Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification FRONT MOUNTED EQUIPMENTS CT Sec: 5A, PT Sec:110V AC (PH-PH) Aux. Supply : 220V DC 15B/I, 20B/O + 1 LIVE STATUS CONTACT Case Size : 1/1 19", IEC61850 PROTOCOL MLFB : 7UM6225-6EB92-3CB0-LOS

Make

Dis

Type 10CHA00GH001 10CHA00GH002 0

QTY / Panel 10CHA00GH003 0

Total Qty. 10CHA00GH004 0 10CHA00GH005 0 1

GR1

Generator Differential Protn (87G) Gen. B/U Impedence Protn - Stage-1(21G1) Gen. B/U Impedence Protn - Stage-2(21G1) Gen. Under Frequency Stage -1(81UF) Gen. Under Frequency Stage -2(81UF) Time Stage-1&2 Gen. Over Frequency Protn. (81OF) Reverse Power Relay(32G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Time Stage-1 Reverse Power Relay(32G) +Time Stage-2 Low Power Relay(37G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Timer Gen. Under Voltage Protn. (27G) Gen. Over Voltage Stage-1 & 2 (59G) Gen. Over Fluxing Stage-1 (99G) Gen. Over Fluxing Stage-2 (99G) With GCB Open & Closed Gen. Pole Slipping (78G) Gen. Loss of Excitation (40G) Gen. Loss of Excitation With Under Voltage (27/40G) Gen. Negetive Phase Sequence (46) Stage-1 Gen. Neg. Phase Sequence (46) Stage-2 Time Stage-1&2 Gen. Stator Over load (50GS) Gen. Stator earth fault 95% (64G2) GCB Local Breaker Backup (50LBB) Dead machine Protection (61B) Voltage Balance Protection (60G21, 60G22, 60G23) Gen. Open delta earth Fault Protection (59N)

SIEMENS

7UM62

60G11,60G12 60G13,60G21 60G22,60G23

Voltage Balance Relay

Aux. Supply : 220V DC, 2NO+4CO, S/R PT Sec:110V AC (PH-PH) , Case Size: Midos Case - 4 Wiring diagram: F1MVAPM32001 Model: MVAPM32D1AA2001A Aux. Supply : 220V DC Case: Midos size:4 Contacts: 14NO+6NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush Model: MVAJ205LA1006A Aux. Supply : 220V DC Case: Midos size:4 Contacts: 14NO+6NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush Model: MVAJ205LA1006A

AREVA

MVAPM32

186A1,186A2-1 186A2-2, 186A2-3 186C-1,

High speed G roup-1 Class A//C 3 phase trip relay (Hand/Electrical Reset)

AREVA

MVAJ20

286A1, 286A2-1 286A2-2, 286A2-3 286C-1,

High speed G roup-2 Class A//C 3 phase trip relay (Hand/Electrical Reset)

AREVA

MVAJ20

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 1 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref GR2

Description Generator Differential Protn (87G) Gen. B/U Impedence Protn - Stage-1(21G1) Gen. B/U Impedence Protn - Stage-2(21G1) Gen. Under Frequency Stage -1(81UF) Gen. Under Frequency Stage -2(81UF) Time Stage-1&2 Gen. Over Frequency Protn. (81OF) Reverse Power Relay(32G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Time Stage-1 Reverse Power Relay(32G) +Time Stage-2 Low Power Relay(37G)+Turbine trip Relay Operated/ Turbine stop Volve Closed+Timer Gen. Under Voltage Protn. (27G) Gen. Over Voltage Stage-1 & 2 (59G) Gen. Over Fluxing Stage-1 (99G) Gen. Over Fluxing Stage-2 (99G) With GCB Open & Closed Gen. Pole Slipping (78G) Gen. Loss of Excitation (40G) Gen. Loss of Excitation With Under Voltage (27/40G) Gen. Negetive Phase Sequence (46) Stage-1 Gen. Neg. Phase Sequence (46) Stage-2 Time Stage-1&2 Gen. Stator Over load (50GS) Gen. Stator earth fault 95% (64G2) GCB Local Breaker Backup (50LBB) Dead machine Protection (61B) Voltage Balance Protection (60G21, 60G22, 60G23) Gen. Open delta earth Fault Protection (59N) Supervision relay for High Speed Triping relay

Specification CT Sec: 5A, PT Sec:110V AC (PH-PH) Aux. Supply : 220V DC 15B/I, 20B/O + 1 LIVE STATUS CONTACT Case Size : 1/1 19", IEC61850 PROTOCOL MLFB : 7UM6225-6EB92-3CB0-LOS

Make SIEMENS

Dis 3

Type 7UM62 10CHA00GH001 0 10CHA00GH002 1

QTY / Panel 10CHA00GH003 0

Total Qty. 10CHA00GH004 0 10CHA00GH005 0 1

95/186A1,95/186A2-1 95/186A2-2,95/186A2-3 95/186B,95/186C-1, 95/186C-2,95/186DUT10A, 95/186DUT10B, 95/186DST1

Trip Relay Supervision Relay Aux. Supply: 220V DC, Contacts: 1NO+2NC S/R Flag: Yes, Case:-Size 3 Midos: Mounting-Flush Model no: MVAXM21C1CE3005A WDG: F1MVAXM21001

AREVA

MVAXM21

10

95/286A1,95/286A2-1 95/286A2-2,95/286A2-3 95/286B, 95/286C-1, 95/286C-2,95/286DUT10A, 95/286DUT10B, 95/286DST1 80A, 80B

Supervision relay for High Speed Triping relay

Trip Relay Supervision Relay Aux. Supply: 220V DC, Contacts: 1NO+2NC S/R Flag: Yes, Case:-Size 3 Midos: Mounting-Flush Model no: MVAXM21C1CE3005A WDG: F1MVAXM21001

AREVA

MVAXM21

10

DC Supervision cum changeover Relay

Aux. Volt:220V DC, 2N/O, 2C/O, Flag- NO, S/R Slug: 80+/-20ms on D/O Size:2 MIDOS,Flush Model No:MVAAM11BIAG1030A WDG: Z1MVAAM11011

AREVA

MVAAM11

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 2 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification

Make

Dis

Type 10CHA00GH001 10CHA00GH002 0

QTY / Panel 10CHA00GH003 1

Total Qty. 10CHA00GH004 0 10CHA00GH005 0 1

87GT/64GT/99GT,

Numerical Generator Transformer Differential, With inbuilt Over fluxing & High impedance REF

CT Sec: 1A Aux. Supply : 220V DC, 110V AC 21B/I, 24B/O + 1 LIVE STATUS CONTACT Case Size : 1 /1 x 19", IEC 61850 PROTOCOL, MLFB : 7UT6331-6EB92-1BB1-LOS

SIEMENS

7UT633

87/51UT-10A 87/51UT-10B

Numerical Unit Transformer for Differential protection relay With Inbuilt O/C Relay

CT Sec: 1A Aux. Supply : 220V DC 21B/I, 24B/O + 1 LIVE STATUS CONTACT Case Size : 1 /1 x 19", IEC 61850 PROTOCOL, MLFB : 7UT6331-6EB92-1AA1-LOS

SIEMENS

7UT633

87/51ST1

Numerical station Transformer for Differential protection relay With Inbuilt O/C Relay

CT Sec: 1A Aux. Supply : 220V DC 21B/I, 24B/O + 1 LIVE STATUS CONTACT Case Size : 1 /1 x 19", IEC 61850 PROTOCOL, FO DOUBLE, ST CONNECTOR MLFB : 7UT6331-6EB92-1AA1-LOS

SIEMENS

7UT633

51NGT

GT Backup earth fault protection Relay

CT SEC:1A Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL MLFB: 7SJ8011-5EB96-1FA0-LOS CT SEC:1A Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL MLFB: 7SJ8011-5EB96-1FA0-LOS CT SEC:1A Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL MLFB: 7SJ8011-5EB96-1FA0-LOS

SIEMENS

7SJ80

50-UT10A 50-UT10B

Instantaneous over current protection relay for unit transformers

SIEMENS

7SJ80

50-ST1

Instantaneous over current protection relay for station transformer

SIEMENS

7SJ80

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 3 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification

Make

Dis

Type 10CHA00GH001 10CHA00GH002 0

QTY / Panel 10CHA00GH003 0

Total Qty. 10CHA00GH004 4 10CHA00GH005 0 4

64-1-UT10A 64-2-UT10A 64-1-UT10B 64-2-UT10B

Restricted earth fault protection relay for LV Side Unit transformer

CT SEC:1A Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL, FO DOUBLE, ST CONNECTOR MLFB: 7SJ8011-5EB96-1FA0-LOS CT SEC:1A Auxiliary voltage: 220V DC Size: 1/6 19"; Mounting: Flush 3 BI; 5 BO +1 LIVE STATUS CONTACT IEC 61850 PROTOCOL, FO DOUBLE, ST CONNECTOR MLFB: 7SJ8011-5EB96-1FA0-LOS

SIEMENS

7SJ80

64-1-ST1 64-2-ST1

Restricted earth fault protection relay for LV Side Station transformer

SIEMENS

7SJ80

BLK - GR1A / 1B /1C BLK - GR2A / 2B /2C BLK - 87G1 / 87G2 / 87A BLK - 50A / 64A / 87B BLK - 50B / 64B / 87 / 50 /64 G20Hz

Test Block

10 Terminal

AREVA

MPG

17

20Hz Generator for 100% SEF (For 100% Stator Earth Fault) Bandpass Filter for 100% SEF (For 100% Stator Earth Fault) Controlling Unit for Rotor Earth Fault (For Rotor Earth Fault) Resistor for 1-3Hz Rotor Earth Fault Protection (For Rotor Earth Fault) Neutral Displacement earth fault protection relay

Model No : 7XT33 in 7XP20 Case MLFB NO: 7XT3300-0CA00 Model No : 7XT34 in 7XP20 Case MLFB NO: 7XT3400-0CA00 MLFB NO: 7XT7100-0EA00

