Professional Documents
Culture Documents
Developed by a working group of the Power System Relay Committee (PSRC) First published in 1995 widely presented within the industry, including a presentation at the 2003 PPIC Conference Updated, published, and presented for the first time at the 2011 57th IEEE Pulp and Paper Industry Conference
Michael Thompson, Chair Christopher Ruckman, Vice Chair Hasnain Ashrafi Gabirel Benmouyal Zeeky Bukhala Stephen P. Conrad Everett Fennell Dale Finney Dale Fredrickson Jonathan D. Gardell Juan Gers Randy Hamilton Wayne Hartmann Gerald Johnson Patrick M. Kerrigan Sungsoo Kim Prem Kumar
Hugo Monterrubio Charles Mozina Mukesh Nagpal Brent Oxandale Russell W. Patterson Mike Reichard Mohindar Sachdev Kevin Stephan Sudhir Thakur Demetrios Tziouvaras Joe Uchiyama Quintin Verzosa, Jr. Thomas Wiedman Michael Wright John Wang Murty V. V. S. Yalla
Fundamentals Multifunction Generator Protection Systems Stator Phase Fault Protection Stator Ground Fault Protection Field Fault Protection System Backup Protection Generator Breaker Failure Abnormal Frequency Protection Overexcitation and Overvoltage Protection
Underexcitation / Loss-of-Excitation Protection Current Unbalance (Negative-Sequence) Protection Loss of Prime Mover (Antimotoring) Protection Out-of-Step Protection Voltage Transformer Signal Loss Inadvertent Energization Protection Other Protective Considerations Tripping Modes
Basic design and operation of synchronous generators Power system connections Behavior under short-circuit conditions Generator grounding Generator stability IEEE guidelines Device numbers
MW G System MVAR Normal Overexcited Operation Stator Winding Limited + MW Real Power Into System
Underexcitation Limiter (UEL) Underexcited MVAR Reactive Power Into Generator Stator End Iron Limited Steady-State Stability Limit MW G MVAR Underexcited Operation System
kV 2 RC MVA = Z RV kV 2 RC Z= MVA R V
X
Angle Angle
R Z
Current
Current
Current
Types of Instability
Pmax =
Eg Es X
Pe =
Eg Es X
sin g s
SYSTEM
Egg
Ess
GSU
System Reactance
XS Where: XT Xe = XT + XS Xe
V2 2
1 1 X X d e
V2 2
1 1 + X X d e
Xd Xe 2
Xd + Xe 2
Per-Unit MW
Power System
Ess
Three-Phase Short Circuit
Substation 1
GSU 78 = Out-of-Step Protection Es = System Voltage Eg = Generator Voltage s = System Voltage Phase Angle g = Generator Voltage Phase Angle 78 G T
Egg
Pmax =
Eg Es X
A2 PM = Pe
Pe =
A1 C 0 90 g s 180
Eg Es X
sin g s
Occurs when fast-acting AVR control amplifies rather than damps small MW oscillations Most likely to occur when generators are remote from load centers Power system stabilizer (PSS) damps oscillations required in Western United States
Std. 242, IAS Buff Book C37.102, IEEE Guide for Generator Protection C37.101, IEEE Guide for AC Generator Ground Protection C37.106, IEEE Guide for Abnormal Frequency Protection for Power Generating Plants
Created / maintained by the IEEE PSRC & IAS updated every 5 years
C37.102-2006 updated version now available includes significant changes and additions
Device Number
Function
Tutorial Chapter
Multifunction Protection System Distance Relay Backup for System and Generator Zone Phase Faults Volts / Hertz Protection for Generator Overexcitation 100 Percent Stator Ground Fault Protection Reverse Power Relay Antimotoring Protection Loss-of-Field Protection Negative-Sequence Current Unbalance Protection for Generators Stator Thermal Protection Time-Overcurrent Ground Relay Backup for Ground Faults
Device Number
Function
Tutorial Chapter
Voltage-Controlled or Voltage-Restrained Time-Overcurrent Relay Backup for System and Generator Phase Faults Overvoltage Protection Overvoltage Relay Stator Ground Fault Protection for Generators Voltage Balance Relay Detection of Blown Voltage Transformer Fuses Transformer Fault Pressure Relay Breaker Failure Timer Field Ground Fault Protection Transformer Oil or Gas Level Loss-of-Synchronism Protection
Device Number
Function
Tutorial Chapter
Frequency Relay Both Underfrequency and Overfrequency Protection Hand-Reset Lockout Auxiliary Relay Differential Relay Primary Phase Fault Protection for Generators Stator Ground Fault Differential Protection Differential Relay Primary Protection for Transformers Differential Relay Overall Generator and Transformer Protection
87T
Unit Transformer
87O Unit Differential 24 2 Second V/Hz UAT Oil Low Voltage Balance 71 UAT Fault Pressure 63 UAT Overvoltage 59 50/ 27 Inadv. Energ. (Note 4) 78 Loss of Synchronism 24 1 Loss of Field 40 V/Hz 51 51 TG1 TG2 51 Unit Auxiliary Bus Phase Time Overcurrent UAT Neutral Overcurrent 50 51 UAT Backup
60
81
Frequency
87T
UAT Differential
Field Breaker
32 49 Reverse Power
Auxiliary VTs
41
Stat. Temp 64F 53 87G
Generator Differential
Field (Note 1) Ground 46 Negative Sequence Generator Neutral Overvoltage 21/ 51V System Backup (Note 2)
59G
27 TN
50/ 51G
Notes: 1. Dotted devices optional. 2. Device 21 requires external timer. See Chapter 2.4. 3. See Chapter 2.2 regarding 100 percent ground protection. 4. Device 50 requires external timer. See Chapter 4.1.
