Digital Protective Relays

Larsen & Toubro


Larsen & Toubro is a technology-driven company that infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering, Construction, Electrical & Automation, Machinery and Information Technology. L&T Switchgear, a part of the Electrical & Automation business, is India's largest manufacturer of low voltage switchgear, with the scale, sophistication and range to meet global benchmarks. With over five decades of experience in this field, the Company today enjoys a leadership position in the Indian market with a growing international presence. It offers a complete range of products including powergear, controlgear, industrial automation, building electricals & automation, reactive power management, energy meters, and protective relays. These products conform to Indian and International Standards. L&T limited offers a wide range of Microprocessor based State-of-the-art digital protective relays suitable for LV, MV and HV power distribution systems. These relays are manufactured at L&Ts Mysore works equipped with modern infrastructure and employing latest manufacturing and testing equipments. L&Ts range also include relays for special applications manufactured by Microelettrica Scientifica, Italy. The applications include Feeder Management, Load Sharing, Load Shedding, Synchronising, Grid Islanding etc. L&T also manufactures a range of electronic single phase energy meters, three phase energy meters and trivector meters at the Mysore works.

Mysore Works

Contents

Pages ANSI / IEEE Device Function Number Details Time - Current Characteristics Over Current Relays & Earth Fault Relays - MC31A, MC61A, MC61C Current Sensing Relays - MC12A, ME12A, SC14S Reverse Power Relay - MRP11 Voltage Relay - MV12 Power Factor Control Relays - etaCON Series RPM14, RPM08 Motor Protection Relays - MM30, MM30W, N-DIN-MA MCOMP, MPR300 Generator Protection Relays - MG30, MG30I, MD32G Transformer Protection Relays - IM30T, MD32T, MD32TM Feeder Protection Relays - MC20, MC30 Vector Surge Protection Relay - UM30A, FMR Control & Supervision Relays - MW33 Synchronising Load Sharing Relays - SPM21, RRS Voltage and Frequency Relays - MC1V, MC3V, UFD34 Schematic - Relay Application 1 2 3 5 7

9 11 13 15 17 19 21 23 25

27 29

ANSI/IEEE

Correlation between ANSI/IEEE device function number and relays


Device No. Function Name L&T Relays MS Relays

21 25 27 32 37 40 45 46 47 49

Under impedance relay / Distance relay Auto synchronising Synchro-check relay AC under voltage relay Power directional relay Under current or under power relay Field control (loss of field) relay DC over voltage relay Reverse phase or phase balance current relay Phase-sequence or single-phasing voltage relay Machine or transformer thermal relay

MV12 MRP11

MPR300 50 Instantaneous over current (or rate-of-rise) relay ME12 MC12A MC61A / MC61C 51V, 50V 50BF 50N Voltage restrained over current relay Breaker - failure Instanteneous earth fault over current relay

51

AC time over current relay

51N-(51G)

Ground fault time over current relay

58 59 59/81 60 64 64S 64R 67 67N-(67G) 76 78 79 80 81 86 87 87N-(87G) 90 95 df/dt

Rectifier failure relay (rotating diodes) AC over voltage relay

Overexcitation relay V/Hz Voltage balance relay Ground detector (insulation to ground failure of machine or other apparatus) Machine stator ground fault detector relay -Machine rotor ground fault detector relay -AC directional over current relay -Directional ground fault over current relay -DC over current relay Phase angle measuring or out of-step protection relay Reclosing relay -DC under voltage relay -Frequency relay -Lock-out relay -Differential protective relay SC14S -Ground fault differential protective relay Regulating device to adjust a quantity Automatic active or reactive load sharing relay Vector surge protection relay Rate of change of frequency

MC12A MC61A MC61C MC12A MC61A MC31A MC61C MC12A MC61A MC31A MC61C MV12 ---

MG30 / MG30-I SPM21 SCM21 UM30-A / MC1V / MC3V UFD34 MG30 / MW33 / MG30-I MM30 MW33 MG30 / MG30-I UBC / 45 IM30T MM30 UM30-A, MC3V IM30T MG30 / MG30-I MM30 / MM30-W MC20 / MC30 IM30-T / IM30-AP FMR MG30 / MG30-I MG30 / MG30-I MC20 / MC30 / FMR / IM30T / IM30AP IM30 AP / IM30-T MC20 / MC30 FMR / IM30-T IM30-AP / IM30-T MC20 / MC30 FMR / IM30-T -IM30-AP / IM30-T MC20 / MC30 FMR -RHS -UFD34, MW33 UM30-A / MG30 / MG30-I UM30-A MG30 MG30 UBO / CR FMR FMR IM30-GOS MC20R UBC / 80 UM30-ASV / MG30 UFD34 / MC1V / MC3V / MW33 -MD32G MD32T / MD32TM MD32G, MD32T -RRS UM30-A UFD34

Time - Current Characteristics

Product Design Standards


Reference standards Dielectric test Impulse test HF disturbance test Electrostatic discharge test Electrical fast transient Radiated electro magnetic field test Surge immunity Ring wave test Voltage dips & interruption test Power frequency magnetic test : : : : : : : : : : : IEC 60255, IEC 61000, IS3231, IS8686 IS 3231 / IEC 60255-5 IS 8686 / IEC 60255- 5 IS 8686 / IEC 60255-22-1 IEC 61000-4-2 IEC 61000-4-4 IEC 61000-4-3 IEC 61000-4-5 IEC 61000-4-12 IEC 61000-4-11 IEC 61000-4-8

Time - Current Characteristics (At TMS = 1)


1,000

100

Trip Time (Sec.)

10

A 1 B C

D 01 1 10 20

Multiple of set current (Is)

For Trip time at TMS other than 1 Trip time = (Trip time at TMS = 1) x TMS or 50 msec whichever is more.

A : Normal Inverse 3.0 sec B : Normal Inverse 1.3 sec C : Very Inverse D : Extreme Inverse

Over Current and Earth Fault Relays


Three phase over current & earth fault relays Salient Features Display of currents, settings, Trip data & Trip history for analysis & trouble shooting Built in self supervision & self testing feature to ensure continuous reliability Separate indication for power ON & programming mode on relay fault Separate fault indication In MC61C - Communication with computer & breaker control through RS485 Port Four user programmable output relays

Model
Description

MC31A
3 Phase O/C + E/F

MC61A
3 Phase O/C + E/F + Highset

MC61C

3 Phase O/C + E/F + Highset Communication and breaker control Device code 50/51 RYBN 51 RYBN 50/51 RYBN Design Numerical relay Numerical relay Numerical relay Lowset O/C - Is Lowset O/C - Is Lowset O/C - Is Highset O/C - Ihs Lowset E/F - Os Highset O/C - Ihs Functions available Lowset E/F - Os Lowset E/F - Os Highset E/F - Ohs Highset E/F - Ohs O/C Is = 20-200% step 5% O/C Is = 20-200% step 5% O/C Is = 20-200% step 5% E/F Os = 5-80% step 5% E/F Os = 5-80% step 5% E/F Os = 5-80% step 5% HS O/C = (0.2 to 40) x in step of - HS O/C = (0.2 to 40) x in step of Time characteristics available 0.2 in or disable 0.2 in or disable NI, VI, EI, definite time Settings HS E/F = (0.1 to 20) x on step of - HS E/F = (0.1 to 20) x on step of TMS 0.1 - 1.6 step 0.05 0.1 on or disable 0.1 on or disable Time characteristics available Time characteristics available NI, VI, EI, definite time NI, VI, EI, definite time TMS : 0.1 - 1.6 step 0.05 TMS : 0.1 - 1.6 step 0.05 HS delay:0.1-2 sec step 0.01 Site selectable trip time char. Site selectable trip time char. sec or inst. RS485 communication Highset can be disabled Other features Breaker control Display of currents, trip count Display of currents, trip count Auto doubling of highset, Self supervision feature Self supervision feature Relay co-ordination - BI & BO Burden on CT 0.25 VA on CT/Phase 0.25 VA on CT/Phase 0.25 VA on CT/Phase Burden on PT Not applicable Not applicable Not applicable Operating temp 00C to 600C 00C to 600C 0 0C to 600C Weight < 2kg < 2kg < 2kg Burden on auxiliary supply 10 VA 10 VA 10 VA Output contact 1 N/O Contact for self supervision 1 N/O Contact for self supervision 1 N/O Contact for self supervision, 1N/O for trip Construction Drawout Drawout Drawout 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224 Dim W x H x D in mm 113 x 142 113 x 142 113 x 142 Panel cutout Ordering Information 20-110 V AC / DC or 20-110 V AC / DC or Auxiliary supply Type 1 20-110 V AC / DC or 88-264 V AC / DC Type 2 88-264 V AC / DC 88-264 V AC / DC 1 A or 5 A 1 A or 5 A 1 A or 5 A CT Rating (not site selectable) (site selectable) (site selectable) 4 NO 4 NO or 2 NO + 2 NC 4 NO or 2 NO + 2 NC Output contacts

