You are on page 1of 54

POWER SYSTEM PROTECTION COORDINATION

REPORT

Client:

M/s. LBR Hotels & Hospitality Pvt Ltd

Project:

M/s. TAJ GATEWAY, OMR Chennai

Project Management Consultant:

M/s. Jones Lang Lasalle

Service Consultant:

M/s. SPECTRAL Services Consultant Pvt Ltd

Compiled by :

C B Ramesh
13 Nana Street,T Nagar,
Chennai,600017
Mob no:98843 70326
email:ife@vsnl.com
website:www.ifepwrana.com

Sl.No
1
2
3
4
5
6
7
8
9
10
11

Contents

Descriptiion
Executive Summary
Reference Documents
Device Details
Single Line Diagram
Short Circuit Report
Transformer Relay Setting Calculations
Setting Details for 11 kV Panels
Setting Details for LT Panels
Setting Details for DG AMF Panels
Time Current Characteristic Curves
Comments

Page No
3
4
5
6
8
24
25
31
44
49
54

Introduction

Executive Summary

We were requested to prepare a Protection Co-Ordination Report for 11//0.415 kV Electrical Distribution, for
Taj Gateway,Chennai.
This report includes calculation results of the study 11/0.433 kV Switchgear.
The system data for calculation are based on thedata provided by the Project Management Consultant
M/sJones Lang Lasalle,Chennai.
The most important tool for documentation of over current protection co-ordination is Paladin Design Base 5.
Typical grading paths have been chosen in a single line and in a current/time diagram the selectivity of the
characteristic curves of the devices are shown.

2 Power System Data


The single line diagrams, and documents as listed in the report were used as data input for this network
calculation study.

2.3 Infeed Data

The Source fault MVA at the point of supply was not available, therefore short circuit currents at various switch
Board Busbars were calculated with assumed maximum source fault as 500 MVA sec and minimum source fault
of 250 MVAsec.

3.0 Protection Coordination


The short circuit currents at various busbars are calculated based on the above assumptions.
Based on the short circuit calculations protection coordination study was carried out for this Project
Short circuit currents calculated for each of the bus bar are tabulated in the report , and also indicated in the
SLD.Selectivity of relays have been worked out for 11/0.415 kV Switchgear Panel and indicated in the setting
sheets

4.0 Comments
Certain devices in the system do not satisfy the interrupting current requirement.Specific details are given the
comments section.

5.0 Conclusion

Setting sketches for the over current devices have been performed for the 11/0.415 kV network The selectivity
of the protection settings for characteristic feeders was verified with the protection grading diagrams prepared
with software Paladin Design base5 Generally, attention was given to provide the largest possible safety
clearance between the individual protective devices.Our observations and recommendations are given in the
last page for implementation.

Reference Documents / Drawings


Sl.No

1
2
3
4
5
6
7
8
9
10

Drawing Title

Main Single Line Diagram


DG set Details
HT Panel
11 kV Indoor 3 Unit VCB Panel
11 kV Indoor RMG Panel
11 kV Outdoor Kiosk
Bill of material for DG1 AMF Panel
Bill of material for DG1 AMF Panel
Bill of material for DG1 AMF Panel
Transformer Data sheets

File reference
Main SLD
Taj Gateway-1010kVA-04.04.12.rar
HT panel.rar
811.pdf
811A.pdf
811B.pdf
18-BOM1.dwg
18-BOM2.dwg
18-BOM3.dwg
Transformer Technical Submittal Approval.PDF

Drawing No
EL06 Sh 1 to 4
IS 466
IS 467
IS 468
1112-GCP-403-01
1112-GCP-403-01
1112-GCP-403-01
-

Device Details
2-Winding Transformers
Details of Equipment
Transformers 1
Transformers 2

kVA rating High


Voltage
side
1000
11000V
1000
11000V

Low voltage
side
433 V
433 V

Percentage Low
High
Impedance winding winding

Grounding Vector
Mode
Group

5.11
5.11

Star
Star

Delta
Delta

Direct
Direct

Sub
Transient
Reactance X
" dv
in %
13
13

Transient
Reactanc
e X'dv in
%

Synchrono Power
us
Factor
Reactance
Xd in %

DY11
DY11

Diesel Generating sets


Details of Equipment

Rating in
kVA

Groundi Operating
ng
voltage

DG Set 1
DG Set 2

1010
1010

Solid
Solid

415 V
415 V

15
15

100
100

80%
80%

RPM

1500
1500

Type of Cooling

Supply Variation on 66
kV side

AN
AN

-20% to +5% tapping


-20% to +5% tapping

Single Line Diagram

GRID

GRID

SOURCE 1

SOURCE 2

5
RMU EB OUTDOOR
RP1
50
51

cab:ic
RP2
50
51

cab:ic1
RP3
50
51

11kV _3PNL
RP5

RP4

50
51

50
51

DG1

busduct_dg2

busduct_tr2
EB_IC2

Main LT Panel RHS


DGAUX2

KITCH_U

SPARE2

UPS2

SPARE3

SPARE4

cab: RM2
191

226

Cab:DGAUX2

Cab:RM1_1F

Cab:RM2_1F
229

166

169

199

VENT.PNL2
272

142

145

148

154

219

175

178

Cab:RM1_2F

SUB LIGHTING PNL


181

216

160

LIFT MAIN PNL

M.HVAC PNL

151

218

APFC PNL2

LAUNDRY PNL

Cab:RM1_3F

KITCHEN PNL UB

VENT.PNL

217

FL PNL 2nd

252

184

261

136

TERR.VENT.PNL

Cab:RM2_2F
247

187

RM1

UPS PNL

KITCHEN MAIN PNL G

FL PNL 1st

241

250

139

VENT.PNL1

APFC PNL 1

Plumb. MAIN PNL

236

202

239

163

RM2

cab:APFC1

SUBLIGHT FFRHS

228

Cab:lift

HVAC2

Cab:ups2

Cab:Plumb

Cab:RM1

APFC2

Cab:Kitchen U

Cab:kitchen G

HVAC_P2

Cab:firefight2

cab:ventpnl1

RM2

HVAC1

CAB:SLP

cab:terventpnl

RM1

VENT

cab:vpnl_m

Cab:SUBpwr

HVAC_P1

Cab:vpnl1

LIFT

Cab:Laundry

PLUMB

Cab:main hvac 2

KITCHEN

LAUNDRY VENT1

CAB:APFC2

VENT2

cab:hvacpump2

T_VENT

Cab:main hvac 1

PWRSB

cab:hvacpump1

UPS_LHS

Cab:ups1

Cab:firefight1

DGAUX

Cab:DGaux1

FF_LHS

APFC1

193

Main LT Panel LHS


Spare1

DG_IC2

BC

EB_IC1

240

busduct_tr1

busduct_dg1
DG_IC1

RP7

TR2

Cab:RM1_4F

FL PNL 3rd

263

SUB POWER PNL

Cab:RM2_3F

251

TR1

DG2

258

Cab:RM2_4F

262

RP6

GEN

cab:tr2_HV

cab:tr1_HV

GEN

269

FL PNL 4 th
161

279

DG AUX PNL

FIRE FIGHT PNL


M.HVAC PUMP PNL

282
294

AHU PNL UB

265
Cab:FL_AHUPNL

Cab:pdb

cab:ahu_mz

cab:ahu_UB
164

291

288

REV. DATE

ECO#

SINGLE LINE DIAGRAM FOR COORDINATION


STUDY
DRAWN BY/DATE:

AHU PNL MZ
PDB

AHU_PNL_FLOOR

DESCRIPTION

DWN APP

TH IS DRAWING IS PROPRIE TARY INFORM AT ION

DWG No .:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PAR T No.:
DWG SIZE:

RE V.

Short Circuit Current Report

SOURCE 1
Sym : 26243.19A

GRID

SOURCE 2
Sym : 26243.19A

GRID

RMU EB OUTDOOR
Sym : 26229.71A
RP1
50
51

cab:ic
RP2
50
51

cab:ic1
RP3
50
51

11kV _3PNL
Sym : 25326.4A
RP5

RP4

50
51

50
51

DG1
Sym : 11644.75A

RP6

DG_IC2

Main LT Panel RHS


Sym : 24679.87A
DGAUX2

KITCH_U

SPARE2

UPS2

SPARE3

SPARE4

cab: RM2
191

226

Cab:DGAUX2

Cab:RM1_1F

Cab:RM2_1F
229

166

169

199

VENT.PNL2
Sym : 13754.57A
272

142

145

148

154

219

175

178

Cab:RM1_2F

SUB LIGHTING PNL


Sym : 18234.23A
181

216

KITCHEN MAIN PNL G


Sym : 20250.64A

160

LIFT MAIN PNL


Sym : 13754.57A

M.HVAC PNL
Sym : 22260.61A

151

218

APFC PNL2
Sym : 22265.02A

LAUNDRY PNL
Sym : 13756.75A

VENT.PNL
Sym : 9103.4A

217

161

M.HVAC PUMP PNL


Sym : 19523.23A

FIRE FIGHT PNL


Sym : 19523.23A

291

Cab:RM2_4F
269

265
Cab:FL_AHUPNL

282

AHU PNL MZ
Sym : 13684.14A

FL PNL 3rd
Sym : 19649.61A

263

294

AHU PNL UB
Sym : 7605.53A

Cab:RM1_4F

Cab:RM2_3F
258

FL PNL 4 th
Sym : 19649.61A

Cab:pdb

cab:ahu_mz

cab:ahu_UB
164

279

FL PNL 2nd
Sym : 19649.61A

252

184

SUB POWER PNL


Sym : 18230.67A
DG AUX PNL
Sym : 18230.67A

Cab:RM1_3F

KITCHEN PNL UB
Sym : 20254.47A

261

136

TERR.VENT.PNL
Sym : 13754.57A

Cab:RM2_2F
247

187

RM1
Sym : 21555.39A

UPS PNL
Sym : 11185.06A

FL PNL 1st
Sym : 19649.61A

241

250

139

VENT.PNL1
Sym : 9103.4A

APFC PNL 1
Sym : 22260.61A

Plumb. MAIN PNL


Sym : 18230.67A

236

202

239

163

RM2
Sym : 21559.6A

cab:APFC1

SUBLIGHT FFRHS

193

Cab:lift

HVAC2

Cab:ups2

Cab:Plumb

Cab:RM1

APFC2

Cab:Kitchen U

Cab:kitchen G

HVAC_P2

Cab:firefight2

cab:ventpnl1

RM2

HVAC1

CAB:SLP

cab:terventpnl

RM1

VENT

cab:vpnl_m

Cab:SUBpwr

HVAC_P1

Cab:vpnl1

LIFT

Cab:Laundry

PLUMB

Cab:main hvac 2

KITCHEN

CAB:APFC2

VENT2

cab:hvacpump2

T_VENT

Cab:main hvac 1

PWRSB

cab:hvacpump1

UPS_LHS

Cab:ups1

Cab:firefight1

DGAUX

LAUNDRY VENT1

228

BC

EB_IC2

APFC1

240

busduct_tr2

EB_IC1

251

DG_IC1

busduct_dg2

busduct_tr1

busduct_dg1

FF_LHS

RP7

TR2

Cab:DGaux1

Spare1

DG2
Sym : 11644.75A

262

TR1

Main LT Panel LHS


Sym : 24674.86A

GEN

cab:tr2_HV

cab:tr1_HV

GEN

288

REV. DATE

ECO#

Short Circuit Currents at Busbars for source fault


level of 500 MVA (EB feeding)
DRAWN BY/DATE:

PDB
Sym : 3814.16A

AHU_PNL_FLOOR
Sym : 3814.16A

DESCRIPTION

DWN APP

TH IS DRAWING IS PROPRIE TARY INFORM AT ION

DWG No .:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PAR T No.:
DWG SIZE:

RE V.