Generator protective relaying technology has evolved from discrete electromechanical and static relays to digital multifunction protection systems With availability, additional performance, economic advantages, and reliability of digital multifunction protection systems, this advanced technology is incorporated into most new protection schemes
In most cases, new generators are protected with one of the following:
Inputs ROM Voltage Inputs RAM EEPROM Current Inputs Data Acquisition System User Interface Microprocessor
Outputs
Digital Inputs
Communications
52 87T
87O 11G MGPS #1 Relaying Functions 24 27/59 32-1 32-2 40 46 49 50 51V or 21 50/51G 59G 60 78 81 87G 27TH or 59THD or 64S 11G MGPS #2 Relaying Functions 24 27/59 32-1 32-2 40 46 49 50 51V or 21 50/51G 59G 60 64F 81 87G 27TH or 59THD or 64S
Field
Saturation
Stator differential protection does not detect turn-to-turn faults Current can be 6 to 7 times nominal and can damage stator Use turn-to-turn protection schemes to detect and avoid damage
Imperfection in generator construction Temperature variations Winding connections External faults Terminal voltage and load variations
The Method of Generator Neutral Grounding Determines its Performance During Ground Faults
Solidly Grounded Low Impedance High Impedance Hybrid Grounding Ungrounded
BUS
and isolated systems May have problems with circulating 3rd harmonic
Use of single grounded machine can help
45MVA Generator
2000/5 CTs
80% 87
2000/5
400 A
62
87G Generator Differential 87GD Generator Ground Differential 51N Neutral Overcurrent
IA IB
Residual current calculated from individual phase currents. Paralleled CTs shown to illustrate principle.
IC IG
IG 3 I0
90 3I O 180 0 IG 270
IA IB
Residual current calculated from individual phase currents. Paralleled CTs shown to illustrate principle.
IC IG
IG 3I 0
90
180
0 3I O 270
IG
High-impedance ground limits ground fault current (limits damage on internal winding to ground fault) Conventional neutral or zerosequence overvoltage relay (59G) provides coverage for the ground faults involving up to 90%95% of the winding from phase terminal
R
59G
51G connected in the primary or secondary neutral circuit can be used as a backup to 59G
Last 5%10% near neutral not covered by neutral overvoltage relay (59G) because a ground fault in this winding region bypasses grounding transformer or resistor (R) or 59G, solidly grounding the machine
59G
XHL
Sensitively set 59G relay to detect ground faults (up to 95% of the winding) can also pick up for faults on the HV side of GSU or in the VT secondary circuit
59G
Io
Co
CHL
Zero-Sequence Network
Z0 VR := V0 Z + X HL 0
XHL
R 3Io
VR
3R
Xo
V0
Third-harmonic voltage develops in stator due to inherent presence of third harmonic flux in the rotor field
Rotor MMF
I3h A, B, C
Co
Generator winding and terminal capacitances provide path for the third-harmonic stator current via grounding resistor
R 3I3h
Machine construction the pitch of the stator Levels of excitation (MVAR) and machine output (MW) Terminal capacitance
Normal Operation Neutral No Load Full Load V3RD Fault at Neutral Neutral Fault at Terminal Neutral No Load Full Load V3RD
+V3RD
Present in terminal and neutral ends Can vary with loading Detects ground faults near neutral
Note: If third harmonic goes away across neutral resistor, conclude a ground fault near neutral
Terminal
I3h
C0
Under normal conditions, 27N3 is picked up because of the third-harmonic voltage drop across neutral resistor
3I3h
59G
27N3
I3h
C0
For a fault close to neutral of the stator winding, 27N3 drops out because the fault bypasses the neutral resistor A supervisory overvoltage (59C) relay located at the generator terminal blocks 27N3 operation during startup or shutdown to avoid misoperation
3I3h
59G
27N3
100%
59G
~95% of winding from terminal by 59G ~15%30% of winding from neutral by 27N3
27N3 5% 0%
59G
27N3
Compares third-harmonic voltage magnitude at the generator neutral to that at the generator terminals
Ferroresonance damping resistor
59D
59G
100%
59G
~95% of winding from terminal by 59G ~15%30% of winding from neutral and terminal by 59D
59D
59D 5% 0% 59D
59G
Does not rely on third-harmonic signature of generator Provides full coverage protection Provides online and offline protection prevents serious damage upon application of excitation Is frequency independent