Wiring Diagrams
MC31A
R Y B 1 2 3 4 13 5 6 15 16 7 8 R Y B 1 2 3 4 13 5 F50(Is) 6 F51(0s) 15 16 7 8 21 22 L/+ 25 PROG. ERROR R5 29 30 R Y B E R4 27 28 R3 12 17 18 MICRO CONTROLLER

R1

N0 9 10

MC31A
PROTECTION R2

NC 11

In = 0n =

1A; 1A;

5A 5A

N/- 26

MC61A
R Y B 1 2 3 4 13 5 6 15 16 7 8 R Y B 1 2 3 4 13 5 F50(Is) 6 15 16 7 8 21 22 In = 0n = 1A; 1A; 5A 5A L/+ N/25 26 PROG ERROR R5 29 30 R Y B E F51(Os) F50(Ihs) F51(Ohs) R4 27 28 18 R3 17 12 MICRO CONTROLLER

R1 9

N0

MC61A
PROTECTION R2

10 NC 11

MC61C
R Y B 1 2 3 4 13 5 6 15 16 7 8 R Y B 1 2 3 4 13 5 F50(Is) 6 15 16 7 8 21 22 L/+ 25 PROG ERROR C SS+ 9 PIN MALE D1 R Y B E D2 D3 30 19 L/R 20 BI* 31 32 F51(Os) F50(Ihs) F51(Ohs) R5 29 R4 MICRO CONTROLLER R2 R1 9 10 11 12 R3 17 18 27 28 NC BKR OPEN BKR CLOSE NO

MC61C
PROTECTION

In = 0n =

1A ; 1A ;

5A 5A

N/- 26

Current Sensing Relays


Single phase over current / earth fault relay Sensitive E/F relay / instantaneous current relay Salient Features Easy setting through front panel DIP switches Indication for power ON and trip status Test feature - helps in better maintenance Compact, light weight helps in reducing panel size & thickness

Model
Description Device code Design Functions available

MC12A
1 Ph O/C or E/F 50/51 or 50N/51N Microcontroller based Lowset O/C - Is Highset O/C - Ihs Lowset E/F - Os Highset E/F - Is O/C Is = 50-200% Step 10% or E/F Is = 10-40% Step 2% or E/F Is = 20-80% Step 4% HS O/C = (2-16) xls step 2 Is HS E/F = (2-16) xls step 2 Is Time characteristics availableNl, VI, EI, Definite time 3 ranges of def time (1, 10,100) TMS : 0.1 - 1.6 Step 0.1 Site selectable trip time char. Highset can be disabled

ME12A
1 Ph Sensitive E/F 50N/51N Microcontroller based Lowset S E/F - Is Highset S E/F - Ihs

SC14S
Instantaneous current relay 87N/64R Static

S E/F = 1-16% step 1% HS S E/F = (2-16) xls in steps of 2 ls

Is = 10-40% step 5% or 20-80% step 10%

Settings

Other features Burden on CT Burden on PT Operating temp Weight Burden on auxiliary supply Output contacts Construction Dim W x H x D in mm Panel cutout Auxiliary supply CT Rating Range setting Type 1 Type 2

Time characteristics availableNI, VI, EI, Definite Time 3 ranges of def Time (1, 10, 100) TMS : 0.1 - 1.6 Step 0.1 Site selectable trip time char. Highset can be disabled Harmonic rejection 0.25 VA on CT 0.25 VA on CT Not applicable Not applicable 00C to 600C 00C - 600C < 1.5kg < 1.5kg 5.5 VA 5.5 VA 2 C/O Contacts (S/R) 2 C/O Contacts (S/R) Drawout Drawout 71 x 158 x 224 71 x 158 x 224 62 x 142 62 x 142 Ordering Information 20-110 V AC / DC or 20-110 V AC / DC or 88-264 V AC / DC 88-264 V AC / DC 1 A or 5 A 1 A or 5 A 10-40% or 20-80% or 50-200% Site selectable

Time characteristics availableInstantaneous (25ms) or time delayed 100ms / 200ms Self powered Relay testing possible by ext. 24 V Supply Flag indication / LED indication 6 VA Not applicable 00C to 600C < 1.5kg Not applicable 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142 Not applicable 1 A or 5 A 10-40% or 20-80%

Wiring Diagrams

MC12A / ME12A

COM

+VE/PH. Aux. Supply -VE/N P. Control Ckt. F50/50N F51/51N R1

10 11 12

COM

MC12A / ME12
SETTING RANGE (Is) In 1A 5A AUX SUPPLY 24 - 110V AC/DC 95 - 240V AC/DC MC12A (10-40)% In (20-80)% In (50-200)% In ME12 (1-16)% In

SC14S

11 10 9

DC-DC Test Convrt.

1 Control Ckt. R 3 5 6

7 + Test (24V) Voltage 8 12

SC14S
In 1A 5A CT OPERATED RELAY NO AUXILIARY SUPPLY REQUIRED SETTING RANGE (Is) (10-40)% IN (20-80)% IN

Reverse Power Relay, Under Voltage or Over Voltage Relay

Salient Features Easy setting through front panel DIP switches LED indication for power ON and trip status Test feature - helps in better maintenance Compact, light weight helps in reducing panel size & thickness

Model
Description Device code Design Functions available

MRP11
Reverse power 32 Microcontroller based Reverse power level PT input Vn 110 V, 415 V AC CT input In 1 A / 5 A Pick up level 1% - 15% Min. setting 0.5% TMS 0 to 1.5 step 0.1 Definite time characteristics LED indication Test feature < 0.25 VA < 0.05 VA 00C to 600C < 1.5kg < 8 VA 1 N/O + 1 C/O Drawout 71 x 158 x 224 62 x 142 Ordering Information 20-110 V AC / DC 88-264 V AC / DC 1 A or 5 A Upto 380 V AC

MV12
1 Ph U/V or O/V 27 or 59 Microcontroller based Lowset U/V - Vs Lowset O/V - Vs U/V Vs = 95-20% step 5% O/V Vs = 105-180% step 5% Time characteristics availableInverse time, definite time TMS : 0.1 - 1.6 Step 0.1 Site selectable U/V or O/V Site selectable trip time char. < 0.25 VA 0.075 VA on PT 00C to 600C < 1.5kg 8 VA 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142 20-110 V AC / DC 88-264 V AC / DC Not applicable 110 V / 240 V / 415 V (site selectable)

Settings

Other features Burden on PT Burden on CT Operating temp Weight Burden on auxiliary supply Output contacts Construction Dim W x H x D in mm Panel cutout Auxiliary supply CT Rating PT Rating Type 1 Type 2

Wiring Diagrams

MRP11

1 R Y B

4 + VE / PH. Aux. Supply VE / N P. Control Ckt. F32 R1 5

2 3 11

7 8 6

12 9 10 Vn 110 V AC 415 V AC In 1A 5A AUX SUPPLY 24110 V AC/DC 95240 V AC/DC

MRP11

MV12

1 5 2 3 4 11 9 12 7 +VE/PH. Aux. Supply -VE/N R1 P.Control Ckt. F27 F59 6 8 4

MV12

Power Factor Control Monitoring Relays


Intelligent Power factor controllers with Automatic set-up and TTL/RS232 Port
w

Salient Features Auto / Manual mode Measurement Sensitivity - 2.5% 4 Quadrant / 2 Quadrant operation Automatic recognition of current flow direction Online display of PF, Voltage, Current, kVAr, capacitor overload and Panel temperature The last two contacts are programmable as alarm and / or fan control except for etaCON 3 Capacitor over-current and panel over-heating protection Use in co-generation systems - 4 Quadarant operation
etaCON Series

Ne

096

Inbuilt Controller Set-up feature provides an option of Automatic configuration of etaCON controller. TTL / RS232 Communication port to interface with PC for quick set-up, function and alarm customising and testing.

