite can occur in interior bays and exterior bays of
large, but they will be considerably less than those framed buildings when:
calculated by use of elastic properties of concrete “The space between the ends of precast units
and steel, together with appropriate coefficients of and the vertical faces of supports, or between the
expansion. At high temperatures, creep and stress ends of solid or hollow core slab units does not ex-
relaxation play an important role. Nevertheless, ceed 0.25 percent of the length for normal weight
the thrust is generally great enough to increase the concrete members or 0.1 percent of the length for
fire endurance significantly, in some instances by structural lightweight concrete members”.
more than 2 hours. In most fire tests of restrained Sketches illustrating typical conditions de-
assemblies, the fire endurance is determined by scribed above are shown in Figure 6.4.3.

6--12
Fig. 6.4.2. Examples of typical restrained and unrestrained construction classifications (from
Appendix X3 of ASTM E119-88)
I. Wall Bearing:
Single span and simply supported end spans of multiple baysa
(1) Open-web steel joists or steel beams, supporting concrete slab, precast units or metal decking unrestrained
(2) Concrete slabs, precast units or metal decking unrestrained
Interior spans of multiple bays:
(1) Open-web steel joists, steel beams or metal decking, supporting continuous concrete slab restrained
(2) Open-web steel joists or steel beams, supporting precast units or metal decking unrestrained
(3) Cast-in-place concrete slab systems restrained
(4) Precast concrete where the potential thermal expansion is resisted by adjacent constructionb restrained
II. Steel Framing:
(1) Steel beams welded, riveted, or bolted to the framing members restrained
(2) All types of cast-in-place floor and roof systems (such as beam-and-slabs, flat slabs, pan joints, and
waffle slabs) where the floor or roof system is secured to the framing members restrained
(3) All types of prefabricated floor or roof systems where the structural members are secured to the framing
members and the potential thermal expansion of the floor or roof system is resisted by the framing
system or the adjoining floor or roof constructionb restrained
III. Concrete Framing:
(1) Beams securely fastened to the framing members restrained
(2) All types of cast-in-place floor or roof systems (such as beam-and-slabs, flat slabs, pan joists, and
waffle slabs) where the floor system is cast with framing members restrained
(3) Interior and exterior spans of precast systems with cast-in-place joints resulting in restraint equivalent
to that which would exist in condition III(1) restrained
(4) All types of prefabricated floor or roof systems where the structural members are secured to such
systems and the potential thermal expansion of the floor or roof system is resisted by the framing
system or the adjoining floor or roof constructionb restrained
IV. Wood Construction
All Types unrestrained
aFloor and roof systems can be considered restrained when they are tied into walls with or without tie beams, the walls being
designed and detailed to resist thermal thrust from the floor or roof system.
bFor example, resistance to potential thermal expansion is considered to be achieved when:
(1) Continuous structural concrete topping is used.
(2) The space between the ends of precast units or between the ends of units and the vertical face of supports is filled with concrete
or mortar.
(3) The space between the ends of precast units and the vertical faces of supports, or between the ends of solid or hollow core
slab units does not exceed 0.25 percent of the length for normal weight concrete members or 0.1 percent of the length for structural
lightweight concrete members.

Fig. 6.4.3. Typical examples of restrained floors or roofs of precast construction

Hollow-Core Slabs or Double Tees


c1 c2

Hollow-Core or Solid Slabs


c1 c2

To be considered as restrained:
c1 + c2 < 0.0025 ℓ for normal weight concrete
c1 + c2 < 0.0010 ℓ for lightweight concrete
Example: Determine maximum value of c1 + c2 for normal weight hollow core slabs with a clear span of 30 ft
Solution: c1 + c2 = 0.0025(30 x 12) = 0.90 in

6--13
Example 6.4.1 strength, the assembly will generally be satisfac-
Hollow core floor slabs were installed in a tory structurally.
building several years ago when a 1 hr. fire endur-
ance was required. The occupancy of the building
will be changed and the floors must qualify for a 3
hr. fire endurance. What can be done to upgrade
the fire endurance?
Given:
Slabs are 4 ft wide, 8 in deep, prestressed with
five 3/8 in 270 ksi strands located 1 in above the
bottom of the slab, and span 24 ft. Slabs are made
with 5000 psi siliceous aggregate concrete, have
an equivalent thickness of 3.75 in, and weigh 47
psf. The slabs are untopped and the superimposed
load will be 50 psf.
Solution:
There are a number of possible solutions. The
appropriate solution will depend on architectural
or functional requirements and economics.
For some parts of the building, the slabs might
be made to qualify as “restrained” in accordance
with Figure 6.4.2 and Figure 6.4.3, in which case
those slabs would qualify structurally for 3 hours,
but would still have to be upgraded to qualify for 3
hours by heat transmission.
A gypsum wallboard ceiling installed as shown
in Figure 6.2.3 would provide three hours both
structurally and for heat transmission. Calcula-
tions of the ultimate capacity and stresses should
be made to assure that the added weight of the ceil-
ing can be adequately supported.
A spray-applied undercoating of vermiculite
cementitious material or sprayed mineral fiber
can also be used. For heat transmission, the re-
quired thickness for three hours of undercoating is
0.6 in (see Figure 6.2.2.1). From Figure 6.3.2, it
can be seen that with a thickness of 0.6 in of VCM
or SMF, the equivalent thickness of concrete cov-
er is more than 2 in. Thus, the equivalent “u” dis-
tance is more than 2 in plus 1 in or more than 3 in.
From Figure 6.3.1.4, with u more than 3 in, the
strand temperature will be less than 600 degrees F
at three hours, so the strength of the prestressing
steel will be 65% of its 70 degrees F strength (Fig-
ure 6.3.1.5) or more than 0.65 x 270 = 175.5 ksi.
Calculations can be made in accordance with the
procedures in the section headed “Simply Sup-
ported Slabs”, but if the strand strength is reduced
less than about 50% of its room temperature

6--14
CHAPTER 7

ACOUSTICAL PROPERTIES OF
HOLLOW CORE FLOOR SLABS

7.1 Glossary Room Criteria (RC) Curves - a revision of the NC


Airborne Sound - sound that reaches the point of curves based on empirical studies of background
interest by propagation through air. sounds.
Background Level - the ambient sound pressure Sabin - the unit of measure of sound absorption
level existing in a space. (ASTM C423).

Decibel (dB) - a logarithmic unit of measure of Sound Absorption Coefficient (α) - the fraction of
sound pressure or sound power. Zero on the deci- randomly incident sound energy absorbed or
bel scale corresponds to a standardized references otherwise not reflected off a surface (ASTM
pressure (20 µPa) or sound power (10-12 watt). C423).
Sound Pressure Level (SPL) - ten times the com-
Flanking Transmission - transmission of sound by
mon logarithm of the ratio of the square of the
indirect paths other than through the primary bar-
sound pressure to the square of the standard refer-
rier.
ence pressure of 20 µPa. Commonly measured
Frequency (Hz) - the number of complete vibra- with a sound level meter and microphone, this
tion cycles per second. quantity is expressed in decibels.

Impact Insulation Class (IIC) - a single figure rat- Sound Transmission Class (STC) - the single
ing of the overall impact sound insulation merits number rating system used to give a preliminary
of floor-ceiling assemblies in terms of a reference estimate of the sound insulation properties of a
contour (ASTM E989). partition system. This rating is derived from mea-
sured values of transmission loss (ASTM E413).
Impact Noise - the sound produced by one object Sound Transmission Loss (TL) - ten times the
striking another. common logarithm of the ratio, expressed in deci-
Noise - unwanted sound. bels, of the airborne sound power incident on the
partition that is transmitted by the partition and ra-
Noise Criteria (NC) - a series of curves, used as diated on the other side (ASTM E90).
design goals to specify satisfactory background
Structureborne Sound - sound that reaches the
sound levels as they relate to particular use func-
point of interest over at least part of its path by
tions.
vibration of a solid structure.
Noise Reduction (NR) - the difference in decibels
between the space-time average sound pressure 7.2 General
levels produced in two enclosed spaces by one or The basic purpose of architectural acoustics is
more sound sources in one of them. to provide a satisfactory environment in which de-
Noise Reduction Coefficient (NRC) - the arithme- sired sounds are clearly heard by the intended lis-
tic average of the sound absorption coefficients at teners and unwanted sounds (noise) are isolated or
250, 500, 1000 and 2000 Hz expressed to the near- absorbed.
est multiple of 0.05 (ASTM C423). Under most conditions, the architect/ engineer
can determine the acoustical needs of the space
Reverberation - the persistence of sound in an en- and then design the building to satisfy those
closed or partially enclosed space after the source needs. Good acoustical design utilizes both ab-
of sound has stopped. sorptive and reflective surfaces, sound barriers

