Professional Documents
Culture Documents
50 THK. GROUT
PL
215
1300
FGL
AS PER SITE
650
10-12 T
10 T @ 200 C/C
1500 MIN. 75
250
75
1800
75
1800 950
4-M20 X 400 FOUNDATION BOLT
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE SPECIFIED 2. FGL CORRESPONDS TO FINISHED GROUND LEVEL R.L. +10.00M. 3. EGL CORRESPONDS TO EXISTING GROUND LEVEL OF R.L. +8.16M OPTED FROM MINIMUM VALUE OF R.L. FROM CONTOUR DRAWING.
1200
420
650
4. PLINTH LEVEL (PL) = +200mm ABOVE FGL . 5. ALL STRUCTURAL CONCRETE SHALL BE OF M20 GRADE (1:1.5:3) CONFORMING TO IS:456 -2000
6. ALL REINF. SHALL BE H.Y.S.D. BARS OF GRADE Fe 415 CONFORMING TO IS:1786 LATEST EDITION 7. THE CLEAR COVER FOR REINF. SHALL BE 50mm FOR FOOTINGS & 40mm FOR PEDESTALS. 8. LAP/ANCHOR LENGTH SHALL BE 50 x DIA. OF BARS. 9. PROVIDE 50mm GROUTING FOR FIXING ALL FOUNDATION BOLT
1300
10. SBC CONSIDERED = 13 TON/SQM 11. FOR FURTHER REFERENCE REFER CORRESPONDING STRUCTURE DRAWING.