SIEMENS

7XT33

FGR1

SIEMENS

7XT34

SCUGRI

SIEMENS

7XT71

RCUGR

MLFB NO: 7XR6004-0CA00

SIEMENS

7X600

59N

PT Sec , 110V AC Aux. Supply : 220V DC 11B/I,6 B/O+1 LIVE STATUS CONTACT CASE SIZE:1/3x19", IEC 61850 PROTOCOL MLFB:7SJ6221-6EB92-1FE0-LOS

SIEMENS

7SJ62

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 4 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification

Make

Dis

Type 10CHA00GH001 10CHA00GH002

QTY / Panel 10CHA00GH003

Total Qty. 10CHA00GH004 10CHA00GH005

195, 295

Trip Circuit Supervision relay for GCB

220V DC, 1N/O + 2N/C SR,Flag-Yes, Size:4 Midos: Mounting: Flush Model No:MVAXM31D1CE3005A WDG: F1MVAXM31001

AREVA

MVAXM31

GCB, GISOLA, GISOLB

Contact multiplication relay For GCB / Generator &I solator

Aux. Supply:220V DC Case:1/2NV Contacts:4NO + 4N/C E/R Mounting:Flush, Flag: Yes WDG: BDZ075.6-9 MLFB NO: VAJC11ZF8305A(CH)

AREVA

VAJC11

186B 186C-2 186D-UT10A 186D-UT10B 286B 286C-2 286D-UT10A 286D-UT10B 186D-ST 286D-ST

Trip Relay For UTA, UTB

Trip Relay Case : Midos case size :2 Contacts : 8NO+2NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush Aux supply : 220V DC Electrical Reset Model : MVAJ105JA1002A

AREVA

MVAJ10

Trip Relay For ST

Trip Relay Case : Midos case size :2 Contacts : 8NO+2NC (Hand/Electrical Reset) Flag: Yes, Mounting: Flush Aux supply : 220V DC Electrical Reset Model : MVAJ105JA1002A 10 Port Switch 10/100 MBPS Aus supply: 220V DC, Dual Supply 19" Rack Mounting Type 6 Optical Port (ST Connector) 4 RJ45 Port
RSG2100 -R-RM-HI-HI-FX01-FX01-FX01-XXXX-XXXX-XXXX--XXXX-XXXX-TX01-TX01

AREVA

MVAJ10

ES-1, ES-2

Earthernet Swithes

RUGGED COM

RSG2100

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 5 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification

Make

Dis

Type 10CHA00GH001 10CHA00GH002

QTY / Panel 10CHA00GH003

Total Qty. 10CHA00GH004 10CHA00GH005

2/186A1, 2/186A2 2/186B, 2/186C 2/286A1, 2/286A2 2/286B, 2/286C

Wipe out Timer

Aux. Volt:220V DC, Contact : 2N/O , 2C/O , S/R Delay on Pick up : 0.01 - 9.99s Case : Midos case size :3 MIDOS Model No:MVTTM14C1AA1002A WDG: F10MVTTM14501

AREVA

MVTTM

PB01,PB02,PB03,PB04

Push Buttton for Trip Relay Reset- GROUP A

Normal actuator with plastic front ring and holder of black colour 3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A contact block for rear connection 3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A contact block for rear connection 3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A contact block for rear connection 3SB1200- 0AB01 (ACTUATOR)+ 3SB1400-0A

SIEMENS

3SB

PB05,PB06,PB07,PB08

Push Buttton for Trip Relay Reset- GROUP B

SIEMENS

3SB

PB09,PB10,PB11,PB12

Pushbutton

SIEMENS

3SB

PB13, PB14

Pushbutton

SIEMENS

3SB

LBBSW1, LBBSW2

LBB In-Out Selector switch for LBB protn. Indicating lamp for Relay DC1/DC2 healthy

Handle: Pistol Grip, Black,8 Ways Position: IN/OUT,Stayput , LOCKABLE in both position White Holder with indicator - 3SB14052WZ3 Lamp Holder with Rear Connection-3SB04012C

SWITRON

SPC32P

SL01, SL02

SIEMENS

3SB

DCSS

DC Supply Selector Switch

Stay Put Non-Lockable With Pistol Grip Handle Position (1) DC1 (2) INDEPENDENT (3) DC2 Bezel size: 75 Sq.mm No. of Ways : 8

SWITRON

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 6 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification

Make

Dis

Type 10CHA00GH001 10CHA00GH002

QTY / Panel 10CHA00GH003

Total Qty. 10CHA00GH004 10CHA00GH005

INTERNALLY MOUNTED EQUIPMENTS HT Space heater 100W,230V AC APT CONTROL Anchor Anchor APT CONTROL SIEMENS Philips SIEMENS SIEMENS 3 1 1 1 1 1 5

HTS PS TH

ON\OFF switch Power socket Thermostat

15 A 5/15A, 3Pin 30-90 deg cent

1 1 3

1 1 1

1 1 1

1 1 1

1 1 1

1 1 1

5 5 5

CILS CFL LK CT-1, CT-2 LOOSE SUPPLY

Cubicle Door Operated Switch Compact Fluoroscent Lamp Link Base + Link and holder NCT for 100% SEF Protection Loose supply and same to be provided in NGT cubicle Surge Divertor Stablizing Resistor DC MCB Double Pole , Aux contact:1NC

Limit Switch(1No+2Nc)-3SE30230A 240 V AC, 20W 3NW20NNSF+3NWNNSL 400/5A, 5VA Model No : 4NC 5225 MLFB NO: 4NC5225-2CE20 Model No.: C53207-A401-D77-1 Range : 0 - 1000 Ohms , 200Watts 32A, 220VDC 10A, 220VDC 4A, 220VDC

1 1 1 5 4NC5225

1 1 5 0

1 1 5 0

1 1 3 0

1 1 15 0

1 1 4 0

5 5 32 2

SD1 SR1 DC MCB

SIEMENS AREVA SIEMENS SIEMENS SIEMENS

3 3 3 3 3

0 0 1 3 1

0 0 1 3 1

1 1 0 0 10

4 4 0 0 4

2 2 0 0 2

7 7 2 6 18

AC MCB

AC MCB Single Pole & Neutral , Aux contact:1NC Test plug

16A, 230VAC

SIEMENS

MPB Test Plug (LOOSE SUPPLY)

AREVA

MPB

FO CABLE

CABLE

FO patch cable (ST-ST) 100BaseFX 1300nm, MultiMode 62,5/125m,2 core, Fibre Glass a. 10m b. 5m c. 3m

DLINK/ EQUIVALENT

5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 6 13

D1 to D32

DIODE

CDL4U(E)D3

CONNECTWELL

BY127

16

16

32

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT ENGINEER : TCE CONSULTING ENGINEERS LIMITED R4 R3 R2 Issue Original/Replacement for/ Replaced by :QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name Date : 30.04.09 PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934 Item No : Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Page 7 of 8

Equipment List for Protn. for Generator Relay Panel

Func. Ref

Description

Specification

Make

Dis

Type 10CHA00GH001 10CHA00GH002

QTY / Panel 10CHA00GH003

Total Qty. 10CHA00GH004 10CHA00GH005

TM1703 (For Transformer (4 - 20mA) Analog Input to Suitable for 12AI) Mounted in DIN Channel

CP-6014 Master Control Module Network interface Processor SM-2556 CM-2860 Patch Plug standard V28,ET,TR PS-6630 Power Supply 24-60VDC EMC+ AI-6300 Analog Input 2x2 20mA/10V DI-6102 Digital Input 2x8, 24-60VDC, Ims PE-6410 Peripheral Contr. Ax-Bus electr. Flash Card 256MB USB-Cable Type A-A AWG20/28 3m TPP 3M TP Patch cable 3m Cat 5, grey Converter CM-0843 Bus Interfaces Module Electrical AC MCB Four Pole Aux contact:1 NC Resistor for under excitation protection (Voltage divider, 20:1), group 012009 Capacitor for Excitation circuit

MLFB: 6MF1113-0GA140-AA0BB MLFB: 6MF1013-0CF56-0AA1 MLFB: 6MF1211-0CJ60-0AC0 MLFB: 6MF1113-0GG30-0AA1 MLFB: 6MF1113-0GD00-0AA1 MLFB: 6MF1113-0GB002-0AA1 MLFB: 6MF1113-0GE100-AF0 MLFB: 6MF1213-1GA05-0AD0 MLFB: 6MF1313-0GC01-0AA1 MLFB: 6MF1304-0BC52-0AA1 Input:220v DC Output:48V DC MLFB: 6MF11110AJ430AH0 2A, 110VAC

SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS SIEMENS Phoenix SIEMENS SIEMENS

3 3 3 3 3 3 3 3 3 3 3 3 3

CP-6014 SM-2556 CM-2860 PS-6630 AI-6300 DI-6102 PE-6410 --CM-0843

0 0 0 0 0 0 0 0 0 0 0 0 3

0 0 0 0 0 0 0 0 0 0 0 0 3

1 2 2 3 6 12 3 1 3 3 1 1 3

0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0

1 2 2 3 6 12 3 1 3 3 1 1 9

PT MCB

3PP13

MLFB NO: 3PP1326-OBZ-K2Y

SIEMENS

3PP13

CAPACITOR

10F,250V

Reputed

Dis: 1- W Stock, 2- W non stock, 3- W non stock others, 4- Project Supply, 5- Loose Supply Client : COASTAL GUJARAT POWER LIMITED Project ENGINEER : 4000 MW ULTRA MEGA POWER PLANT AT MUNDRA, GUJARAT : TCE CONSULTING ENGINEERS LIMITED Date : 30.04.09 R4 R3 R2 Issue Original/Replacement for/ QT CORRECTED REVISED AS PER COMMENTS DT. 22.12.09 REVISED AS PER COMMENTS DT. 25.09.09 Remarks 09.06.10 23.12.09 11.11.09 Date KRK KRK KRK Name PREP : MR CHKD : MS APPD : MS

Sales Ref : 3001506934

Item No :