7--1
and vibration isolators. Some surfaces must re- introduce resilient layers or discontinuities into
flect sound so that the loudness will be adequate in the barrier.
all areas where listeners are located. Other sur- Sound absorbing materials and sound insulat-
faces absorb sound to avoid echoes, sound distor- ing materials are used for different purposes.
tion and long reverberation times. Sound is iso- There is not much sound absorption from an 8 in
lated from rooms where it is not wanted by se- (200 mm) hollow core concrete slab; similarly,
lected wall and floor-ceiling constructions. high sound insulation is not available from a po-
Vibration generated by mechanical equipment rous lightweight material that may be applied to
must be isolated from the structural frame of the room surfaces. It is important to recognize that the
building. basic mechanisms of sound absorption and sound
Most acoustical situations can be described in insulation are quite different.
terms of: (1) sound source, (2) sound transmis-
sion path, and (3) sound receiver. Sometimes the 7.4 Sound Transmission Loss
source strength and path can be controlled and the Sound transmission loss measurements are
receiver made more attentive by removing dis- made at 16 frequencies at one-third octave inter-
traction or made more tolerant of disturbance. vals covering the range from 125 to 4000 Hz. The
Acoustical design must include consideration of testing procedure is ASTM Specification E90,
these three elements. Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions. To sim-
7.3 Approaching the Design Process plify specification of desired performance charac-
Criteria must be established before the acousti- teristics, the single number Sound Transmission
cal design of a building can begin. Basically a sat- Class (STC) was developed.
isfactory acoustical environment is one in which Airborne sound reaching a floor or ceiling pro-
the character and magnitude of all sounds are duces vibration in the slab and is radiated with re-
compatible with the intended space function. duced intensity on the other side. Airborne sound
Although a reasonable objective, it is not al- transmission loss of a floor-ceiling assembly is a
ways easy to express these intentions in quantita- function of its weight, stiffness and vibration
tive terms. In addition to the amplitude of sound, damping characteristics.
the properties such as spectral characteristics, Weight is concrete’s greatest asset when it is
continuity, reverberation and intelligibility must used as a sound insulator. For sections of similar
be specified. design, but different weights, the STC increases
People are highly adaptable to the sensations of approximately 6 units for each doubling of weight
heat, light, odor, sound, etc. with sensitivities va- as shown in Figure 7.4.1.
rying widely. The human ear can detect a sound
Fig. 7.4.1 Sound Transmission Class as a
intensity of rustling leaves, 10 dB, and can toler- function of weight of floor
ate, if even briefly, the powerful exhaust of a jet
engine at 120 dB, 1012 times the intensity of the 65
Sound Transmission Class (STC)

rustling sound.
60

7.3.1 Dealing with Sound Levels hollow core slabs


55
The problems of sound insulation are usually
considerably more complicated than those of
50
sound absorption. The former involves reduc- STC = 0.1304 W + 43.48
tions of sound level, which are of the greater or- statistical tolerance +
_ 2.5 STC
45
ders of magnitude than can be achieved by absorp-
tion. These reductions of sound level from space
to space can be achieved only by continuous, im- 40
40 50 60 70 80 90 100
pervious barriers. If the problem also involves Weight Per Unit Area, psf
structure borne sound, it may be necessary to

7--2
Fig. 7.4.2 Acoustical test data of hollow core slabs (normal weight concrete)

Sound Transmission Loss Impact Insulation

70 70
8 in. hollow core (bare).IIC-28

6 in. hollow core (bare).IIC-23


60 60
8 in. hollow core. STC-50

Impact Sound Pressure Level dB


Sound Transmission Loss, dB

50 50

40 40 6 in. hollow core


6 in. hollow core. STC-48 with carpet and pad. IIC-69

30 30

8 in. hollow core


with carpet and pad. IIC-73
20 20

10 10
125

315

125

315
100

160
200
250

400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000

100

160
200
250

400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
Frequency, Hz

Precast concrete floors and roofs usually do not The test method used to evaluate systems for
need additional treatments in order to provide ad- impact sound insulation is described in ASTM
equate sound insulation. If desired, greater sound Specification E492, Laboratory Measurement of
insulation can be obtained by using a resiliently Impact Sound Transmission Using the Tapping
attached layer(s) of gypsum board or other build- Machine. As with the airborne standard, mea-
ing material. The increased transmission loss oc- surements are made at 16 one-third octave inter-
curs because the energy flow path is now in- vals but in the range from 100 to 3150 Hz. For per-
creased to include a dissipative air column and formance specification purposes, the single num-
additional mass. ber Impact Insulation Class (IIC) is used.
The acoustical test results of both airborne Hollow core floors in combination with resil-
sound transmission loss and impact insulation of 6 ient materials effectively control impact sound.
and 8 in (150 and 200 mm) hollow core slabs are One simple solution consists of good carpeting on
shown in Figure 7.4.2. Table 7.4.1 presents the resilient padding. Table 7.4.1 shows that a carpet
ratings for various floor-ceiling assemblies. and pad over a bare slab will significantly increase
the impact noise reduction. The overall efficiency
varies according to the characteristics of the car-
7.5 Impact Noise Reduction peting and padding such as resilience, thickness
Footsteps, dragged chairs, dropped objects, and weight. So called resilient flooring materials,
slammed doors, and plumbing generate impact such as linoleum, rubber, asphalt vinyl, etc. are
noise. Even when airborne sounds are adequately not entirely satisfactory directly on concrete, nor
controlled there can be severe impact noise prob- are parquet or strip wood floors when applied di-
lems. rectly. Impact sound also may be controlled by

7--3
Table 7.4.1 Airborne sound transmission and impact insulation class ratings from laboratory
tests of hollow core slab floor-ceiling assemblies
Assembly
No. Description STC IIC
1. 6 in (150 mm) hollow core slabs 48 23
2. Assembly 1 with carpet and pad 48 69
3. Assembly 1 with 1/2 in (13 mm) wood block flooring adhered directly 48 48
4. Assembly 1 with 1/2 in (13 mm) wood block flooring adhered to 1/2 in (13 mm)
sound-deadening board underlayment adhered to concrete 49 49
5. Assembly 1 with 3/4 in (19 mm) gypsum concrete 50 41
6. Assembly 1 with 3/4 in (19 mm) gypsum concrete on 1/2 in (13 mm) sound-
deadening board underlayment adhered to concrete 50 50
7. Assembly 1 with carpet and pad on 3/4 in (19 mm) gypsum concrete on
1/ in (13 mm) sound-deadening board underlayment adhered to concrete 50 72
2

8. 8 in (200 mm) hollow core slabs 50 28


9. Assembly 8 with carpet and pad 50 73
10. Assembly 8 with 1/2 in (13 mm) wood block flooring adhered directly 51 47
11. Assembly 8 with 1/2 in (13 mm) wood block flooring adhered to 1/2 in (13 mm)
sound-deadening board underlayment adhered to concrete 52 54
12. Assembly 8 with 1/2 in (13 mm) wood block flooring adhered to 1/2 in (13 mm)
plywood adhered to 7/16 in (11 mm) sound-deadening board underlayment
adhered to concrete 52 55
13. Assembly 8 with 5/16 in (8 mm) wood block flooring adhered to 1/4 in (6 mm)
polystyrene underlayment adhered to concrete 50 51
14. Assembly 8 with vinyl tile adhered to 1/2 in (13 mm) plywood adhered to
7/ in (11 mm) sound-deadening board underlayment adhered to concrete 50 55
16
15. Assembly 8 with vinyl tile adhered to 1/4 in (6 mm) inorganic felt supported
cushion underlayment adhered to concrete 50 51
16. Assembly 8 with vinyl tile adhered to 1/8 in (3 mm) polyethylene foam under-
layment adhered to concrete 50 58
17. Assembly 8 with 1 1/2 in (38 mm) concrete topping with carpet and pad 50 76
18. Assembly 8 with 1 1/2 in (38 mm) concrete topping with vinyl tile adhered to
concrete 50 44
19. Assembly 8 with 1 1/2 in (38 mm) concrete topping with vinyl tile adhered
to 3/8 in (9 mm) plywood adhered to 1/2 in (13 mm) sound-deadening board
adhered to concrete 52 55
20. Assembly 8 with 1 1/2 in (38 mm) concrete with 1/2 in (13 mm) wood block
flooring adhered to 1/2 in (13 mm) sound-deadening board adhered to concrete 51 53
21. Assembly 8 with 1 1/2 in (38 mm) concrete with 5/16 in (8 mm) wood block
flooring adhered to foam backing adhered to concrete 51 54
22. Assembly 8 with 3/4 in (19 mm) gypsum concrete with 5/16 in (8 mm) wood
block flooring adhered to foam backing adhered to concrete 50 53
23. Assembly 11 with acoustical ceiling 59 61
24. Assembly 8 with quarry tile, 1 1/4 in (32 mm) reinforced mortar bed with
0.4 in (10 mm) nylon and carbon black spinerette matting 60 54
25. Assembly 24 with suspended 5/8 in (16 mm) gypsum board ceiling with
3 1/2 in (90 mm) insulation 61 62