Product
Model No.of steps Design Display Current Input Voltage Input Rated Frequency Measurement

etaCON L series APFC relay


etaCON L3; etaCON L5; etaCON L7 3, 5, 7 etaCON L8; etaCON L12 8, 12 Digital Microprocessor based 3 Digit LED 5 Amp 415 VAC 15% 50/ 60 Hz

Instantaneous PF, V, I, kVAr, Capacitor Over load Panel temperature, Average weekly PF, Maximum Voltage, current, capacitor overload, panel temperature value Target PF adjustment: 0.8 inductive to 0.8 capacitive Reconnection time of same capacitor: 5 - 240 secs Switching time sensitivity: 5 - 600 secs Under/ Over compensation; Low/ High Current; Low/ High Voltage; Capacitor Overload due to harmonic Voltage; Over temperature; No-voltage release Less than 10 VA Less than 0.8 VA 144 x 144 x 93 mm 138.5 x 138.5 mm Ordering Information 415 V AC 5 A secondary 8; 12 steps

Setting

Alarms

Power consumption Burden on CT Dimensions W x H x D in mm 96 x 96 x 96 mm Panel cutout 92 x 92 mm Voltage Input CT Input No.of steps 415 V AC 5 A secondary 3; 5; 7 steps

Wiring Diagrams

etaCON L3/L5/L7

MAINS L1 L2L3 1 2 3 4 5 6 7

Current /5A S1 S2

Voltage 415V 9 10 C 1 2 3 4 5 6 7 8

FU11 CT1

OS1

FU1
FU8 FU9 FU10

FU2

FU7

KM1

KM2

KM7

LOAD

K1

K2

K7

etaCON L8/L12

MAINS L1 L2 L3 1 2 3 4 5 6 7 8 9 10 11 12

Current /5A S1 S2
CT1

Voltage 415V 15 16 C 1 2 3 4 5 6 7 8 9 10 11 12 13 14

FU16

OS1

FU1 FU13 FU14 FU15

FU2

FU12

KM1

KM2

KM12

LOAD

K1

K2

K12

10

Power Factor Control Monitoring Relays


(8 & 14 Stages) Intelligent power factor controller relay Salient Features On line display of system PF Easy setting through - front panel push button Suitable for non-uniform banks LED indication for alarm code, no. of banks selected, PF status-lead / lag / unity Auto / Manual mode Measurement sensitivity of 1% Automatic C/K correction Display of Current, Voltage, kVAr, & Capacitor values

Model
Description Device code Design Functions available

RPM-8
Automatic power factor controller 8 stage Microcontroller based Automatic PF control upto 8 stage Switching time 1-255 sec in step of 1 sec for same Bank switching Auto C/K selection PF control range 1% to 120% of rated current Can accept unequal banks Display of PF, V, l, kVAr LED indications for faults Alarm signal for CT reversal, under current, under compensation, over compensation, over voltage, 1 A / 5 A field selectable 0.3 VA 15 VA 00C to 600C < 2kg 8 N/O 1 N/O contact for alarm 144 x 144 x 100 138 x 138 Ordering Information 240 V AC

RPM-14
Automatic power factor controller 14 stage Microcontroller based Automatic PF control upto 14 stage Switching time 1-255 sec in step of 1 sec for same Bank switching Auto C/K selection PF control range 1% to 120% of rated current Can accept unequal banks Display of PF, V, l, kVAr LED indications for faults Alarm signal for CT reversal, under current, under compensation, over compensation, over voltage, 1 A / 5 A field selectable 0.3 VA 15 VA 00C to 600C < 2kg 14 N/O 1 N/O contact for alarm 144 x 144 x 100 138 x 138 240 V AC

Settings

Other features

Burden on CT Burden on PT Operating temp Weight Output contacts Dim W x H x D in mm Panel cutout Auxiliary supply

11

Wiring Diagrams

RPM-8

Ph 230V AC 1 2 3 ALARM 4 5 6 S1(5A) S1(1A) S2 7 8 9 10 11 12 13 14 15 16 R8 R7 R6 R5 R4 R3 R2 R1 17 18 19 20 21 22 23 24 Bank #1 R Y B N To Load Bank #8 50 Hz N

+ + -

RPM-14
Ph 240V AC R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 1 2 3 4 5 6 7 8 9 10 11 12 R13 R14 13 14 15 50 Hz N

+ +

16 17 18 19 20 21 22 23 24

S2 S1(1A) S1(5A) Bank #1 ALARM

Bank #14 R Y B N To Load

12

Motor Protection Relay


Motor protection relay Motor protection relay with voltage input Salient Features Display of various parameters, trip count and trip data LEDs for fault indication User programmable output relays Built in self supervision & self testing feature helps maintenance RS485 Port for serial communication with MSCOM user friendly software

Model
Description

MM30
Motor protection 50/51, 51LR, 64, 68, 49, 46, 37, St no, ltr Numeric Trip circuit supervision Thermal O/L and Pre-alarm Locked rotor Current unbalance, phase reversal, Phase loss Over current Earth fault Repeat and prolonged starts Restart inhibition No load running Blocking function

MM30W

N-DIN-MA
Motor protection 49, 51LR, 46, 37, 50/51, 64, St no, Itr Numeric Thermal O/L and Pre-alarm Locked rotor Current unbalance, phase reversal, phase loss Over current Earth fault Repeat and prolonged starts Restart inhibition No load running Blocking function

Motor protection 50/51, 51LR, 64, 49, 46, 37, St no, Device code ltr, 55, 68, 81, 47, 12/14, 27/59 Numeric Design Trip circuit supervision Thermal O/L and Pre-alarm Locked rotor Current unbalance, phase reversal, phase loss Over current Earth fault Functions available Repeat and prolonged starts Restart inhibition No load running Blocking function Under frequency / Over frequency Under voltage / Over voltage Running hours Low PF Auto setting Auto setting 1 A or 5 A site selectable 1 A or 5 A site selectable (Default 5 Amp) (Default 5 Amp) Selectable motor time constant Selectable motor time constant Other features (1 - 60 min) (1 - 60 min) Display of parameters Display of parameters Built in self supervision Built in self supervision RS485 port RS485 port 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A Burden on CT 0.04 VA Not applicable Burden on PT 100C to 600C 100C to 600C Operating temp < 2kg < 2kg Weight 8.5 VA 8.5 VA Burden on auxiliary 4 C/O + 1 C/O for self supervision 4 C/O + 1 C/O for self supervision Output contacts Drawout Drawout Construction 121 x 158 x 224 121 x 158 x 224 Dim W x H x D in mm 113 x 142 113 x 142 Ordering Information 20-110 V AC / DC or 20-110 V AC / DC or Auxiliary supply 88-264 V AC / DC 88-264 V AC / DC

2 Programable digital inputs 1 Removable front face panel LCD Display 1 A or 5 A site selectable (Default 5 Amp) Selectable motor time constant (1-60 min) Display of parameters Built in self supervision RS485 port, front RS232 port (on FFP) 0.075 VA for 5 A, 0.01 VA for 1 A Not applicable 100C to 600C < 1kg 3 VA 2 C/O contacts DIN rail mounting FFP = 106 x 45 x 16 RMB = 106 x 85 x 72 20-110 V AC / DC or 88-264 V AC / DC

13

Wiring Diagrams

MM30
A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 In=5A In=1A A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 44 PRESA/TAP 31:Ion=5A PRESA/TAP 33:Ion=1A Display Microp. R1 21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3 2 1 34/38 23 24
IEC 255

(21) N.O. N.C.