Short Circuit Detailed Report

EB Feeding- Source fault 500 MVA

3P Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
68832
26243
26243
26243
26243
26243
26243
11000
68770
26230
26230
26230
26230
26230
26230
11000
68709
26216
26216
26216
26216
26216
26216
11000
63130
25326
25326
25326
25326
25326
25326
433
54274
24680
24680
24680
24680
24680
24680
433
54250
24675
24675
24675
24675
24675
24675
433
44834
22265
22265
22265
22265
22265
22265
433
44818
22261
22261
22261
22261
22261
22261
433
44818
22261
22261
22261
22261
22261
22261
433
42573
21560
21560
21560
21560
21560
21560
433
42558
21555
21555
21555
21555
21555
21555
433
38668
20254
20254
20254
20254
20254
20254
433
38655
20251
20251
20251
20251
20251
20251
433
35895
19650
19650
19650
19650
19650
19650
433
35895
19650
19650
19650
19650
19650
19650
433
35895
19650
19650
19650
19650
19650
19650
433
35895
19650
19650
19650
19650
19650
19650
433
34731
19523
19523
19523
19523
19523
19523
433
34731
19523
19523
19523
19523
19523
19523
433
29702
18234
18234
18234
18234
18234
18234
433
29695
18231
18231
18231
18231
18231
18231
433
29695
18231
18231
18231
18231
18231
18231
433
29695
18231
18231
18231
18231
18231
18231
433
20632
13757
13757
13757
13757
13757
13757
433
20629
13755
13755
13755
13755
13755
13755
433
20629
13755
13755
13755
13755
13755
13755
433
20629
13755
13755
13755
13755
13755
13755
433
20486
13684
13684
13684
13684
13684
13684
433
16088
11185
11185
11185
11185
11185
11185
433
12933
9103
9103
9103
9103
9103
9103
433
12933
9103
9103
9103
9103
9103
9103
433
10788
7606
7606
7606
7606
7606
7606
433
5394
3814
3814
3814
3814
3814
3814
433
5394
3814
3814
3814
3814
3814
3814

Short Circuit Detailed Report

EB Feeding- Source fault 500 MVA (Contd)

LL Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
68832
26243
26243
26243
26243
26243
26243
11000
68761
26228
26228
26228
26228
26228
26228
11000
68690
26212
26212
26212
26212
26212
26212
11000
62327
25187
25187
25187
25187
25187
25187
433
47198
21479
21479
21479
21479
21479
21479
433
47177
21475
21475
21475
21475
21475
21475
433
38960
19367
19367
19367
19367
19367
19367
433
38946
19363
19363
19363
19363
19363
19363
433
38946
19363
19363
19363
19363
19363
19363
433
36989
18750
18750
18750
18750
18750
18750
433
36976
18746
18746
18746
18746
18746
18746
433
33586
17610
17610
17610
17610
17610
17610
433
33575
17607
17607
17607
17607
17607
17607
433
31171
17081
17081
17081
17081
17081
17081
433
31171
17081
17081
17081
17081
17081
17081
433
31171
17081
17081
17081
17081
17081
17081
433
31171
17081
17081
17081
17081
17081
17081
433
30157
16970
16970
16970
16970
16970
16970
433
30157
16970
16970
16970
16970
16970
16970
433
25781
15842
15842
15842
15842
15842
15842
433
25775
15839
15839
15839
15839
15839
15839
433
25775
15839
15839
15839
15839
15839
15839
433
25775
15839
15839
15839
15839
15839
15839
433
17897
11939
11939
11939
11939
11939
11939
433
17894
11937
11937
11937
11937
11937
11937
433
17894
11937
11937
11937
11937
11937
11937
433
17894
11937
11937
11937
11937
11937
11937
433
17769
11876
11876
11876
11876
11876
11876
433
13950
9701
9701
9701
9701
9701
9701
433
11211
7892
7892
7892
7892
7892
7892
433
11211
7892
7892
7892
7892
7892
7892
433
9350
6592
6592
6592
6592
6592
6592
433
4672
3304
3304
3304
3304
3304
3304
433
4672
3304
3304
3304
3304
3304
3304

Short Circuit Detailed Report

EB Feeding- Source fault 500 MVA (Contd)

LG Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FIRE FIGHT PNL
M.HVAC PUMP PNL
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
68832
26243
26243
26243
26243
26243
26243
11000
68770
26230
26230
26230
26230
26230
26230
11000
68709
26216
26216
26216
26216
26216
26216
11000
60739
24716
24716
24716
24716
24716
24716
433
54827
25150
25150
25150
25150
25150
25150
433
54810
25147
25147
25147
25147
25147
25147
433
39267
20277
20277
20277
20277
20277
20277
433
39259
20275
20275
20275
20275
20275
20275
433
39259
20275
20275
20275
20275
20275
20275
433
36011
19030
19030
19030
19030
19030
19030
433
36004
19028
19028
19028
19028
19028
19028
433
30886
16921
16921
16921
16921
16921
16921
433
30881
16919
16919
16919
16919
16919
16919
433
29127
16550
16550
16550
16550
16550
16550
433
29127
16550
16550
16550
16550
16550
16550
433
29045
16349
16349
16349
16349
16349
16349
433
29045
16349
16349
16349
16349
16349
16349
433
29045
16349
16349
16349
16349
16349
16349
433
29045
16349
16349
16349
16349
16349
16349
433
26606
15932
15932
15932
15932
15932
15932
433
26602
15930
15930
15930
15930
15930
15930
433
26602
15930
15930
15930
15930
15930
15930
433
26602
15930
15930
15930
15930
15930
15930
433
17685
11351
11351
11351
11351
11351
11351
433
17683
11350
11350
11350
11350
11350
11350
433
17683
11350
11350
11350
11350
11350
11350
433
17683
11350
11350
11350
11350
11350
11350
433
17577
11307
11307
11307
11307
11307
11307
433
15228
10223
10223
10223
10223
10223
10223
433
13235
9113
9113
9113
9113
9113
9113
433
13235
9113
9113
9113
9113
9113
9113
433
10548
7287
7287
7287
7287
7287
7287
433
6503
4594
4594
4594
4594
4594
4594
433
6503
4594
4594
4594
4594
4594
4594

Short Circuit Detailed Report

EB Feeding- Source fault 500 MVA (Contd)

LLG Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
71359
27206
27206
27206
27206
27206
27206
11000
71293
27193
27193
27193
27193
27193
27193
11000
71228
27179
27179
27179
27179
27179
27179
11000
64670
26107
26107
26107
26107
26107
26107
433
54874
25065
25065
25065
25065
25065
25065
433
54850
25059
25059
25059
25059
25059
25059
433
43634
22015
22015
22015
22015
22015
22015
433
43618
22010
22010
22010
22010
22010
22010
433
43618
22010
22010
22010
22010
22010
22010
433
41081
21144
21144
21144
21144
21144
21144
433
41067
21140
21140
21140
21140
21140
21140
433
36809
19580
19580
19580
19580
19580
19580
433
36797
19576
19576
19576
19576
19576
19576
433
34001
18791
18791
18791
18791
18791
18791
433
34001
18791
18791
18791
18791
18791
18791
433
34001
18791
18791
18791
18791
18791
18791
433
34001
18791
18791
18791
18791
18791
18791
433
32843
18534
18534
18534
18534
18534
18534
433
32843
18534
18534
18534
18534
18534
18534
433
29265
17815
17815
17815
17815
17815
17815
433
29259
17812
17812
17812
17812
17812
17812
433
29259
17812
17812
17812
17812
17812
17812
433
29259
17812
17812
17812
17812
17812
17812
433
20615
13601
13601
13601
13601
13601
13601
433
20612
13599
13599
13599
13599
13599
13599
433
20612
13599
13599
13599
13599
13599
13599
433
20612
13599
13599
13599
13599
13599
13599
433
20483
13539
13539
13539
13539
13539
13539
433
17295
11898
11898
11898
11898
11898
11898
433
14791
10336
10336
10336
10336
10336
10336
433
14791
10336
10336
10336
10336
10336
10336
433
12050
8450
8450
8450
8450
8450
8450
433
7210
5096
5096
5096
5096
5096
5096
433
7210
5096
5096
5096
5096
5096
5096

SOURCE 1
Sym : 13121.6A

GRID

SOURCE 2
Sym : 13121.6A

GRID

RMU EB OUTDOOR
Sym : 13118.23A
RP1
50
51

cab:ic
RP2
50
51

cab:ic1
RP3
50
51

11kV _3PNL
Sym : 12890.42A
RP5

RP4

50
51

50
51

DG1
Sym : 11644.75A

RP6

DG_IC2

Main LT Panel RHS


Sym : 23806.36A
DGAUX2

KITCH_U

SPARE2

UPS2

SPARE3

SPARE4

cab: RM2
191

226

Cab:DGAUX2

Cab:RM1_1F

Cab:RM2_1F
229

166

169

199

VENT.PNL2
Sym : 13536.11A

APFC PNL 1
Sym : 21557.14A

VENT.PNL1
Sym : 9035.38A

272

142

145

148

154

219

175

178

Cab:RM1_2F

SUB LIGHTING PNL


Sym : 17803.27A
181

216

KITCHEN MAIN PNL G


Sym : 19674.48A

160

LIFT MAIN PNL


Sym : 13536.11A

M.HVAC PNL
Sym : 21557.14A

151

218

APFC PNL2
Sym : 21561.26A

LAUNDRY PNL
Sym : 13538.21A

VENT.PNL
Sym : 9035.38A

217

161

M.HVAC PUMP PNL


Sym : 19000.97A

FIRE FIGHT PNL


Sym : 19000.97A

291

Cab:RM2_4F
269

265
Cab:FL_AHUPNL

282

AHU PNL MZ
Sym : 13468.87A

FL PNL 3rd
Sym : 19114.68A

263

294

AHU PNL UB
Sym : 7560.39A

Cab:RM1_4F

Cab:RM2_3F
258

FL PNL 4 th
Sym : 19114.68A

Cab:pdb

cab:ahu_mz

cab:ahu_UB
164

279

FL PNL 2nd
Sym : 19114.68A

252

184

SUB POWER PNL


Sym : 17799.9A
DG AUX PNL
Sym : 17799.9A

Cab:RM1_3F

KITCHEN PNL UB
Sym : 19678.07A

261

136

TERR.VENT.PNL
Sym : 13536.11A

Cab:RM2_2F
247

187

RM1
Sym : 20897.97A

UPS PNL
Sym : 11063.55A

FL PNL 1st
Sym : 19114.68A

241

250

139

Plumb. MAIN PNL


Sym : 17799.9A

236

202

239

163

RM2
Sym : 20901.91A

cab:APFC1

SUBLIGHT FFRHS

193

Cab:lift

HVAC2

Cab:ups2

Cab:Plumb

Cab:RM1

APFC2

Cab:Kitchen U

Cab:kitchen G

HVAC_P2

Cab:firefight2

cab:ventpnl1

RM2

HVAC1

CAB:SLP

cab:terventpnl

RM1

VENT

cab:vpnl_m

Cab:SUBpwr

HVAC_P1

Cab:vpnl1

LIFT

Cab:Laundry

PLUMB

Cab:main hvac 2

KITCHEN

CAB:APFC2

VENT2

cab:hvacpump2

T_VENT

Cab:main hvac 1

PWRSB

cab:hvacpump1

UPS_LHS

Cab:ups1

Cab:firefight1

DGAUX

LAUNDRY VENT1

228

BC

EB_IC2

APFC1

240

busduct_tr2

EB_IC1

251

DG_IC1

busduct_dg2

busduct_tr1

busduct_dg1

FF_LHS

RP7

TR2

Cab:DGaux1

Spare1

DG2
Sym : 11644.75A

262

TR1

Main LT Panel LHS


Sym : 23801.72A

GEN

cab:tr2_HV

cab:tr1_HV

GEN

288

REV. DATE

ECO#

Short Circuit Currents at Busbars for source fault


level of 250 MVA (EB feeding)
DRAWN BY/DATE:

PDB
Sym : 3807.79A

AHU_PNL_FLOOR
Sym : 3807.79A

DESCRIPTION

DWN APP

TH IS DRAWING IS PROPRIE TARY INFORM AT ION

DWG No .:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PAR T No.:
DWG SIZE:

RE V.

Short Circuit Detailed Report

EB Feeding- Source fault 250 MVA

3P Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
34416
13122
13122
13122
13122
13122
13122
11000
34401
13118
13118
13118
13118
13118
13118
11000
34385
13115
13115
13115
13115
13115
13115
11000
32933
12890
12890
12890
12890
12890
12890
433
52648
23806
23806
23806
23806
23806
23806
433
52625
23802
23802
23802
23802
23802
23802
433
43724
21561
21561
21561
21561
21561
21561
433
43708
21557
21557
21557
21557
21557
21557
433
43708
21557
21557
21557
21557
21557
21557
433
41572
20902
20902
20902
20902
20902
20902
433
41557
20898
20898
20898
20898
20898
20898
433
37841
19678
19678
19678
19678
19678
19678
433
37829
19674
19674
19674
19674
19674
19674
433
35182
19115
19115
19115
19115
19115
19115
433
35182
19115
19115
19115
19115
19115
19115
433
35182
19115
19115
19115
19115
19115
19115
433
35182
19115
19115
19115
19115
19115
19115
433
34063
19001
19001
19001
19001
19001
19001
433
34063
19001
19001
19001
19001
19001
19001
433
29209
17803
17803
17803
17803
17803
17803
433
29202
17800
17800
17800
17800
17800
17800
433
29202
17800
17800
17800
17800
17800
17800
433
29202
17800
17800
17800
17800
17800
17800
433
20390
13538
13538
13538
13538
13538
13538
433
20387
13536
13536
13536
13536
13536
13536
433
20387
13536
13536
13536
13536
13536
13536
433
20387
13536
13536
13536
13536
13536
13536
433
20247
13469
13469
13469
13469
13469
13469
433
15943
11064
11064
11064
11064
11064
11064
433
12845
9035
9035
9035
9035
9035
9035
433
12845
9035
9035
9035
9035
9035
9035
433
10729
7560
7560
7560
7560
7560
7560
433
5385
3808
3808
3808
3808
3808
3808
433
5385
3808
3808
3808
3808
3808
3808

Short Circuit Detailed Report

EB Feeding- Source fault 250 MVA (Contd)

LL Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
34416
13122
13122
13122
13122
13122
13122
11000
34398
13118
13118
13118
13118
13118
13118
11000
34380
13114
13114
13114
13114
13114
13114
11000
32714
12855
12855
12855
12855
12855
12855
433
45963
20814
20814
20814
20814
20814
20814
433
45943
20810
20810
20810
20810
20810
20810
433
38119
18832
18832
18832
18832
18832
18832
433
38105
18829
18829
18829
18829
18829
18829
433
38105
18829
18829
18829
18829
18829
18829
433
36231
18251
18251
18251
18251
18251
18251
433
36218
18247
18247
18247
18247
18247
18247
433
32960
17173
17173
17173
17173
17173
17173
433
32950
17170
17170
17170
17170
17170
17170
433
30632
16676
16676
16676
16676
16676
16676
433
30632
16676
16676
16676
16676
16676
16676
433
30632
16676
16676
16676
16676
16676
16676
433
30632
16676
16676
16676
16676
16676
16676
433
29652
16574
16574
16574
16574
16574
16574
433
29652
16574
16574
16574
16574
16574
16574
433
25409
15517
15517
15517
15517
15517
15517
433
25403
15514
15514
15514
15514
15514
15514
433
25403
15514
15514
15514
15514
15514
15514
433
25403
15514
15514
15514
15514
15514
15514
433
17714
11775
11775
11775
11775
11775
11775
433
17711
11773
11773
11773
11773
11773
11773
433
17711
11773
11773
11773
11773
11773
11773
433
17711
11773
11773
11773
11773
11773
11773
433
17589
11714
11714
11714
11714
11714
11714
433
13841
9609
9609
9609
9609
9609
9609
433
11145
7841
7841
7841
7841
7841
7841
433
11145
7841
7841
7841
7841
7841
7841
433
9305
6558
6558
6558
6558
6558
6558
433
4666
3299
3299
3299
3299
3299
3299
433
4666
3299
3299
3299
3299
3299
3299

Short Circuit Detailed Report

EB Feeding- Source fault 250 MVA (Contd)

LG Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FIRE FIGHT PNL
M.HVAC PUMP PNL
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
34416
13122
13122
13122
13122
13122
13122
11000
34401
13118
13118
13118
13118
13118
13118
11000
34385
13115
13115
13115
13115
13115
13115
11000
32272
12732
12732
12732
12732
12732
12732
433
53857
24619
24619
24619
24619
24619
24619
433
53841
24616
24616
24616
24616
24616
24616
433
38770
19938
19938
19938
19938
19938
19938
433
38762
19936
19936
19936
19936
19936
19936
433
38762
19936
19936
19936
19936
19936
19936
433
35593
18733
18733
18733
18733
18733
18733
433
35586
18731
18731
18731
18731
18731
18731
433
30578
16689
16689
16689
16689
16689
16689
433
30573
16687
16687
16687
16687
16687
16687
433
28853
16332
16332
16332
16332
16332
16332
433
28853
16332
16332
16332
16332
16332
16332
433
28772
16135
16135
16135
16135
16135
16135
433
28772
16135
16135
16135
16135
16135
16135
433
28772
16135
16135
16135
16135
16135
16135
433
28772
16135
16135
16135
16135
16135
16135
433
26377
15736
15736
15736
15736
15736
15736
433
26373
15734
15734
15734
15734
15734
15734
433
26373
15734
15734
15734
15734
15734
15734
433
26373
15734
15734
15734
15734
15734
15734
433
17582
11258
11258
11258
11258
11258
11258
433
17580
11257
11257
11257
11257
11257
11257
433
17580
11257
11257
11257
11257
11257
11257
433
17580
11257
11257
11257
11257
11257
11257
433
17476
11216
11216
11216
11216
11216
11216
433
15152
10155
10155
10155
10155
10155
10155
433
13177
9063
9063
9063
9063
9063
9063
433
13177
9063
9063
9063
9063
9063
9063
433
10511
7256
7256
7256
7256
7256
7256
433
6492
4586
4586
4586
4586
4586
4586
433
6492
4586
4586
4586
4586
4586
4586

Short Circuit Detailed Report

EB Feeding- Source fault 250 MVA (Contd)

LLG Fault - IEC60909 Method


Bus Name

SOURCE 1
RMU EB OUTDOOR
SOURCE 2
11kV _3PNL
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
11000
35679
13603
13603
13603
13603
13603
13603
11000
35663
13600
13600
13600
13600
13600
13600
11000
35647
13596
13596
13596
13596
13596
13596
11000
33932
13327
13327
13327
13327
13327
13327
433
53628
24387
24387
24387
24387
24387
24387
433
53605
24382
24382
24382
24382
24382
24382
433
42813
21485
21485
21485
21485
21485
21485
433
42798
21480
21480
21480
21480
21480
21480
433
42798
21480
21480
21480
21480
21480
21480
433
40346
20653
20653
20653
20653
20653
20653
433
40332
20648
20648
20648
20648
20648
20648
433
36210
19155
19155
19155
19155
19155
19155
433
36199
19152
19152
19152
19152
19152
19152
433
33498
18406
18406
18406
18406
18406
18406
433
33498
18406
18406
18406
18406
18406
18406
433
33498
18406
18406
18406
18406
18406
18406
433
33498
18406
18406
18406
18406
18406
18406
433
32383
18165
18165
18165
18165
18165
18165
433
32383
18165
18165
18165
18165
18165
18165
433
28803
17430
17430
17430
17430
17430
17430
433
28797
17428
17428
17428
17428
17428
17428
433
28797
17428
17428
17428
17428
17428
17428
433
28797
17428
17428
17428
17428
17428
17428
433
20378
13395
13395
13395
13395
13395
13395
433
20376
13393
13393
13393
13393
13393
13393
433
20376
13393
13393
13393
13393
13393
13393
433
20376
13393
13393
13393
13393
13393
13393
433
20249
13336
13336
13336
13336
13336
13336
433
17140
11768
11768
11768
11768
11768
11768
433
14687
10253
10253
10253
10253
10253
10253
433
14687
10253
10253
10253
10253
10253
10253
433
11980
8395
8395
8395
8395
8395
8395
433
7192
5083
5083
5083
5083
5083
5083
433
7192
5083
5083
5083
5083
5083
5083

