Alarms, Indications: for UPS(i4 series)
ALARMS Hi-Rels Reply at
prebid stage
In drawing (drwg
no: REL-
BGCPP-405-
D-000041)
AC input under voltage Input UV alarm provided
through LCD.
Under voltage
through LCD.
DC output over voltage DC over voltage alarm
provided through LCD.
DC over voltage text
readout through LCD.
DC output under voltage Low Batt trip alarm
provided through LCD.
Low Batt through
LCD
DC output circuit breaker fuse
trip
Visual Indication
provided.
Batt iso. LA LED
indication on MIMIC.
Common trouble alarm for
switchboard bus under voltage
Common alarm indication
provided.
Common alarm
through LED
indication on MIMIC.
Battery ground detection DC ground LED indication
provided through LCD.
DC ground Alarm
through LCD.
Switch board breaker / Fuse
open
Not Envisaged. ----
Static switch transferred to other
source
Transfer to ALT alarm
shall be provided through
LCD.
Transfer to ALT alarm
shall be provided
through LCD.
Manual Bypass transfer to
alternate source
Transfer to ALT alarm
shall be provided through
LCD.
Transfer to ALT alarm
shall be provided
through LCD.
Bypass source fail ALT OV & UV alarm
provided through LCD.
ALT OV & UV alarm
provided through
LCD.
AC input fail Input UV & OV alarm
provided through LCD.
Input UV & OV alarm
provided through
LCD.
AC output fail Inverter UV & OV alarm
provided through LCD.
Inverter UV & OV
alarm provided
through LCD.
UPS battery fail Battery LOW alarm
provided through LCD.
LOW BATT through
LCD
DC Ground fault DC ground indication
provided.
DC Ground through
LCD.
Load on Battery LED indication provided
on Mimic.
Load on Battery
indication on MIMIC
through LED.
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-405-D-0000 41
HI-REL DOC NO : 105UL12341
Rev : A
---------------------------------------------------------------------------------------------------------------------
Alarms, Indications: for UPS(i4 series)
Load on Bypass LED indication provided
on Mimic.
BYP/ALT ON led
indication on MIMIC.
UPS failure (Common Alarm) Common Alarm Common alarm
through LED
indication on MIMIC.
Charger / Inverter Trip Charger /Inverter UV &
OV alarm provided
through LCD.
Charger /Inverter UV
& OV alarm provided
through LCD.
Charger / Bypass AC mains fail Charger /ALT UV & OV
alarm provided through
LCD.
Charger /ALT UV &
OV alarm provided
through LCD.
Charger / Battery output hi DC over voltage alarm
provided through LCD.
DC over voltage text
readout through LCD.
Charger output voltage low Not provided. ----
Fan failure or Temperature Hi LED indication, OT alarm
provided through LCD.
INV OVER LD TRIP
through LCD.
Charger / Inverter fuse failure LED indication LED indication
provided.
UPS overload Inverter Overload alarm
provided through LCD.
Overload through
LCD.
Battery disconnected LED indication Batt iso. LA LED
indication on MIMIC.
Inverter and bypass not
synchronized
Frequency out of limit
alarm provided through
LCD.
Frequency out of
limit alarm provided
through LCD.
Earth output (if floating) No alarm. ----
We confirm that common alarm will be generated when any alarm is raised from
the above list of alarms.
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-405-D-0000 41
HI-REL DOC NO : 105UL12341
Rev : A
---------------------------------------------------------------------------------------------------------------------
1
2
.
0
5
.
1
1
B
.
B
.
N
.
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
B
.
B
.
N
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
B
.
B
.
N
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
B
.
B
.
N
.
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
B
.
B
.
N
.