(10) N.O. N.C.

MM30
Function

R2

R3

F37 F46 F49 F51 F51R F64 St.No.> AI.0> Itr Progr. Int. Fault Keyboard

R1 R2 R3 R4

R4

R5

R5 C SS+ 9 Pin Male

L/+ N/-

12 13

N-DIN-M
N-DIN-M
A B C
10

C
10

C
10 FFP Display / Keyboard / Signals A B + 0

RS485 11 11 11 RS485 8 8 8 A B + 0 RMB

N - DIN - M
9 9 9

Functions F26 F37 F46


17

R1

16

12

12

12

F49 F51
BT 2 1

13

13

13

F51LR F64

R2

15

Digital Input 1 Digital Input 2 Thermistor Input Common

T T
0

6 7 C 2 1 21 22

D1 D2 RTD

St.Ctrl PWR / I.R.F Trip ON OFF


B (S-) A (S+)

14 4 5

RS485

MS - SCE 1752 - R1

14

Motor Protection Relay


Intelligent motor protection & control relay - MCOMP Economical motor protection relay - MPR 300

MCOMP Relay

MPR 300

Model
Description Device code Design

MCOMP
Motor protection 49, 14, 46, 50N, 3, 59, 27, 47, 81H, 81L, 66, 27LV, 47a, 47b Numeric Thermal over load Locked rotor Current unbalance Phase loss Under current Over voltage Under voltage Over frequency Under frequency Max. no. of starts Reacceleration Phase reversal Intelligent relay with separate protection, display and CT modules Suitable for 50/ 60 Hz Can be used with DOL, RDOL and Star delta starters Communication options Modbus RTU, Modbus TCP IP and Profbus Not applicable Not applicable 0 10 to 60 C < 2kg < 8 VA 4 C/O Split protection unit 92 x 123 x 103.95 80 - 240 V AC/DC

MPR 300
Motor protection 49, 51LR, 64, 46, 37 Numeric Thermal overload Locked rotor Earth fault Single phasing No load running

Functions available

Other features

upto 88 A Trip time characteristics as per IEC947

Burden on PT Burden on CT Operating temp Weight Burden on auxiliary supply Output contacts Dim W x H x D in mm Auxiliary supply

Not applicable Not applicable 0 0-60 C < 0.5kg < 8 VA 1NO+1NC Not applicable 240 V AC

15

Wiring Diagrams

MCOMP Relay
Typical Dol feeder with
R Y B N 415V, 3PH, 4-wire, 50Hz PH N X-25 T X-26 T 240V AC Test Bus

M COMP

NLK

Q1

F11 111 6A 112 F12 1216A122 F13 1316A132

L11 - 201

N11 - 201
2 4 6 Drive Available 1 3 5 Run Trip Unused Do

K4 K3 T5 R Y B
CBCT

P1 T1 P2

S1 S2

XC1-1 XC1-2 XC1-3 XC1-4 XC1-5 XC1-6 XC1-7 XC1-8 XC1-9 XC1-10

1 2 3 8 N BY R
C1 Ref. Voltage C2

81 82 83 84 85 86 87 88 89 90 91 92

D1
PMR/ COMM

C8

Digital Output Relay

P1 T2 P2

S1 S2

P1 T3 P2 R T4 CBCT Y

S1 S2

M COMP CT UNIT

L&T Make MCOMP


C7 AUX. VOLT C6 DIGITAL INPUTS N PH 61 62 63 64 65 66 67 71 72 C4 RS 485

C3

Motor Status
ESE

LED DISPLAY
ESC

PMR/ CO
P 75

Alarm Pickup TRIP

ELECT

N 76 E 77
M COMP

Stop Command Start Command Start Command

S1

X-42
S
PH

Run

83

86

Unused DI

Hand RST P.B.

43 K4 44

89

Run Led

K4 A2

H2 R

H1 G 12

22

Trip Led

S1

11 Stop P.B 12

A1

21

11

Trip

S2

K3 106 82 Hand Start P.B.

81

Drive Available

X-43 S

K3 106 85

84 K3 106 88

87

MPR300 Relay

Start N/O Stop (N/C)

Aux. N/O

2 NC

NO

MPR300 Typical connection diagram for Direct Starting application

Aux Supply

16

Generator Protection Relays


Multifunction generator protection relays Percentage based generator differential relay Salient Features Display of various parameters, trip count & trip data on 8 digit alphanumeric display Separate LEDs for various fault indication Four user programmable output relays Built in self supervision & self testing feature help maintenance Easy operation by 5 push buttons RS485 Port for serial communication with MSCOM user friendly software

Model
Description

MG30

MG30-I

MD32-G
Generator differential 87, 50/51, 64S/87N, 68 Numeric Generator differential Bias % with dual adjustable slope Over current Stator E/F CB failure protection

Generator protection Generator protection 21, 24, 27/59, 32, 37, 40, 46, 49, 50/27, 21, 24, 27/59, 32, 37, 40, 46, 49, 50/27, Device code 50V/51V, 51BF, 60FL, 64S, 68, 81 50V/51V, 51BF, 60FL, 64S, 68, 81 Design Numeric Numeric Two levels of voltage controlled O/C, Two levels of voltage controlled O/C, Thermal image with pre-alarm, Thermal image with pre-alarm, Two levels of current unbalance Two levels of current unbalance Two levels of under / over voltage Two levels of under / over voltage Two levels of under / over frequency Two levels of under / over frequency Functions available 95% + 100% stator earth fault 95% stator earth fault Two levels of over excitation Two levels of over excitation Two levels of under impedance, Two levels of under impedance, Loss of field, under power Loss of field, under power PT Fuse failure, breaker failure, PT Fuse failure, breaker failure, Inadvertent C/B closure etc. Inadvertent C/B closure etc. 1 A or 5 A site selectable 1 A or 5 A site selectable Display of parameters Display of parameters Other features Built in self supervision Built in self supervision RS485 port, MODBUS protocol RS485 port, MODBUS protocol Blocking inputs & Blocking outputs Blocking inputs & Blocking outputs Burden on CT 0.25 VA for 5 Amp CT 0.25 VA for 5 Amp CT 0.01 VA for 1 Amp CT 0.01 VA for 1 Amp CT Burden on PT 0.05 VA (MG30) 0.05 VA (MG30) Burden on auxiliary supply 8.5 VA 8.5 VA Operating temp 100C to 600C 100C to 600C Weight < 2kg < 2kg 3 C/O + (1 N/O + N/C) + separate relay 3 C/O + (1 N/O + N/C) + separate relay Output contacts 1 C/O for self supervision 1 C/O for self supervision Construction Drawout Drawout Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 Panel cutout 113 x 142 113 x 142 Ordering Information Type 1 20-110 V AC / DC or 20-110 V AC / DC or Auxiliary supply Type 2 88-264 V AC / DC 88-264 V AC / DC

1 A or 5 A site selectable Display of parameters Wave form capture feature Built in self supervision, - RS485 port 0.2 VA for 5 A, 0.01 VA for 1 A Not applicable 8.5 VA -100C to 600C < 2kg 4 C/O, S/R or H/R or time del 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142 20-110 V AC / DC or 88-264 V AC / DC

17

Wiring Diagrams

MG30
25 Display
1/5A

R1

21 10 11 22

(21 22) N.O. N.C. (10 11) N.O. N.C.