Pickup Setting
64S
Hazards of field faults Field ground protection Tripping considerations Field ground relay selection and settings Field overcurrent
Field
Exciter
Field Breaker
64F DC
Ground #1 Ground #2
Shorts out part of field winding expect unit vibrations, possible damage Causes local rotor current expect rotor heating, distorted rotor, vibration Causes arc damage at fault points
Field
64F DC
Positive
R2 Generator Generator Field 64F Test Pushbutton (optional) Voltage Relay R2 + Exciter
Negative
Field +
Brush CR C1 AC R 64F C2
Immediate tripping is recommended on first ground However, most installations alarm and shutdown the machine in orderly manner if ground alarm persists Relays should also be provided with time delays to override transients
System backup protection for generators consists of time-delayed protection for phase-to-ground and multiphase fault conditions Backup generator protection schemes protect against failure of system protection and subsequent long-clearing system faults
Relay settings for backup relaying must be sensitive to detect low fault current conditions Settings must balance opposing sensitivity requirements to detect distant faults and security to prevent unnecessary generator tripping
Use either distance or voltagerestrained overcurrent relay to detect system multiphase faults.
Use a time-inverse transformer neutral connected overcurrent relay for system ground faults.
98
V-C overcurrent
Voltage element supervises (torque controls) a sensitive, low pickup time-overcurrent element Under fault conditions, voltage drops below set level dropping out voltage element and permitting overcurrent element to operate
Current Level
V-R overcurrent consists of an overcurrent element whose pickup level varies as a function of voltage applied to relay Normally, generator terminal voltage is above voltage setting, VS1, and current pickup setting is IS
When close-in fault occurs, voltage can drop below voltage setting, VS2, and current pickup level is reduced by factor k to kIS For voltages between VS1 and VS2, pickup level varies proportionately between IS and kIS
Calculate 51V voltage element setting to avoid 51V relay misoperation under extreme emergency conditions (with lowest expected system voltage)
To allow for selectivity, time-delay settings must be coordinated with transmission system primary and backup protection, including breaker failure time Coordination is usually calculated with zero voltage restraint
Use three V-C or V-R time-overcurrent relays for complete multiphase fault coverage Note that generator fault current may decay rapidly when low voltage is at generator terminals overcurrent phase fault backup may not operate for system faults Check setting with fault current decrement curve for particular generator and excitation system
Setting detects line fault when protection equipment fails Relay impedance reach and time delay must be coordinated with system primary and backup protection, including breaker failure time Setting must remain conservatively above machine rating to prevent inadvertent trips on generator swings and severe voltage disturbances
F5
FLT
F4
F1
The impedance relay for each generator requires sensitive settings to detect faults at the ends of long lines in the presence of other sources.
F3
F2
Sensitive settings may cause backup relays to unnecessarily trip generator under some loading conditions or for minor, stable swings With this system configuration, it is generally possible to set backup relays to detect only close-in faults Redundant line relaying and breaker failure relaying are necessary for line, bus, and transformer protection
120% of longest line (with infeed) if unit is connected to breaker-and-a-half bus, calculate percent using adjacent line length 50%66.7% of load impedance (200%150% of generator capability curve) at machine-rated power factor 80%90% of load impedance (125%111% of generator capability curve) at relay maximum torque angle (MTA)
25.0
Zone 2 reach will not provide adequate phase fault system backup protection as it would require an extremely large setting. The only way to ensure adequate protection to avoid sustained currents to the fault is to provide redundant transmission system protection.