7--4
providing a discontinuity in the structure such as same, regardless of the original sound pressure
would be obtained by adding a resilient-mounted level and depends only on the absorption ratio.
plaster or drywall suspended ceiling. This is due to the fact that the decibel scale is itself
a scale of ratios, rather than difference in sound
7.6 Absorption of Sound energy.
A sound wave always loses part of its energy as While a decibel difference is an engineering
it is reflected by a surface. This loss of energy is quantity which can be physically measured, it is
termed sound absorption. It appears as a decrease also important to know how the ear judges the
in sound pressure of the reflected wave. The change in sound energy due to sound condition-
sound absorption coefficient is the fraction of en- ing. Apart from the subjective annoyance factors
ergy incident but not reflected per unit of surface associated with excessive sound reflection, the ear
area. Sound absorption can be specified at indi- can make accurate judgments of the relative loud-
vidual frequencies or as an average of absorption ness between sounds. An approximate relation
coefficients (NRC). between percentage loudness, reduction of re-
A dense, non-porous concrete surface typically flected sound and absorption ratio is plotted in
absorbs 1 to 2% of incident sound and has an NCR Figure 7.6.2
of 0.015. In the case where additional sound ab- The percentage loudness reduction does not de-
sorption of precast concrete is desired, a coating pend on the original loudness, but only on the ab-
of acoustical material can be spray applied, acous- sorption ratio. (The curve is drawn for loudness
tical tile can be applied with adhesive, or an acous- within the normal range of hearing and does not
tical ceiling can be suspended. Most of the spray apply to extremely faint sounds.) Referring again
applied fire retardant materials used to increase to the absorption ratio of 5, the loudness reduction
the fire resistance of precast concrete and other is read from Figure 7.6.2 as approximately 40 per-
floor-ceiling systems can also be used to absorb cent.
sound. The NCR of the sprayed fiber types range
from 0.25 to 0.75. Most cementitious types have
7.7 Acceptable Noise Criteria
an NCR from 0.25 to 0.50.
As a rule, a certain amount of continuous sound
If an acoustical ceiling were added to Assem-
can be tolerated before it becomes noise. An “ac-
bly 11 of Table 7.4.1 (as in Assembly 23), the
ceptable” level neither disturbs room occupants
sound entry through a floor or roof would be re-
nor interferes with the communication of wanted
duced 7dB. In addition, the acoustical ceiling
sound.
would absorb a portion of the sound after entry
The most widely accepted and used noise crite-
and provide a few more decibels of quieting. Use
ria today are expressed as the Noise Criterion
of the following expression can be made to deter-
(NC) curves, Figure 7.7.1a. The figures in Table
mine the intra-room noise or loudness reduction
7.7.1 represent general acoustical goals. They can
due to the absorption of sound.
also be compared with anticipated noise levels in
Ao + Aa specific rooms to assist in evaluating noise reduc-
NR = 10 log (Eq. 7.6.1)
Aa tion problems.
where The main criticism of NC curves is that they are
NR = sound pressure level reduction, dB too permissive when the control of low or high
Ao = original absorption, Sabins frequency noise is of concern. For this reason,
Room Criterion (RC) Curves were developed
Aa = added absorption, Sabins (Figure 7.7.1b).39,40 RC curves are the result of
Values for Ao and Aa are the products of the ab- extensive studies based on the human response to
sorption coefficients of the various room materi- both sound pressure level and frequency and take
als and their surface areas. into account the requirements for speech intelligi-
A plot of this equation is shown in Figure 7.6.1. bility.
For an absorption ratio of 5, the decibel reduction A low background level obviously is necessary
is 7dB. Note that the decibel reduction is the where listening and speech intelligibility is im-

7--5
Fig. 7.6.1 Relation of decibel reduction of Fig. 7.7.1b RC (Room Criteria) Curves
reflected sound to absorption ratio

Octave Band Sound Pressure Level, dB re 20 micropascals


90
14
A
12 80
B
10
SPL Reduction, dB

70
8

6 60

4 50
RC
2
40 50
0 C
0 2 4 6 8 10 12 14 16 18 20 45
Absorption Ratio, A2 /A1 30 40
35
20 30
Fig. 7.6.2 Relation of percent loudness reduction
25
of reflected sound to absorption ratio
10
16 31.5 63 125 250 500 1000 2000 4000
Octave Band Center Frequencies, Hz
Percent Loudness Reduction

60

50
Region A: High probability that noise-induced vibration levels in
40
lightweight wall/ceiling constructions will be clearly feelable; antic-
30 ipate audible rattles in light fixtures, doors, windows, etc.
Region B: Noise-induced vibration levels in lightweight wall/ceil-
20 ing constructions may be moderately feelable; slight possibility of
rattles in light fixtures, doors, windows, etc.
10 Region C: Below threshold of hearing for continuous noise.

0
0 2 4 6 8 10 12 14 16 18 20
Absorption Ratio, A 2 /A 1
portant. Conversely, higher levels can persist in
large business offices or factories where speech
Fig. 7.7.1a NC (Noise Criteria) Curves
communication is limited to short distances.
Often it is just as important to be interested in the
Octave Band Sound Pressure Level, dB re 20 micropascals

90 minimum as in the maximum permissible levels


of Table 7.7.1. In an office or residence, it is desir-
80
able to have a certain ambient sound level to as-
70 sure adequate acoustical privacy between spaces,
NC-65 thus, minimizing the transmission loss require-
60 NC-60 ments of unwanted sound (noise).
NC-55 These undesirable sounds may be from an exte-
50 NC-50
NC-45
rior source such as automobiles or aircraft, or they
40 NC-40 may be generated as speech in an adjacent class-
NC-35 room or music in an adjacent apartment. They
30 NC-30 may be direct impact-induced sound such as foot-
Approximate
threshold of NC-25 falls on the floor above, rain impact on a light-
20 hearing for NC-20
continuous
NC-15
weight roof construction or vibrating mechanical
noise
10 equipment.
63 125 250 500 2000 8000
Octave Band Center Frequencies, Hz

7--6
Thus, the designer must always be ready to ac- Table 7.7.1 Recommended category classi-
cept the task of analyzing the many potential fication and suggested Noise
sources of intruding sound as related to their fre- Criteria range for steady back-
quency characteristics and the rates at which they ground noise as heard in various
occur. The level of toleration that is to be expected in-door functional activity
by those who will occupy the space must also be areas*39
established. Figures 7.7.2 and 7.7.3 are the spec-
NC OR RC
tral characteristics of common noise sources.
TYPE OF SPACE CURVE
Fig. 7.7.2 Sound pressure levels - exterior noise 1. Private residences 25 to 30
sources
2. Apartments 30 to 35
120 3. Hotels/motels
jet aircraft takeoff
500 ft a. Individual rooms or suites 30 to 35
b. Meeting/banquet rooms 30 to 35
100
bus c. Halls, corridors, lobbies 35 to 40
d. Service/support areas 40 to 45
Sound Pressure Level, dB

propeller aircraft
80 takeoff-500 ft 4. Offices
heavy truck - 20 ft
a. Executive 25 to 30
60 b. Conference rooms 25 to 30
automobiles - 20 ft c. Private 30 to 35
40 d. Open-plan areas 35 to 40
e. Computer/business
machine areas 40 to 45
20
f. Public circulation 40 to 45
5. Hospitals and clinics
0
63 125 250 500 1000 2000 4000 8000 a. Private rooms 25 to 30
Frequency, Hz. b. Wards 30 to 35
c. Operating rooms 25 to 30
d. Laboratories 30 to 35
Fig. 7.7.3 Sound pressure levels - interior noise e. Corridors 30 to 35
sources f. Public areas 35 to 40
6. Churches 25 to 30**
120
7. Schools
riveting a. Lecture and classrooms 25 to 30
b. Open-plan classrooms 30 to 35**
100 8. Libraries 30 to 35
stero phonograph
teenager level 9. Concert Halls **
Sound Pressure Level, dB

typical office
80 10. Legitimate theatres **
11. Recording studios **
60 business machine 12. Movie theatres 30 to 35
tabulating room
bed or dining room * Design goals can be increased by 5 dB when
40
kitchen dictated by budget constraints or when noise
intrusion from other sources represents a lim-
20 iting condition.
**An acoustical expert should be consulted for
0 guidance on these critical spaces.
63 125 250 500 1000 2000 4000 8000
Frequency, Hz.