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
DETAIL BILL OF MATERIAL OF 5 KVA UPS
UPS
Sr. No. Components Description Make Ckt. Ref. Rating Qty(n)
1 AC Capacitor Alcon/Epcos/Systec CO-n 50uF 500VAC 2
2 DC Capacitor Alcon/Epcos/BC(philips) CD-n 3300uFD 350V 2
3 Cooling Fans Rexnord/Nadi/Nisiki Fan-n 230Vac 50Hz 6
4 Rectifier nput Fuses Ge/Bussmann/Farraz FR-n 75A 3
5 DC Fuse (Battery) Ge/Bussmann/Farraz FB 75A 1
6 DC Fuse Ge/Bussmann/Farraz FD 75A 1
7 Bypass Fuse Ge/Bussmann/Farraz FA 75A 1
8 Free Wheeling Diode (Charger) Semikron D1 DD-26A,1600V 1
9 Thyristor (Charger) Semikron THC-n TT-26A,1600V 3
10 Thyristor (S/S) Semikron THS-n TT-26A, 1600V 2
11 GBT Semikron TR-n 75A 600V 2
12 nput MCCB L&T CB 32A 50KA 1
13 Bypass solator L&T CBA 32A 1
14 Manual Bypass Switch Kaycee / Switch-On MBS 40A 2W 1P 1
15 Battery MCCB L&T CBB 63A 1
16 DC choke Hi - Rel LD 5.25mH 45A 1
17 Output choke Hi - Rel LO 400UH 60A 1
18 nput solation Transformer Hi - Rel TF-1 13KVA 1
19 Output solation Transformer Hi - Rel T2 5KVA 1
20 Rectifier Snubber Card Hi - Rel H7-n - 3
21 Static Snubber Card Hi - Rel H8 - 1
22 4 Power Supply & Feedback Card Hi - Rel H6 - 1
23 4 System Control Card Hi - Rel H2 - 1
24 4 Gate Driver Card Hi - Rel H5-n - 2
25 SMPS Card Hi - Rel H4A - 1
26 4 System Manager+ Modbus Card Hi - Rel H1 - 1
27 Bypass Square Card Hi - Rel H11 - 1
28 3Ph Charger Card Hi - Rel H3 - 1
29 Switcher Card Hi - Rel H4C - 1
30 Terminal Elmex/Connect Well - - -
31 Panel SKE/ABHSHEK - - -
32 UPS to battery cable Uninyvin ndustrial glass - - 20MTR
33 UPS to ACDB cable Uninyvin ndustrial glass - - 20MTR
PROJECT 2X300MW COAL BASED GROUP CAPTVE POWER PROJECT
CLENT RELANCE NFRASTRUCTURE LTD.
RNFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 47
HREL DWG NO. 105UB12341 REV:B
PAGE 1 OF 1
12.05.11
12.05.11
B.B.N.
V6/1087
DETAIL BILL OF MATERIAL OF ACDB FOR 5KVA UPS
Make Ckt. Ref. Rating Qty(n)
1 Incomer DPMCB L&T CBI 63A 10KA 1
2 Incomer Fuse Ge/Bussman/Farraz FL,N 63A 2
3 Feeder DPMCB L&T CBF1-3 32A 3
4 Feeder DPMCB L&T CBF4-10 16A 7
5 Feeder DPMCB L&T CBF11-14 10A 4
6 HRC Fuse Ge/Bussman/Farraz FL,N1-3 32A 6
7 HRC Fuse Ge/Bussman/Farraz FL,N4-10 16A 14
8 HRC Fuse Ge/Bussman/Farraz FL,N11-14 10A 8
9 I/P Voltmeter (72X72) Meco/Rishabh VM1 0-300VAC 1
10 I/P Ampmeter (72X72) Meco/Rishabh AM1 0-50A 1
11 Terminal Elmex/Connect Well - - -
12 Panel SKE/ABHISHEK - - -
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 48
HIREL DWG NO. 105AB12341 REV:B
PAGE 1 OF 1
Sr.
No.
Components
Description
12.05.11
B.B.N.
V6/1087 12.05.11
DETAIL BILL OF MATERIAL OF AUXILLARY PANEL FOR 5KVA UPS
Sr. No. Components Description Make Ckt. Ref. Rating Qty(n)
1 Input MCCB L&T CBI 32A 50KA 1
2 Bypass Isolation Transformer (3Ph-1Ph) HI-REL TF1 5KVA 1
3 Servo Control Voltage Stabilizer (240V,1Ph/240V, 1Ph) HI-REL SCVS 5KVA 1
4 O/P Voltmeter (72x72) Meco/Rishabh VM1 0-300V 1
5 O/P Ampmeter (72x72) Meco/Rishabh AM1 0-50A 1
6 Power Terminal Elmex/Connect well DPBB-50 - -
7 Panel SKE/ABHISHEK - - -
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 49
HIREL DWG NO. 105XB12341 REV:B
PAGE 1 OF 1
12.05.11
B.B.N.
V6/1087 12.05.11
DETAIL BILL OF MATERIAL OF BATTERY JUNCTION BOX FOR 5KVA UPS
Sr. No. Make Ckt. Ref. Rating Qty(n)
1 Fuse Ge/Bussman/Farraz F8,9 32A 2
2 Power Terminal ELMEX/Connect Well DPBB-50 DPBB-50 -
3 Panel SKE/ABHISHEK - - -
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 50
HIREL DWG NO. 105DB12341 REV:B
Components
Description
12.05.11
B.B.N.