GRID

GRID

SOURCE 1

SOURCE 2

5
RMU EB OUTDOOR
RP1
50
51

cab:ic
RP2
50
51

cab:ic1
RP3
50
51

11kV _3PNL
RP5

RP4

50
51

50
51

DG1
Sym : 11644.74A

RP6

DG_IC2

Main LT Panel RHS


Sym : 11309.79A
DGAUX2

KITCH_U

SPARE2

UPS2

SPARE3

SPARE4

cab: RM2
191

226

Cab:DGAUX2

Cab:RM1_1F

Cab:RM2_1F
229

166

169

199

VENT.PNL2
Sym : 8837.57A

APFC PNL 1
Sym : 10826.23A

VENT.PNL1
Sym : 7137.96A

272

142

145

148

154

219

175

178

Cab:RM1_2F

SUB LIGHTING PNL


Sym : 10074.99A
181

216

KITCHEN MAIN PNL G


Sym : 10377.52A

160

LIFT MAIN PNL


Sym : 8837.57A

M.HVAC PNL
Sym : 10826.23A

151

218

APFC PNL2
Sym : 10830.12A

LAUNDRY PNL
Sym : 8839.93A

VENT.PNL
Sym : 7137.96A

217

161

M.HVAC PUMP PNL


Sym : 10268.57A

FIRE FIGHT PNL


Sym : 10268.57A

291

Cab:RM2_4F
269

265
Cab:FL_AHUPNL

282

AHU PNL MZ
Sym : 8819.07A

FL PNL 3rd
Sym : 10267.36A

263

294

AHU PNL UB
Sym : 6259.77A

Cab:RM1_4F

Cab:RM2_3F
258

FL PNL 4 th
Sym : 10267.36A

Cab:pdb

cab:ahu_mz

cab:ahu_UB
164

279

FL PNL 2nd
Sym : 10267.36A

252

184

SUB POWER PNL


Sym : 10071.74A
DG AUX PNL
Sym : 10071.74A

Cab:RM1_3F

KITCHEN PNL UB
Sym : 10381.07A

261

136

TERR.VENT.PNL
Sym : 8837.57A

Cab:RM2_2F
247

187

RM1
Sym : 10673.88A

UPS PNL
Sym : 8027.23A

FL PNL 1st
Sym : 10267.36A

241

250

139

Plumb. MAIN PNL


Sym : 10071.74A

236

202

239

163

RM2
Sym : 10677.64A

cab:APFC1

SUBLIGHT FFRHS

193

Cab:lift

HVAC2

Cab:ups2

Cab:Plumb

Cab:RM1

APFC2

Cab:Kitchen U

Cab:kitchen G

HVAC_P2

Cab:firefight2

cab:ventpnl1

RM2

HVAC1

CAB:SLP

cab:terventpnl

RM1

VENT

cab:vpnl_m

Cab:SUBpwr

HVAC_P1

Cab:vpnl1

LIFT

Cab:Laundry

PLUMB

Cab:main hvac 2

KITCHEN

CAB:APFC2

VENT2

cab:hvacpump2

T_VENT

Cab:main hvac 1

PWRSB

cab:hvacpump1

UPS_LHS

Cab:ups1

Cab:firefight1

DGAUX

LAUNDRY VENT1

228

BC

EB_IC2

APFC1

240

busduct_tr2

EB_IC1

251

DG_IC1

busduct_dg2

busduct_tr1

busduct_dg1

FF_LHS

RP7

TR2

Cab:DGaux1

Spare1

DG2
Sym : 11644.74A

262

TR1

Main LT Panel LHS


Sym : 11305.54A

GEN

cab:tr2_HV

cab:tr1_HV

GEN

288

REV. DATE

ECO#

Short Circuit Currents at Busbars (DG feeding)


DRAWN BY/DATE:

PDB
Sym : 3607.06A

AHU_PNL_FLOOR
Sym : 3607.06A

DESCRIPTION

DWN APP

TH IS DRAWING IS PROPRIE TARY INFORM AT ION

DWG No .:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PAR T No.:
DWG SIZE:

RE V.

Short Circuit Detailed Report

DG Feeding

3P Fault - IEC60909 Method


Bus Name

DG1
DG2
Main LT Panel RHS
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN PNL UB
KITCHEN MAIN PNL G
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LAUNDRY PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

44482
44482
42652
42645
36680
36674
36674
35169
35164
32484
32480
30529
30529
30529
30529
29691
29691
25930
25927
25927
25927
18701
18699
18699
18699
18580
14887
12189
12189
10285
5335
5335

17536
17536
17323
17320
16193
16190
16190
15843
15840
15175
15173
14902
14902
14902
14902
14878
14878
14330
14328
14328
14328
11688
11687
11687
11687
11645
10023
8464
8464
7189
3772
3772

16258
16258
16088
16085
15113
15111
15111
14810
14808
14228
14226
13994
13994
13994
13994
13978
13978
13516
13514
13514
13514
11183
11182
11182
11182
11145
9693
8258
8258
7048
3750
3750

14457
14457
14337
14336
13564
13562
13562
13321
13320
12854
12852
12670
12670
12670
12670
12662
12662
12310
12309
12309
12309
10400
10399
10399
10399
10370
9162
7915
7915
6812
3710
3710

13175
13175
13085
13083
12441
12440
12440
12238
12237
11845
11844
11694
11694
11694
11694
11690
11690
11408
11407
11407
11407
9788
9787
9787
9787
9762
8728
7625
7625
6609
3674
3674

13175
13175
13085
13083
12441
12440
12440
12238
12237
11845
11844
11694
11694
11694
11694
11690
11690
11408
11407
11407
11407
9788
9787
9787
9787
9762
8728
7625
7625
6609
3674
3674

1941
1803
1806
1936
1794
1922
1922
1790
1918
1782
1909
1906
1906
1906
1906
1907
1907
1779
1905
1905
1905
1750
1872
1872
1872
1872
1860
1724
1724
1805
1660
1660

Short Circuit Detailed Report

DG Feeding (Contd)

LL Fault - IEC60909 Method


Bus Name

DG1
Main LT Panel LHS
DG2
Main LT Panel RHS
APFC PNL 1
M.HVAC PNL
RM1
KITCHEN MAIN PNL G
APFC PNL2
RM2
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
KITCHEN PNL UB
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
SUB LIGHTING PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
LAUNDRY PNL
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

42737
40167
35089
34258
34120
34120
32614
29959
29761
28610
28047
28047
28047
28047
27230
27230
26549
23599
23599
23599
21439
16787
16787
16787
16676
15657
13270
10325
10325
9078
4651
4651

16667
16344
14073
13991
15184
15184
14828
14150
13134
12868
13872
13872
13872
13872
13843
13843
12359
13266
13266
13266
11725
10637
10637
10637
10595
9688
9009
7143
7143
6362
3289
3289

15313
15058
13207
13140
14074
14074
13769
13188
12385
12149
12953
12953
12953
12953
12932
12932
11697
12454
12454
12454
11150
10153
10153
10153
10117
9320
8704
6986
6986
6237
3270
3270

13502
13321
11908
11862
12551
12551
12311
11849
11248
11055
11667
11667
11667
11667
11657
11657
10682
11298
11298
11298
10253
9428
9428
9428
9399
8725
8226
6715
6715
6033
3237
3237

12224
12087
10973
10938
11454
11454
11255
10871
10416
10251
10722
10722
10722
10722
10717
10717
9932
10433
10433
10433
9579
8857
8857
8857
8833
8261
7833
6489
6489
5855
3206
3206

12224
12087
10973
10938
11454
11454
11255
10871
10416
10251
10722
10722
10722
10722
10717
10717
9932
10433
10433
10433
9579
8857
8857
8857
8833
8261
7833
6489
6489
5855
3206
3206

3077
3063
2779
2785
3023
3023
3010
2984
2751
2740
2976
2976
2976
2976
2978
2978
2719
2970
2970
2970
2706
2871
2871
2871
2870
2623
2822
2529
2529
2638
2158
2158

Short Circuit Detailed Report

DG Feeding (Contd)

LG Fault - IEC60909 Method


Bus Name

DG1
DG2
Main LT Panel LHS
Main LT Panel RHS
APFC PNL 1
M.HVAC PNL
APFC PNL2
RM1
RM2
KITCHEN MAIN PNL G
KITCHEN PNL UB
FIRE FIGHT PNL
M.HVAC PUMP PNL
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
SUB LIGHTING PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
LAUNDRY PNL
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

56072
55653
54914
51147
39399
39399
37416
36132
34458
30983
29744
29220
29220
29137
29137
29137
29137
26675
26675
26675
25752
17704
17704
17704
17598
17291
15238
13008
13008
10554
6523
6523

22717
22349
22873
21508
18917
18917
17967
17859
17010
16034
15348
15748
15748
15554
15554
15554
15554
15260
15260
15260
14647
11082
11082
11082
11045
10767
10065
8841
8841
7240
4606
4606

21024
20905
21272
20249
17822
17822
17093
16885
16229
15253
14716
15003
15003
14825
14825
14825
14825
14577
14577
14577
14092
10741
10741
10741
10707
10484
9804
8679
8679
7119
4572
4572

18770
18812
19089
18377
16282
16282
15756
15502
15024
14125
13728
13922
13922
13766
13766
13766
13766
13576
13576
13576
13211
10221
10221
10221
10191
10019
9400
8404
8404
6926
4517
4517

17167
17310
17512
17010
15132
15132
14751
14460
14112
13262
12968
13090
13090
12950
12950
12950
12950
12799
12799
12799
12526
9799
9799
9799
9773
9643
9065
8173
8173
6762
4468
4468

17167
17310
17512
17010
15132
15132
14751
14460
14112
13262
12968
13090
13090
12950
12950
12950
12950
12799
12799
12799
12526
9799
9799
9799
9773
9643
9065
8173
8173
6762
4468
4468

5076
4731
5080
4707
4870
4870
4525
4803
4467
4674
4355
4663
4663
4643
4643
4643
4643
4647
4647
4647
4331
4252
4252
4252
4250
3986
4179
3839
3839
3728
3141
3141

Short Circuit Detailed Report

DG Feeding (Contd)

LLG Fault - IEC60909 Method


Bus Name

DG2
Main LT Panel RHS
DG1
Main LT Panel LHS
APFC PNL2
APFC PNL 1
M.HVAC PNL
RM2
RM1
KITCHEN MAIN PNL G
KITCHEN PNL UB
FL PNL 1st
FL PNL 2nd
FL PNL 3rd
FL PNL 4 th
FIRE FIGHT PNL
M.HVAC PUMP PNL
SUB LIGHTING PNL
DG AUX PNL
Plumb. MAIN PNL
SUB POWER PNL
LIFT MAIN PNL
TERR.VENT.PNL
VENT.PNL2
AHU PNL MZ
LAUNDRY PNL
UPS PNL
VENT.PNL
VENT.PNL1
AHU PNL UB
AHU_PNL_FLOOR
PDB

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Voltage
Circuit Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
Current in
al
al SC
al SC
al SC
al SC
al SC
Amps
SCCurrent Current in Current in Current in Current in Current in
in Amps
Amps
Amps
Amps
Amps
Amps
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

61501
55129
52162
50707
40716
40237
40237
37939
37921
34097
33625
31822
31822
31822
31822
30980
30980
27271
26665
26665
26665
18859
18859
18859
18747
18243
16197
13607
13607
11569
7126
7126

24361
23278
21033
20979
19337
18589
18589
18375
17901
16679
16794
16166
16166
16166
16166
16053
16053
15397
14984
14984
14984
11828
11828
11828
11790
11376
10831
9344
9344
8032
5033
5033

22492
21713
19601
19633
18256
17490
17490
17392
16869
15763
15960
15312
15312
15312
15312
15223
15223
14724
14299
14299
14299
11271
11271
11271
11237
11021
10431
9112
9112
7845
4987
4987