Qty : 1

Description :- Equipment List

Circuit: GRP # UNIT10

SIEMENS
(4)-G719EA-XG970-ER901-R4

Replaced by :-

Page 8 of 8

SIEMENS

SITE1

DT 10.03.11 MARKED THUS CORRECTION / MODIFICATION TO BE DONE AT SITE BY COMMISIONING ENGINEER

TCE.5146A-704-0009

SHEET
00 01 01A 02 03 04 05 06 07 08 09 10 11 12 13 13A 14 15 16 17 18 19 20 21 22 23 24 25 26 26A 27 28 29 30

DRAWING DESCRIPTION
LIST OF DRAWINGS LIST OF DRAWINGS LIST OF DRAWINGS LIST OF REFERENCE DRAWINGS LIST OF DRAWINGS PROTECTION TRIP LOGIC - GROUP-1 PROTECTION TRIP INITIATION - GROUP-1 PROTECTION TRIP INITIATION - GROUP-1 PROTECTION TRIP INITIATION - GROUP-1 PROTECTION TRIP LOGIC - GROUP-2 PROTECTION TRIP INITIATION - GROUP-2 PROTECTION TRIP INITIATION - GROUP-2 PROTECTION TRIP INITIATION - GROUP-2 PROTECTION TRIP INITIATION - GROUP-2 & 4-20mA INPUTS TO RTU DIGITAL INPUTS TO RTU DIGITAL INPUTS TO RTU SYSTEM SINGLE LINE DIAGRAM PROTECTION SINGLE LINE DIAGRAM PROTECTION SINGLE LINE DIAGRAM GEN. LINE SIDE CT CORE DISTRIBUTION GEN. NEUTRAL SIDE CT CORE DISTRIBUTION UT-10A CT CORE DISTRIBUTION UT-10B CT CORE DISTRIBUTION ST-1 CT CORE DISTRIBUTION VT-1 CORE DISTRIBUTION VT-2 CORE DISTRIBUTION VT-3 CORE DISTRIBUTION AC SUPPLY DISTRIBUTION DC SUPPLY DISTRIBUTION CIRCUIT DC SUPPLY DISTRIBUTION CIRCUIT VOLTAGE SUPVN. (60G11) RELAY CKT VOLTAGE SUPVN. (60G12) RELAY CKT VOLTAGE SUPVN. (60G13) RELAY CKT VOLTAGE SUPVN. (60G21) RELAY CKT

REV-0 REV-1 REV-2 REV-3 REV-4

SHEET
31 32 33 34 35 36 37 38 39 40 41 42 43

DRAWING DESCRIPTION
VOLTAGE SUPVN. (60G22) RELAY CKT VOLTAGE SUPVN. (60G23) RELAY CKT GEN. PROTN. RELAY (GR-1) AC CKT GEN. PROTN. RELAY (GR-1) B/I CKT GEN. PROTN. RELAY (GR-1) B/I CKT GEN. PROTN. RELAY (GR-1) B/O CKT GEN. PROTN. RELAY (GR-1) B/O CKT GEN. PROTN. RELAY (GR-2) AC CKT GEN.- PROTN. RELAY (GR-2) B/I CKT GEN. PROTN. RELAY (GR-2) B/I CKT GEN. PROTN. RELAY (GR-2) B/O CKT GEN. PROTN. RELAY (GR-2) B/O CKT GEN. OPEN DELTA E/F PROTN. AC CKT GEN. OPEN DELTA E/F PROTN. BI CKT GEN. OPEN DELTA PROTN. BO CKT GEN. GROUP-1 CLASS-A1 TRIP RELAY CKT GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT GEN. GROUP-1 CLASS-A2 TRIP RELAY CKT GEN. GROUP-1 CLASS-B TRIP RELAY CKT GEN. GROUP-1 CLASS-C TRIP RELAY CKT GEN. GROUP-1 CLASS-C TRIP RELAY CKT GEN. GROUP-2 CLASS-A1 TRIP RELAY CKT GEN. GROUP-2 CLASS-A2 TRIP RELAY CKT GEN. GROUP-2 CLASS-A2 TRIP RELAY CKT GEN. GROUP-2 CLASS A2 TRIP RELAY CKT GEN. GROUP-2 CLASS A2 TRIP RELAY CKT GEN. GROUP-2 CLASS B TRIP RELAY CKT GEN. GROUP-2 CLASS C TRIP RELAY CKT GEN. GROUP-2 CLASS C TRIP RELAY CKT GT DIFF. PROTN. AC CIRCUIT GT DIFF. PROTN. AC CIRCUIT GT DIFF. PROTN. B/I CIRCUIT GT DIFF. PROTN. B/I CIRCUIT GT DIFF. PROTN. B/I CIRCUIT

REV-0 REV-1 REV-2 REV-3 REV-4

44 45 46 47

47A 48 49

50 51 52 53 54 54A 55 56 57 58 59 60 61 62 63

NOTE:TB NOS & WIRE NOS MAY CHANGE DURING MANUFACTURING

64

SHEET
65 66 67 68 69 69A 70 71 72 73 74 75 76 76A 76B 76C 76D 76E 76F 76G 76H 76J 76K 76L 76M 76N 76P 77 78 79 80 81 82 83 84 85

DRAWING DESCRIPTION
GT DIFF. PROTN. B/O CIRCUIT GT DIFF. PROTN. B/O CIRCUIT GT STAND BY E/F PROTN. AC CIRCUIT GT STANDBY E/F PROTN B/I & B/O CIRCUIT GCB CLOSING & TRIP COIL-1 CIRCUIT TRIP COIL-2 CIRCUIT ISOLATOR CONTACT MULTI. CIRCUIT BREAKER CONTACT MULTI. CIRCUIT RTU DC DISTRIBUTION CIRCUIT RTU ANALOG INPUT CARD-1 (4-20mA) CIRCUIT RTU ANALOG INPUT CARD-2 (4-20mA) CIRCUIT RTU ANALOG INPUT CARD-3 (4-20mA) CIRCUIT RTU ANALOG INPUT CARD-4 (4-20mA) CIRCUIT RTU ANALOG INPUT CARD-5 (4-20mA) CIRCUIT RTU ANALOG INPUT CARD-6 (4-20mA) CIRCUIT RTU DIGTAL INPUT CARD-1 CIRCUIT RTU DIGTAL INPUT CARD-2 CIRCUIT RTU DIGTAL INPUT CARD-3 CIRCUIT RTU DIGTAL INPUT CARD-4 CIRCUIT RTU DIGTAL INPUT CARD-5 CIRCUIT RTU DIGTAL INPUT CARD-6 CIRCUIT RTU DIGTAL INPUT CARD-7 CIRCUIT RTU DIGTAL INPUT CARD-8 CIRCUIT RTU DIGTAL INPUT CARD-9 CIRCUIT RTU DIGTAL INPUT CARD-10 CIRCUIT RTU DIGTAL INPUT CARD-11 CIRCUIT RTU DIGTAL INPUT CARD-12 CIRCUIT UT-A DIFF. PROTN. AC CIRCUIT UT-A DIFF. PROTN. AC CIRCUIT UT-A DIFF. PROTN. B/I CIRCUIT UT-A DIFF. PROTN. B/I CIRCUIT UT-A DIFF. PROTN. B/I CIRCUIT UT-A DIFF. PROTN. B/O CIRCUIT UT-A DIFF. PROTN. B/O CIRCUIT UT-A HV SIDE O/C PROTN. AC CIRCUIT UT-A HV O/C PROTN. B/I & B/O CIRCUIT

REV-0 REV-1 REV-2 REV-3 REV-4

SHEET
86 87

DRAWING DESCRIPTION
UNIT-10A SWGR-A LV REF PROTN. AC CIRCUIT UNIT-10A SWGR-A LV REF. PROTN. B/I & B/O CIRCUIT UNIT-10A SWGR-B LV REF PROTN. AC CIRCUIT UNIT-10A SWGR-B REF. LV PROTN. B/I & B/O CIRCUIT UNIT-10A GROUP-1 TRIP RELAY CKT UNIT-10A GROUP-2 TRIP RELAY CKT BLANK SHEET UT-B DIFF. PROTN. AC CIRCUIT UT-B DIFF. PROTN. AC CIRCUIT UT-B DIFF. PROTN. B/I CIRCUIT UT-B DIFF. PROTN. B/I CIRCUIT UT-B DIFF. PROTN. B/I CIRCUIT UT-A DIFF. PROTN. B/O CIRCUIT UT-A DIFF. PROTN. B/O CIRCUIT UT-B HV SIDE O/C PROTN. AC CIRCUIT UT-B HV O/C PROTN. B/I & B/O CIRCUIT UNIT-10B SWGR-A LV REF PROTN. AC CIRCUIT UNIT-10B SWGR-A LV REF. PROTN. B/I & B/O CIRCUIT UNIT-10B SWGR-B LV REF PROTN. AC CIRCUIT UNIT-10B SWGR-B LV REF. PROTN. B/I & B/O CIRCUIT UNIT-10B GROUP-1 TRIP RELAY CKT UNIT-10B GROUP-2 TRIP RELAY CKT ST DIFF. PROTN. AC CIRCUIT ST DIFF. PROTN. AC CIRCUIT ST DIFF. PROTN. B/I CIRCUIT ST DIFF. PROTN. B/I CIRCUIT ST-1 DIFF. PROTN. B/I CIRCUIT ST DIFF. PROTN. B/O CIRCUIT ST DIFF. PROTN. B/O CIRCUIT ST HV SIDE O/C PROTN. AC CIRCUIT ST HV O/C PROTN. B/I & B/O CIRCUIT ST SWGR-A LV REF PROTN. AC CIRCUIT ST SWGR-A LV REF. PROTN. B/I & B/O CIRCUIT ST SWGR-B LV REF PROTN. AC CIRCUIT