GCC
Zone 2 limited to 67% of generator capability curve at rated power factor. Zone 1 set to cover 120% of GSU impedance.
10.0
5.0
5.0
10.0
15.0
Provides for tripping of backup breakers when the generator breaker does not open after trip initiation upon detection of
Open circuit to trip coil Mechanism fails to open breaker Breaker opens but breaker contacts fail to interrupt fault Tripping of circuit breaker left open after maintenance
Need to include breaker auxiliary contact status in addition to current detection BF protection should be fast enough to maintain stability but not so fast as to compromise tripping security
Breaker flashover is a type of breaker failure Breaker flashover is most likely to occur just prior to synchronizing or just after generator is removed from service
Three-phase simultaneous flashovers are rare, thus most protection schemes are designed to detect the flashover of one or two poles
Underfrequency occurs as the result of sudden reduction in input power through loss of generators or key intertie importing power Overfrequency occurs as the result of sudden loss of load or key intertie exporting power
Regional reliability councils will typically provide settings for underfrequency load shedding and generator tripping Load shedding schemes must coordinate and meet regional criteria Generator tripping criteria must accommodate any frequency excursion during any islanding scenario
60
59
Frequency (Hz)
58
57 Generator tripping permitted on or below curve without requiring additional equivalent automatic load shedding.
56
V%
Operation outside shaded area is limited in extent, duration, and frequency of occurrence Severe restrictions could be imposed on the generator itself
94 96 98 100
106
104
102
102
104
f%
98
96
Possibility of frequency operational limits exists for the generator in the form of time-frequency characteristics
94
Protection of the long tuned blading in the low-pressure turbine element for steam units Possibility of cumulative blading fatigue and blading failure Similar limitations for combustion and combined-cycle turbines Virtually no frequency limitations for hydro generating units
Continuous Operation
Prohibited Operation 0.005 0.01 0.05 0.50 0.10 1.0 Time (Minutes) 5.0 10.0 50.0 100.0
Obtain turbine capability 63 62 from manufacturer 61 Verify if IEC 60034-3: 2007 is applicable Have manufacturer approve protection scheme
60 59 58 57 56 55 54 1 10 100 1000 Total Accumulated Time Limit (Minutes) 10-Minute Maximum Continuous Operating Region
Frequency (Hz)
additional heating
Overvoltage application:
Stresses stator insulation and connected components Cannot be reliably detected using V/Hz alone
System problems
Unit load rejection: full load, partial rejection Power system islanding during major disturbances
V% 106
104
98
96
94
Copyright 2005 IEC, Geneva, Switzerland
140
130
120 Individual manufacturers should be consulted for limits of a specific transformer. 110 0.01
0.1
1 Time (minutes)
10
100
V/Hz (%)
Limiting factors are rotor and stator thermal limits Underexcited limiting factor is stator end iron heat Excitation control setting control is coordinated with steady-state stability limit (SSSL) Minimum excitation limiter (MEL) prevents exciter from reducing the field below SSSL
MEL Underexcited MVAR Reactive Power Into Generator MW SSSL Stator End Iron Limited G MVAR System
Field open circuit Field short circuit (flashover across slip rings) Accidental tripping of field breaker Voltage regulator control system failure LOF to main exciter Loss of ac supply to excitation system
Impedance variation with the machine operating at or near full load locus follows path from C to D Machine that initially operates at 30% load and underexcited. Impedance locus follows path from E to F to G and oscillates in region between F and G Generally for any loading, impedance terminates on or varies from D to L
Two modern offset mho relays can be used Relay with 1.0 pu impedance diameter detects LOF condition from full load to about 30% load First relay is set with short time delay; 0.1-second delay suggested for security against misoperation during transients
+X
+R Offset =
X d 2
2 Diameter = Xd 1 X 1 2
Second relay is set with time delay; 0.5 to 0.6 seconds provides protection for LOE condition up to no load Two offset mho relays provide LOE protection for any loading level Both relays are set with offset of Xd/2
+X
+R Offset =
X d 2
2 Diameter = Xd 1 X 1 2
Experience has shown that these settings are secure over a wide range of system conditions. However, transient stability analysis should be performed to verify this.