V6/1087 12.05.11
DETAIL BILL OF MATERIAL OF MANDATORY SPARES FOR 5KVA UPS
Sr. No. Components Description Make Rating Qty(n)
1 Static Switch Thyristor Semikron TT-26A, 1600V 2
2 Manual Bypass Switch Kaycee / Switch on 40A 2W 1P 2
3 IGBT Semikron 75A 600V 1
4 Diode Semikron DD-26A,1600V 1
5 Input MCCB L&T 32A 50KA 1
6 Bypass Isolator L&T 32A 1
7 Battery MCCB L&T 63A 1
8 Rectifier Input Fuses Ge/Bussmann/Farraz 75A 3
9 Rectifier output Fuse Ge/Bussmann/Farraz 75A 1
10 Battery Fuse Ge/Bussmann/Farraz 75A 1
11 Bypass Fuse Ge/Bussmann/Farraz 75A 1
12 Electronics Card Module 1 SET
12.1 Rectifier Snubber Card HI-REL - 1
12.2 Static Snubber Card HI-REL - 1
12.3 I4 Power Supply & Feedback Card HI-REL - 1
12.4 I4 System Control Card HI-REL - 1
12.5 I4 Gate Driver Card HI-REL - 1
12.6 SMPS Card HI-REL - 1
12.7 I4 System Manager+ Modbus Card HI-REL - 1
12.8 Bypass Square Card HI-REL - 1
12.9 3Ph Charger Card HI-REL - 1
12.10 Switcher Card HI-REL - 1
13 Current Transformer (i/p) G.Mexwell CT 50/5 1
14 Current Transformer (o/p) G.Mexwell CT 50/5 1
15 Cooling Fans (4) Rexnord/Nadi/Nisiki 230Vac 50Hz 1
16 LED Lamp Precifine 230VAC 5
17 AC Capacitor ALCON/Epcos/Systec 50uF 500VAC 4
18 DC Capacitor ALCON/Epcos/BC(philips) 3300uFD 350V 8
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 51
HIREL DWG NO. 105SB12341 REV:B
12.05.11
12.05.11 V6/1087
B.B.N.
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
A UPS SYSTEM
1.0 Model : I4 Series
1.1 Make : HI REL ELECTRONICS PVT LTD
1.2 Type : PWM IGBT based
1.3 Reference Standard : IEC 62040 3
2.0 Dimension & Weights :
2.1 Number of cabinets : Three
2.2 Dimension of Inverter cabinet (W x H x
D) mm
: 660 X 1715 X 750
2.3 Dimension of static switch cabinet (W x
H x D) mm
: Included in inverter panel
2.4 Dimension of Charger cabinet (W x H x
D) mm
: Included in inverter panel
2.5 Dimension of D.C. distribution board
(batt jn Box ) (W x H x D) mm
: 650 x 550 x 300
2.6 Dimension of A.C. distribution board (W
x H X D) mm
: 700 x 1500 x 750
2.7 Dimension of transformer and stabilizer
panel (WxHxD) mm
: 660 x 1715 x 750
2.8 Dimension of any other UPS cabinet, if
furnished (WxHxD)mm
: NIL
2.9 Overall dimension (LxHxD) mm : 1360 x 1715 x 750
2.10 Weight of the following with all
equipment installed.
a. Inverter cabinet (Kg) : 300 Kg (approx)
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
12.05.11
B.B.N
V6/1087 12.05.11
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
b. Static switch cabinet (Kg) : Included in inverter panel
c. Charger cabinet (Kg): : Included in inverter panel
d. D.C. Distribution boards (Kg.) : 50 Kg (approx)
e. A.C. Distribution boards (Kg.) : 150 Kg (approx)
f. Transformer and stabilizer panel
(Kg)
: 200 Kg (approx)
g. Other UPS cabinet (Kg.) : NIL
h. Total weight (Kg) : 500 Kg (approx)
3.0 Heat load for Ventilation/Air Conditioning
requirement
a. Inverter and static switch at 100%
load
: 0.44 KW
b. Inverter and static switch at 50%
load
: 0.26 KW
c. Inverter and static switch at 33%
load
: 0.2 KW
d. Charger and accessories at 100%
load
: 0.34 KW
e. Charger and accessories at 50%
load
: 0.28 KW
f. UPS battery : Not in scope of Hi-Rel
B. STATIC INVERTER
1.0 General
1.1 Make : HI-REL ELECTRONICS PVT LTD
1.2 Cat. No : I4 Series
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
1.3 Type : PWM using IGBT
1.4 Reference Standard : IEC 62040 3
2.0 D.C. Input :
2.1 Voltage (Volt) : 220 VDC Nominal
2.2 Current
a. No load (Amp) : 0.8 Amp
b. Full load (Amp) : 18.16 Amp
3.0 A.C. Output
3.1 Voltage + % variation (Volt) : 230VAC, 1Ph +/- 1%
3.2 Frequency +_ % variation (Hz) : 50 Hz +/- 0.1% (free running
mode)
3.3 No load Current (Amp) : Nil
3.4 Full load Current (Amp) : 21.74 Amp
3.5 Maximum inrush current during inverter
energisation (Amp)
: Nil, soft start provided
4.0 Capacity
4.1 Rated full load capacity at unity power
factor
: 4 KVA / 4KW
4.2 Rated full load capacity at 0.8 power
factor
: 5 KVA / 4 KW
5.0 Performance