7--7
Sound Pressure Level - (dB)
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000
Stereo Source Noise (teenager) 60 72 84 82 82 80 75 60
(Figure 7.7.3)
Bedroom Room Criteria 50 45 40 35 30 25 20 15
RC 30 (Figure 7.7.l)
Required Insulation 10 27 44 47 52 55 55 45

Sound Pressure Level - (dB)


Frequency (Hz) 125 250 500 1000 2000 4000
Required Insulation 27 44 47 52 55 55
8 in H.C. (Figure 7.4.2) 34 39 46 53 59 64
Deficiencies ---- 5 1 ---- ---- ----

With these criteria, the problem of sound isola- termined analytically by (1) identifying exterior
tion now must be solved, namely, the reduction and/or interior noise sources, and (2) by establish-
process between the high unwanted noise source ing acceptable interior noise criteria.
and the desired ambient level. For this solution,
two related yet mutually exclusive processes must Example 7.8.1
be incorporated, i.e., sound transmission loss and Assume a precast prestressed concrete apart-
sound absorption. ment building with hollow core floor slabs. The
first step is to determine the degree of acoustical
7.8 Establishment of Noise Insulation objec- insulation required of the floor-ceiling assembly
tives by using Figures 7.4.1 and 7.7.3
Often acoustical control is specified as to the The 500 Hz requirement, 47 dB, can be used as
minimum insulation values of the dividing parti- the first approximation of the floor STC category.
tion system. Municipal building codes, lending The selected floor should meet or exceed the
institutions and the Department of Housing and insulation needs at 11 frequencies. However, to
Urban Development (HUD) list both airborne achieve the most efficient design conditions, cer-
STC and impact IIC values for different living en- tain limited deficiencies can be tolerated. Experi-
vironments. For example, the HUD minimum ence has shown that the maximum deficiencies
property standards41 are: are 3 dB on one frequency point.

LOCATION STC IIC 7.9 Leaks and Flanking


The performance of a building section with an
Between living units 45 45 otherwise adequate STC can be seriously reduced
Between living units and 50 50 by a relatively small hole or any other path which
public space allows sound to bypass the acoustical barrier. All
noise which reaches a space by paths other than
Once the objectives are established, the design- through the primary barrier is called flanking.
er then should refer to available data, e.g., Fig. Common flanking paths are openings around
7.4.2 or Table 7.4.1 and select the system which doors or windows, at electrical outlets, telephone
best meets these requirements. In this respect, and television connections, and pipe and duct pe-
concrete systems have superior properties and netrations. Suspended ceilings in rooms where
can, with minimal effort, comply with these crite- walls do not extend from the ceiling to the roof or
ria. When the insulation value has not been speci- floor above allow sound to travel to adjacent
fied, selection of the necessary barrier can be de- rooms.

7--8
Fig. 7.9.1 Effect of safing insulation seals structure is much less than in one of steel or wood
frame.
concrete floor
In addition to using basic structural materials,
inorganic
mineral wool flanking paths can be minimized by:
insulation
1. Interrupting the continuous flow of energy
with dissimilar material, i.e., expansion or con-
exterior
wall trol joints or air gaps.
steel bent plate
gap 2. Increasing the resistance to energy flow with
floating floor systems, full height and/or
Combined
double partitions and suspended ceilings.
Transmission Loss
No closure 14 STC 7.10 Human Response to Building Vibrations
With steel vent plate closure 28 STC Modern buildings often use components with
With 4 in thick safing insulation 30 STC
steel bent plate added 42 STC
low weight-to-strength ratios, which allow longer
With 6 in thick safing insulation 38 STC spans with less mass. This trend increasingly re-
steel bent plate added 45 STC sults in transient vibrations which are annoying to
the occupants. Unlike equipment vibration, a per-
son often causes the vibration and also senses it.
Anticipation and prevention of leaks begins at These vibrations usually have very small ampli-
the design stage. Flanking paths (gaps) at the pe- tudes (less than 0.05 in [1 mm]) and were not not-
rimeters of interior precast walls and floors are iced in older structures with heavier framing and
generally sealed during construction with grout or more numerous and heavier partitions, which pro-
drypack. In addition, all openings around pe- vided greater damping and other beneficial dy-
netrations through walls or floors should be as namic characteristics.
small as possible and must be sealed airtight. The This problem is not well understood. Predict-
higher the STC of the barrier, the greater the effect ing human response to floor motion and the dy-
of an unsealed opening. namic response to floor motion and the dynamic
Perimeter leakage more commonly occurs at response of a floor system to moving loads are de-
the intersection between an exterior curtain wall veloping technologies. A number of discomfort
and floor slab. It is of vital importance to seal this criteria have been published44-51, but they often
gap in order to retain the acoustical integrity of the give contradictory results.
system as well as provide the required fire stop be- The vibration problem is most effectively
tween floors. One way to achieve this seal is to treated by modifying the structural system. The
place a 4 pcf (64 kg/m3) density mineral wood natural period (or its inverse, frequency), stiff-
blanket between the floor slab and the exterior ness, mass, and damping are the structural param-
wall. Figure 7.9.1 demonstrates the acoustical eters related to vibration control. Stiffness is in-
isolation effects of this treatment. creased by providing greater section properties
In exterior walls, the proper application of seal- than may be required for supporting loads. An in-
ant and backup materials in the joints between crease in mass improves the natural frequency, but
units will not allow sound to flank the wall. increases deflections and stresses, so by itself is
If the acoustical design is balanced, the maxi- only partially effective in controlling vibrations.
mum amount of acoustic energy reaching a space For example, increasing the depth of a flexural
via flanking should not equal the energy trans- member will aid greatly in vibration control, but
mitted through the primary barriers. increasing the width will not.
Although not easily quantified, an inverse rela- Recent research has emphasized the effect that
tionship exists between the performance of an ele- damping plays in the human perception of vibra-
ment as a primary barrier and its propensity to tion. In a study of 91 floor systems it was con-
transmit flanking sound. In other words, the prob- cluded that with damping greater than 5.5 to 6 per-
ability of existing flanking paths in a concrete cent of critical, structural systems were accept-

7--9
able; systems with less were not46. Damping is From the above, the required static deflection
usually attributed to the existence of partitions, of an isolator can be determined as follows:
supported mechanical work, ceilings and similar
items, but is really not well understood. Guides fn = fd/3 = 188 1∕∆ i or
for quantifying damping effect are scarce, and
∆i = (564/fd)2 (Eq. 7.11.2)
those that are available are very approximate49-51.
and:
7.11 Vibration Isolation for Mechanical
Equipment ∆f ≤ 0.15 ∆i (Eq. 7.11.3)
Vibration produced by equipment with unbal-
where:
anced operating or starting forces can usually be
isolated from the structure by mounting on a fd = driving frequency of the equipment
heavy concrete slab placed on resilient supports.
This type of slab, called an inertia block, provides ∆f = static deflection of the floor system caused
a low center of gravity to compensate for thrusts by the weight of the equipment, including
such as those generated by large fans. inertia block, at the location of the equip-
For equipment with less unbalanced weight, a ment.
“housekeeping” slab is sometimes used below the
resilient mounts to provide a rigid support for the
mounts and to keep them above the floor so they
are easier to clean and inspect. This slab may also Example 7.11.1 - Vibration Isolation
be mounted on pads of precompressed glass fiber Given:
or neoprene. A piece of mechanical equipment has a driving
The natural frequency of the total load on resil- frequency of 800 CPM.
ient mounts must be well below the frequency
Problem:
generated by the equipment. The required weight
of an inertia block depends on the total weight of Determine the approximate minimum deflec-
the machine and the unbalanced force. For a long tion of the isolator and the maximum deflection of
stroke compressor, five to seven times its weight the floor system that should be allowed.
might be needed. For high pressure fans, one to Solution:
five times the fan weight is usually sufficient. Isolator, ∆i = (564/800)2 = 0.50 in.
A floor supporting resiliently mounted equip- Floor, ∆f = 0.15(0.50) = 0.07 in.
ment must be much stiffer than the isolation sys-
tem. If the static deflection of the floor ap- Additional Bibliography
proaches the static deflection of the mounts, the L.L. Beranek; Noise Reduction, McGraw-Hill
floor becomes a part of the vibrating system, and Book Co., New York, 1960.
little vibration isolation is achieved. In general,
the floor deflection should be limited to about 15 Ceramic Tile Institute of America and American
percent of the deflection of the mounts. Enka Company unpublished floor/ceiling tests.
Simplified theory shows that for 90% vibration
isolation, a single resilient supported mass (isola- C.M. Harris, Handbook of Noise Control,
tor) should have a natural frequency of about 1/3 McGraw-Hill Book Co., New York, 1967.
the driving frequency of the equipment. The natu-
ral frequency of this mass can be calculated by:52 C.M. Harris, C.E. Crede; Shock & Vibration
Handbook - 2nd ed., McGraw-Hill Book Co.,
fn = 188 1∕∆ i (Eq. 7.11.1) New York, 1976.
where:
A. Litvin, H.W. Belliston; “Sound Transmission
fn = natural frequency of the isolator, CPM Loss Through Concrete and Concrete Masonry
∆i = static deflection of the isolator, in Walls”, ACI Journal, December, 1978.

7--10
CHAPTER 8

GUIDE SPECIFICATION FOR PRECAST,


PRESTRESSED HOLLOW CORE SLABS

This Guide Specification is intended to be used as a basis for the development of an office
master specification or in the preparation of specifications for a particular project. In either
case, this Guide Specification must be edited to fit the conditions of use.
Particular attention should be given to the deletion of inapplicable provisions. Necessary
items related to a particular project should be included. Also, appropriate requirements
should be added where blank spaces have been provided
The Guide Specifications are on the left. Notes to Specifiers are on the right.