26
1/5A

Microp.

MG30
Funzioni Function

27
1/5A

R2 R3

7 9 8 18 20 19 4 6 5 15 17 16

28 39 29
1/5A

1>,Z<,Uo> 12>,T> Zc<, O>


1/5A

R1 R2

R4

30 41 31 42 32 43 33

U,f W<, Ir> R3 R4

R5

1/5A

IC, 60FL B.I./B.F.

14 3 2

14 3 2 1 37(b) To Rex Relay 38(a) Expansion 23 24

MG30
44

1/5A

Progr. Int. Fault

R5
C S S+

12 13

Keyb0ard Tastiera

9 PIN MALE

CE MS-SCE 1629-R0 In=1A In=5A Un=100V

MG30-I
25
Display

R1

21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 18 14 3 2 1 37(b)
c ss+

(21 - 22) N.O. N.C. (10 - 11) N.O. N.C.

26 27 28 39 29
1/5A

Microp.

MG30-I
Funzioni Function

R2 R3

I>, Z<, Io> I2>, T> Zc<,


1/5A

R1 R2

R4 R5

30 41 31 42 32 43

>

U, 1 w<+ Ir> R3 R4

1/5A

IC, 60FL B.I / B.F.

14 3 2

Progr.

33

1/5A

Int.fault

R5

12 In = In = 1A 5A 13 MS-SCE1759-R0

Keyboard Tastiera

38(0) 23 24

To Rex Relay Expansion

RS485

MD32-G
A 87G + 87N B C I1A I1B I1C 26
1/5A

25
1/5A

Display Microp.

R1

21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3

(21) N.O. N.C. (10) N.O. N.C.

R2

27 28 39 G 29
1/5A 1/5A

MD32-G
Function F187G F287G F87N R1 R2 R3 R4 R5 R3

R4

I2A I2B R = Stabilising resistor Z = Protection surge arrester (if required) I2C

30 41 31 42 32 43 Z R 33

1/5A

B3
1/5A

Progr. Int. Fault

R5

B2 B1
C SS+

1/5A

50-60

L/+ 12 N/- 13

Keyboard

2 1 34/38 23 24

9 Pin Male

18

Transformer Protection Relay


Percentage based transformer differential relay 3 Phase thermal + over current + earth fault relay for transformer protection Salient Features Display of various parameters, trip count & trip data on 8 digit alphanumeric display Separate LEDs for individual fault indication Four user programmable output relays Built in self supervision & self testing feature help maintenance Easy operation by 5 push buttons RS485 Port for serial communication with MSCOM user friendly software

Model
Description Device code Design

MD32T
Transformer differential + Restricted E/F 87 RYB, 87N

MD32TM
Transformer differential 87 RYB

IM30T
3 Ph O/C, E/F + Thermal

Functions available

Other features

Burden on CT Operating temp Weight Burden on auxiliary supply Output contacts Construction Dim W x H x D in mm Panel cutout Auxiliary supply Type 1 Type 2

Numeric Lowset differential Lowset op time : <=30mS Highset differential Highset op time : 6-20mS Restricted earth fault Dual slope bias Highset can be Biased / Unbiased 2nd harmonic restraint setting 5th harmonic restraint setting Auto correction of CT ratio Zero sequence compensation Blocking function Display of parameters Display of parameters Built in self supervision Built in self supervision RS485 port RS485 port 1 A or 5 A site selectable 1 A or 5 A site selectable Waveform capture feature Waveform capture feature 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A 100C to 600C 100C to 600C < 2kg < 2kg 8.5 VA 8.5 VA 5 C/O, S/R or H/R or Time del 5 C/O, S/R or H/R or Time del Draw out Draw out 121 x 158 x 224 121 x 158 x 224 113 x 142 113 x 142 Ordering Information 20-110 V AC / DC 20-110 V AC / DC 88-264 V AC / DC 88-264 V AC / DC

50/51 RYBN, 49, 46, I2t, 51BF, 50N/51N Numeric Numeric Lowset differential Lowset O/C Lowset op time : <=30mS Highset O/C Highset differential Lowset E/F Highset op time : 6-20mS Highset E/F Dual slope bias Thermal overload Highset can be Biased / Unbiased Lowset current unbalance with 2nd harmonic restraint setting Definite / Inverse time tripping 5th harmonic restraint setting Highset current unbalance Auto correction of CT ratio Inrush energy protection Zero sequence compensation CB failure function Blocking function Blocking function Display of parameters Built in self supervision RS485 port 1 A or 5 A site selectable 0.2 VA for 5 A, 0.01 VA for 1 A 100C to 600C < 2kg 8.5 VA 5 C/O, S/R or H/R or Time del Draw out 121 x 158 x 224 113 x 142 20-110 V AC / DC 88-264 V AC / DC

19

Wiring Diagrams

MD32T / MD32TM
A 87T + 87N In1 B C I1A I1B I1C 26
1/5A

25
1/5A

Display Microp.

R1

21 10

(21) N.O.

27 V1 V2
V1 V2 Kv = V1 V2

MD32T
Function
F187T F287T F87N

R2

28 39

1/5A

R3

11 22 7 N.C. 9 (10) 8 18 N.O. 20 19 N.C. 4 6 5 15 17 16 14 3 2 1 34/38 23 24

29
1/5A

R1 R2 R3 R4

R4

I2A

R5

R = Stabilising resistor Z = Protection surge arrester (if required)

I2B

30 41 31 42 32 43 Z R 33 L/+ 12

1/5A

I2C

B3
1/5A

Progr. R5 Int. Fault

B2 B1
C SS+

1/5A

50-60

Keyboard

IEC 255

N/- 13

9 Pin Male

IM30T
A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 A B C 25 Display
1/5A

R1

21 10

(21) N.O.

26 27
1/5A

Microp. R2

IM30T
Function R3

11 22 N.C. 7 9 (10) 8 N.O. 18 20 N.C. 19 4 6 5 15 17 16

28 39 29
1/5A

41 30 32 43 31 42 33

1/5A

BT 2 50

F46 F49 F50 F51 F50N F51N F51BF I2t = K

R1 R2

R4

R5 R3 R4
RT

14 3 2 1
C SS+

44 In = 5A In = 1A L/+ 12
IEC 255

Progr. Int.fault
_

BIO

R5

BIF

PRESA/TAP 31 Ion = 5A PRESA/TAP 33 Ion = 1A

N/- 13

Keyboard

34/38 23 24

9 Pin Male

20

Feeder Protection Relays


3 Phase O/C & E/F relay with Highset + Auto Reclosure (Optional) 3 Phase directional O/C & E/F relay with highset Salient Features Display of various parameters, trip count & trip data on LCD screen Separate LEDs for various fault indication Built in self supervision & self testing feature Wave form capturing RS485 Port for serial communication with MSCOM user friendly software Front RS232 Port for local programming

Model
Description Device code Design

MC20
3P O/C + E/F + Highset + Autoreclosing (optional) 51, 51N, 50, 50N, 51BF, 79 (optional) Numeric Lowset O/C 2 Highset O/C levels Lowset E/F 2 Highset E/F levels Time current curves selectable according to IEC/IEEE standards Auto reclose (In MC20-R) Breaker failure protection Circuit breaker control via serial port Blocking output and blocking input for pilot wire selectivity co-ordination Time tagged multiple event recording Oscillographic wave form capture Accepts 3 digital inputs Display LCD 16 (2 x 8) characters 3rd Harmonic filter on the neutral input current Password protection facility 1 A or 5 A site selectable Display of parameters Built in supervision Modbus RTU / IEC870-5-103 Communication protocols Front RS232 port for local programming Oscillographic recording of input quantities RS485 serial communication port on back panel 0.1 VA for 1 A, 0.3 VA for 5 A NA < 7 VA -100C to 550C < 1.5kg 4 C/O contacts Drawout 83 x 164 x 225 64 x 137 Ordering Information 24-110 V AC/DC 88-264 V AC/DC