5.1 Regulation for 0-100% rated load at all
Input voltage (%)
: +/- 1%
5.2 Transient output voltage regulation on
application and removal of 100% load
(%)
: +/- 5%, 98% recovery within 20ms
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
5.3 Frequency variation for all conditions of
input supply, load and temperature
occurring simultaneously or in any
combination (%)
: +/- 0.1% (Free Running), +/- 1% to
+/-6% field settable
synchronization range in step of
1%
5.4 Total harmonic content at rated load : <2.5% for linear load
5.5 Overload capacity at 100 percent voltage
a For 4 milliseconds (%) (for clearing) : 300%
b For 100 milliseconds % : 200%
c. For 60 seconds (%) : 150%
d. Capacity to clear maximum fuse
rating and duration
: Semi conductor fuse of 30%
of rated capacity & 4 msec
5.6 Overload capacity at 90 percent voltage
a. For 4 milliseconds (%) : 300%
b. For 100 milliseconds (%) : 200%
c. For 60 seconds : 150%
5.7 Inverter Efficiency (Watt output/Watt
input)
a. Rated load at 1.0 PF/0.8 PF(%) : 89%
b. 50% Rated load at 1.0 PF/0.8 PF
(%):
: 87%
c. 33% Rated load at 1.0 PF/0.8 PF
(%)
: 85%
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
6.0 Miscellaneous
6.1 Inverter provided with following features
a. Automatic voltage regulation : Provided
b. Current limiting circuitry : Provided
c. Wave shaping circuit : Provided
d. Transient recovery circuit : Provided
e. Automatic synchronising circuit : Provided
f. Soft-start feature : Provided
g. Smoothing filter circuit : Provided
6.2 SCR elements provided with
a. Surge protection : Provided
b. Fast acting HRC fuse : Provided
6.3 Fuse type size and characteristics.
a. Inverter input : Not envisaged as output is
current limited
b. Inverter output : Not envisaged as output is
current limited
6.4 Inverter auxiliary equipment along with
necessary alarms furnished as per
specification (Yes/No)
: Yes
6.5 Cooling
a. Type : Forced air cooled
b. Number of fans : Six
c. Operating time at full load without
forced air cooling
: 30 mins
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
6.6 Technical literature for inverter and
auxiliary equipment furnished? (Yes/No)
: Provided with O&M manual
C. STATIC TRANSFER SWITCH
1.0 General
1.1 Make : HI-REL ELECTRONICS PVT
LTD
1.2 Cat. No : ---
1.3 Type : Bi-Directional Thyristorized
1.4 Reference Standard : IEC 62040 3
2.0 Ratings : 21.74 Amp
2.1 Rated voltage (Volt) : 230 VAC
2.2 Rated current : 21.74 Amp
2.3 Transfer time (ms) : < 4 msec in sync mode &
< 20 msec in Async mode
3.0 Performance :
3.1 Overload capacity
a. For 100 milliseconds (%) : 750%
b. For 60 seconds (%) : 150%
c. For indefinite period (%) : 100%
4.0 Miscellaneous
4.1 Oscillographic records for transfer
operation furnished? (Yes/No)
: During the Factory Test
4.2 Static transfer switch auxiliary equipment
along with necessary alarm furnished as
per specification? (Yes/No)
: Yes
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
4.3 Technical literature for static transfer
switch and auxiliary equipment
furnished? (Yes/No
: Provided with O&M manual
D MANUAL BY-PASS SWITCH
1.0 General
1.1 Make : Kaycee / Switch-On
1.2 Cat. No : --
1.3 Type : Make before break
1.4 Reference Standard : ---
2.0 Ratings :
2.1 Rated voltage (Volt) : 230 VAC
2.2 Rated current (Amp) : 40 Amp
3.0 Miscellaneous
3.1 Contact configuration and type of switch
as per specification furnished? (Yes/No)
: Yes
3.2 Technical literature on manual by-pass
switch furnished? (Yes/No)
: Provided with O&M manual
E. BATTERY CHARGER
1.0 General
1.1 Make : HI REL ELECTRONICS PVT LTD
1.2 Cat. No. : I4
1.3 Type : 6 pulse full wave
1.4 Reference Standard : IEC 62040 3
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
2.0 A.C. Input
2.1 Voltage % variation (Volt) : 415 VAC +10%, -15%
2.2 Phase (No) : Three
2.3 Frequency % variation (Hz) : 50 Hz + 6%
2.4 Input amps at the following loads in
addition to supply the battery charging
current.