REV-0 REV-1 REV-2 REV-3 REV-4

88 89 90 91 92 93

94 95 96 97 98 99 100 101 102 103 104 105 106

107 108 109 110 111

112 113 114

115 116 117 118 119

SHEET
120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137

DRAWING DESCRIPTION
ST SWGR-B LV REF. PROTN. B/I & B/O CIRCUIT ST GROUP-1 TRIP RELAY CKT ST GROUP-2 TRIP RELAY CKT BLANK SHEET 400KV MAIN CB & TIE CB TRIPPING CKT 400KV MAIN CB & TIE CB LBB & CLOSING INTERLOCK CIRCUIT STEAM TURBINE INTERLOCK CIRCUIT FIELD EXCITATION INTERLOCK CIRCUIT UNIT-10A SWGR. INTERLOCK CIRCUIT UNIT-10 SWGR. INTERLOCK CIRCUIT ST-1 SWGR INTERLOCK CIRCUIT BLOCK CONTACT DISTRIBUTION BLOCK CONTACT DISTRIBUTION BLOCK CONTACT DISTRIBUTION SWITCH CONTACT DISTRIBUTION DCS CIRCUIT STAND ALONE DISTURBANCE RECORDER COMMUNICATION DIAGRAM

REV-0 REV-1 REV-2 REV-3 REV-4

LIST OF REFERENCE DRAWINGS/DOCUMENTS DESCRIPTION


MAIN ONE LINE DIAGRAM GCB ENCLOSURE 1. 26KV BREKAER 2. 26KV ISOLATOR 2. 26KV CVT 960MVA,26KV GENERATOR 310MVA ,400KV/26KV GENERATOR TRANSFORMER 63/31.5/31.5 MVA,,26/11.5/11.5KV UNIT TRANSFORMER 63/31.5/31.5MVA,26/11.5/11.5KV STATION TRANSFORMER NEUTRAL GROUNDING TRANSFORMER DCDB DRAWING ACDB DRAWING CONTROL ROOM LAYOUT TCE.5146A-580-GA-1701A TCE INDIVIDUAL KIOSK-34526200113 BHEL COMMON KIOSK-34526200112 TOSHIBA VS121888AEDD01D AREVA

DRAWING REF.
TCE.5146A-739-AU-3001 - SHEET 1 & 2

MAKE
TCE

34566250672 - COOLER CONTROL GEAR

BHEL, JHANSI

LEGEND SYMBOLS DESCRIPTOIN TERMINAL STRIP


X11A X13A X2A X3A X41A X42A X43A X45A X46A BAY MARSHALLING BOX TERMINATIONS DISCONNECTING TERMINAL BLOCK RELAY PANEL TERMINAL BLOCK OTHER SUPPLIER'S PANEL TB X47A X50A X51A X61 X62 X63 X71 X77 X79 X91A DC SUPPLY BUS WIRE AC SUPPLY BUS WIRE TO ALARM

DESCRIPTOIN-10CHA00GH001
CT CIRCUIT PT CIRCUIT TO BREAKER (GCB) TO ISOLATOR TO SRP TO GT, UT, ST TO EXCITER, AVR, TURBINE CIRCUITS TO 11kV UNIT-10A SWGR-A,B TO 11kV UNIT-10B SWGR-A,B TO 11kV STATION SWGR-A,B DIODE TERRMINAL BLOCK SPARE TO ACDB TO DCDB-1 TO DCDB-2

TERMINAL STRIP
X11B X13B X2B X3B X41B X42B X43B X45A X46A X47A X50B X51B X61 X62 X63 X71 X77 X79 X91B

DESCRIPTOIN-10CHA00GH002
CT CIRCUIT PT CIRCUIT TO BREAKER (GCB) TO ISOLATOR TO SRP TO GT, UT, ST TO EXCITER, AVR, TURBINE CIRCUITS TO 11kV UNIT-10A SWGR-A,B TO 11kV UNIT-10B SWGR-A,B TO 11kV STATION SWGR-A,B DIODE TERRMINAL BLOCK SPARE TO ACDB TO DCDB-1 TO DCDB-2 DC SUPPLY BUS WIRE AC SUPPLY BUS WIRE TO ALARM

TERMINAL STRIP
X11C X13C X2C X3C X41C X42C X43C X44C X51C X71 X77 X79 X81C X82C

DESCRIPTOIN-10CHA00GH003
CT CIRCUIT PT CIRCUIT TO BREAKER (GCB) TO ISOLATOR TO SRP TO GT, UT, ST TO EXCITER, AVR, TURBINE CIRCUITS TO RTU SPARE DC SUPPLY BUS WIRE AC SUPPLY BUS WIRE GCP CIRCUIT GCP CIRCUIT

CT TERMINATIONS

PT TERMINATIONS CB TERMINATIONS ISOLATOR TERMINATIONS

WIRE CROSS REFERENCE STANDARDS REPRESENTATION DESCRIPTOIN TERMINAL STRIP


X11DA X13DA X2DA X3DA X41DA X42DA X43DA X51DA X71 X77 X79 X11DB X13DB X2DB X3DB X41DB X42DB X43DB X51DB X83D X84D

DESCRIPTOIN-10CHA00GH004
CT CIRCUIT PT CIRCUIT TO BREAKER (GCB) TO ISOLATOR TO SRP TO GT, UT, ST TO EXCITER, AVR, TURBINE CIRCUITS SPARE DC SUPPLY BUS WIRE AC SUPPLY BUS WIRE CT CIRCUIT PT CIRCUIT TO BREAKER (GCB) TO ISOLATOR TO SRP TO GT, UT, ST TO EXCITER, AVR, TURBINE CIRCUITS SPARE TO DCS TO DISTURBANCE RECORDER

TERMINAL STRIP
X11E X13E X2E X3E X41E X42E X43E X51E X71 X77 X79

DESCRIPTOIN-10CHA00GH005
CT CIRCUIT PT CIRCUIT TO BREAKER (GCB) TO ISOLATOR TO SRP TO GT, UT, ST TO EXCITER, AVR, TURBINE CIRCUITS SPARE DC SUPPLY BUS WIRE AC SUPPLY BUS WIRE

TRIP BUS WIRE NUMBER GROUP-1 CLASS-A1 CLASS-A2 CLASS-B CLASS-C CLASS-D-UT10A CLASS-D-UT10B CLASS-D-ST K103 K303 K503 K703 K903 K1103 K1303 GROUP-2 K203 K403 K603 K803 K1003 K1203 K1403

K101 12 W951-03

FERRULE NUMBER SHEET NUMBER DRAWING NO. WITH SHEET NO.

PROTECTION TRIP LOGIC - GROUP-1


11KV STATION, SWITCHGEAR-A INCOMER TRIP COIL 11KV STATION, SWITCHGEAR-B INCOMER TRIP COIL 11KV UNIT-A, SWITCHGEAR-A INCOMER TRIP COIL 11KV UNIT-A, SWITCHGEAR-B INCOMER TRIP COIL 11KV UNIT-B, SWITCHGEAR-A INCOMER TRIP COIL 11KV UNIT-B, SWITCHGEAR-B INCOMER TRIP COIL

11KV STATION,,SWITCHGEAR-A INCOMER LBB

11KV STATION ,SWITCHGEAR-B INCOMER LBB

11KV UNIT-A, SWITCHGEAR-A INCOMER LBB

11KV UNIT-A,SWITCHGEAR-B INCOMER LBB

11KV UNIT-B,SWITCHGEAR-A INCOMER LBB

11KV UNIT-B,SWITCHGEAR-B INCOMER LBB

GT HV MIDDLE CB, TRIP COIL-1

GT HV MIDDLE CB, TRIP COIL-2

GT HV MAIN CB, TRIP COIL-1

GT HV MAIN CB, TRIP COIL-2

TURBINE TRIP CHANNEL-1

TURBINE TRIP CHANNEL-2

GT HV MIDDLE CB, 50LBB

WIPEOUT TIMER 2/286A1

WIPEOUT TIMER 2/286A2

GROUP-1 PROTECTIONS 186A1 186A2 186B 186C 186D-UT1A 186D-UT1B 186D-ST

X X X X

X X

X X X X X X X X X X X X

X X

X X X

X X X X X X X X X

X X X X

X X X X X X X X X X X X X

LEGEND OF TRIP RELAYS - GROUP-1


186A1 186A2 186B 186C 186D-UT 186D-ST GROUP-1 CLASS A1 MASTER TRIP RELAY GROUP-1 CLASS A2 MASTER TRIP RELAY GROUP-1 CLASS B MASTER TRIP RELAY GROUP-1 CLASS C MASTER TRIP RELAY GROUP-1 UT CLASS D MASTER TRIP RELAY GROUP-1 ST CLASS D MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST FOR NON CRITICAL GENERATOR FAULTS FOR FAULTS EXTERNAL TO THE PLANT FOR THERMAL OVER LOAD PROTECTIONS OF UT FOR THERMAL OVER LOAD PROTECTIONS OF ST

LEGEND OF TRIP RELAYS - GROUP-2


286A1 286A2 286B 286C 286D-UT 286D-ST GROUP-2 CLASS A1 MASTER TRIP RELAY GROUP-2 CLASS A2 MASTER TRIP RELAY GROUP-2 CLASS B MASTER TRIP RELAY GROUP-2 CLASS C MASTER TRIP RELAY GROUP-2 UT CLASS D MASTER TRIP RELAY GROUP-2 ST CLASS D MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST FOR NON CRITICAL GENERATOR FAULTS FOR FAULTS EXTERNAL TO THE PLANT FOR THERMAL OVER LOAD PROTECTIONS OF UT FOR THERMAL OVER LOAD PROTECTIONS OF ST