MEL and LOF characteristic are coordinated so they do not overlap MEL prevents leading var excursions into the LOF characteristic to avoid relay misoperation for system transients Negative-offset mho element characteristic leaves underprotected area relative to SSSL and stator end iron limit curve of the machine capability
0.8
0.4
Generator Capability
0.4
P pu (MW)
Generator
GSU
G
Per Unit Mvar
Xd
XT
V2 2
1 Xe
1 Xd
V2 2
1_ + 1 Xe Xd
Xd - Xe 2 Xd + Xe 2
Per Unit MW
This scheme combines positive-offset mho relay, directional relay, and undervoltage relay applied at generator terminals and set to look into machine 1.1 (X )
d
Z2 Setting
XS
X d Offset = 2
Z1 Setting R
Machine Capability
Directional unit supervises mho unit because positiveoffset allows it to operate for faults external to generator terminals
MEL
SSSL
Improves coverage
System Asymmetries
Unbalanced loads
Untransposed transmission lines Single-phase GSU with unequal impedances
Strongest I2 source is generator phase-tophase fault Generators connected with delta-wye GSU transformer
System ground faults appear as phase-to-
as much I2
I2 in the stator creates a magnetic field component that rotates in opposite direction of rotor and power system (positive-sequence) field component
As a result, double-frequency current is induced in rotor At twice fundamental frequency, skin effect promotes current in rotor surface areas and, to a smaller degree, in the field winding
Beyond a point, the induced surface currents can cause heating of metal wedges that hold field windings and / or retaining rings on rotor ends, causing them to anneal, expand, and loosen with catastrophic results
For salient-pole machines, double-frequency currents concentrate at pole faces and teeth Much current appears in the pole-face amortisseur windings
40 30
I2 2 t = 10
I2 2 t Capability
I2 2 t = 10 [(0.00625)(MVA 800)]
Values shown in Tables I and II of this chapter are for machines manufactured to IEEE C50 standards since 2005 Equipment nameplate data and / or the manufacturer may be consulted to verify machine capabilities
open conductors
Limited protection as damaging heat can
Allows relay characteristics that can match generator I2 capabilities Allows I2 pickup settings down to 0.03 pu Can be set to alarm at lower than generator limits, allowing plant operator to attempt to reduce I2 before trip occurs
1 103
100
Time (seconds)
40
10 5 2
0.1 0.01
10
The 78 protection scheme protects the generator from OOS or pole-slip conditions Common relay schemes for detecting generator OOS events include:
Single blinder Double blinder Concentric circle
When a Generator Goes Out-of-Step (Synchronism) with the Power System, High Levels of Transient Shaft Torque are Developed. If the Slip Frequency Approaches Natural Shaft Frequency, Torque Produced can Break the Shaft. High Stator Core End Iron Flux can Overheat and Damage the Generator Stator Core. GSU Subjected to High Transient Currents and Mechanical Stresses.
171
172
One pair of blinders (vertical lines) Supervisory offset mho Mho limits reach of scheme to swings near the generator
The most popular OOS protection is the single blinder scheme Pickup area is restricted to shaded area defined by inner region of mho circle and area between Blinders A and B
Z3(t3)
Positive-sequence impedance must originate outside either Blinder A or Blinder B It should swing through the pickup area and progress to the opposing blinder Swing time should be greater than time-delay setting
Rotor Angle Generator G_1 Angle (degrees) Case 1 (tc = 90 ms), with controls Case 2 (tc = 180 ms), with controls Case 3 (tc = 190 ms), with controls
Case 1 (tc = 90 ms), without controls Case 2 (tc = 180 ms), without controls Case 3 (tc = 190 ms), without controls
Time (seconds)
R-X diagrams show trajectory followed by impedance seen by relay during disturbance When an oscillation in the generator is stable, the point of impedance does not cross the line of the system When an OOS condition occurs, the point of impedance crosses the line of the system impedance each time the slip is completed
R (ohm)
X (ohm)
R (ohm)
X (ohm)
R (ohm)
Case 1 Tc = 0.09 ms
Case 2 Tc = 0.18 ms
Case 3 Tc = 0.19 ms
Apply OOS if swing impedance passes through GSU or generator This zone is protected by differential relays that do not respond to power swings Consider application of OOS if swing passes outside GSU but line protection is blocked or does not respond to swings
Common causes
Wiring failure Open in VT draw-out assembly Blown fuse due to short-circuit Fuse left out after maintenance
Affected functions
21, 27, 32, 40, 50/27, 51V, 67N, 78, 81 Automatic voltage regulator (AVR runaway)
When fuse blows, unbalanced voltages created Two sets of VTs required
Three-Phase Loss
Low three-phase voltages
Operating errors Breaker head flashovers Control circuit malfunctions Combination of above
Typically, normal generator relaying is not adequate to detect inadvertent energizing Generator behaves as induction motor Flux induced into generator rotor causing rapid rotor heating Rotor current is forced into negativesequence path in rotor body
X1S = system positive-sequence reactance X1T = transformer positive-sequence reactance X2G = generator negative-sequence reactance
Gen.