a. 50% rated load (Amp) : 14 Amp
b. 100% rated load (Amp) : 18 Amp
c. 110% rated load (Amp) : 19 Amp
2.5 Charger maximum inrush current: :
3.0 D.C. Output
a. Voltage (Volt/Cell) : 2 V/ Cell
b. Current (Amp) : 38 Amp
4.0 Performance :
4.1 Regulation for 0-100% rated load with
10% Input voltage and 5% input
frequency variation (%)
: +/- 1%
4.2 Ripple content in D.C. output:
a. With battery (%) : + 1% RMS
b. Without battery (%) : + 2% RMS
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
4.3 Efficiency at
a. 50% rated load (%) : 93%
b. 100% rated load (%) : 89%
4.4 Power Factor at rated load (%) : 0.8
4.5 Maximum fault current for the short
circuit at output terminals.
a. With current limiting device
operative (KA)
: 10 KA
b. With current limiting device in
operative (KA):
: 10 KA
5.0 Miscellaneous
5.1 Charger provided with following features
a. Automatic voltage regulation : Provided
b. Current limiting circuitry : Provided
c. Smoothing filter circuit : Provided
d. Soft-start feature : Provided
e. Automatic load sharing during
parallel operation
: NA for Stand Alone UPS
5.2 SCR elements provided with
a. Surge protection : Provided
b. Fast acting HRC fuse : Provided
5.3 Maximum temp. within cubicle above
50
o
C ambient
a. Rectifier transformer (
o
C) : 85 Deg C
b. SCR (
o
C) : 35 Deg C
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
5.4 Charger auxiliary equipment along with
necessary alarms furnished as per
specification (Yes/No)
: Yes
5.5 Cooling
a. Type : Forced
b. Number of fans : Common panel for Inverter &
charger
c. Operating time at full load without
forced air cooling
: 30 mins
5.6 Technical literature for charger and
auxiliary equipment furnished?
: Provided in O&M manual
F. STEP DOWN TRANSFORMER
1.0 General
1.1 Make : HI-REL ELECTRONICS PVT
LTD
1.2 Type : Open Delta (3Ph to 1 Ph)
1.3 Number of phase : 3 Phase in primary & 1 Phase
in secondary
1.4 Frequency (Hz) : 50 Hz
1.5 Type of cooling : Natural
1.6 Class of insulation : F
2.0 Rating :
2.1 Capacity (KVA): : 5 KVA
2.2 Rated voltage
a. H.V. (KV) : 0.415 KV
b. L.V. (KV) : 0.230 KV
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
2.3 Rated current
a. H.V. (Amp) : 13 Amp
b. L.V. (Amp) : 21.74 Amp
3.0 Performance :
3.1 Guaranteed loss at 100% rated voltage
and rated frequency (KW)
: 0.35 KW
3.2 No load loss (KW) : 0.14 KW
3.3 Copper loss at full load at 75
o
C (KW) : 0.21 KW
3.4 Efficiency at 75
o
C at unity power factor
a. at full load (%) : 94%
b. at 3/4
th.
load (%) : 92.7%
c. at load (%) : 91%
G. VOLTAGE STABILIZER
1.0 General
1.1 Make : HI-REL ELECTRONICS PVT
LTD
1.2 Type : Servo controlled
1.3 Number of phase : 1 Phase
1.4 Frequency (Hz) : 50 Hz
1.5 Type of cooling : Natural
1.6 Class of insulation : F
2.0 Rating
2.1 Capacity (KVA) : 5 KVA
2.2 Rated voltage : 230 VAC
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
3.0 Performance
3.1 Guaranteed loss at 100% rated voltage
and rated frequency KW
0.06 KW
3.2 No load loss (KW) : 0.02 KW
3.3 Copper loss at full load at 75
o
C (KW) : 0.04 KW
3.4 Efficiency at 75
o
C at unity power factor
a. at full load (%) : 98.5%
b. at 3/4
th.
load (%) : 97.8%
c. at load (%) : 97.2%
H. DISTRIBUTION BOARD
1.0 General
1.1 Make & Type : HI-REL ELECTRONICS PVT
LIMITED
Non-compartmentalized
1.2 Degree of protection : IP-52
1.3 Sheet steel thickness : 2 mm for load bearing & 1.6
mm for non-load bearing
1.4 Mounting : Floor mounted
1.5 Dimension (W x H x D) (mm) : 700 x 1500 x 750
1.6 Weight (Kg) : 150 kG (approx)
1.7 Fuse
a. Make : For Fuse = GE / Bussman /
Ferraz
For MCB = Scheider / GE /
L&T
b. Type & characteristic for branch
circuit protection
: HRC type fuses
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE II : TECHNICAL PARTICULARS
HI REL ELECTRONICS PVT LTD
Bidder's Name
1.8 Terminals
a. Make & Type : Elemax
b. 20% spare terminals furnished?