GUIDE SPECIFICATIONS NOTES TO SPECIFIERS


1. GENERAL
1.01 Description
A. Work Included: 1.01.A This Section is to be in Division 3 of
Construction Specifications Institute format.
1. These specifications cover manufacture,
transportation, and erection of precast,
prestressed concrete hollow core slabs in-
cluding grouting of joints between adja-
cent slab units.
B. Related Work Specified Elsewhere:
1. Cast-in-Place Concrete: Section 1.01.B.1 Includes structural or non-structural
_________. topping. See Section 2.5 for discussion of com-
posite, structural topping.
2. Architectural Precast Concrete: Section
_________.
3. Precast Structural Concrete: Section 1.01.B.3 Beams, columns, etc.
_________. Prestressed concrete may be specified in Section
_________.
4. Structural Metal Framing: Section 1.01.B.4 Includes support framework not sup-
_________. plied by Hollow Core Slab Manufacturer.
5. Masonry Bearing Walls: Section 1.01.B.5 Include any inserts or anchoring de-
_________. vices required for slab connections.
6. Underlayments: Section_________. 1.01.B.6 Underlayment may be any of the follow-
ing general types: asphaltic concrete, gypsum
concrete, latex concrete, mastic underlayment.

8--1
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

7. Caulking and Sealants: Section 1.01.B.7 Caulking between slab edges at exposed
_________. underside of floor members and/or perimeter
caulking may be included in this section.
8. Holes for Mechanical Equipment: Sec- 1.01.B.8 Holes may be drilled or cut and trimmed
tion _______. with a chisel. Cut outline of hole through lower
portion of slab from underside, after which the top
side may be removed from above. Do not cut pre-
stressing strand without permission of engineer.
9. Painting: Section _________. 1.01.B.9 Prime coat should be a latex base paint.
Finish coat may be an oil base, flat wall or emulsi-
fied finish
10. Carpet and Pad: Section _________. 1.01.B.10 Specify minimum 55 oz. pad when no
cast-in-place topping is used
11. Roofing and Roof Insulation: 1.01.B.11 Non-absorbent rigid board insulation
Section _________. 1” or more in thickness should be used on roofs.
Check local energy code for exact requirements.

1.02 Quality Assurance


A. The precast concrete manufacturing plant 1.02.A Structural Precast Products must meet the
shall be certified by the Precast/Prestressed requirements of PCI Manual, MNL-116.
Concrete Institute (PCI) Plant Certification
Program. Manufacturer shall be certified at In Canada, the manufacture, transportation and
the time of bidding in Category C2. erection of precast prestressed hollow core slabs
is governed by the Canadian Standards Associa-
tion Standard A23.4-94, “Precast Concrete - Ma-
terials and Construction”.

Assurance of plant capability to produce quality


precast concrete products is set by the CSA Stan-
dard A23.4-94. This Standard forms the basis of a
certification program which sets rigid capability
criteria for precast manufacturers, their person-
nel and operations.
B. Erector Qualifications: Regularly engaged 1.02.B Usually 2 to 5 years.
for at least _______ years in the erection of
precast structural concrete similar to the re-
quirements of this project.
C. Qualifications of Welders: In accordance 1.02.C Qualified within the past year.
with AWS D1.1.

D. Testing: In general compliance with applica-


ble provisions of Precast/Prestressed Con-
crete Institute MNL-116, Manual for Quality
Control for Plants and Production of Precast
Prestressed Concrete Products.

8--2
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

E. Requirements of Regulatory Agencies: All 1.02.E Always include the specific year or edi-
local codes plus the following specifications, tion of the specifications, codes and standards
standards and codes are a part of these specifi- used in the design of the project and made part of
cations: the specifications. Fire safety and resistance re-
1. ACI 318-Building Code Requirements quirements are specified in local or model codes.
for Structural Concrete. When required, fire rated products shall be clear-
2. AWS D1.1-Structural Welding Code - ly identified on the design drawings.
Steel. For projects in Canada, the National Building
3. AWS D1.4-Structural Welding Code - Re- Code of Canada governs design. Canadian Stan-
inforcing Steel. dards Association Standards A23.3-94, “Design
4. ASTM Specifications - As referred to in of Concrete Structures” and A23.4-94, “Precast
Part 2 - Products, of this Specification. Concrete - Materials and Construction” also ap-
ply. Fire resistance is specified in the National
Building Code and the National Fire Code.

1.03 Submittals

A. Shop Drawings
1. Erection Drawings
a. Plans locating and defining all hollow 1.03.A.1.a Openings shown on erection draw-
core slab units furnished by the ings are considered in the slab design. Verify slab
manufacturer, with all openings larger adequacy for any other openings with the Engi-
than 10 in (250 mm) shown and lo- neer of Record.
cated.
b. Sections and details showing connec-
tions, edge conditions and support
conditions of the hollow core slab
units.
c. All dead, live and other applicable
loads used in the design.
d. Estimated cambers. 1.03.A.1.d Floor slabs receiving cast-in-place
topping. The elevation of top of floor and amount
of concrete topping must allow for camber of pre-
stressed concrete members.
2. Production Drawings 1.03.A.2 Production drawings are normally sub-
a. Plan view of each hollow core slab mitted only upon request.
unit type.
b. Sections and details to indicate quanti-
ties, location and type of reinforcing
steel and prestressing strands.
c. Lifting and erection inserts.
d. Dimensions and finishes.
e. Prestress for strand and concrete
strength.

8--3
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

f. Estimated camber at release.


g. Method of transportation.
B. Product Design Criteria 1.03 B and C Contract drawings normally will be
1. Loadings for design prepared using a local precast prestressed con-
a. Initial handling and erection stresses. crete hollow core slab manufacturer’s design data
b. All dead and live loads as specified on and load tables. Dimensional changes which
the contract drawings would not materially affect architectural and
c. All other loads specified for hollow structural properties or details usually are per-
core slab units where applicable. missible.
2. Design calculations of products not com- Be sure that loads shown on the contract draw-
pleted on the contract drawings shall be ings are easily interpreted. For instance, on mem-
performed by a registered engineer expe- bers which are to receive concrete topping, be
rienced in precast prestressed concrete sure to state whether all superimposed dead and
design and submitted for approval upon live loads on precast prestressed members do or
request. do not include the weight of the concrete topping.
3. Design shall be in accordance with ACI It is best to list the live load, superimposed dead
318 or applicable codes. load, topping weight, and weight of the member,
C. Permissible Design Deviations all as separate loads. Where there are two differ-
1. Design deviations will be permitted only ent live loads (e.g., roof level of a parking struc-
after the Architect/Engineer’s written ap- ture) indicate how they are to be combined.
proval of the manufacturer’s proposed de- Where additional structural support is required
sign supported by complete design cal- for openings, design headers in accordance with
culations and drawings. hollow core slab manufacturer’s recommenda-
2. Design deviation shall provide an installa- tions.
tion equivalent to the basic intent without
incurring additional cost to the owner.
D. Test Report: Reports of tests on concrete and
other materials upon request.

2. PRODUCTS
2.01 Materials 2.01 Delete or add materials that may be re-
quired for the particular job.
A. Portland Cement:
1. ASTM C150 - Type I or III
B. Admixtures: 2.01.B Verify ability of local producer to use ad-
mixtures
1. Air-Entraining Admixtures: ASTM
C260.
2. Water Reducing, Retarding, Accelerat-
ing, High Range Water Reducing Admix-
tures: ASTM C494.
C. Aggregates:
1. ASTM C33 or C330.

8--4
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

D. Water:
Potable or free from foreign materials in
amounts harmful to concrete and embedded
steel.
E. Reinforcing Steel:
1. Bars: 2.01.E.1 When welding of bars is required, weld-
Deformed Billet Steel: ASTM A615. ability must be established to conform to AWS
Deformed Rail Steel: ASTM A616. D1.4.
Deformed Axle Steel: ASTM A617.
Deformed Low Alloy Steel: ASTM
A706.
2. Wire:
Cold Drawn Steel: ASTM A82.
F. Prestressing Strand: 2.01.F Low-relaxation strand is the predominant
1. Uncoated, 7-Wire, Stress-Relieved strand in use. References to stress-relieved strand
Strand: ASTM A416 (including supple- are from the ASTM titles.
ment) - Grade 250K or 270K.
2. Uncoated, Weldless 2- and 3-Wire Strand:
ASTM A910
3. Indented, 7-Wire, Stress-Relieved Strand:
ASTM A886 (including supplement)
G. Welded Studs: In accordance with AWS
D1.1.
H. Structural Steel Plates and Shapes: ASTM 2.01.H When required for anchorage or lateral
A36. bracing to structural steel members, some meth-
ods of manufacturing hollow core slabs preclude
the use of anchors and inserts
I. Grout: 2.01.I Grout strengths of 2000 psi to 3000 psi
1. Cement grout: Grout shall be a mixture of (13.8 - 20.7 MPa) can generally be achieved with
not less than one part portland cement to the proportions noted. Rarely is higher strength
three parts fine sand, and the consistency grout required. Non-shrink grout is not required
shall be such that joints can be completely for satisfactory performance of hollow core slab
filled but without seepage over adjacent systems.
surfaces. Any grout that seeps from the
joint shall be completely removed before
it hardens.
J. Bearing Strips:
1. Random Oriented Fiber Reinforced: 2.01.J.1 Standard guide specifications are not
Shall support a compressive stress of 3000 available for random-oriented, fiber-reinforced
psi (20.7 MPa) with no cracking, splitting pads. Proof testing of a sample from each group
or delaminating in the internal portions of of 200 pads is suggested. Normal design working
the pad. One specimen shall be tested for stresses are 1500 psi (10.3 MPa), so the 3000 psi
each 200 pads used in the project. (20.7 MPa) test load provides a factor of 2 over
design stress. The shape factor for the test speci-
mens should not be less than 2.