SITE1

WIPEOUT TIMER 2/286C

WIPEOUT TIMER 2/286B

GT HV MAIN CB, 50LBB

FIELD CB TRIP COIL

GCB TRIP COIL-1

GCB TRIP COIL-2

GCB 50LBB,GR-1

GROUP-1 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES SL. NO. GROUP-1 PROTECTIONS I. GENERATOR PROTECTION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 29 30 31 32 GENERATOR UNDER VOLTAGE (27G) GENERATOR OVER VOLTAGE STAGE-1 (59G) GENERATOR OVER VOLATGE STAGE-2 (59G) GENERATOR OVER EXCITATION STAGE-1 (99G) 7UM62 GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB CLOSED GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB OPEN GENERATOR POLE SLIPPING (78G) GENERATOR LOSS OF EXCITATION (40G) GENERATOR LOSS OF EXCITATION WITH UNDER VOLTAGE(27/40G) GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-1 GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-1 GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-2 GENERATOR STATOR OVER LOAD (50GS) GENERATOR STATOR EARTH FAULT 95% (64G3) GENERATOR STATOR EARTH FAULT 100% (64G1) GENERATOR ROTOR EARTH FAULT (64F2) - STAGE-1 GENERATOR ROTOR EARTH FAULT (64F2) - STAGE-2 EXCITATION TRANSFORMER VERY HIGH GCB LOCAL BREAKER BACKUP (50LBB) DEAD MACHINE PROTECTION (61B) GENERATOR ROTOR EARTH FAULT (64F1) VOLATGE BALANCE PROTECTION (60G11) VOLATGE BALANCE PROTECTION (60G12) VOLATGE BALANCE PROTECTION (60G13) SITE1 TOSHIBA MVAPM32 MVAPM32 MVAPM32 TOSHIBA 60G11 60G12 60G13 GR1 REVERSE POWER RELAY(32G) + TIMER STAGE -2 SITE1 GENERATOR DIFFERENTIAL PROTECTION(87G) GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -1 GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -2 GENERATOR UNDER FREQUENCY STAGE-1 (81UF) GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-1 GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-2 GENERATOR OVER FREQUENCY (81OF)

RELAY TYPE RELAY REF.

186A1

186A2

186B

186C

186D-UT1A186D-UT1B 186D-ST

286A2

ALARM

X X X X X X X X X

X X X X

X X X X X

X X X X

X X X

X X X

SITE1

X X X X X

GROUP-1 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES SL. NO. GROUP-1 PROTECTIONS II. GENERATOR TRANSFORMER PROTECTION
1 2 3 4 5 6 GT STANDBY EARTH FAULT (51NGT) WITHOUT TIMER GT STANDBY EARTH FAULT WITH TIMER GT BUCHHOLZ TRIP (63T) GT PRESSURE RELIEF VALVE-A OPTD. GT OIL TEMPERATURE TRIP GT FIRE PROTECTION TRIP (63FT) BI OF 7UT633 7SJ80 SITE1 51NGT

RELAY TYPE RELAY REF.

186A1

186A2

186B

186C

186D-UT1A186D-UT1B 186D-ST

286A2

ALARM

X X X X X X
SITE1

III. UNIT TRANSFORMER-10A PROTECTIONS


1 2 3 4 5 6 7 8 UT INSTANTANEOUS OVER CURRENT (50UT) 7SJ80 UT HV SIDE IDMT OVER CURRENT (51UT) UT LV SIDE IDMT EARTH FAULT (51NUT-LV1 & LV2) UT BUCHHOLZ TRIP (63T) UT OIL TEMPERATURE TRIP (49OT) UT OIL TEMPERATURE ALARM (OTA) BI OF 7UT633 UT BUCHHOLZ ALARM(63A) UT PUMP OIL FLOW LOW ALARM GROUP-1 87/51-UT10A 50-UT10A

X X X X X X X X

IV. UNIT TRANSFORMER-10B PROTECTIONS


1 2 3 4 5 6 7 8 UT INSTANTANEOUS OVER CURRENT (50UT) 7SJ80 UT HV SIDE IDMT OVER CURRENT (51UT) UT LV SIDE IDMT EARTH FAULT (51NUT-LV1 & LV2) UT BUCHHOLZ TRIP (63T) UT OIL TEMPERATURE TRIP (49OT) UT OIL TEMPERATURE ALARM (OTA) BI OF 7UT633 UT BUCHHOLZ ALARM(63A) UT PUMP OIL FLOW LOW ALARM GROUP-1 87/51-UT10B 50-UT10B

X X X X X X X X

GROUP-1 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES V. STATION TRANSFORMER PROTECTIONS
1 2 3 4 5 6 7 8 ST INSTANTANEOUS OVER CURRENT (50ST) 7SJ80 ST HV SIDE IDMT OVER CURRENT (51ST) ST LV SIDE IDMT EARTH FAULT (51NST-LV1 & LV2) ST BUCHHOLZ TRIP (63T) ST OIL TEMPERATURE TRIP (49OT) ST OIL TEMPERATURE ALARM (OTA) BI OF 7UT633 ST BUCHHOLZ ALARM(63A) ST PUMP OIL FLOW LOW ALARM GROUP-1 87/51-ST1 50-ST1

X X X X X X X X

VI. AVR
1 2 EXCITATION SYSTEM FAULTS - NON CRITICAL EXCITATION SYSTEM FAULTS - CRITICAL AVR AVR -

X X

VII. OVERALL PROTECTIONS


1 2 3 4 5 6 7 8 9 10 11 12 13 OVERALL DIFFERENTIAL (87OA) 11KV UNIT A, SWITCHGEAR-A INCOMER LBB 11KV UNIT A, SWITCHGEAR-B INCOMER LBB 11KV UNIT B, SWITCHGEAR-A INCOMER LBB 11KV UNIT B, SWITCHGEAR-B INCOMER LBB 11KV STATION, SWITCHGEAR-A INCOMER LBB 11KV STATION, SWITCHGEAR-B INCOMER LBB GT HV MAIN CB LBB GT HV MIDDLE CB LBB WIPE OUT TIMER 2/186A1 WIPE OUT TIMER 2/186A2 WIPE OUT TIMER 2/186B WIPE OUT TIMER 2/186C FROM SRP UNIT-A SWITCHGEAR-A UNIT-A SWITCHGEAR-B UNIT-B SWITCHGEAR-A UNIT-B SWITCHGEAR-B STATION SWITCHGEAR-A STATION SWITCHGEAR-B FROM SRP FROM SRP 87OA -

X X X X X X X X X X X X X

PROTECTION TRIP LOGIC - GROUP-2


11KV STATION, SWITCHGEAR-A INCOMER TRIP COIL 11KV STATION, SWITCHGEAR-B INCOMER TRIP COIL

11KV UNIT-A, SWITCHGEAR-A INCOMER TRIP COIL

11KV UNIT-A, SWITCHGEAR-B INCOMER TRIP COIL

11KV UNIT-B, SWITCHGEAR-A INCOMER TRIP COIL

11KV UNIT-B, SWITCHGEAR-B INCOMER TRIP COIL

11KV STATION,,SWITCHGEAR-A INCOMER LBB

11KV STATION ,SWITCHGEAR-B INCOMER LBB

11KV UNIT-A, SWITCHGEAR-A INCOMER LBB

11KV UNIT-A,SWITCHGEAR-B INCOMER LBB

11KV UNIT-B,SWITCHGEAR-A INCOMER LBB

11KV UNIT-B,SWITCHGEAR-B INCOMER LBB

GT HV MIDDLE CB, TRIP COIL-1

GT HV MIDDLE CB, TRIP COIL-2

GT HV MAIN CB, TRIP COIL-1

GT HV MAIN CB, TRIP COIL-2

TURBINE TRIP CHANNEL-1

TURBINE TRIP CHANNEL-2

GT HV MIDDLE CB, 50LBB

WIPEOUT TIMER 2/286A1

WIPEOUT TIMER 2/186A2

GROUP-2 PROTECTIONS 286A1 286A2 286B 286C 286D-UT1A 286D-UT1B 286D-ST

X X X X

X X

X X X X X X X X X X X X

X X

X X X

X X X X X X X X X

X X X X

X X X X X X X X X X X X X

LEGEND OF TRIP RELAYS - GROUP-1


186A1 186A2 186B 186C 186D-UT 186D-ST GROUP-1 CLASS A1 MASTER TRIP RELAY GROUP-1 CLASS A2 MASTER TRIP RELAY GROUP-1 CLASS B MASTER TRIP RELAY GROUP-1 CLASS C MASTER TRIP RELAY GROUP-1 UT CLASS D MASTER TRIP RELAY GROUP-1 ST CLASS D MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST FOR NON CRITICAL GENERATOR FAULTS FOR FAULLTS EXTERNAL TO THE PLANT FOR THERMAL OVER LOAD PROTECTIONS OF UT FOR THERMAL OVER LOAD PROTECTIONS OF ST

LEGEND OF TRIP RELAYS - GROUP-2


286A1 286A2 286B 286C 286D-UT 286D-ST GROUP-2 CLASS A1 MASTER TRIP RELAY GROUP-2 CLASS A2 MASTER TRIP RELAY GROUP-2 CLASS B MASTER TRIP RELAY GROUP-2 CLASS C MASTER TRIP RELAY GROUP-2 UT CLASS D MASTER TRIP RELAY GROUP-2 ST CLASS D MASTER TRIP RELAY FOR CRITICAL GENERATOR FAULTS FOR CRITICAL GENERATOR FAULTS IN GT,UT & ST FOR NON CRITICAL GENERATOR FAULTS FOR FAULLTS EXTERNAL TO THE PLANT FOR THERMAL OVER LOAD PROTECTIONS OF UT FOR THERMAL OVER LOAD PROTECTIONS OF ST