19988
19525
17626
17746
16682
15930
15930
15950
15399
14450
14720
14079
14079
14079
14079
14018
14018
13706
13280
13280
13280
10443
10443
10443
10416
10459
9813
8724
8724
7543
4908
4908

18218
17938
16218
16386
15511
14791
14791
14872
14321
13479
13786
13161
13161
13161
13161
13118
13118
12921
12502
12502
12502
9804
9804
9804
9780
10009
9316
8403
8403
7287
4839
4839

18218
17938
16218
16386
15511
14791
14791
14872
14321
13479
13786
13161
13161
13161
13161
13118
13118
12921
12502
12502
12502
9804
9804
9804
9780
10009
9316
8403
8403
7287
4839
4839

2882
2904
2950
2926
2860
2942
2942
2838
2933
2906
2795
2874
2874
2874
2874
2844
2844
2680
2743
2743
2743
2684
2684
2684
2685
2479
2790
2562
2562
2745
2599
2599

Transformers Relay Setting Calculations Transformer 1 and 2 - 1000 kVA


Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side ACB Rating
Percentage Impedance of Transformer
Fault Current at 11 kV Bus as per report
Fault current at 0.415kV Bus as per report
Transformer Full Load HV side Current at 0% tapping as per
Data sheet
Transformer Full Load HV side Current at -20 % tapping as per
Data sheet
Transformer Full Load LV side Current as per Data sheet

1000
11
0.433
50/5
10
1600
5.11%
12676
15740
52.49

kVA
kV
kV

65.87

Amps

1333.37

Amps

Amps
A
A
Amps

Transformer HV side current with 10 % Over load on lowest tap 72.46

Amps

Transformer HV side current with 10 % Over load on normal


tap
IDMT setting at 11kV side

57.74

Amps

Setting proposed on 11 kV side relay Ip>

x In
1.45
1.45 x 5
Amps
7.25
IEC Extreme Inverse

Relay setting Current


Curve

Transformer LV side Current with 10 % Over load


Over current setting at 0.415 kV side ACB
L setting proposed in ACB
Fault current at 11 kV Bus as per report
Fault current at 0.415kV Bus as per report
HV side Current due fault at 0.415 kV Bus
Setting I>> on HV side should be greater than

Setting proposed on11 kV side relay I>>


Relay setting Current

Setting proposed on 0.415 kV side ACB I

72.46/50
1.4492

1466.71
1466.71/1600
0.91669375
0.9
12676.00
15740.00
619.58
1.2*619
742.80
742.8/60
12.38
12.50
12.5 x 5
72.50
6.00

Amps

x In
Amps
Amps
Amps
Amps
Amps
x In
x In
Amps
x In

Setting Details
for

11kV RMG Panel,


11kV Outdoor Panel &
11kV 3 Panel Board

1.1 11kV RMG Panel


Relay type: Easun Reyrolle MIT 113
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

Relay Point RP1


Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

100 A
5A

Range

Setting

0.4~40 x In
0.02..99.9 s
0.4~4 x In
0.02..99.9 s
0.4~4.00 x In
0.025~1.20
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

9.5
0.6

1.1
0.6
Extreme
Inverse (EI)

110

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.01~1 x In
0.02..99.90 s
0.01~1.0 x In
0.02..99.90 s

0.25
0.6

Prim.
Current
25

Io>>
To>>
Io>
To>

8 8

I>>
T I>>
I>
T-I>
Ip
Tp

8 8

50-2 Pickup
50-2 Delay
50-1Pickup
50-1Delay
Ip pickup
Tp time dial
IEC Curve

Prim.
Current
950

2.1 11kV Outdoor Panel


Relay type: Areva P111 L
SCOPE OF FUNCTION
Address

Relay Point RP2


Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

10..50000 A
1A/5A

100 A
5A

Range

Setting

50-2 Pickup
50-2 Delay
50-1Pickup
50-1Delay
Ip pickup
Tp time dial
IEC Curve

0.4~40 x In
0.02..99.9 s
0.4~4 x In
0.02..99.9 s
0.4~4.00 x In
0.025~1.20
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

8.5
0.45

1.1
0.45
Extreme
Inverse (EI)

110

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.01~1 x In
0.02..99.90 s
0.01~1.0 x In
0.02..99.90 s

0.22
0.45

Prim.
Current
22

Other functions are disabled


Power System Data 1
CTs

Io>>
To>>
Io>
To>

8 8
8 8

I>>
T I>>
I>
T-I>
Ip
Tp

Prim.
Current
850

3.1 11kV Indoor 3 PNL Board


Relay type: Areva P111 L
SCOPE OF FUNCTION
Address

- Incomer
Relay Point RP3
Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

10..50000 A
1A/5A

100 A
5A

Range

Setting

50-2 Pickup
50-2 Delay
50-1Pickup
50-1Delay
Ip pickup
Tp time dial
IEC Curve

0.4~40 x In
0.02..99.9 s
0.4~4 x In
0.02..99.9 s
0.4~4.00 x In
0.025~1.20
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

7.5
0.3

1
0.35
Extreme
Inverse (EI)

100

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.01~1 x In
0.02..99.90 s
0.01~1.0 x In
0.02..99.90 s

0.2
0.3

Prim.
Current
20

Other functions are disabled


Power System Data 1
CTs

Io>>
To>>
Io>
To>

8 8
8 8

I>>
T I>>
I>
T-I>
Ip
Tp

Prim.
Current
750

3.2 11kV Indoor 3 PNL Board - Transformer 1 Feeder


Relay type: Areva P111 L
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

Relay Point RP4


Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

50 A
5A

Range

Setting

0.4~40 x In
0.02..99.9 s
0.4~4 x In
0.02..99.9 s
0.4~4.00 x In
0.025~1.20
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

13
0.15

1.45
0.4
Extreme
Inverse (EI)

72.5

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.01~1 x In
0.02..99.90 s
0.01~1.0 x In
0.02..99.90 s

0.3
0.15

Prim.
Current
15

Io>>
To>>
Io>
To>

8 8

I>>
T I>>
I>
T-I>
Ip
Tp

8 8

50-2 Pickup
50-2 Delay
50-1Pickup
50-1Delay
Ip pickup
Tp time dial
IEC Curve

Prim.
Current
650

3.3 11kV Indoor 3 PNL Board - Transformer 2 Feeder


Relay type: Areva P111 L
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

Relay Point RP5


Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

50 A
5A

Range

Setting

0.4~40 x In
0.02..99.9 s
0.4~4 x In
0.02..99.9 s
0.4~4.00 x In
0.025~1.20
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

12.5
0.15

1.45
0.4
Extreme
Inverse (EI)

72.5

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.01~1 x In
0.02..99.90 s
0.01~1.0 x In
0.02..99.90 s

0.3
0.15

Prim.
Current
15

Io>>
To>>
Io>
To>

8 8

I>>
T I>>
I>
T-I>
Ip
Tp

8 8

50-2 Pickup
50-2 Delay
50-1Pickup
50-1Delay
Ip pickup
Tp time dial
IEC Curve

Prim.
Current
625

Setting Details
for

MAIN LT Panel
Sub Power Panel,
Sub Lighting Panel &
Other Panels

4.1 Main LT Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

EB Incomer1
EB Incomer2
DG Incomer1
DG Incomer2
Spare1
Fire Fighting Panel LHS
DG AUX Panel LHS
UPS LHS
SUB Power Panel
Terrace Ventilation Panel
Ventilation Panel 2
Kitchen main Panel (Ground)
Plumbing main Panel
Lift main Panel
APFC 1 Panel
Main HVAC Panel LHS
RM1
Main HVAC Pump Panel LHS
RM2
Main HVAC Panel RHS
APFC 2 Panel
Main HVAC Pump Panel RHS
Laundry Panel
Ventilation Panel 1
Ventilation Panel
SUB Lighting Panel
Fire Fighting Panel RHS
DG AUX Panel RHS
Spare2
Spare3
Kitchen main Panel (UB)
UPS RHS
Spare4

24680

Symmetrical Fault Current in Amps ( DG Feed)

17323

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
1600
0.9
1440
36
9600
0.1
320
1600
0.9
1440
36
9600
0.1
320
1600
0.9
1440
36
9600
0.1
320
1600
0.9
1440
36
9600
0.1
320
200
1
200
36
1200
0.1 NA
400
1
400
36
2400
0.1 NA
315
1
315
36
1890
0.1 NA
200
0.75
150
36
1200
0.1 NA
400
1
400
36
2400
0.1 NA
200
1
200
36
1200
0.1 NA
200
1
200
36
1200
0.1 NA
800
0.95
760
36
4800
0.1 NA
400
1
400
36
2400
0.1 NA
200
1
200
36
1200
0.1 NA
1250
1
1250
36
7500
0.1 NA
1250
1
1250
36
7500
0.1 NA
1000
1
1000
36
6000
0.1 NA
630
0.85
535.5
36
3780
0.1 NA
1000
1
1000
36
6000
0.1 NA
1250
1
1250
36
7500
0.1 NA
1250
1
1250
36
7500
0.1 NA
630
0.85
535.5
36
3780
0.1 NA
315
0.65
204.75
36
1890
0.1 NA
315
0.65
204.75
36
1890
0.1 NA
160
0.75
120
36
960
0.1 NA
400
1
400
36
2400
0.1 NA
400
1
400
36
2400
0.1 NA
315
1
315
36
1890
0.1 NA
1250
1
1250
36
7500
0.1 NA
1000
1
1000
36
6000
0.1 NA
400
1
400
36
2400
0.1 NA
200
0.9
0.75
36
1200
0.1 NA
1000
0.9
900
36
6000
0.1 NA

4.2 Sub Lighting Panel


Symmetrical Fault Current in Amps ( EB Feed)

Incomer
FPDB1
FPDB1
FPDB2
FPDB3
FPDB4
FPDB5
FPDB6
20 kVA UPS
20 kVA UPS
Upper Basement AHU Panel
G Floor VDB
Mezzanine AHU Panel
Spare 1
Spare 2

4.3 Sub Power Panel


Symmetrical Fault Current in Amps ( EB Feed)

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

14330

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
400
0.95
380
35
2000
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
160
0.75
120
36
960
0.1 NA
160
0.75
120
36
960
0.1 NA
160
0.75
120
36
960
0.1 NA
63
1
63
36
378
0.1 NA
160
1
160
36
960
0.1 NA

Feeder Description

Sl.No

Symmetrical Fault Current in Amps ( DG Feed)

Incomer
FLDB1
FLDB1
FLDB2
FLDB3
FLDB4
FLDB5
FLDB6
FLDB7
FLDB8
FLDB9
FLDB10
FLDB11
FLDB12
FLDB13
FLDB14
FLDB15
FLDB16
FLDB17
FLDB18
FLDB19
FLDB20
FLDB21
Spare1
Spare2
Spare3
Spare4

Sl.No

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27

18234

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
400
0.95
380
35
2000
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
125
0.4
50
36
750
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA

18231

Symmetrical Fault Current in Amps ( DG Feed)

14328

4.4 APFC 1 Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12

Incomer
50 kVAR Bank 1
50 kVAR Bank 2
50 kVAR Bank 3
50 kVAR Bank 4
50 kVAR Bank 5
25 kVAR Bank 1
25 kVAR Bank 2
25 kVAR Bank3
25 kVAR Bank 4
25 kVAR Bank5
25 kVAR Bank 6