X2G
ES
EG = generator terminal voltage ES = system voltage ET = transformer high-side voltage I = current R2G = generator negative-sequence resistance
Gen.
R2G
Undervoltage (27) supervises low-set, instant overcurrent (50) recommended 27 setting is 50% or lower of normal voltage Pickup timer ensures generator is dead for fixed time to ride through three-phase system faults Dropout timer ensures that overcurrent element gets a chance to trip if voltage is higher than 27 setting during event
Large gas turbines are started as a motor using static frequency converter V/Hz is maintained constant until rated voltage is reached, after which rated voltage is maintained Extended operation occurs at low speeds while purging and firing cycles are completed Generator must be protected during low-frequency operation
Some protection such as phase overcurrent and phase unbalance is provided by converter controls To be effective, multifunction generator relays must maintain protection down to low frequencies At lower frequencies, protective functions may deviate from normal specifications In some cases, protective functions may have to be disabled during starting because of possible false operation
Fault-to-ground on dc link cannot be detected by converter controls Fault causes dc current to flow through any wye-connected VTs and generator ground
.
DC current saturates magnetic elements (VTs and distribution transformer in generator neutral) Damage can occur if fault is not cleared PT can be damaged in approximately 50 ms Two strategies to address this fault include
Measure dc current in generator neutral (e.g., with
transducer) and use dc relay and turn converter off before damage occurs
Eliminate any ground path through magnetic elements
during starting (use delta-connected VTs and disconnect generator neutral while starting)
To avoid damage to generator or GSU unit, synchronizing across breaker should be done within tight limits Typical recommendations are
Electrical degrees 10 Voltage 0 to +5 percent
Synchronizing equipment or supervising relays should take into account breaker closing time and relative slip, closing breaker in advance so that angle between generator and system at closing is as close to zero as possible
Generators may be operated at lower frequency during startup and shutdown Electromechanical relays can become very insensitive at off nominal frequencies Plunger-type overcurrent relays have flat characteristics down to low frequencies and are used to provide supplementary protection during start up and shutdown these relays cannot be energized continuously and have to be disconnected during normal operation Microprocessor-based relays can provide protection down to lower frequencies and generally do not require supplementary protection
Pickup in Multiples of 60 Hz Pickup
(B) (D)
(C)
(D)
(E)
(B) (C)
(F) 30 40 50 Frequency in Hz 60 70 80
Plunger-Type Current Relay Induction Overcurrent Relay Generator Differential Relay Generator Ground Relay Harmonic Restraint Transformer Differential Relay Plunger-Type Voltage Relay
Generator protection functions with same trip / shutdown modes are grouped together
Operated by protective functions, auxiliary lockout relays, 86G (usually hand-reset), perform most tripping Where possible, primary and backup relays trip via separate paths / lockouts
Includes tripping of all electrical and mechanical power sources Provides fastest way to isolate generator
Does not shut down prime mover Used when abnormality can be corrected quickly allowing fast reconnection
Only trips generator breaker(s) Used when disturbance is on system and it is desired to have generator run its own auxiliaries
Used to prevent overspeed when delayed tripping of breakers is not detrimental following a prime mover trip, planned or unplanned, breakers are tripped after reverse or low (hydro) power is detected Not used for clearing faults
Much tripping philosophy depends on ability of generating unit to continue operating after disconnection from system (full load rejection) If unit cannot support its own auxiliaries, then a tripping mode that transfers auxiliaries should be incorporated
Table II provides suggested steam unit trip logic by IEEE protective function numbers Some functions are alarmed only In general, G means generator and N means neutral or ground
51TG1 and 81 are examples of functions set to trip in unit separation mode
Table III provides typical tripping for hydroelectric units Trip requirements are similar to thermal generators but may need slightly different slip / shutdown operations
Slower rotation devices Different mechanical control devices
A generator disconnect switch is often used when tie to transmission system is dual-breaker arrangement
Sometimes generator protective functions are enabled / disabled by utilizing auxiliary switch contacts based on position of disconnect switch Be cautious about bad or incorrect disconnect position status leaving generator unprotected