WIPEOUT TIMER 2/186C

WIPEOUT TIMER 2/186B

GT HV MAIN CB, 50LBB

FIELD CB TRIP COIL

GCB TRIP COIL-1

GCB TRIP COIL-2

GCB 50LBB,GR-2

GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES SL. NO. GROUP-2 PROTECTIONS I. GENERATOR PROTECTION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 26 27 27 27 28 29 30 GENERATOR DIFFERENTIAL PROTECTION(87G) GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -1 GENERATOR UNDER IMPEDANCE (21G),TIMER STAGE -2 GENERATOR UNDER FREQUENCY STAGE-1 (81UF) GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-1 GENERATOR UNDER FREQUENCY STAGE-2 (81UF) TIME STAGE-2 GENERATOR OVER FREQUENCY (81OF) REVERSE POWER RELAY(32G)+TURBINE TRIP RELAY OPERATED/ TIME STAGE-1 +TURBINE TRIP CH- 1/2 REVERSE POWER RELAY(32G) + TIME STAGE -2 LOW POWER RELAY(37G)+TURBINE TRIP RELAY OPERATED/ TIMER + TURBINE TRIP CH- 1/2 GENERATOR UNDER VOLTAGE (27G) GENERATOR OVER VOLTAGE STAGE-1 (59G) GENERATOR OVER VOLATGE STAGE-2 (59G) GENERATOR OVER EXCITATION STAGE-1 (24G) 7UM62 GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB CLOSED GENERATOR OVER EXCITATION STAGE-2 (24G) WITH GCB OPEN GENERATOR POLE SLIPPING (78G) GENERATOR LOSS OF EXCITATION (40G) GENERATOR LOSS OF EXCITATION WITH UNDER VOLTAGE(27/40G) GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-1 GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-1 GENERATOR NEGATIVE PHASE SEQUENCE(46) STAGE-2, TIMER STAGE-2 GENERATOR STATOR OVER LOAD (50GS) GENERATOR STATOR EARTH FAULT 95% (64G3) GCB LOCAL BREAKER BACKUP (50LBB) DEAD MACHINE PROTECTION (61B) GENERATOR ROTOR EARTH FAULT (64F2) STAGE-1 GENERATOR ROTOR EARTH FAULT (64F2) STAGE-2 GENERATOR ROTOR EARTH FAULT (64F1) VOLATGE BALANCE PROTECTION (60G21) VOLATGE BALANCE PROTECTION (60G22) VOLATGE BALANCE PROTECTION (60G23) GENERATOR OPEN DELTA EARTH FAULT PROTECTION (59N) TOSHIBA MVAPM32 MVAPM32 MVAPM32 7SJ62 TOSHIBA 60G21 60G22 60G23 59N SITE1 GR2 SITE1 SITE1

RELAY TYPE RELAY REF.

286A1

286A2

286B

286C

286D-UT1A286D-UT1B 286D-ST

186A2

ALARM

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES SL. NO. GROUP-2 PROTECTIONS II. GENERATOR TRANSFORMER PROTECTION
1 2 3 4 5 6 7 8 9 10 GT OVERHEAD LINE DIFFERENTIAL PROTECTION (87OH) GT SUDDEN PRESSURE RELAY TRIP GT RESTRICTED EARTH FAULT (64GT) GT DIFFERENTIAL (87GT) 7UT633 GT OVER FLUXING PROTECTION (99GT) STAGE-1 GT OVER FLUXING PROTECTION (99GT) STAGE-2 GT HV WINDING TEMPERATURE TRIP GT LV WINDING TEMPERATURE TRIP GT PRESSURE RELIEF VALVE-B TRIP BI OF 59N GT OLTC OIL SURGE TRIP SITE1 FROM SRP 87OH

RELAY TYPE RELAY REF.

286A1

286A2

286B

286C

286D-UT1A286D-UT1B 286D-ST

186A2

ALARM

X X X X X X X X X X

III. UNIT TRANSFORMER-10A PROTECTIONS


1 2 3 4 5 6 7 8 9 10 11 12 UT DIFFERENTIAL PROTECTION (87UT) UT RESTRICTED EARTH FAULT (64UT) - LV1 & LV2 UT FIRE PROTECTION TRIP (63FT) UT PRESSURE RELIEF DEVICE TRIP (63PRD) UT HV WINDING TEMPERATURE TRIP (49WT) UT LV1 WINDING TEMPERATURE TRIP (49WT) UT LV2 WINDING TEMPERATURE TRIP (49WT) UT OFF CIRCUIT TRIP SWITCH ABNORMAL POSITION TRIP UT HV WINDING TERMPERATURE ALARM UT LV1 WINDING TERMPERATURE ALARM UT LV2 WINDING TERMPERATURE ALARM PUMP OIL FLOW LOW GROUP-2 ALARM BI OF 7UT633 87/51-UT10A 7UT633 7SJ80 87/51-UT10A 64-1-UT10A 64-2-UT10A

X X X X X X X X X X X X

GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES SL. NO. GROUP-2 PROTECTIONS IV. UNIT TRANSFORMER-10B PROTECTIONS
1 2 3 4 5 6 7 8 9 10 11 12 UT DIFFERENTIAL PROTECTION (87UT) UT RESTRICTED EARTH FAULT (64UT) - LV1 & LV2 UT FIRE PROTECTION TRIP (63FT) UT PRESSURE RELIEF DEVICE TRIP (63PRD) UT HV WINDING TEMPERATURE TRIP (49WT) UT LV1 WINDING TEMPERATURE TRIP (49WT) UT LV2 WINDING TEMPERATURE TRIP (49WT) UT OFF CIRCUIT TRIP SWITCH ABNORMAL POSITION TRIP UT HV WINDING TERMPERATURE ALARM UT LV1 WINDING TERMPERATURE ALARM UT LV2 WINDING TERMPERATURE ALARM PUMP OIL FLOW LOW GROUP-2 ALARM BI OF 7UT633 87/51-UT10B 7UT633 7SJ80 87/51-UT10B 64-1-UT10B 64-2-UT10B

RELAY TYPE RELAY REF.

286A1

286A2

286B

286C

286D-UT1A286D-UT1B 286D-ST

186A2

ALARM

X X X X X X X X X X X X

V. STATION TRANDFORMER PROTECTIONS


1 2 3 4 5 6 7 8 9 10 11 12 ST DIFFERENTIAL PROTECTION (87ST) ST RESTRICTED EARTH FAULT (64ST) - LV1 & LV2 ST FIRE PROTECTION TRIP (63FT) ST PRESSURE RELIEF DEVICE TRIP (63PRD) ST HV WINDING TEMPERATURE TRIP (49WT) ST LV1 WINDING TEMPERATURE TRIP (49WT) ST LV2 WINDING TEMPERATURE TRIP (49WT) ST OFF CIRCUIT TRIP SWITCH ABNORMAL POSITION TRIP ST HV WINDING TERMPERATURE ALARM ST LV1 WINDING TERMPERATURE ALARM ST LV2 WINDING TERMPERATURE ALARM PUMP OIL FLOW LOW GROUP-2 ALARM BI OF 7UT633 87/51-ST1 7UT633 7SJ80 87/51-ST1 64-1-ST1 64-2-ST1

X X X X X X X X X X X X

GROUP-2 PROTECTION INITIATION OF MASTER TRIP RELAYS BY PROTECTIVE DEVICES SL. NO. GROUP-2 PROTECTIONS VI. OVERALL PROTECTIONS
1 2 3 4 5 6 7 8 9 10 11 12 11KV UNIT A, SWITCHGEAR-A INCOMER LBB 11KV UNIT A, SWITCHGEAR-B INCOMER LBB 11KV UNIT B, SWITCHGEAR-A INCOMER LBB 11KV UNIT B, SWITCHGEAR-B INCOMER LBB 11KV STATION, SWITCHGEAR-A INCOMER LBB 11KV STATION, SWITCHGEAR-B INCOMER LBB GT HV MAIN CB LBB GT HV MIDDLE CB LBB WIPE OUT TIMER 2/286A1 WIPE OUT TIMER 2/286A2 WIPE OUT TIMER 2/286B WIPE OUT TIMER 2/286C UNIT-A SWITCHGEAR-A UNIT-A SWITCHGEAR-B UNIT-B SWITCHGEAR-A UNIT-B SWITCHGEAR-B STATION SWITCHGEAR-A STATION SWITCHGEAR-B FROM SRP FROM SRP -

FROM

RELAY REF.

286A1

286A2

286B

286C

286D-UT1A286D-UT1B 286D-ST

186A2

ALARM

X X X X X X X X X X X X 4-20mA INPUTS TO ANALOG CARD - AI4

4-20mA INPUTS TO ANALOG CARD - AI1 INPUT


1 2 3 4

FUNCTIONS
GT-1 HV R-Ph WINDING TEMPERATURE INDICATION GT-1 LV R-Ph WINDING TEMPERATURE INDICATION

PAGE

INPUT
1 2

FUNCTIONS
UT-10B LV1 WINDING TEMPERATURE INDICATION UT-10B LV2 WINDING TEMPERATURE INDICATION

PAGE

73
GT-1 HV Y-Ph WINDING TEMPERATURE INDICATION GT-1 LV Y-Ph WINDING TEMPERATURE INDICATION 3 4 UT-10B OIL TEMPERATURE INDICATION ST-1 HV WINDING TERMPERATURE INDICATION

76

4-20mA INPUTS TO ANALOG CARD - AI2 INPUT


1 2 3 4

4-20mA INPUTS TO ANALOG CARD - AI5 PAGE INPUT


1 2

FUNCTIONS
GT-1 HV B-Ph WINDING TEMPERATURE INDICATION GT-1 LV B-Ph WINDING TEMPERATURE INDICATION

FUNCTIONS
ST-1 LV1 WINDING TEMPERATURE INDICATION ST-1 LV2 WINDING TEMPERATURE INDICATION

PAGE

74
GT-1 B-Ph OIL TEMPERATURE INDICATION UT-10A HV WINDING TERMPERATURE INDICATION 3 4 ST-1 OIL TEMPERATURE INDICATION GT-1 R-Ph OIL TEMPERATURE INDICATION

76A

4-20mA INPUTS TO ANALOG CARD - AI3 INPUT


1 2 3 4

4-20mA INPUTS TO ANALOG CARD - AI6 PAGE INPUT


1 2

FUNCTIONS
UT-10A LV1 WINDING TEMPERATURE INDICATION UT-10A LV2 WINDING TEMPERATURE INDICATION

FUNCTIONS
GT-1 R-PH OLTC TAP POSITION GT-1 Y-PH OLTC TAP POSITION

PAGE

75
UT-10A OIL TEMPERATURE INDICATION UT-10B HV WINDING TERMPERATURE INDICATION 3 4 GT-1 B-PH OLTC TAP POSITION GT-1 Y-Ph OIL TEMPERATURE INDICATION