(Yes/No)
: NO
1.9 Technical literature/curves for fuse,
circuit breakers switches furnished?
(Yes/No)
: Provided with O&M Manual
---------------------------------------------------------------------------------------------------------------------
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
HI - REL ELECTROINCS LIMITED
CABLE SCHEDULE FOR 5 KVA UPS
EXTERNAL POWER CABLE
Sr. No From Location From TerminaI To Location To TerminaI Recommended CabIe size
1
R
UPS
TA-1 - 1
DPBB 50
RNFRA
3C x 10 SQMM AYFY
Y TA-1 - 2
(MAX.USE 50 SQMM AYFY)
B TA-1 - 3
2
R
AUX
TA-1 - 1
RNFRA
3C x 10 SQMM AYFY
Y TA-1 - 2
(MAX.USE 50 SQMM AYFY)
B TA-1 - 3
3 UPS
TA-1 6
BJB
.+ VE
H-REL 20MTR
TA-1 7 .- VE
4 UPS
TA-1 8
ACDB
L
H-REL 20MTR
TA-1 9 N
POTENTIAL FREE CONTACTS(0.5A,220VDC/5A 200VAC)
Sr. No From Location PotentiaI free Contact TerminaI No TerminaI type Recommended CabIe size
1 UPS COMMON ALARM
TA-3 - 1 (NO)
KUT 2.5
RNFRA
2C X 1.5 SQMM HRPVC CU
TA-3 - 2 (C)
(MAX. USE 1.5 SQMM HRPVC CU)
TA-3 - 3 (NC)
2 UPS
TA-3 - 4 (NO)
RNFRA
2C X 1.5 SQMM HRPVC CU
TA-3 - 5 (C)
(MAX. USE 1.5 SQMM HRPVC CU)
TA-3 - 6 (NC)
3 UPS LOAD ON BYPASS
TA-3 - 7 (NO)
RNFRA
2C X 1.5 SQMM HRPVC CU
TA-3 - 8 (C)
(MAX. USE 1.5 SQMM HRPVC CU)
TA-3 - 9 (NC)
4 UPS NVERTER OVERLOAD
TA-3 - 10 (NO)
RNFRA
2C X 1.5 SQMM HRPVC CU
TA-3 - 11 (C)
(MAX. USE 1.5 SQMM HRPVC CU)
TA-3 - 12 (NC)
5 UPS LOW BATTERY
TA-3 - 13 (NO)
RNFRA
2C X 1.5 SQMM HRPVC CU
TA-3 - 14 (C)
(MAX. USE 1.5 SQMM HRPVC CU)
TA-3 - 15 (NC)
6 UPS NVERTER LOW
TA-3 - 16 (NO)
RNFRA
2C X 1.5 SQMM HRPVC CU
TA-3 - 17 (C)
(MAX. USE 1.5 SQMM HRPVC CU)
TA-3 - 18 (NC)
PROJECT 2X300MW COAL BASED GROUP CAPTVE POWER PROJECT
CLENT RELANCE NFRASTRUCTURE LTD.
RNFRA DWG NO. REL-BGCPP-VEN-405-K-0000 53
HREL DWG NO. 105CL12341 REV:A DATE:26.5.11
PAGE 0 OF 2
Type of
TerminaI
CabIe in
Scope
CabIe
Length
2 X 1C X UN-10, UNNYVN FLEXBLE
CU. CABLE
2 X 1C X UN-8, UNNYVN FLEXBLE
CU. CABLE
CabIe in
Scope
BYPASS FREQ. OUT
OF RANGE
14.06.11
14.06.11 V6/1142
B.B.N.
Alarms, Indications: for UPS(i4 series)
ALARMS Hi-Rels Reply at
prebid stage
In drawing (drwg
no: REL-
BGCPP-405-
D-000041)
AC input under voltage Input UV alarm provided
through LCD.
Under voltage
through LCD.
DC output over voltage DC over voltage alarm
provided through LCD.
DC over voltage text
readout through LCD.
DC output under voltage Low Batt trip alarm
provided through LCD.
Low Batt through
LCD
DC output circuit breaker fuse
trip
Visual Indication
provided.
Batt iso. LA LED
indication on MIMIC.
Common trouble alarm for
switchboard bus under voltage
Common alarm indication
provided.
Common alarm
through LED
indication on MIMIC.
Battery ground detection DC ground LED indication
provided through LCD.
DC ground Alarm
through LCD.
Switch board breaker / Fuse
open
Not Envisaged. ----
Static switch transferred to other
source
Transfer to ALT alarm
shall be provided through
LCD.
Transfer to ALT alarm
shall be provided
through LCD.
Manual Bypass transfer to
alternate source
Transfer to ALT alarm
shall be provided through
LCD.