MC30
3P O/C + E/F + Highset 51, 51N, 50, 50N, 49, 51BF Numeric Lowset O/C 2 Highset O/C levels Lowset E/F 2 Highset E/F levels Thermal image Breaker failure protection Circuit breaker control via serial port Blocking output and blocking input for pilot Wire selectivity co-ordination Time tagged multiple event recording Oscillographic wave form capture Accepts 3 digital inputs Display LCD 16 (2 x 8) characters Time current curves selectable according to IEC/IEEE standards Password protection facility 1 A or 5 A site selectable Display of parameters Built in supervision Modbus RTU / IEC870-5-103 Communication protocols Front RS232 port for local programming Oscillographic recording of input quantities RS485 serial communication port on back panel 0.1 VA for 1 A, 0.3 VA for 5 A NA < 7 VA -100C to 550C < 1.5kg 4 C/O Contacts Drawout 83 x 164 x 225 64 x 137 24-110 V AC/DC 88-264 V AC/DC

Functions available

Rating

Other features

Burden on CT Burden on PT Burden on aux. supply Operating temp Weight Output contacts Construction Dim W x H x D in mm Panel cutout Auxiliary supply Type 1 Type 2

21

Wiring Diagrams

MC20
A B C
6 7

A B C
6
1/5A

Display Microp.

R1

16

R1

16 Output Relays Rele DI Uscita

MC20
4 5 8 9 4
1/5A

R2

18 17 Output Relays Rele DI Uscita

R2

18 17

Funzioni Functions
F50 F51 F50N F51N
1/5A

R3

14 15

R3

14 15

5 8 9

R1 R2

R4

13 12
D3

20 21 19 22

BT 2

50

Progr. Int.fault

R3 R4

D3 D2 D1

20 21 19 22

Digital Inputs Ingressi Digitali

D2 D1

Digital Inputs Ingressi Digitali

In = 1A 5A lon = 1A 5A
Auxiliary Supply Alimentazione Ausiliaria
10
RS232
C A (S+) B (S+)

H L

13 12

To I/0 Relay Expansion All Espansione DI I/0 Comune Comune RS485

3 2 1

3 2 1

RS485
A (S+) B (S-)

11

Keyboard Tastiera

MS - SCE 1828 - R1

BPMC

MS - SCE 1828 - R1 Standard Output

MS - SCE 1839 - R2 I/O Output

MC30

4 5 6 7 8 9
1/5A 1/5A 1/5A

Display Microp.

R1 R2 R3 R1 R2 R3
D3 D2 D1

16 18 17 Output 14 Relays Rele 15 DI Uscita 13 12 20 Digital 21 Inputs 19 Incressi 22 Digital

R1 R2 R3

16 Output 18 Relays 17 Rele 14 DI Uscita 15

MC30
Funzion Functions F50 F51 F50N F51N

R4

D3 D2 D1

1/5A

20 21 19 22
L H C

Digital Input Ingress Digital

R4 Progr. Int.fault

In=

1A

5A

Auxiliary Supply

10 11

RS232
Keyboard Tastiera

C A (S+) B (S-)

3 2 1

RS485

A (S+) B (S-)

To I/0 Relay 13 Expansion 12 All Espansione DI I/0 3 Comune Comune 2 RS485 1

BPMC MS-SCE1895-R2 Standard Output MS -SCE1924-R2 I/O Output

22

Feeder Protection Relays / Vector Shift Relay


3 Phase directional O/C & E/F relay with Highset 3 Phase voltage and frequency relay with vector shift

FMR - Salient Features : Display of various parameters, trip count & trip data on LCD screen Separate LEDs for various fault indication Built in self supervision & self testing feature Wave form capturing RS485 Port for serial communication with MSCOM user friendly software Front RS232 Port for local programming

Model
Description Device code Design

FMR
Feeder manager relay 2 46, 49, 50/51, 67, 50N/51N, 67N, 27/59, 59UO, 74, 81, 86, 121, I t Numeric Three levels for phase over current independently programmable as directional or non directional Three levels for earth fault independently programmable as directional or non directional Thermal image Selectable time current curves according to IEC and IEEE standards Two over/under voltage levels Two over/under frequency levels Zero sequence over voltage level Two negative sequence current levels One positive sequence over voltage level One negative sequence undervoltage level Trip circuit supervision Associated circuit breaker control Breaker failure protection Breaker interruption energy 1 A or 5 A site selectable / 100-125 V PTI Graphical display 128 x 64 dots Display of V, I, PF, kW, kVA, kVAr and thermal status Modbus RTU / IEC870-5 communication protocols RS232 serial communication port on front face MIMIC diagram on LCD Oscillographic recording of input quantities RS485 serial communication port on back panel Phase 0.01 VA at In = 1 A; 0.2 VA at In = 5 A neutral 0.01 VA at In = 1 A; 0.2 VA at In = 5 A 0.1 VA at UN -100C to 550C < 2kg < 10 VA 6 C/O contacts Drawout 121 x 164 x 224 113 x 142 Ordering Information 20-110 V AC/DC or 88-264 V AC/DC

UM30A
3 Phase V and F relay with vector shift 24, 27d/59d, 47, 59, 59Uo, 78, 81 Numeric Over fluxing Two levels of under / over voltage Two levels of under / over frequency Zero seq. voltage Voltage unbalance Vector shift detection

Functions available

Rating

Display of parameters Built in self supervision RS485 Port

Other features

Burden on CT Burden on PT Burden on aux. supply Operating temp Weight Burden on aux. Output contacts Construction Dim W x H x D in mm Panel cutout Auxiliary supply Type 1 Type 2

NA 0.2 VA / phase at UN 8.5 VA 100C to 600C < 2kg 3 C/O + (1 N/O + 1 N/C) + separate relay 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142 20-110 V AC / DC or 88-264 V AC / DC

23

Wiring Diagrams

FMR
A B C
2 3 4 5 6 7 8 9 41 42 43 44 45 46 47 48

A B C

2
R1

25 28 15 14

3 4 5 6 7 8 9 41 42 43 44 45 46 47 48

ULTRA Feeder Manager Relay


R2

Trip Oxi. sup.

(25) N.O N.C

24 35 34

R3

25

R4

33
R1 POWER R2 TRIP ON R3 R6 R4 R5 OFF R6
D1 D2 D3 D4 + -

R5

32 15 22 31 12 25 15 25 19 38 27 17 16 Ingressi Digitali Digital Inputs

In = 1A 5A lon = 1A 5A
Un = 230Vac Max.
Auxiliary Supply Alimentazione Ausiliaria 11 21 Front-RS252

H L
ON

MS - SCE 1844-R3

BPU

34 37

UM30A
(21) 21 10 N.O. 11 22 N.C. 7 9 (10) 8 18 N.O. 20 19 N.C. 4 6 5 15 17 16 14 3 2 1 34/38 23 24

25 26

Display Microp.