4.5 APFC2 Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12

Incomer
50 kVAR Bank 1
50 kVAR Bank 2
50 kVAR Bank 3
50 kVAR Bank 4
50 kVAR Bank 5
25 kVAR Bank 1
25 kVAR Bank 2
25 kVAR Bank3
25 kVAR Bank 4
25 kVAR Bank5
25 kVAR Bank 6

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12

Incomer
Hydraulic System
STP
Filter Feed Pump
Hot Water Generator
Collection Pit Sump Pump
Swimming Pool Equipment
Filter Feed Pump
Plumbing Plant Room Sump-1
Plumbing Plant Room Sump-2
Spare 1
Spare 2

Symmetrical Fault Current in Amps ( DG Feed)

16193

22265

Symmetrical Fault Current in Amps ( DG Feed)

16190

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
1250
0.95
1187.5
35
6250
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA

4.6 Plumbing Main Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

22261

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
1250
0.95
1187.5
35
6250
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
200
0.5
100
36
1200
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA
100
0.5
50
36
600
0.1 NA

18231

Symmetrical Fault Current in Amps ( DG Feed)

14328

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
400
0.95
380
35
2000
0.1 NA
63
1
63
36
378
0.1 NA
200
1
200
36
1200
0.1 NA
63
1
63
36
378
0.1 NA
100
1
100
36
600
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.7 Kitchen main Panel UPPER BASEMENT


Symmetrical Fault Current in Amps ( EB Feed)

Incomer
DG Fresh Air1
DG Fresh Air2
DG Exhaust Air1
DG Exhaust Air2
DG Cooling Tower Pump 1
DG Cooling Tower Pump2
DG Cooling Tower Pump 3
DG Cooling Tower Pump 4
DG Cooling Tower Pump 5
DG HSD Yard Panel
Spare 1
Spare 2

4.8 DG Aux Panel


Symmetrical Fault Current in Amps ( EB Feed)

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13

4.9 UPS Main Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

15175

ACB/MC
Phase Current Settings
Motor
CB
Long
Primary
Long Instantan Primary Rating in
HP
Time
eous
Current
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
315
0.95
299.25
3
5
1575 63
1
63
3
5
315
15
63
1
63
3
5
315
15
63
1
63
3
5
315
15
63
1
63
3
5
315
15
63
1
63
3
5
315
10
63
1
63
3
5
315
10
63
1
63
3
5
315
10
63
1
63
3
5
315
10
63
1
63
3
5
315
10
63
1
63
3
5
315 63
1
63
3
5
315 63
1
63
3
5
315 -

Feeder Description

Sl.No

Symmetrical Fault Current in Amps ( DG Feed)

Incomer
KPDB 1
KPDB 2
KPDB 3
KPDB 4
KPDB 5
KPDB 6
TPN 30
TPN 31
TPN 32
TPN 33
TPN 34
TPN 35
Spare 1
Spare 2
Spare 3
Spare 4
Spare 5

Sl.No

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

20254

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
400
0.95
380
35
2000
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
100
0.95
95
36
600
0.1 NA
63
1
63
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
100
1
100
36
600
0.1 NA
100
1
100
36
600
0.1 NA

Incomer1
Incomer2
UPS UPS DB1
UPS UPS DB2
UPS UPS DB3
UPS UPS DB4
UPS UPS DB5
UPS UPS DB6
UPS UPS DB7
UPS UPS DB8
UPS UPS DB9
UPS UPS DB10
UPS UPS DB11
Spare 1
Spare 2

18231

11185

Symmetrical Fault Current in Amps ( DG Feed)


Motor
Line
Current
in Amps
-

Motor
Phase
Current
in Amps
-

20.8
20.8
20.8
20.8
16
16
16
16
16
-

12
12
12
12
9.2
9.2
9.2
9.2
9.2
-

14328
TOLR
Range

8~12.5
8~12.5
8~12.5
8~12.5
6.3~10
6.3~10
6.3~10
6.3~10
6.3~10
-

Symmetrical Fault Current in Amps ( DG Feed)

TOLR Setting

12.5
12.5
12.5
12.5
10
10
10
10
10
-

10023

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
200
0.5
100
35
1000
0.1 NA
200
0.5
100
35
1000
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.10 Collection Pit Sump Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
12
13

Incomer
Sump Pump 1
Sump Pump 2
Sump Pump 3
Sump Pump 4
Sump Pump 5
Sump Pump 7
Sump Pump 7
Sump Pump8
Sump Pump 1
Sump Pump 2
Sump Pump 3
Sump Pump 4
Sump Pump 5
Sump Pump 7
Sump Pump 7
Sump Pump8
Spare 1
Spare 2

4.11 Lift Main Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10

Incomer1
Guest Lift 1
Guest Lift 2
Guest Lift 3
Service Lift 1
Service Lift 2
Service Lift 3
Baggage Lift
Lift Machine Room DB
Spare

Feeder Description

1
2
3
4
5
6
7
8

Incomer1
VTPN DB1
LAUNDRY EQUIPMENT 1
LAUNDRY EQUIPMENT 2
Spare 1
Spare 2
Spare 3
Spare 4

Symmetrical Fault Current in Amps ( DG Feed)

13755

Motor
Primary Rating in
HP
Current

315 -

Motor
Line
Current
in Amps
-

1.5
1.5
1.5
1.5
1.5
1.5
1.5
2
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2
-

Motor
Phase
Current
in Amps
-

2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.7
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.7
-

2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.7
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.7
-

7189
TOLR
Range

2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.5~4
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.2~3.2
2.5~4
-

Symmetrical Fault Current in Amps ( DG Feed)

TOLR Setting

2.9
2.9
2.9
2.9
2.9
2.9
2.9
4
2.9
2.9
2.9
2.9
2.9
2.9
2.9
4
-

11687

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
200
0.95
190
35
1000
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.12 Laundry Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

7606

ACB/MC
Phase Current Settings
CB
Long
Primary
Long Instantan
Time
eous
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
63
0.75
47.25
3
5
40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 40
1
40 -

13757

Symmetrical Fault Current in Amps ( DG Feed)

11688

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
315
0.6
189
35
1575
0.1 NA
100
0.65
65
36
600
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.13 Kitchen Main Panel GROUND FLOOR


Symmetrical Fault Current in Amps ( EB Feed)

Incomer1
Incomer2
PDU 1 for Server
PDU 2 for Server
Spare 1
Spare 2

4.14 UPS Panel 20 kVA


Symmetrical Fault Current in Amps ( EB Feed)

Feeder Description

1
2
3
4
5
6

4.15 Fire Fighting Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9

15173

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
63
1
63
35
315
0.1 NA
63
1
63
35
315
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA

Feeder Description

Sl.No

Symmetrical Fault Current in Amps ( DG Feed)

Incomer
KPDB 1
KPDB 2
KPDB 3
KPDB 4
KPDB 5
KPDB 6
KPDB7
TPN 4
TPN 5
TPN 8
Spare 1
Spare 2
Spare 3
Spare 4
Spare 5

Sl.No

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

20251

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
800
0.9
720
35
4000
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
100
0.65
65
36
600
0.1 NA
160
0.4
64
36
960
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
100
0.9
90
36
600
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
160
1
160
36
960
0.1 NA
100
1
100
36
600
0.1 NA

Incomer 1
Incomer2
Fire Hydrant Pump
Sprinkler Pump
Jockey Pump
Terrace Booster Pump 1
Terrace Booster Pump 2
Spare 1
Spare 2

11185

19523

Symmetrical Fault Current in Amps ( DG Feed)

Symmetrical Fault Current in Amps ( DG Feed)

10023

14878

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
400
0.9
360
35
2000
0.1 NA
400
0.9
360
35
2000
0.1 NA
250
0.8
200
36
1500
0.1 NA
250
0.8
200
36
1500
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
63
0.75
47.25
36
378
0.1 NA
125
1
125
36
750
0.1 NA
250
1
250
36
1500
0.1 NA

4.16 Main HVAC Pump Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

Incomer 1
Incomer 2
Primary Chiller Water Pump 1
Primary Chiller Water Pump 2
Primary Chiller Water Pump 3
Secondary Chiller Water Pump 1 (
Public Area)
Secondary Chiller Water Pump 2 (
Public Area)
Secondary Chiller Water Pump 1 (
Rooms)
Secondary Chiller Water Pump 2 (
Rooms)
Secondary Chiller Water Pump 3 (
Rooms)
Condenser Pumps 1
Condenser Pumps 2
Condenser Pumps 3
Cooling Tower Pump 1
Cooling Tower Pump 2
Cooling Tower Pump 3
Spare 1
Spare 2
Spare3
Spare 4
Spare 5

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Incomer 1
Car Park Tube Axial fresh 1
Car Park Tube Axial fresh 2
Car Park Tube Axial fresh 3
Car Park Tube Axial fresh 4
Car Park DIDW Exhaust
Car Park Emergency Exhaust 1
Car Park Emergency Exhaust 2
Car Park Exhaust Jet
Fresh Air HVAC Plumbing
Exhaust Air HVAC Plumbing
STP Ventilation Fresh Air
STP Ventilation Exhaust Air
Laundry Fresh Air
Laundry Exhaust Air
Spare 1
Spare 2
Spare 3

Symmetrical Fault Current in Amps ( DG Feed)


Motor
Line
Current
in Amps
-

Motor
Phase
Current
in Amps
-

20.8
20.8
20.8
-

14878
TOLR
Range

12 8~12.5
12 8~12.5
12 8~12.5
-

TOLR Setting

12.5
12.5
12.5
-

125

0.8

100

625 -

125

0.8

100

625 -

125

0.8

100

625 -

125

0.8

100

625 -

125
125
125
63
63
63
125
125
63
63
63

0.8
0.8
0.8
1
1
1
1
1
1
1
1

100
100
100
63
63
63
125
125
63
63
63

3
3
3
3
3
3
3
3
3
3
3

5
5
5
5
5
5
5
5
5
5
5

625
625
625
315
315
315
625
625
315
315
315

4.17 Basement Ventilation Panel 1


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

19523

ACB/MC
Phase Current Settings
Motor
CB
Long
Primary
Long Instantan Primary Rating in
HP
Time
eous
Current
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
630
0.8
504
3
5
3150 630
0.8
504
3
5
3150 63
1
63
3
5
315
15
63
1
63
3
5
315
15
63
1
63
3
5
315
15
125
0.8
100
3
5
625 -

9103

30
30
30
15
15
15
-

40
40
40
20.8
20.8
20.8
-

23.2
23.2
23.2
12
12
12
-

16~25
16~25
16~25
8~12.5
8~12.5
8~12.5
-

Symmetrical Fault Current in Amps ( DG Feed)