8--5
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

2. Plastic: Multi-monomer plastic strips 2.01.J.2 Plastic pads are widely used with hollow
shall be non-leaching and support core slabs. Compression stress in use is not nor-
construction loads with no visible overall mally over a few hundred psi and proof testing is
expansion. not considered necessary. No standard guide
specifications are available.
3. Tempered Hardboard. 2.01.J.3 Hardboard bearing strips should not be
used in areas where undesirable staining is pos-
sible or where bearing strips may be continually
wet.
4. Untempered Hardboard

2.02 Concrete Mixes


A. 28-day compressive strength: Minimum of 2.02.A and B Verify with local manufacturer.
____ psi. 5000 (35 MPa) psi for prestressed products is nor-
B. Release strength: Minimum of ____ psi. mal practice, with release strength of 3000 psi
(20.7 MPa).
C. Use of calcium chloride, chloride ions or oth-
er salts is not permitted.

2.03 Manufacture
A. Manufacturing procedures shall be in com-
pliance with PCI MNL-116.

B. Manufacturing Tolerances: Manufacturing


tolerances shall comply with PCI MNL-116.
C. Openings: Manufacturer shall provide for 2.03.C This paragraph requires other trades to
those openings 10 in (250 mm) round or field drill holes needed for their work, and such
square or larger as shown on the structural trades should be alerted to this requirement
drawings. Other openings shall be located through proper notation in their sections of the
and field drilled or cut by the trade requiring specifications. Some manufacturers prefer to
them after the hollow core slab units have install openings smaller than 10 in (250 mm)
been erected. Openings and/or cutting of pre- which is acceptable if their locations are properly
stressing strand shall be approved by Archi- identified on the contract drawings
tect/Engineer and manufacturer before dril-
ling or cutting.
D. Patching: Will be acceptable providing the
structural adequacy of the hollow core unit is
not impaired.

3. EXECUTION
3.01 Product Deliver, Storage, and Handling
A. Delivery and Handling:

8--6
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

1. Hollow core slab units shall be lifted and


supported during manufacturing, stock-
piling, transporting and erection opera-
tions only at the lifting or supporting
point, or both, as shown on the shop draw-
ings, and with approved lifting devices.
Lifting inserts shall have a minimum safe-
ty factor of 4. Exterior lifting hardware
shall have a minimum safety factor of 5.
2. Transportation, site handling, and erec-
tion shall be performed with acceptable
equipment and methods, and by qualified
personnel.
B. Storage:
1. Store all units off ground.
2. Place stored units so that identification
marks are discernible.
3. Separate stacked members by battens
across full width of each slab unit.
4. Stack so that lifting devices are accessible
and undamaged.
5. Do not use upper member of stacked tier
as storage area for shorter member or
heavy equipment.

3.02 Erection
A. Site Access: The General Contractor shall be
responsible for providing suitable access to
the building, proper drainage and firm level
bearing for the hauling and erection equip-
ment to operate under their own power.
B. Preparation: The General Contractor shall be 3.02.B Construction tolerances for cast-in-place
responsible for: concrete, masonry, etc., should be specified in
those sections of the specifications.
1. Providing true, level bearing surfaces on
all field placed bearing walls and other
field placed supporting members.
2. All pipes, stacks, conduits and other such 3.02.B.2 Should be in Electrical, Mechanical,
items shall be stubbed off at a level lower and Plumbing sections of project specifications.
than the bearing plane of the prestressed
concrete products until after the latter are
set.

8--7
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

C. Installation: Installation of hollow core slab


units shall be performed by the manufacturer
or a competent erector. Members shall be
lifted by means of suitable lifting devices at
points provided by the manufacturer. Bearing
strips shall be set, where required. Temporary
shoring and bracing, if necessary, shall com-
ply with manufacturer’s recommendations.
Grout keys shall be filled.
D. At Slab Ends (where shown on Drawings): 3.02.D If a bearing wall building, special care
Provide suitable end cap or dam in voids as re- must be taken. Delete when end grouting is not re-
quired. quired.
E. For areas where slab voids are to be used as 3.02.E Delete when voids not used for electrical
electrical raceways or mechanical ducts pro- or mechanical.
vide a taped butt joint at end of slabs, making
sure the voids are aligned.
F. Alignment: Members shall be properly 3.02.F Tolerances should comply with industry
aligned and leveled as required by the ap- tolerances published in ”Tolerances for Precast
proved shop drawings. Variations between and Prestressed Concrete”, Prestressed Concrete
adjacent members shall be reasonably leveled Institute, JR307, 1985. 3
out by jacking, loading, or any other feasible
method as recommended by the manufacturer
and acceptable to the Architect/Engineer.

3.03 Field Welding


A. Field welding is to be done by qualified weld-
ers using equipment and materials compatible
with the base material.

3.04 Attachments
A. Subject to approval of the Architect/Engineer,
hollow core slab units may be drilled or ”shot”
provided no contact is made with the pre-
stressing steel. Should spalling occur, it shall
be repaired by the trade doing the drilling or
the shooting.

3.05 Inspection and Acceptance


A. Final observation of erected hollow core slab
units shall be made by Architect/Engineer for
purposes of final payment.