76B

INPUTS TO RTU DIGITAL CARD - DI1 INPUT


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

INPUTS TO RTU DIGITAL CARD - DI3 PAGE INPUT


1 2 3 4 5 6 7 8 76C 9 10 11 12 13 14 15 16

INPUTS TO RTU DIGITAL CARD - DI5 PAGE INPUT


1 2 3 4 5 6 7 8 76E 9 10 11 12 13 14 15 16

FUNCTIONS
UT-10A BANK-1 FANS ON UT-10A BANK-2 FANS ON UT-10A BANK-1 PUMPS ON UT-10A BANK-2 PUMPS ON UT-10A 415V AC SUPPLY-1 ON UT-10A 415V AC SUPPLY-2 ON UT-10A FAN CONTROL ON - MANUAL UT-10A FAN CONTROL ON - AUTO UT-10A PUMPS CONTROL ON -MANUAL UT-10A PUMPS CONTROL ON -AUTO UT-10A BANK-1 FAN FAIL UT-10A BANK-2 FAN FAIL UT-10A BANK-1 PUMP FAIL UT-10A BANK-2 PUMP FAIL UT-10A COOLER POWER SUPPLY AUTO CHANGEOVER FAIL UT-10A CONTROL SUPPLY FAIL

FUNCTIONS
GT-1 R-Ph NORMAL COOLER FAIL GT-1 R-Ph STANDBY COOLER FAIL GT-1 R-Ph COOLER CONTROL SUPPLY FAIL GT-1 R-Ph OIL FLOW LOW COOLER-A GT-1 R-Ph OIL FLOW LOW COOLER-B GT-1 R-Ph OIL FLOW LOW COOLER-C GT-1 R-Ph OIL FLOW LOW COOLER-D GT-1 R-Ph OIL FLOW LOW COOLER-E GT-1 R-Ph OIL FLOW LOW COOLER-F GT-1 R-Ph LOW OIL LEVEL ALARM GT-1 R-Ph HV WTI ALARM GT-1 R-Ph LV WTI ALARM GT-1 R-Ph HOTSPOT WDG. TEMP. ALARM THROUGH FOTS GT-1 R-Ph OTI ALARM GT-1 R-Ph BUCHHOLZ ALARM SPARE

FUNCTIONS
GT-1 B-Ph NORMAL COOLER FAIL GT-1 B-Ph STANDBY COOLER FAIL GT-1 B-Ph COOLER CONTROL SUPPLY FAIL GT-1 B-Ph OIL FLOW LOW COOLER-A GT-1 B-Ph OIL FLOW LOW COOLER-B GT-1 B-Ph OIL FLOW LOW COOLER-C GT-1 B-Ph OIL FLOW LOW COOLER-D GT-1 B-Ph OIL FLOW LOW COOLER-E GT-1 B-Ph OIL FLOW LOW COOLER-F GT-1 B-Ph LOW OIL LEVEL ALARM GT-1 B-Ph HV WTI ALARM GT-1 B-Ph LV WTI ALARM GT-1 B-Ph HOTSPOT WDG. TEMP. ALARM THROUGH FOTS GT-1 B-Ph OTI ALARM GT-1 B-Ph BUCHHOLZ ALARM SPARE

PAGE

76G

INPUTS TO RTU DIGITAL CARD - DI2 INPUT


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

INPUTS TO RTU DIGITAL CARD - DI4 PAGE INPUT


1 2 3 4 5 6 7 8 76D 9 10 11 12 13 14 15 16

INPUTS TO RTU DIGITAL CARD - DI6 PAGE INPUT


1 2 3 4 5 6 7 8 76F 9 10 11 12 13 14 15 16

FUNCTIONS
UT-10B BANK-1 FANS ON UT-10B BANK-2 FANS ON UT-10B BANK-1 PUMPS ON UT-10B BANK-2 PUMPS ON UT-10B 415V AC SUPPLY-1 ON UT-10B 415V AC SUPPLY-2 ON UT-10B FAN CONTROL ON - MANUAL UT-10B FAN CONTROL ON - AUTO UT-10B PUMPS CONTROL ON -MANUAL UT-10B PUMPS CONTROL ON -AUTO UT-10B BANK-1 FAN FAIL UT-10B BANK-2 FAN FAIL UT-10B BANK-1 PUMP FAIL UT-10B BANK-2 PUMP FAIL UT-10B COOLER POWER SUPPLY AUTO CHANGEOVER FAIL UT-10B CONTROL SUPPLY FAIL

FUNCTIONS
GT-1 Y-Ph NORMAL COOLER FAIL GT-1 Y-Ph STANDBY COOLER FAIL GT-1 Y-Ph COOLER CONTROL SUPPLY FAIL GT-1 Y-Ph OIL FLOW LOW COOLER-A GT-1 Y-Ph OIL FLOW LOW COOLER-B GT-1 Y-Ph OIL FLOW LOW COOLER-C GT-1 Y-Ph OIL FLOW LOW COOLER-D GT-1 Y-Ph OIL FLOW LOW COOLER-E GT-1 Y-Ph OIL FLOW LOW COOLER-F GT-1 Y-Ph LOW OIL LEVEL ALARM GT-1 Y-Ph HV WTI ALARM GT-1 Y-Ph LV WTI ALARM GT-1 Y-Ph HOTSPOT WDG. TEMP. ALARM THROUGH FOTS GT-1 Y-Ph OTI ALARM GT-1 Y-Ph BUCHHOLZ ALARM SPARE

FUNCTIONS
GT-1 R-Ph THERMAL OVERLOAD RELAY TRIP GT-1 R-Ph COOLER DIRECT ON GT-1 R-Ph COOLER COOLER ON THRO. WTI/FOTS/ GEN.FAS HV CB ON/FIELD CB ON/GCB ON GT-1 R-Ph COOLER FAIL GT-1 R-Ph DRIVE MOTOR AUTO TRIP/TAP CHANGE DELAYED COMMON KIOSK COOLER SUPPLY-A FAIL COMMON KIOSK COOLER SUPPLY-B FAIL COMMON KIOSK COOLER POWER SUPPLY AUTO CHANGEOVER FAIL GT-1 Y-Ph THERMAL OVERLOAD RELAY TRIP GT-1 Y-Ph COOLER DIRECT ON GT-1 Y-Ph COOLER COOLER ON THRO. WTI/FOTS/ GEN.FAS HV CB ON/FIELD CB ON/GCB ON GT-1 Y-Ph COOLER FAIL GT-1 Y-Ph DRIVE MOTOR AUTO TRIP/TAP CHANGE DELAYED COMMON KIOSK OUT OF STEP IN 3-1 PHASE TAP POSITION COMMON KIOSK FOTS FAULTY SPARE

PAGE

76H

INPUTS TO RTU DIGITAL CARD - DI7 INPUT


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

INPUTS TO RTU DIGITAL CARD - DI9 PAGE INPUT


1 2 3 4 5 6 7 8 76J 9 10 11 12 13 14 15 16

INPUTS TO RTU DIGITAL CARD - DI11 PAGE INPUT


1 2 3 4 5 6 7 8 76L 9 10 11 12 13 14 15 16

FUNCTIONS
GT-1 B-Ph THERMAL OVERLOAD RELAY TRIP GT-1 B-Ph COOLER DIRECT ON GT-1 B-Ph COOLER COOLER ON THRO. WTI/FOTS/ GEN.FAS HV CB ON/FIELD CB ON/GCB ON GT-1 B-Ph COOLER FAIL GT-1 B-Ph DRIVE MOTOR AUTO TRIP/TAP CHANGE DELAYED SPARE SPARE GRP DC-1 SUPPLY MCB UNHEALTHY UT-10A 415V AC SUPPLY-1 FAIL UT-10A 415V AC SUPPLY-2 FAIL UT-10B 415V AC SUPPLY-1 FAIL UT-10B 415V AC SUPPLY-2 FAIL ST-1 415V AC SUPPLY-1 FAIL ST-1 415V AC SUPPLY-2 FAIL SPARE SPARE

FUNCTIONS
GEN. GROUP-1 CLASS-A1 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-B TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-C TRIP RELAY UNHEALTHY GEN. GROUP-1 CLASS-C TRIP RELAY UNHEALTHY SPARE GEN. GROUP-2 CLASS-A1 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-A2 TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-B TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-C TRIP RELAY UNHEALTHY GEN. GROUP-2 CLASS-C TRIP RELAY UNHEALTHY SPARE

FUNCTIONS
FOR GT-1 R-Ph COOLER LOGIC - K42 FOR GT-1 R-Ph COOLER LOGIC - K1 FOR GT-1 R-Ph COOLER LOGIC - K2 FOR GT-1 R-Ph COOLER LOGIC - K3 FOR GT-1 R-Ph COOLER LOGIC - K4 FOR GT-1 R-Ph COOLER LOGIC - K5 FOR GT-1 R-Ph COOLER LOGIC - K6 SPARE FOR GT-1 Y-Ph COOLER LOGIC - K42 FOR GT-1 Y-Ph COOLER LOGIC - K1 FOR GT-1 Y-Ph COOLER LOGIC - K2 FOR GT-1 Y-Ph COOLER LOGIC - K3 FOR GT-1 Y-Ph COOLER LOGIC - K4 FOR GT-1 Y-Ph COOLER LOGIC - K5 FOR GT-1 Y-Ph COOLER LOGIC - K6 SPARE

PAGE

76N

INPUTS TO RTU DIGITAL CARD - DI8 INPUT


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SPARE SPARE GT-1 Y-Ph HYDRAN SYSTEM FAIL ALARM SPARE GT-1 R-Ph TAP CHANGE SUPPLY FAIL GT-1 Y-Ph TAP CHANGE SUPPLY FAIL GT-1 B-Ph TAP CHANGE SUPPLY FAIL GT-1 B-Ph HYDRAN SYSTEM FAIL ALARM SPARE SPARE GCB TC-1 UNHEALTHY GCB TC-2 UNHEALTHY GMP DC SUPPLY UNHEALTHY GRP DC-2 SUPPLY UNHEALTHY SPARE 76K