ACB/MC
Phase Current Settings
Motor
CB
Long
Primary
Long Instantan Primary Rating in
HP
Time
eous
Current
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
315
0.6
189
3
5
1575 63
0.8
50.4
3
5
315
7.5
63
0.8
50.4
3
5
315
7.5
63
0.8
50.4
3
5
315
7.5
63
0.8
50.4
3
5
315
7.5
63
1
63
3
5
315
25
200
1
200
3
5
1000
40
200
1
200
3
5
1000
40
63
0.8
50.4
3
5
315 63
1
63
3
5
315
15
63
1
63
3
5
315
15
63
0.8
50.4
3
5
315
7.5
63
0.8
50.4
3
5
315
7.5
63
0.8
50.4
3
5
315
5
63
0.8
50.4
3
5
315
5
125
1
125
3
5
625 63
1
63
3
5
315 63
1
63
3
5
315 -

Motor
Line
Current
in Amps
-

Motor
Phase
Current
in Amps
-

11.2
11.2
11.2
11.2
34
53
53
-

6.5
6.5
6.5
6.5
19.7
30.6
30.6
-

20.8
20.8
11.2
11.2
7.8
7.8
-

12
12
6.5
6.5
7.8
7.8
-

25
25
25
12.5
12.5
12.5
-

8464
TOLR
Range

5~8
5~8
5~8
5~8
16~25
20~32
20~32
8~12.5
8~12.5
5~8
5~8
5.5~8
5.5~8
-

TOLR Setting

7.2
7.2
7.2
7.2
21.5
32
32
12.5
12.5
7.2
7.2
8
8
-

4.18 Basement Ventilation Panel 2


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14

Incomer 1
Car Park Normal Exhaust 1
Car Park Normal Exhaust 2
Car Park Emergency Exhaust 1
Car Park Emergency Exhaust 2
Car Park Exhaust Jet
Kitchen Fresh Air
Bakery Fresh Air
Stacking P. S.area Exhaust air
Dead Store exhaust air unit
Fresh Air Fan for Kitchen
Storage Equipment
Spare 1
Spare 2

4.19 Main HVAC Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4

Incomer 1
Chiller 1
Chiller 2
Chiller 3

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
12
13
14
15
16
17
18
19
20

Incomer
Shaft Creation Room
Purchase Manager Room 1
Purchase Manager Room 2
HR Personal Room
HKP 1
HKP 2
Employee Kitchen
Female Locker
Dead Storage Sample Room
Liquir Storage
Meat Preparation
Sea Food Preparation
Vegetable Preparation
Chocolate Room
Office
LB 1
LB 2
LB 3
Staff Cafeteria 1
Staff Cafeteria 2
Staff Cafeteria 3
Staff Cafeteria 4
Spare 1
Spare 2
Spare 3

Symmetrical Fault Current in Amps ( DG Feed)

22261

Motor
Line
Current
in Amps
-

Motor
Phase
Current
in Amps
-

16
16
34
34
-

9.2
9.2
19.7
19.7
-

7.8
3.7
1
2.6
7.8
3.7
-

7.8
3.7
1
2.6
7.8
3.7
-

11687
TOLR
Range

6.3~10
6.3~10
16~25
16~25
5.5~8
2.5~4
0.9~1.25
2.2~3.2
5.5~8
2.5~4
-

Symmetrical Fault Current in Amps ( DG Feed)

TOLR Setting

10
10
21.5
21.5
8
4
1.1
2.9
8
4
-

16190

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
1250
0.9
1125
35
6250
0.1 NA
630
1
630
35
3150
0.1 NA
630
1
630
35
3150
0.1 NA
630
1
630
35
3150
0.1 NA

4.20 Upper Basement AHU Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

13755

ACB/MC
Phase Current Settings
Motor
CB
Long
Primary
Long Instantan Primary Rating in
HP
Time
eous
Current
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
315
0.6
189
3
5
1575 63
0.8
50.4
3
5
315
10
63
0.8
50.4
3
5
315
10
63
1
63
3
5
315
25
63
1
63
3
5
315
25
63
0.8
50.4
3
5
315 32
0.8
25.6
3
5
160
5
32
0.8
25.6
3
5
160
2
32
0.7
22.4
3
5
160
0.3
32
0.7
22.4
3
5
160
1.5
32
0.8
25.6
3
5
160
5
32
0.8
25.6
3
5
160
2
63
1
63
3
5
315 63
1
63
3
5
315 -

7606

Symmetrical Fault Current in Amps ( DG Feed)

ACB/MC
Phase Current Settings
CB
Long
Primary
Long Instantan
Time
eous
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
160
0.75
120
3
5
20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 -

Motor
Primary Rating in
HP
Current

800 -

Motor
Line
Current
in Amps
-

0.5
0.5
0.5
0.5
0.3
0.3
0.5
2.5
3
0.5
0.5
0.5
1
1.5
1.5
0.8
3
2
0.5
0.5
0.5
0.5
-

Motor
Phase
Current
in Amps
-

1
1
1
1
1
1
1
4.2
4.8
1
1
1
1.9
2.6
4.2
1.3
4.8
3.7
1
1
1
1
-

1
1
1
1
1
1
1
4.2
4.8
1
1
1
1.9
2.6
4.2
3.7
3.7
3.7
1
1
1
1
-

7189
TOLR
Range

0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
3.2~5
3.2~5
0.9~1.25
0.9~1.25
0.9~1.25
1.4~2
2.2~3.2
3.2~5
1.1~1.6
3.5~5
2.5~4
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
-

TOLR Setting

1.1
1.1
1.1
1.1
1.1
1.1
1.1
4.6
5
1.1
1.1
1.1
2
2.9
2.9
1.4
5
4
1.1
1.1
1.1
1.1
-

4.21Mezzanine AHU Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27

Incomer
Pre Function 1
Pre Function 2
Function Room1
Function Room2
Coffee shop
Ssecurity Restaurant
Lobby
Lobby Bar
Kitchen Tea
Chairman suite
Hall 01
Hall 02 A
Hall 02 B
Hall 03
Hall 04
Health Club
GYM
Executive Office
IT Office
Ladies Toilet
Gents Toilet
Spare 1
Spare 2
Spare 3
Spare 4
Spare 5

4.22 Terrace Floor Ventilation Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23

Incomer
Mezzanine Floor Toilet
Storage Presurasation 3
Toilet Exhaust Fans DB 1
Toilet Exhaust Fans DB 2
Lift Well Presurasation 1
Lift Well Presurasation 2
GF Kitchen Exhaust Air Fan 1
GF Kitchen Exhaust Air Fan 1
UB Kitchen Exhaust Air Fan 1
UB Kitchen Exhaust Air Fan 2
Dry Type Scrubber 1 (GF Kitchen)
Dry Type Scrubber 2 (GF Kitchen)
Dry Type Scrubber 3 (GF Kitchen)
Dry Type Scrubber 4 (GF Kitchen)
Dry Type Scrubber 5 (GF Kitchen)
Dry Type Scrubber 1 (UB Kitchen)
Dry Type Scrubber 2 (UB Kitchen)
UB Toilet Exhaust
Spare 1
Spare 2
Spare 3
Spare 4

3814

Symmetrical Fault Current in Amps ( DG Feed)

ACB/MC
Phase Current Settings
CB
Long
Primary
Long Instantan
Time
eous
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
160
0.95
152
3
5
20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 40
1
40 -

13755

Motor
Primary Rating in
HP
Current

800 -

Motor
Line
Current
in Amps
-

3
3
5
5
5
3
7.5
3
5
1.5
0.8
0.3
0.3
1
1
1.5
5
2
1
0.3
0.3
0.5
-

Motor
Phase
Current
in Amps
-

4.8
4.8
7.8
7.8
7.8
4.8
11.2
4.8
7.8
2.6
1.3
1
1
1.9
1.9
2.6
7.8
3.7
1.9
1
1
1
-

4.8
4.8
7.8
7.8
7.8
4.8
11.2
4.8
7.8
2.6
3.7
1
1
1.9
1.9
2.6
7.8
3.7
1.9
1
1
1
-

3772
TOLR
Range

3.2~5
3.2~5
5.5~8
5.5~8
5.5~8
3.2~5
9~12.5
3.2~5
5.5~8
2.2~3.2
1.1~1.6
0.9~1.25
0.9~1.25
1.4~2
1.4~2
2.2~3.2
5.5~8
2.5~4
1.4~2
0.9~1.25
0.9~1.25
0.9~1.25
-

Symmetrical Fault Current in Amps ( DG Feed)

ACB/MC
Phase Current Settings
CB
Long
Primary
Long Instantan
Time
eous
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
200
0.95
190
3
5
20
1
20 20
1
20 63
1
63 63
1
63 20
1
20 20
1
20 63
1
63 63
1
63 63
1
63 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 -

Motor
Primary Rating in
HP
Current

1000 -

Motor
Line
Current
in Amps
-

1
5
-

1.9
7.8

2
2
25
15
15
5
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.8
0.5

Motor
Phase
Current
in Amps

3.7
3.7
34
20.8
20.8
7.8
1
1
1
1
1
1
1
1.3
1

TOLR Setting

5
5
8
8
8
5
12.25
5
8
2.9
1.4
1.1
1.1
2
2
2.9
8
4
2
1.1
1.1
1.1
-

11687
TOLR
Range

1.9 1.4~2
7.8 5.5~8
3.7 2.5~4
3.7 2.5~4
19.7 16~25
12 8~12.5
12 8~12.5
7.8 5.5~8
1 0.9~1.25
1 0.9~1.25
1 0.9~1.25
1 0.9~1.25
1 0.9~1.25
1 0.9~1.25
1 0.9~1.25
3.7 1.1~1.6
1 0.9~1.25
-

TOLR Setting

2
8
4
4
21.5
12.5
12.5
8
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.4
1.1
-

4.23 Mezzanine Floor Ventilation Panel


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Incomer
Gents-Ladies Toilet EX 1
Gents-Ladies Toilet EX 2
Gents-Ladies Toilet EX 3
Gents-Ladies Toilet EX 4
Kitchen Fresh Air 1
Kitchen Fresh Air 1
Chairman Suite Toilet EX
Fresh Air Fan AHU 1
Fresh Air Fan AHU 2
Fresh Air Fan AHU 3
Fresh Air Fan AHU 4
Fresh Air Fan AHU 5
Spare 1
Spare 2
Spare 3
Spare 4

4.24 Ground Floor VDB


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14

Incomer
Ladies Toilet 1
Ladies Toilet 2
Gents Toilet 1
Gents Toilet 2
Purchasing Staff
Security Office
Chef's Office
Trolley Set up
R SOT
Spare 1
Spare 2
Spare 3
Spare 4

Feeder Description

1
2
3
4
5
6
7

Incomer
Guest Room DB 1
Guest Room DB 2
Guest Room DB 3
CLP DB-4 I Floor
AHU Panel
Spare

Symmetrical Fault Current in Amps ( DG Feed)

7606

19650

Motor
Primary Rating in
HP
Current

1000 -

Motor
Line
Current
in Amps
-

0.8
0.8
0.8
0.8
10
10
0.3
0.3
0.3
0.3
1
1.5
0.5
-

Motor
Phase
Current
in Amps
-

1.3
1.3
1.3
1.3
16
16
1
1
1
1
1.9
2.6
1
-

3.7
3.7
3.7
3.7
9.2
9.2
1
1
1
1
1.9
2.6
1
-

11687
TOLR
Range

1.1~1.6
1.1~1.6
1.1~1.6
1.1~1.6
6.3~10
6.3~10
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
1.4~2
2.2~3.2
0.9~1.25
-