R1

27 28 39 29 41 30

UM30A
Function F27 / 59 F27d / 59d F59s F59U F81 F59 / 81 Progr. Int. Fault Keyboard R1 R2 R3 R4 R5

R2 R3 R4 R5
14 BI< BI> C SS+

EA UC EC UB Uo UA EB
L/+ 12 N/- 13 44
BT 2 50

9 Pin Male

IEC 255

24 (-20%) - 110 (+20%) Vac 24 (-20%) - 125 (+20%) Vdc

80 (-20%) - 220 (+20%) Vac 90 (-20%) - 250 (+20%) Vdc

24

Control & Supervision Relays


Power management relay Multifunction 3 phase measuring instrument Salient Features Display of various parameters, event count & event data on 8 digit alphanumeric display Separate LEDs for various fault indication Four user programmable output relays Built in self supervision & self testing feature help maintenance Easy operation by 5 push buttons RS485 Port for serial communication with MSCOM user friendly software

Model
Description Device code Design

MW33
Power management 81, 27, 59, 32P, 32Q Numeric Frequence 2 stages, Voltage 2 stage, Power factor 2 stage, Active power 2 stage, Capacitor reactive power 2 stage. Actual measurement of freq, V, I, PF, active power, reactive power

SPM21

RRS
Generator load sharing 95 Static Active / reactive power Over power Load sharing Frequency control

Functions available

Other features Burden on CT Burden on PT Operating temp Weight Burden on auxiliary supply Output contacts Construction Dim W x H x D in mm Panel cutout Auxiliary supply Type 1 Type 2

Auto synchronising relay 25, 27 Numeric Auto synchronising with Adjustable voltage, Adjustable frequency, Adjustable phase angle Adjustable reclose time, Bus Live / Dead operation, Speed regular control, Voltage regulator control, Digital inputs to monitor CB position 110V - 125 V PT input Display of parameters Display of parameters, MD recording & data logging Built in self supervision, RS485 port, event recording RS485 port NA O.2 VA for 5 A, 0.01 VA for 1 A 0.04 VA 0.04 VA 100C to 600C 100C to 600C < 2kg < 2kg 8.5 VA 8.5 VA max 5 C/O 5 C/O Drawout Drawout 121 x 158 x 224 121 x 158 x 224 113 x 142 113 x 142 Ordering Information 20-110 V AC / DC or 20-110 V AC / DC 88-264 V AC / DC 88-264 V AC / DC

110 V PT input 1 A / 5 A CT input

NA < 5 VA 100C to 600C < 1.5kg 8.5 VA 3 N/O Drawout 71 x 158 x 224 62 x 142 20-110 V AC / DC or 88-264 V AC / DC Upto 380 V AC 1 A / 5 A

25

Wiring Diagrams

MW33
25 26 27 28 39 29 41
30
1/5A 1/5A

Display Microp.

R1

MW33
Funzioni Finction

R2 R3 R1 R2 R3 R4 R4 R5

1/5A

F32 W F32 VAR Wh VARh

Un Un

32 43 31 42 33 44

Progr. R5 Int.fault Keyboard Tastiera


=

14 3 2
C SS+

In = 5A

In = 1A

Un = 100V

L/+12 L/- 13

21 (21) 10 11 N.O. 22 7 N.C. 9 8 (10) 18 20 N.O. 19 4 N.C. 6 5 15 17 16 14 3 2 1 34/38 23 24

9 Pin Male

IEC 255

SPM21

Display 25 UG Microp. 26

R1

21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16

52 C

SPM21
Function F25SX Progr. Int. Fault F+

R2

29 UB 30 41 R1

R3

R4 R2 R3 R4 R5
BX BR SX C SS+

G1

R5

UG
SPM21

U B.I. BR 52 (N.O.)

F44 U+ UB UL/+ 12

52

14 3 2 1 34/38 23 24

Keybord

IEC 255

N/- 13

9 PIN MALE

RRS
+

Media Average 3 4 1 7 6 OPTO 8 9


+ + (.) (.)

15 12 Increase 13

14 To other RRS Relays

R1

Settings

VOIOCOS

Operation + R2 1 2 Decrease

OPTO R3

17 Over Power 18

Lood Shedding 22 2

Freq. control 21 11 10 3 1 Open Open Open Open 2 Open Open Open Open Lood Shedding Yes Yes Yes Yes 3 Open Close Freq. control Yes No

26

Voltage and Frequency Relays


3 Phase voltage and frequency relay with df/dt & dv/dt 1 Phase voltage and frequency relay Salient Features Display of various parameters, trip count & trip data on LCD screen Separate LEDs for individual fault indication Built in self supervision & self testing feature RS485 port for serial communication with MSCOM software Easy operation by push buttons

Model
Description Device code Design

UFD34
3 Ph voltage and Frequency relay 81, 27, 59, df/dt, dv/dt Numeric Selectable 4 stages of frequency as under/ over frequency Selectable 2 stages of voltage as under/over voltage Selectable 2 stages of df/dt Selectable 1 stages of de/dt Blocking output and Blocking Input Time tagged multiple event recording 100-125 V Display of parameters Built in self supervision Oscillogarphic recording of input quantities RS485 serial communication port on back panel

MC1V
Single phase voltage and Frequency relay 27, 59, 81 Numeric Two under voltage elements Two over voltage elements One under frequency element One over frequency element Blocking output and Blocking input Time tagged multiple event recording Oscillogarphic wave form capture Display LCD 16 (2 x 8) characters

MC3V
3 Ph voltage and Frequency relay 27, 59, 47, 59 V 0, 81 Numeric Two under voltage elements Two over voltage elements One under frequency element One over frequency element One zero sequence over voltage element One negative sequence under voltage element One positive sequence over voltage element Oscillographic wave form capture Modbus RTU / IEC870-5-103 Communication Protocols Display LCD 16 (2 x 8) characters 100-125 V Display of parameters Built in self supervision Modbus RTU / IEC870-5-103 Communication protocols Front RS232 port for local Programming Oscillogarphic recording of input quantities RS485 serial communication port on Back panel 0.1 VA for 1 A, 0.3 VA for 5 A NA 0 0 -10 C to 55 C < 1.5kg < 7 VA 4 C/O Contacts + 1 C/O for self supervision Drawout 83 x 164 x 224 64 x 137 20-110 V AC/DC or 88-264 V AC/DC

Functions available

Rating

Other features

Not applicable 0.04 VA -100C to 600C < 2.5kg 8.5 VA 4 C/O contacts + 1 C/O for Output Contacts self supervision Construction Drawout Dim W x H x D in mm 121 x 164 x 224 Panel cutout 113 x 142 Auxiliary supply 20-110 V AC/DC or 88-264 V AC/DC

Burden on CT Burden on PT Operating temp Weight Burden on auxiliary

100-125 V Display of parameters Built inSelf supervision Modbus RTU / IEC870-5-103 Communication protocols Front RS232 port for local Programming Oscillogarphic recording of input quantities RS485 serial comunication port on Back panel 0.1 VA for 1 A, 0.3 VA for 5 A NA -100C to 550C < 1.5kg < 7 VA 4 C/O Contacts + 1 C/O for self supervision Drawout 83 x 164 x 224 64 x 137 Ordering Information 20-110 V AC/DC or 88-264 V AC/DC

27

Wiring Diagrams

UFD34
(21) N.O. N.C. (10) N.O. N.C.

25 26

Display Microp.

R1

21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3 2 1 34/38 23 24

27 28 39 29 41 30

UFD34
Function F81 - 1 F81 - 2 F81 - 3 F81 - 4 Fdf / dt F27 / 59 Progr. Int. Fault R1 R2 R3 R4 R5

R2

R3

R4

R5

14 BI< BI> C SS+

L/+ 12
IEC 255

N/- 13

Keyboard

9 Pin Male

MC1V

Display
Microp.

R1

R1

16
R2

16
Output Relays Rele DI Uscita

MC1V
4 5 Funzioni Functions 1F27 2F27 1F59 2F59
Progr. Int.fault

R2

18 17
Output Relays Rele DI Uscita

18 17

R3

R3

14 15

14 15

R1 R2

R4

13 12
D3 D2 D1

20 21 19 22

R3 R4

D3 D2 D1

20 Digital 21 Inputs 19 Ingressi Digitali 22

Digital Inputs Ingressi Digitali

H L

13 12

To I/0 Relay Expansion All Espansione DI I/0 Comune Comune

Auxiliary Supply Alimentazione Ausiliaria

10 RS232 11

C A (S+) B (S-)

3 2 1

3 2 1

RS485
A (S+) B (S-)

Keyboard Tastiera MS - SCE 1836 - R2


BPMC

RS485

MS - SCE 1836 - R2 Standard Output

MS - SCE 1837 - R2 I/O Output

MC3V

4 5

Display
Microp.