Transfer to ALT alarm
shall be provided
through LCD.
Bypass source fail ALT OV & UV alarm
provided through LCD.
ALT OV & UV alarm
provided through
LCD.
AC input fail Input UV & OV alarm
provided through LCD.
Input UV & OV alarm
provided through
LCD.
AC output fail Inverter UV & OV alarm
provided through LCD.
Inverter UV & OV
alarm provided
through LCD.
UPS battery fail Battery LOW alarm
provided through LCD.
LOW BATT through
LCD
DC Ground fault DC ground indication
provided.
DC Ground through
LCD.
Load on Battery LED indication provided
on Mimic.
Load on Battery
indication on MIMIC
through LED.
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-VEN-405-K-0000 53
HI-REL DOC NO : 105CL12341
Rev : A DATE:26.5.11 PAGE1 OF 2
---------------------------------------------------------------------------------------------------------------------
Alarms, Indications: for UPS(i4 series)
Load on Bypass LED indication provided
on Mimic.
BYP/ALT ON led
indication on MIMIC.
UPS failure (Common Alarm) Common Alarm Common alarm
through LED
indication on MIMIC.
Charger / Inverter Trip Charger /Inverter UV &
OV alarm provided
through LCD.
Charger /Inverter UV
& OV alarm provided
through LCD.
Charger / Bypass AC mains fail Charger /ALT UV & OV
alarm provided through
LCD.
Charger /ALT UV &
OV alarm provided
through LCD.
Charger / Battery output hi DC over voltage alarm
provided through LCD.
DC over voltage text
readout through LCD.
Charger output voltage low Not provided. ----
Fan failure or Temperature Hi LED indication, OT alarm
provided through LCD.
INV OVER LD TRIP
through LCD.
Charger / Inverter fuse failure LED indication LED indication
provided.
UPS overload Inverter Overload alarm
provided through LCD.
Overload through
LCD.
Battery disconnected LED indication Batt iso. LA LED
indication on MIMIC.
Inverter and bypass not
synchronized
Frequency out of limit
alarm provided through
LCD.
Frequency out of
limit alarm provided
through LCD.
Earth output (if floating) No alarm. ----
M/s HI-REL confirms that common alarm(PF contact) will be generated when any
of the alarms indicated in above mention list appears on the LCD screen of UPS
Panel.
Project : 2 x 300 MW Coal based group captive power project
Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-VEN-405-K-0000 53
HI-REL DOC NO : 105CL12341
Rev : A DATE:26.5.11 PAGE2 OF 2
---------------------------------------------------------------------------------------------------------------------
1
2
.
0
5
.
1
1
B
.
B
.
N
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
Sheet3
Page 2
ACDB FEEDER LIST FOR 5 KVA UPS
Sr. No Feeder No From Location From Terminal Terminal type MCB FUSE
1 FEEDER -1
ACDB
TA-2 - 1 (L)
KUT 10
32A 32A RINFRA
TA-2 - 2 (N)
2 FEEDER -2
TA-2 - 3 (L)
32A 32A RINFRA
TA-2 - 4 (N)
3 FEEDER -3
TA-2 - 5 (L)
32A 32A RINFRA
TA-2 - 6 (N)
4 FEEDER -4
TA-2 - 7 (L)
16A 16A RINFRA
TA-2 - 8 (N)
5 FEEDER -5
TA-2 - 9 (L)
16A 16A RINFRA
TA-2 - 10 (N)
6 FEEDER -6
TA-2 - 11 (L)
16A 16A RINFRA
TA-2 - 12 (N)
7 FEEDER -7
TA-2 - 13 (L)
16A 16A RINFRA
TA-2 - 14 (N)
8 FEEDER -8
TA-2 - 15 (L)
16A 16A RINFRA
TA-2 - 16 (N)
9 FEEDER-9
TA-2 17 (L)
16A 16A RINFRA
TA-2 18 (N)
10 FEEDER -10
TA-2 19 (L)
16A 16A RINFRA
TA-2 20 (N)
11 FEEDER -11
TA-2 21 (L)
10A 10A RINFRA
TA-2 22 (N)
12 FEEDER -12
TA-2 23 (L)
10A 10A RINFRA
TA-2 24 (N)
13
FEEDER -13
TA-2 25 (L)
10A 10A RINFRA
TA-2 26 (N)
14 FEEDER -14
TA-2 27 (L)
10A 10A RINFRA
TA-2 28 (N)
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-K-0000 55
HIREL DWG NO. 105CL12341 REV:A
PAGE 1 OF 1
Cable in
Scope
Recommende
d Cable size
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
2C x 6 Sq mm
AYFY
12.05.11
B.B.N.
V6/1087 12.05.11
1
2
.
0
5
.
1
1
B
.