Symmetrical Fault Current in Amps ( DG Feed)

ACB/MC
Phase Current Settings
CB
Long
Primary
Long Instantan
Time
eous
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
160
0.75
120
3
5
20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 -

4.25 Floor Panel I floor


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

13755

ACB/MC
Phase Current Settings
CB
Long
Primary
Long Instantan
Time
eous
Rating time Pick Current
up
Delay in Current
Current
sec (T1) setting
setting
(I3)
(I1)
200
0.7
140
3
5
20
1
20 20
1
20 20
1
20 20
1
20 40
1
40 40
1
40 63
1
63 63
1
63 63
1
63 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 20
1
20 -

Motor
Primary Rating in
HP
Current

800 -

Motor
Line
Current
in Amps
-

0.5
0.5
0.5
0.5
0.3
0.3
0.3
0.3
0.3
0.5
-

Motor
Phase
Current
in Amps
-

1
1
1
1
1
1
1
1
1
1
-

1
1
1
1
1
1
1
1
1
1
-

TOLR Setting

1.4
1.4
1.4
1.4
10
10
1.1
1.1
1.1
1.1
2
2.9
1.1
-

7189
TOLR
Range

0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
0.9~1.25
-

Symmetrical Fault Current in Amps ( DG Feed)

TOLR Setting

1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
-

14902

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
315
0.85
267.75
35
1575
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
0.8
0.75
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.26 Floor Panel II floor


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7

Incomer
GLP DB1 II floor
GLP DB2 II floor
GLP DB3 II floor
CLP DB4 II floor
AHU Panel
Spare

4.25 Floor Panel III floor


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5
6
7

Incomer
GLP DB1 III floor
GLP DB2 III floor
GLP DB3 III floor
CLP DB4 III floor
AHU Panel
Spare

Feeder Description

1
2
3
4
5
6
7
8

Incomer
GLP DB1 IV floor
GLP DB2 IV floor
GLP DB3 IV floor
CLP DB4 IV floor
AHU Panel
FPDB 5 Terrace Power
Spare

Symmetrical Fault Current in Amps ( DG Feed)

14902

19650

Symmetrical Fault Current in Amps ( DG Feed)

14902

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
315
0.85
267.75
35
1575
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
0.8
0.75
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.26 Floor Panel IV floor


Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

19650

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
315
0.85
267.75
35
1575
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
0.8
0.75
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

19650

Symmetrical Fault Current in Amps ( DG Feed)

14902

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
315
0.8
252
35
1575
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
0.8
0.75
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA
63
1
63
36
378
0.1 NA

4.27 RM1
Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5

Incomer
Tap Off Box
Tap Off Box
Tap Off Box
Tap Off Box

floor I
floor II
floor III
floor IV

4.28 RM2
Symmetrical Fault Current in Amps ( EB Feed)

Sl.No

Feeder Description

1
2
3
4
5

Incomer
Tap Off Box
Tap Off Box
Tap Off Box
Tap Off Box

floor I
floor II
floor III
floor IV

21555

Symmetrical Fault Current in Amps ( DG Feed)

15840

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
1000
0.9
900
35
5000
0.1 NA
315
0.85
267.75
36
1890
0.1 NA
315
0.85
267.75
36
1890
0.1 NA
315
0.85
267.75
36
1890
0.1 NA
315
0.85
267.75
36
1890
0.1 NA

21555

Symmetrical Fault Current in Amps ( DG Feed)

15843

ACB/MC
Phase Current Settings
Earth Fault
setting
CB
Long
Primary
Long
Short
Primary
Short Instantan Primary Min.time
Time time Pick Current
time
eous
Current
for
Rating time Pick Current
up
Delay in
up
delay in Current
Instantan
Current
sec (T1) Current
sec (T2) setting
eous
setting
Settint
(I3)
current
(I1)
(I2)
(T3)
1000
0.9
900
35
5000
0.1 NA
315
0.85
267.75
36
1890
0.1 NA
315
0.85
267.75
36
1890
0.1 NA
315
0.85
267.75
36
1890
0.1 NA
315
0.85
267.75
36
1890
0.1 NA

Setting Details
for

DG AMF Panels

5.1 DG AMF Panel 1


Relay type: C&S IRI-3I-EI
SCOPE OF FUNCTION
Address

OC/SC Relay

Relay Point RP6

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

10..50000 A
1A/5A

1600 A
5A

Range

Setting

50-2 Pickup
50-2 Delay
Ip pickup
Tp time dial
IEC Curve

0.5~25 x In
0.03..20 s
0.2~2.50 x In
0.01~1.50
Normal Inverse 3.0
,Normal Inverse
1.3,Normal Inverse 0.6
Very Inverse,Extremely
Inverse

7
0.1
0.95
0.6
Extreme
Inverse

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.5~15 x In
0.02..20 s
0.05~2.5 x In
0.03..150 s

0.25
0.15

Other functions are disabled


Power System Data 1

I>>
T I>>
I>
T>

Ie>>
Te>>
Ie>
Te>

8 8

CTs

Prim.
Current
11200
1520

Prim.
Current
400

5.2 DG AMF Panel 1


Relay type: C&S IRI-EO
SCOPE OF FUNCTION
Address

REF Relay

Relay Point RP6

Setting Title
Fault Records
Function REF

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

1600 A
5A

Range

Setting

Ie>
Te>

0.05~2.5 x In
0.03..150 s

0.1
1

Negative Sequence

Relay Point RP6

Other functions are disabled


Power System Data 1
CTs

REF Protection:
Ground over current Protection: 50N/51 N
Setting name
Units
50N-1Pickup
50N-1Delay
5.3 DG AMF Panel 1
Relay type: C&S MRS1-I5-L-D
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Fault Records
Enabled/Disabled
Negative Sequence Current

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary
Negative Sequence Current Protection 46
Setting name
Units

10..50000 A
1A/5A

1600 A
5A

Range

Setting

Negative Sequence Current


Warning
Time delay Negative Sequence
Current Warning
Negative Sequence Current
Tripping
Tripping Characteristics
Time delay Negative Sequence
Current Tripping

I2w

0.02~0.5 x In

0.18

tw

0.1..20 s

I2s

0.02~0.5 x In

0.22

CHAR
T(DEFT)
T(INVS)

DEFT/INVS
1200 s
300...3600s

DEFT
2

Prim.
Current
160

Other functions are disabled


Power System Data 1
CTs

Prim.
Current
288

352

6.1 DG AMF Panel 2


Relay type: C&S IRI-3I-EI
SCOPE OF FUNCTION
Address

OC/SC Relay

Relay Point RP6

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units

10..50000 A
1A/5A

1600 A
5A

Range

Setting

50-2 Pickup
50-2 Delay
Ip pickup
Tp time dial
IEC Curve

0.5~25 x In
0.03..20 s
0.2~2.50 x In
0.01~1.50
Normal Inverse 3.0
,Normal Inverse
1.3,Normal Inverse 0.6
Very Inverse,Extremely
Inverse

7
0.1
0.95
0.6
Extreme
Inverse

Ground over current Protection: 50N/51 N


Setting name
Units

Range

Setting

50N-2 Pickup
50N-2 Delay
50N-1Pickup
50N-1Delay

0.5~15 x In
0.02..20 s
0.05~2.5 x In
0.03..150 s

0.25
0.15

Other functions are disabled


Power System Data 1

I>>
T I>>
I>
T>

Ie>>
Te>>
Ie>
Te>

8 8

CTs

Prim.
Current
11200
1520

Prim.
Current
400

6.2 DG AMF Panel 2


Relay type: C&S IRI-EO
SCOPE OF FUNCTION
Address

REF Relay

Relay Point RP6

Setting Title
Fault Records
Function REF

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

1600 A
5A

Range

Setting

Ie>
Te>

0.05~2.5 x In
0.03..150 s

0.1
1

Negative Sequence

Relay Point RP6

Other functions are disabled


Power System Data 1
CTs

REF Protection:
Ground over current Protection: 50N/51 N
Setting name
Units
50N-1Pickup
50N-1Delay
6.3 DG AMF Panel 2
Relay type: C&S MRS1-I5-L-D
SCOPE OF FUNCTION
Address

Setting Title
Setting Range
Fault Records
Enabled/Disabled
Negative Sequence Current

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary
Negative Sequence Current Protection 46
Setting name
Units

10..50000 A
1A/5A

1600 A
5A

Range

Setting

Negative Sequence Current


Warning
Time delay Negative Sequence
Current Warning
Negative Sequence Current
Tripping
Tripping Characteristics
Time delay Negative Sequence
Current Tripping

I2w

0.02~0.5 x In

0.18

tw

0.1..20 s

I2s

0.02~0.5 x In

0.22

CHAR
T(DEFT)
T(INVS)

DEFT/INVS
1200 s
300...3600s

DEFT
2

Prim.
Current
160

Other functions are disabled


Power System Data 1
CTs

Prim.
Current
288

352

Time Current Characterstic Curves

10000
1000

IC1_LTPNL
OUTdoor_vcb

100

TR1_feeder

IC_3pnl

Time in Seconds

10

RMG

TR1

.01

.1

Inrush

.5

11000 Volt Phase


0 - 11kV-ltpanel

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

1000

10000
06-12-2013
21:46:13
TAJGATEWAY

10000
1000
100

DG_IC1_LTPNL

.01

.1

Time in Seconds

10

DG1_AMF PNL_RP6

.5

415 Volt Phase


1 - DG Set Feeding

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

1000

10000
06-16-2013
23:30:34
TAJGATEWAY

10000
1000
100

LTPNL_EB_IC1
10

11kV_RMG_RP1

Time in Seconds

11kV_OD PNL_RP2
11kV_3PNL_IC_RP3

.01

.1

11kV_3PNL_OG_RP4

.5

11000 Volt Ground


0 - 11kV-ltpanel

10

100
Current in Amperes
Time-Current Characteristic Curves

1000

10000
06-17-2013
08:31:52
TAJGATEWAY

10000
1000
1

Time in Seconds

10

100

DG_IC1

.01

.1

RP6

.5

415 Volt Ground


1 - DG Set Feeding

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

1000

10000
06-17-2013
07:50:20
TAJGATEWAY

Comments and Recommendation


1

DG Auxiliary Panel ,Out going MCCBs are rated for 16 kA As per SLD.But as per calculations the Shorcircuit current
of the bus bar is working out to be 18231 A.Therefore all MCCbs in this Panel to be up graded to 25 kA

Mezzanine Floor Ventilation panel has been provided with 10 kA MCBs.The short circuit current of this board is
working out to 13755 Amps.The MCBs will not withstand the fault currents.These MCBs to be upgraded to 25 kA

In Terrace Floor Ventilation panel also has been provided with 10 kA MCBs for certain feeders.The short circuit
current of this board is working out to 13755 Amps.The MCBs will not withstand the fault currents.These MCBs to
be upgraded to 25 kA