R1

16

R1

16 Output Relays Rele Di Uscita

6 7 8 9

MC3V
Funzioni Functions
F24 F27 F47 F59 F27d F59d

R2

18 17 14 15 Output Relays Rele DI Uscita

R2

18 17 14 15

R3

R3

R1 R2

R4

13 12
D3

20 21 19 22

D3 R3 R4 D2 D1

20 21 19 22

EA UC EC UB UA

Digital Inputs Ingressi Digitali

D2 D1

Digital Inputs Ingressi Digitali

Progr. Int.fault

R5

13 12
C

EB
10 RS232 11
C A (S+) B (S-)

To I/0 Relay Expansion All Espansione DI I/0 Comune Comune RS485

Auxiliary Supply Alimentazione Ausiliaria

3 2 1

3 2 1

RS485
A (S+) B (S-)

Keyboard Tastiera MS - SCE 1834 - R1


BPMC

MS - SCE 1834 - R1 Standard Output

MS - SCE 1835 - R1 I/O Output

28

29
MC12/ME12

MV12/MC3V

MD32TM

MC61A/ MC61C

MC31A/MC61A MC61C/FMR

MV12/MC3V

SCM21 UFD34, UM30

Schematic - Relay Application

MG30/ MG30I MC61A/MC61C

SPM21

etaCON L / RPM8 / RPM14

MV12

MRP11 SC14S

MD32G

G1

G2

MPR300

MM30/ MCOMP

Motor

Motor

APFC Panel

scheme - 1

scheme - 2

scheme - 1

scheme - 2

1.12

over

& Vadodara

cover: Low Voltage & Medium Voltage Switchgear Switchboard Electrical Design AC Drives & Building Management Solutions Protective Relays, Earthing & Harmonics Energy Conservation & Management

New

Vadodara Larsen & Toubro Limited Switchgear Training Centre Behind L&T Knowledge City, Near Village Ankhol, Vadodara - 390 019. Tel: +91 265 245 7805 E-mail : STC-VADODARA@LNTEBG.COM

Electrical Standard Products (ESP) Branch Offices:


REGISTERED OFFICE AND HEAD OFFICE L&T House, Ballard Estate P. O. Box 278 Mumbai 400 001 Tel: 022-67525656 Fax: 022-67525858 Website: www.Larsentoubro.com ELECTRICAL STANDARD PRODUCTS (ESP) 501, Sakar Complex I Opp. Gandhigram Rly. Station Ashram Road Ahmedabad 380 009 Tel: 079-66304006-11 Fax: 079-66304025 e-mail: esp-ahm@LNTEBG.com 38, Cubbon Road, P. O. Box 5098 Bangalore 560 001 Tel: 080-25020100 / 25020324 Fax: 080-25580525 e-mail: esp-blr@LNTEBG.com 131/1, Zone II Maharana Pratap Nagar Bhopal 462 011 Tel: 0755-3080511 / 05 / 08 / 13 / 17 / 19 Fax: 0755-3080502 e-mail: esp-bho@LNTEBG.com Plot No. 559, Annapurna Complex Lewis Road Bhubaneswar 751 014 Tel: 0674-6451342, 2436690, 2436696 Fax: 0674-2537309 e-mail: nayakd@LNTEBG.com SCO 32, Sector 26-D Madhya Marg, P. O. Box 14 Chandigarh 160 019 Tel: 0172-4646840, 4646853 Fax: 0172-4646802 e-mail: esp-chd@LNTEBG.com L&T Construction Campus TC-1 Building, II Floor Mount-Poonamallee Road Manapakkam Chennai 600 089 Tel: 044-2270 6800 Fax: 044-22706940 e-mail: esp-maa1@LNTEBG.com 67, Appuswamy Road Post Bag 7156 Opp. Nirmala College Coimbatore 641 045 Tel: 0422-2588120 / 1 / 5 Fax: 0422-2588148 e-mail: esp-cbe@LNTEBG.com Khairasol, Degaul Avenue Durgapur 713 212 Tel: 2559848, 2559849, 2559844 Fax: 0343-2553614 e-mail: esp-dgp@LNTEBG.com 5, Milanpur Road, Bamuni Maidan Guwahati 781 021 Tel: +91 8876554410 / 8876554417 Fax: 361-2551308 e-mail: hazrasudipto@LNTEBG.com II Floor, Vasantha Chambers 5-10-173, Fateh Maidan Road Hyderabad 500 004 Tel: 040-67015052 Fax: 040-23296468 e-mail: esp-hyd@LNTEBG.com Monarch Building, 1st Floor D-236 & 237, Amrapali Marg Vaishali Nagar Jaipur 302 021 Tel: 0141-4385914 to 18 Fax: 0141-4385925 e-mail: esp-jai@LNTEBG.com Akashdeep Plaza, 2nd Floor P. O. Golmuri Jamshedpur 831 003 Jharkhand Tel: 0657-2312205 / 38 Fax: 0657-2341250 e-mail: esp-jam@LNTEBG.com Skybright Bldg; M. G. Road Ravipuram Junction, Ernakulam Kochi 682 016 Tel: 0484-4409420 / 4 / 5 / 7 Fax: 0484-4409426 e-mail: esp-cok@LNTEBG.com 3-B, Shakespeare Sarani Kolkata 700 071 Tel: 033-44002572 / 3 / 4 Fax: 033-22821025 / 7587 e-mail: esp-ccu@LNTEBG.com A28, Indira Nagar, Faizabad Road Lucknow 226 016 Tel: 0522-4929905 / 04 Fax: 0522-2311671 e-mail: esp-Lko@LNTEBG.com No: 73, Karpaga Nagar, 8th Street K. Pudur Madurai 625 007 Tel: 0452-2537404, 2521068 Fax: 0452-2537552 e-mail: esp-mdu@LNTEBG.com EBG North Wing Office-Level 2 Gate 7, Powai Campus Mumbai 400 072 Tel: 022-67052874 / 2737 / 1156 Fax: 022-67051112 e-mail: esp-bom@LNTEBG.com 12, Shivaji Nagar North Ambajhari Road Nagpur 440 010 Tel: 0712-2260012 / 6606421 Fax: 2260030 / 6606434 e-mail: esp-nag@LNTEBG.com 32, Shivaji Marg P. O. Box 6223 New Delhi 110 015 Tel: 011-41419514 / 5 / 6 Fax: 011-41419600 e-mail: esp-del@LNTEBG.com L&T House P. O. Box 119 191/1, Dhole Patil Road Pune 411 001 Tel: 020-66033395 / 66033279 Fax: 020-26164048 / 26164910 e-mail: esp-pnq@LNTEBG.com Crystal Tower, 4th Floor, G. E. Road Telibandha Raipur - 492 006 Tel: 0771-4283214 e-mail: esp-raipur@LNTEBG.com 3rd Floor Vishwakarma Chambers Majura Gate, Ring Road Surat 395 002 Tel: 0261-2473726 Fax: 0261-2477078 e-mail: esp-sur@LNTEBG.com Radhadaya Complex Old Padra Road Near Charotar Society Vadodara 390 007 Tel: 0265-6613610 / 1 / 2 Fax: 0265-2336184 e-mail: esp-bar@LNTEBG.com 48-8-16, Dwarakanagar Visakhapatnam 530 016 Tel: 0891-6701125 to 30 Fax: 0891-6701139 e-mail: esp-viz@LNTEBG.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Larsen & Toubro Limited Electrical Standard Products Powai Campus, Mumbai 400 072 Customer Interaction Center (CIC) BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858 Tel : 022 6774 5858, Fax : 022 6774 5859 E-mail : cic@LNTEBG.com Website : www.LNTEBG.com

Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA

SP 50297-R1