8--8
REFERENCES

1. PCI Design Handbook - Precast and Pre- bers”, ACI Journal, March, 1977, pp
stressed Concrete, Fifth Edition, Precast/ 136-137.
Prestressed Concrete Institute, Chicago, IL 12. Discussion and Closure, “An Assurance
1997. Criterion for Flexural Bond in Preten-
2. ACI Committee 318, “Building Code Re- sioned Hollow Core Units”, ACI Journal,
quirements for Structural Concrete (ACI March, 1977, pp 137-140.
318-95) and Commentary (ACI 13. Zia, Paul and Mostafa, Talat, “Develop-
318R-95)”, American Concrete Institute, ment Length of Prestressing Strands”, PCI
Farmington Hills, MI, 1995. JOURNAL, September-October, 1977, pp
3. PCI Committee on Tolerances, “Toler- 54-65.
ances for Precast and Prestressed Con- 14. Discussion and Closure, “Development
crete”, PCI JOURNAL, Vol. 30, No. 1, Length of Prestressing Strands”, PCI
January-February, 1985, pp. 26-112. JOURNAL, July-August, 1978, pp
4. PCI Technical Activities Council, PCI 97-107.
Committee on Building Code, “PCI Stan- 15. Buckner, C. Dale, “A Review of Strand
dard Design Practice,” PCI JOURNAL, V. Development Length for Pretensioned
42, No. 2, March-April 1997, pp 34-51. Concrete Members”, PCI JOURNAL, V.
5. Zia, Paul, Preston, H. Kent, Scott, Norman 40, No. 2, March-April, 1995, pp 84-105.
L, and Workman, Edwin B., “Estimating 16. Discussion and Closure, “A Review of
Prestress Losses”, Concrete International, Strand Development Length for Preten-
June, 1979, pp 32-38. sioned Concrete Members”, PCI JOUR-
6. Martin, L.D., “A Rational Method for Es- NAL, V. 41, No. 2, March-April, 1996, pp
timating Camber and Deflection of Pre- 112-116.
cast, Prestressed Concrete Members”, PCI 17. Martin, Leslie D. and Korkosz, Walter J.,
JOURNAL, January-February, 1977. “Strength of Prestressed Concrete Mem-
7. ACI Committee 301, “Standard Specifica- bers at Sections Where Strands are not
tions for Structural Concrete (ACI Fully Developed”, PCI JOURNAL, V. 40,
301-96)”, American Concrete Institute, No. 5, September-October, 1995, pp
Farmington Hills, MI, 1996. 58-66.
8. Scott, Norman L., “Performance of Pre- 18. Brooks, Mark D., Gerstle, Kurt H., and
cast, Prestressed Hollow Core Slab with Logan, Donald R., “Effective of Initial
Composite Concrete Topping”, PCI Strand Slip on the Strength of Hollow
JOURNAL, March-April, 1973, pp 64-77. Core Slabs”, PCI JOURNAL, V. 33, No.
9. Martin, Leslie D. and Scott, Norman L., 1, January-February, 1988, pp 90-111.
“Development of Prestressing Strand in 19. LaGue, David J., “Load Distribution Tests
Pretensioned Members”, ACI Journal, Au- on Precast Prestressed Hollow Core Slab
gust 1976, pp 453-456. Construction”, PCI JOURNAL, Novem-
10. Anderson, Arthur R., and Anderson, Rich- ber-December, 1971, pp 10-18.
ard G., “An Assurance Criterion for Flex- 20. Van Acker, A., “Transversal Distribution
ural Bond in Pretensioned Hollow Core of Linear Loadings in Prestressed Hollow
Units”, ACI Journal, August, 1976, pp Core Floors”, BMA/MKT 84/006, Sep-
457-464. tember, 1983.
11. Discussion and Closure, “Development of 21. Johnson, Ted and Ghadiali, Zohair, “Load
Prestressing Strand in Pretensioned Mem- Distribution Test on Precast Hollow Core
Slabs with Openings”, PCI JOURNAL, 31. PCI Manual for Structural Design of Ar-
September-October, 1972, pp 9-19. chitectural Precast Concrete, PCI
MNL-121-77, Prestressed Concrete Insti-
22. Pfeifer, Donald W. and Nelson, Theodore
tute, Chicago, 1977.
A., “Tests to Determine the Lateral Dis-
tribution of Vertical Loads in a Long-Span 32. Uniform Building Code, “Structural Engi-
Hollow Core Floor Assembly”, PCI neering Design Provisions”, V. 2, Interna-
JOURNAL, Vol. 28, No. 6, November-De- tional Conference of Building Officials,
cember, 1983, pp. 42-57. Whittier, CA, 1994.
23. Aswad, Alex and Jacques, Francis J., “Be- 33. The BOCA National Building Code,
havior of Hollow Core Slabs Subject to Thirteenth Edition, Building Officials &
Edge Loads”, PCI JOURNAL, V. 37, No. Code Administrators International, Inc.,
2, March-April, 1992, pp 72-83. Country Club Hills, IL, 1996.
34. Cosper, Steven J., Anderson, Arthur R.,
24. Stanton, John F., “Response of Hollow
Core Slab Floors to Concentrated Loads”, Jobse, Harold J., “Shear Diaphragm Ca-
pacity of Untopped Hollow Core Floor
PCI JOURNAL, V. 37, No. 4, July-Au-
Systems”, Concrete Technology
gust, 1992, pp 98-113.
Associates, Technical Bulletin 80B3,
25. Stanton, John F., “Proposed Design Rules 1981.
for Load Distribution in Precast Concrete 35. Clough, D.P., “Design of Connections for
Decks”, ACI Structural Journal, V. 84, No. Precast Prestressed Concrete Buildings for
5, September-October, 1987, pp 371-382. the Effects of Earthquake”, National Sci-
26. Rosenthal, I., “Full Scale Test of Continu- ence Foundation, 1985.
ous Prestressed Hollow Core Slab”, PCI 36. Moustafa, Saad E., “Effectiveness of
JOURNAL, Vol. 23, No. 3, May-June, Shear-Friction Reinforcement in Shear Di-
1978, pp. 74-81. aphragm Capacity of Hollow Core Slabs”,
27. Harris, Harry G., and Iyengar, Srikanth, PCI JOURNAL, Vol. 26, No. 1, January-
“Full Scale Tests on Horizontal Joints of February, 1981, pp 118-132.
Large Panel Precast Concrete Buildings”, 37. Design and Detailing of Untopped Hollow
PCI JOURNAL, Vol 25, No. 2, March- Core Slab Systems for Diaphragm Shears,
April, 1980, pp. 72-92. Structural Engineer’s Association of Ari-
28. Johal, L.S. and Hanson, N.W., “Design for zona, 1981/82.
Vertical Load on Horizontal Connections 38. PCI Fire Committee, “Design for Fire Re-
in Large Panel Structures”, PCI JOUR- sistance of Precast Prestressed Concreter-
NAL, Vol. 27, No. 1, January-February, Second Edition”, Precast/Prestressed Con-
1982, pp 62-79. crete Institute, Chicago, IL, 1989.
29. PCI Committee on Precast Bearing Wall 39. ASHRAE: ASHRAE Systems Handbook
Buildings, “Considerations for the Design for 1984. American Society of Heating,
of Precast Concrete Bearing Wall Build- Refrigerating & Air Conditioning Engi-
ings to Withstand Abnormal Loads”, PCI neers, Inc., New York, 1984.
JOURNAL, Vol. 21, No. 2., March-April, 40. Blazier, W.E., “Revised Noise Criteria for
1976, pp. 18-51. Design and Rating of HVAC Systems”,
30. Fintel, Mark and Schultz, Donald M., “A paper presented at ASHRAE Semiannual
Philosophy for Structural Integrity of Meeting, Chicago, IL, January 26, 1981.
Large Panel Buildings”, PCI JOURNAL, 41. Berendt, R.D., Winzer, G.E., Burroughs,
Vol. 21, No. 3, May-June, 1976, pp. 46-69. C.B.; “A Guide to Airborne, Impact and
Structureborne Noise Control in Multi- 46. Murray, T.M., “Acceptability Criterion for
family Dwellings”, prepared for Federal Occupant-Induced Floor Vibration”,
Housing Administration, U.S. Govern- Sound and Vibration, November, 1979.
ment Printing Office, Washington, D.C., 47. “Design and Evaluation of Operation
1975. Breakthrough Housing Systems”, NBS
42. Sabine, H.J., Lacher, M.B., Flynn, D.R., Report 10200, Amendment 4, September,
Quindry, T.L.; “Acoustical and Thermal 1970, U.S. Department of Housing and
Performance of Exterior Residential Urban Development, Washington, D.C.
Walls, Doors & Windows”, National Bu- 48. Wiss, J.F. and Parmelee, R.H., “Human
reau of Standards, U.S. Government Print- Perception of Transient Vibrations”, Jour-
ing Office, Washington D.C., 1975. nal of the Structural Division, ASCE, Vol.
100, No. ST4, April, 1974.
43. IITRI; “Compendium of Materials for
49. “Guide to Floor Vibrations”, Steel Struc-
Noise Control”, U.S. Department of
tures for Buildings-Limit States Design
Health, Education & Welfare, U.S. Gov-
CSA S16.1-1974, Appendix G. Canadian
ernment Printing Office, Washington,
Standards Association, Rexdale, Ontario.
D.C., 1980.
50. “Guide for the Evaluation of Human Ex-
44. “Vibrations of Concrete Structures”, Pub- posure to Whole-Body Vibration”, In-
lication SP-60, American Concrete Insti- ternational Standard 2631, International
tute, Detroit, MI. Organization for Standardization, 1974.
45. Galambos, T.V., Gould, P.C., Ravindra, 51. Murray, T.M., “Design to Prevent Floor
M.R., Surgoutomo, H., and Crist, R.A., Vibration”, Engineering Journal, AISC,
“Structural Deflections - A Literature and Third Quarter, 1975.
State-of-the-Art Survey”, Building Sci- 52. Harris, C.M. and Crede, C.E., Shock and
ence Series, Oct., 1973, National Bureau Vibration Handbook, 2nd Edition,
of Standards, Washington, D.C. McGraw-Hill, New York, NY, 1976.
INDEX
A Decibel . . . . . . . . . . . . . . . . . . . . . . 7---1, 7---5, 7---6
Deflection . . . . . . . . . 1---3, 1---4, 3---1, 3---10, 3---12
Acoustical properties . . . . . . . . . . . . . . . . 1---3, 7---1
Deflections . 2---1, 2---5, 2---11 to 2---16, 4---3, 4---7,
Admixtures . . . . . . . . . . . . . . . . . . . 1---1, 1---2, 8---4 4---9
Aggregates . . . . . . . . . . 1---2, 6---1, 6---2, 6---4, 8---4 Design responsibility . . . . . . . . . . . . . . . . 1---5, 4---1
Air entrainment . . . . . . . . . . . . . . . . . . . . . . . . . 1---1 Design strength . . . . . . . . . . . . . 2---2, 2---19, 2---20
Allowable live load . . . . . . . . . . . . . . . . . . . . . . . 1---5 Details - Cantilevers . . . . . . . . . . . . . . . . . . . . 5---20
Details - Concrete beam . . . . . . . . . . . . . . . . . . 5---2
B Details - Miscellaneous . . . . . . . . . . . . . . . . . . 5---23
Details - Steel beams . . . . . . . . . . . . . . . . . . . . 5---15
Bearing strips . . . . . . 3---12, 3---13, 8---5, 8---6, 8---8
Details - Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . 5---9
Bonding agents . . . . . . . . . . . . . . . . . . . . . . . . . 2---16
Development length . . . 2---19 to 2---21, 3---9, 3---12
Boundary element . . . . . . . . . . . 4---4 to 4---8, 4---15
Diaphragm flexibility . . . . . . . . . . . . . . 4---2 to 4---4
Diaphragms . 1---3, 2---15, 2---16, 3---10, 3---14, 4---1,
C to 4---9, 5---1