B
.
N
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
B
.
B
.
N
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
B
.
B
.
N
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
1
2
.
0
5
.
1
1
V
6
/
1
0
8
7
1
2
.
0
5
.
1
1
B
.
B
.
N
.
SCOPE
Page 8
SCOPE OF SUPPLY FOR 5KVA UPS
MARERIAL HEAD Qty (n) REMARKS
1 5 KVA UPS SYSTEM 1 NO. UPS
2 AUXILLARY 1 NO. I/P ISOLATION X'MER + SCVS
3 BATTERY JN. BOX 1 NO. WALL MOUNTED
4 ACDB 1 NO. FLOOR MOUNTED NON-COMPARTMENTALIZED
5 MODBUS CONNECTIVITY ----- IN BUILT IN UPS
6 UPS TO BATTERY CABLE 2 X 20 METERS 1C,UN-10 UNINYVIN Flexible cu cable
7 UPS TO ACDB CABLE 2 X 20 METERS 1C, UN-8 UNINYVIN. Flexible cu cable
Quantity : 2Sets
MARERIAL HEAD Qty (n) REMARKS
1 Mandatroy Spares 1 SET -----
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-000060
HIREL DWG NO. 105GB12341 REV:0
PAGE 1 OF 1
Sr.
No.
Sr.
No.
12.05.11
B.B.N.
V6/1087 12.05.11
STAND ALONE UPS SYSTEM-I4 SERIES
An uninterrupted Power Supply is employed for critical loads which cannot be
powered by utility supply (mains) directly.
OPERATION MODES
1. NORMAL MODE:
When the utility is normal , the UPS powers the load through the rectifier and
inverter and charging the batteries at the same time, as shown in above figure. This is
called Normal Mode.
2. BATTERY MODE:
Failure of the Utility supply or fault in the rectifier/charger section. Inverter will
feed load from the Battery.
After resumption of the Utility supply, battery will undergo chargering & inverter
will feed load from the rectifier/charger.
3. Maintenance Mode
Should the UPS module need to be taken out of service for limited maintenance or
repair, manual activation of the bypass shall cause an immediate transfer of the
connected a.c. load from the inverter to the bypass source. Full electrical isolation of
the UPS system shall therefore be obtained, without disruption to the critical load, by
operation of an integral wrap-around maintenance bypass switch.
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-W-000061
HIREL DWG NO. 105WR12341 REV:0
12.05.11
B.B.N.
V6/1087 12.05.11
HI - REL ELECTROINCS LIMITED
SUB VENDOR LIST FOR 5KVA
Sr. No. Description Name
1 AC CAPACITORS M/S EPCOS
M/S SYSTEC
M/S ALCON
2 DC CAPACITORS M/S EPCOS
M/S PHILLIPS
M/S ALCON
3 COOLING FANS M/S NADI
M/S REXNORD
M/S NISHIKI
4 FUSES M/S GE
M/S FERRAZ
M/S BUSMANN
5 THYRISTORS M/S SEMIKRON
6 IGBT M/S SEMIKRON
7 MCCB M/S L&T
8 ISOLATOR M/S L&T
9 SWITCH KAYCEE / SWITCH-ON
10 CHOKE M/S HI-REL
11 ELECTRONICS CARDS M/S HI-REL
12 METERS M/S MECO
M/S RISHABH
13 TRANSFORMER M/S HI-REL
14 STATIC SWITCH (THY.) M/S SEMIKRON
15 TERMINALS M/S ELMAX
M/S CONNECTWELL
16 SCVS M/S HI-REL
17 MCB M/S L&T
18 POWER CABLE M/S INDUSTRIAL GLASS
19 CONTROL CABLE M/S INDUSTRIAL GLASS
M/S LAPP
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-U-000064
PAGE 1 OF 1
12.05.11
B.B.N.
V6/1087 12.05.11
CABLE SIZING CALCULATION
INPUT CABLE FOR AUX : -
SELECTED TRANSFORMER IS : 5kVA
PRIMARY RATED CURRENT : 6.96 AMPS. 6.96X1.732A = 12.05
(DUE TO OPEN DELTA CONNECTION)
SELECTED CABLE IS 10sqmm 3C AYFY CABLE.
CURRENT HANDLING CAPACITY IS 40 AMPS @ 50 Deg.C AMBIENT.
INPUT CABLE FOR UPS : -
SELECTED TRANSFORMER IS : 13kVA
PRIMARY RATED CURRENT : 18.09 AMPS.
SELECTED CABLE IS 10sqmm 3C AYFY ,CABLE.
CURRENT HANDLING CAPACITY IS 40 AMPS @ 50 Deg.C AMBIENT.
Page : 01 OF 01
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-S-000065
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-S-000065
17.06.11
17.06.11 V6/1152
B.B.N.