Camber . . 1---4, 1---14, 2---3, 2---11 to 2---13, 2---14, Differential shrinkage . . . . . . . . . . . . . 2---15, 2---16
2---15, 2---16, 8---3, 8---4 Drag strut . . . . . . . . . . . . . . . . 4---4, 4---5, 4---7, 4---8
Cantilevers . . . . . . . . . . . . . . . . . . . . 3---10 to 3---12 Dy-Core . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---8
Caulking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8---2 Dynaspan . . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---8
Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8---2
Chord . . . . . . . . . . . . . . . . . . . . . . . . 4---4, 4---5, 4---8 E
Collector . . . . . . . . . . . . 4---4, 4---5, 4---7, 4---8, 4---9
Effective resisting section . 3---2, 3---3, 3---6 to 3---8
Composite ties . . . . . . . . . . . . . . . . . . . . . . . . . 2---16
Elematic . . . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---9
Composite topping 1---3, 2---13, 2---15, 2---16, 3---10,
End restraint . . . . . . . 1---3, 6---5, 6---8, 6---12, 6---13
4---9
End slip . . . . . . . . . . . . . . . . . . . . . . . . . 2---20, 2---21
Connections 1---3, 1---5, 3---10, 4---1, 4---2, 4---4, 4---7
to 4---9, 5---1 Equivalent live load . . . . . . . . . . . . . . . . . . . . . . 1---5
Continuity . . . . . . . . . . . . . . 3---10, 6---5, 6---9, 6---10 Equivalent thickness . 1---2, 1---3, 6---1, 6---2, 6---4,
6---14
Contract documents . . . 1---3, 1---5, 4---1, 8---4, 8---6
Equivalent uniform load . . . . . . . . 1---5, 1---6, 3---7
Control joints . . . . . . . . . . . . . . . . . . . . . . . . . . 2---16
Erection drawings . . . . . . . . . . . . . . . . . . 1---5, 8---3
Cracking moment . . . . . . . . . . . . . . . . . . . . . . . 2---19
Extruder . . . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 2---9
Creep . . . . . . . . . . . . . . . . . . . . 2---11 to 2---16, 6---12
Creep losses . . . . . . . . . . . . . . . . . . 2---1, 2---3, 2---5
Curling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2---16
F
Finishes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---4
Fire endurance 3---10, 6---1, 6---2, 6---4, 6---5, 6---7 to
D 6---14
Damping . . . . . . . . . . . . . . . . . . . . 7---2, 7---9, 7---10 Fire rating . . . . . . . . . . . 1---2, 1---3, 1---5, 1---6, 8---3
Debonded strands . . . . . . 2---2, 2---20, 3---10, 3---11 Fixed form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---1
Flanking . . . . . . . . . . . . . . . . . . . . . 7---1, 7---8, 7---9 M
Flexicore . . . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---9 Manufacturing . . 1---1, 1---5, 1---8, 2---2, 2---3, 2---9,
Flexural bond length . . . . . . . . . . . . . . 2---19, 2---20 3---1, 3---10, 8---1, 8---2, 8---5, 8---6
Flexural design . . . . . . . . . . . . . . . . . . . . . . . . . . 2---1
Flexural strength . . 1---6, 2---1, 2---6, 2---9, 2---19 to N
2---21, 4---8
Non-shrink grout . . . . . . . . . . . . . . . . . . . 1---2, 8---5
Normal end slip . . . . . . . . . . . . . . . . . . . . . . . . 2---21
G
Grout . . . . . . . . . . . . . 1---2, 2---16, 3---12, 4---6, 8---5
O
Grout column . . . . . . . . . . . . . . . . . . . . 3---12, 3---13 Openings . 1---3, 1---5, 3---1, 3---8, 3---9, 3---15, 4---9,
8---3, 8---4, 8---6

H P
Headers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3---8 Partially developed strand . . . . . . . . 2---19 to 2---21

Heat transmission 1---3, 6---1, 6---2, 6---4, 6---8, 6---14 PCI Standard Design Practice . . . . . . . . . . . . . 2---1
Production drawings . . . . . . . . . . . . . . . . . . . . . 8---3
Horizontal joints . . . . . . . . . . . . . . . 3---12 to 3---15
Horizontal shear . . . . . . . . . . . . . . 2---16, 4---8, 4---9
Q
Quality assurance . . . . . . . . . . . . . . . . . . 2---15, 8---2
I
Impact insulation . . . . . . . . . . . . . . . . . . . . . . . . 7---3 R
Impact Insulation Class . . . . . 1---3, 7---1, 7---3, 7---4 Release strength . . . . . . . . . . . . . . . . . . . . 2---2, 2---3
Impact noise . . . . . . . . . . . . . . . . . . . . . . . 7---1, 7---3
Inclined shear . . . . . . . . . . . . 2---10, 3---4, 3---6, 3---7 S
Sandwich panels . . . . . . . . . . . . . . . . . . . . . . . . . 1---4
K Seating losses . . . . . . . . . . . . . . . . . . . . . . . . . . . 2---1
Seismic base shear . . . . . . . . . . . . . . . . . . . . . . . 4---2
Keyways . . . 1---2, 1---3, 3---1, 3---10, 4---5, 4---6, 4---8
Service load stresses . . . . . . . . . . . . 2---1, 2---3, 2---5
Shear friction . . . . . . . . . . . . . . . . . . . . 4---5 to 4---8
L Shear reinforcement . . . . . . . . . . 2---9, 2---11, 3---7
Shrinkage . . . . . . . . . . . . . . . . . . 1---2, 2---15, 2---16
Lateral loads . . . . . . . . . . . . . . . . . 4---1, 4---4 to 4---6
Shrinkage cracks . . . . . . . . . . . . . . 1---2, 3---1, 4---11
Lateral-resisting elements . . . . . . . . . . 4---1 to 4---9
Shrinkage losses . . . . . . . . . . . . . . . . . . . . 2---1, 2---3
Load concentrations . . . . . . 2---20, 3---1, 3---3, 3---8
Slab thickness . . . . . . . . . . . . 1---3, 1---5, 1---6, 3---11
Load distribution . . . . . . . . . . . . . . . . . 3---1 to 3---3 Slip form . . . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---2
Load tables . . . . . . . 1---3, 1---5 to 1---7, 2---1, 2---16 Slump . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---2, 2---20
Longitudinal shear . . . . . . . . . . . . . . . . . . 4---6, 4---7 Sound absorption . . . . . . . . . . 7---1, 7---2, 7---5, 7---8
Loss of Prestress . . 2---1, 2---3 to 2---5, 2---11, 2---13 Sound insulation . . . . . . . . . . . . . . . . . . 7---1 to 7---3
Sound transmission . . . . . . . . . . . . . . . . . . . . . . 1---3 Transfer stresses . . . . . . . . . . . . . . . . . . . . 2---1, 2---2
Sound Transmission Class . . . 1---3, 7---1, 7---2, 7---4 Transverse bending . . . . . . . . . . . . . . . . . 3---1, 3---3
Sound transmission loss . . . . . . . . 7---1 to 7---3, 7---8 Transverse reinforcement . . . . . . . . . . . . . . . . . 3---1
Span-depth ratio . . . . . . . . . . . . . . . . . . . . . . . . 3---3
Spancrete . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---10
U
Spray-applied coatings . . . . . . . . . . . . . . 6---9, 6---14
Ultra-Span . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---11
Steel relaxation . . . . . . . . . . . . . . . . . . . . . 2---1, 2---4
Unit weight . . . . . . . . . . . . . . . . . . . . . . . 1---2, 1---14
Strain compatibility 2---6, 2---7, 2---9, 2---20, 2---21,
3---11
Stress-strain diagram . . . . . . . . . . . . . . . . 2---7, 2---8 V
Structural end point . . . . . . . . . . . . . . . . . . . . . . 6---5
Vibration isolators . . . . . . . . . . . . . . . . . 7---2, 7---10
Structural integrity . . 3---10, 3---14, 4---1, 4---4, 4---5

W
T
Wall panels . . . . . . . . . . . . . . . . . . . . . . . . 1---1, 1---4
Tolerances . . . 1---4, 1---6, 1---14, 1---15, 8---6 to 8---8
Water-cement ratio . . . . . . . . . . . . . . . . . . . . . 2---20
Topping 1---3, 1---4, 2---13, 2---15, 2---16, 3---10, 4---5
4---9, 6---2, 6---4, 6---11, 8---1 to 8---4 Web shear . . . . . . . . . . . . . . . . . . . 2---18, 3---4, 3---7
Torsion . . . . . . . . . . . . . . . . . . . . . . . 3---1, 3---2, 3---8 Weep holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---4
Transfer length . . . . . . 2---10, 2---19 to 2---21, 3---12 Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---2, 1---6

You might also like