INPUTS TO RTU DIGITAL CARD - DI10 PAGE INPUT


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ST-1 BANK-1 FANS ON ST-1 BANK-2 FANS ON ST-1 BANK-1 PUMPS ON ST-1 BANK-2 PUMPS ON ST-1 415V AC SUPPLY-1 ON ST-1 415V AC SUPPLY-2 ON ST-1 FAN CONTROL ON - MANUAL ST-1 FAN CONTROL ON - AUTO ST-1 PUMPS CONTROL ON -MANUAL ST-1 PUMPS CONTROL ON -AUTO ST-1 BANK-1 FAN FAIL ST-1 BANK-2 FAN FAIL ST-1 BANK-1 PUMP FAIL ST-1 BANK-2 PUMP FAIL ST-1 COOLER POWER SUPPLY AUTO CHANGEOVER FAIL ST-1 CONTROL SUPPLY FAIL 76M

INPUTS TO RTU DIGITAL CARD - DI12 PAGE INPUT


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

FUNCTIONS
GT-1 R-Ph HYDRAN SYSTEM FAIL ALARM

FUNCTIONS

FUNCTIONS
FOR GT-1 B-Ph COOLER LOGIC - K42 FOR GT-1 B-Ph COOLER LOGIC - K1 FOR GT-1 B-Ph COOLER LOGIC - K2 FOR GT-1 B-Ph COOLER LOGIC - K3 FOR GT-1 B-Ph COOLER LOGIC - K4 FOR GT-1 B-Ph COOLER LOGIC - K5 FOR GT-1 B-Ph COOLER LOGIC - K6 SPARE VT-1 WDG-1 UNHEALTHY VT-2 WDG-1 UNHEALTHY VT-2 WDG-2 UNHEALTHY VT-3 WDG-1 UNHEALTHY VT-3 WDG-2 UNHEALTHY SPARE SPARE SPARE

PAGE

76P

BUS-2 BUS-1

400 KV, 3PH, 2000A, 40KA, FOR 1 SEC

2500A

2500A

2500A BPT2 P1 CORE-1 CORE-2 CORE-3 CORE-4 P2 CORE-1 CORE-2 CORE-3 CORE-4 BPT1

2500A

2500A

2500A

2500A

P1

P2 2500A

P1

P2 P1 P2 GENERATOR TRANSFORMER-1 310MVA,420KV / 26kV 3 3 SA 30kV,20kA P1 CORE-3 UT10A CORE-2 UT10A CORE-1 UT10A P2 GCB UNIT TRF-10A 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% P2 P1 P1 P2 EXCITATION TRAFO. (TOSHIBA) P1 CORE-4 CORE-3 CORE-2 CORE-N4 CORE-1 P2 CORE-1 P2 CORE-N3 CORE-N2 CORE-N1 11kV, 2000A, 40kA, 1Sec UNIT-10A, SWGR-A 11kV, 2000A, 40kA, 1Sec UNIT-10A, SWGR-B P1 11kV, 2000A, 40kA, 1Sec NGT UNIT-10B, SWGR-A 26kV/240V 50Hz, 400kVA FOR 10 Sec. 11kV, 2000A, 40kA, 1Sec UNIT-10B, SWGR-B 11kV, 2000A, 40kA, 1Sec STATION, SWGR-A 11kV, 2000A, 40kA, 1Sec STATION, SWGR-B CORE-1 P2 CORE-1 P2 CORE-1 P2 CORE-1 P2 STATIC EXCITATION CORE-L3 CORE-L2 CORE-L1 P2 CORE-4 GENERATOR # 1 G 864MW, 960MVA, 26kV ~ 0.9 PF, 3000RPM, CORE-3 98.94% EFFICIENCY P2 CORE-2 P1 CORE-4 CORE-3 CORE-2 P1 CORE-4 CORE-3 CORE-2 P1 CORE-4 CORE-3 CORE-2 P1 VT-2 VT-1 P1 P2 P1 UNIT TRF-10B 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% P1 P2 P2 P1 STATION TRF-1 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% P1 P2 VT-3 CORE-3 UT10B CORE-2 UT10B CORE-1 UT10B P2 P1 CORE-3 ST1 CORE-2 ST1 CORE-1 ST1 P2 P1

P1 CORE-4 CORE-3 CORE-2

TO 400kV SWITCHYARD

OH LINE

360kV 20kA
P1

FROM 400KV BUS/MIDDLE CB CT (SWITCHYARD) GT PROTECTION NUMERICAL RELAY


87 GT
64 GT 99 GT

1500/1A, CL. PS VK84Rct + 250V Im30mA AT Vk/2 DCS


WTI WTI

L R
GRP
51 NGT

SRP
87 OH P2

GENERATOR TRANSFORMER-1 (3x1PH)


P2 P1

(3x1PH)EACH 310MVA, ONAN/ONAF/OFAF, 420 / 26 KV, Ynd1, Z=16% 3 3 TAP CHANGE + 5% TO -15% IN STEPS OF 1% 1500/1A, CL. 5P20 15VA 1500/1A, CL. PS VK84Rct + 250V Im30mA AT Vk/2
P2

14000/5A, CL. PS VK430Rct + 800V Im30mA AT Vk/2


P1

TO UNIT TRANSFORMER # 10A (REFER SHEET 16)

GCB ENCLOSURE VT-3


26kV 3
V MW PF

TO UNIT TRANSFORMER # 10B (REFER SHEET 16)


EXTERNAL METERS FOR PERFORMANCE TESTING

TO STATION TRANSFORMER # 1 (REFER SHEET 16)

110V 110V 3 3

GCP
WDG-1: CL.0.2, 30VA
25C FF W W 25A S W 59N

WDG-2: CL.3P, 30VA G

GRP

VT-2
26kV 3 110V 110V 3 3
60 G11

GRP TURBINE PNL

G WDG-1: CL. 0.2/3P, 30VA


AVR CH-A DEHC 60 G12

GRP

WDG-2: CL. 0.2, 30VA

GCP
SS
60 G21 25C W S W FF W 60 G13 25A

VT-1
26kV 3 110V 110V 3 3

GRP

GRP TURBINE PNL

WDG-1: CL. 0.2/3P, 30VA


60 G23

GRP
WDG-2: CL. 0.2, 30VA

AVR CH-B

DEHC

60 G22

GRP

CORE-L3 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2


P1
3

AVR (TOSHIBA) GR-2


87OA

64 F1 64 F2
3

CORE-L2 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2


3

CORE-L1 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2 SRP


P2

GR-1

64 F2 STATIC EXCITATION CUBICLE G ~


P2

GENERATOR # 1
864MW, 960MVA, 26kV, 50Hz, 0.9PF 3000RPM, 98.94% EFFICIENCY TURBINE PANEL
DEHC AVR

CORE-N4 25000/5A, CL. 0.2S 70VA, ISF10 CORE-N3 25000/5A, CL. 0.2S 70VA, ISF10

GMP
A
MVAR MW MWH MVAH MVARH

GMP
V F PF
MW-1 MW-2 MW-3

EXTERNAL METERS FOR PERFORMANCE TESTING MW MW A

TO DCS

TO DCS TO DCS TO DCS

CORE-N2 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2

GR-2
GEN. PROTECTION NUMERICAL RELAY

64 G1 59 G2

64 G3 81 G2

87 G2 99 G2

78 G2 59 G2

46 G2 64 F2

21 G2

32 G2

40 50 G2 GS2

61 B2

37 G2

50 LBB

CORE-N1 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2


P1

GR-1
GEN. PROTECTION NUMERICAL RELAY

64 G1 59 G1

64 G2 81 G1

87 G1 99 G1

78 G1 59 G1

46 G1 64 F2

21 G1

32 G1

40 50 G1 GS1

61 B1

37 G1

50 LBB

NGT
26kV/240V 50Hz, 400kVA FOR 10 Sec.

20Hz SIGNAL GENE-RATOR

NGR GR-2 GR-1

240V, 0.054548 , 105kW FOR 10Sec.

UNIT TRANSFORMER # 10A


FROM GENERATOR BUSDUCT TAP OFF (REFER SHEET 15)

UNIT TRANSFORMER # 10B


FROM GENERATOR BUSDUCT TAP OFF (REFER SHEET 15)

STATION TRANSFORMER # 1
FROM GENERATOR BUSDUCT TAP OFF (REFER SHEET 15)

CORE-3 UT10A 1600/1A, CL. PS VK31Rct + 100V Im30mA AT Vk/2 CORE-2 UT10A 1600/1A, CL. 0.2S ISF5, 5VA

P1
3

CORE-3 UT10B 1600/1A, CL. PS VK31Rct + 100V Im30mA AT Vk/2 GMP CORE-2 UT10B 1600/1A, CL. 0.2S ISF5, 5VA

P1
3

CORE-3 ST1 1600/1A, CL. PS VK31Rct + 100V Im30mA AT Vk/2 GMP CORE-2 ST1 1600/1A, CL. 0.2S ISF5, 5VA

P1
3

GMP TO DCS
3

TO DCS

TO DCS

GRP CORE-1 UT10A 6000/1A, CL. 5P20 Rct23, 30VA GRP


87 51
3

GRP CORE-1 UT10B 6000/1A, CL. 5P20 Rct23, 30VA GRP


87
R
3

GRP CORE-1 ST1 6000/1A, CL. 5P20 Rct23, 30VA GRP


87
R
3

50

50

50

P2
TO DCS DCS
L
WTI WTI

P2
TO DCS DCS
L
WTI WTI

P2
TO DCS DCS
L
WTI

51

51

R
WTI

UNIT TRF-10A 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2

UNIT TRF-10B 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2

STATION TRF-1 63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2

800/1A, 15VA CL. 5P20

800/1A, 15VA CL. 5P20

800/1A, 15VA CL. 5P20

800/1A, 15VA CL. 5P20

800/1A, 15VA CL. 5P20

NGR

NGR

NGR

NGR

NGR

800/1A, 15VA CL. 5P20

P2

P1

P1

P2

P2

P1

P1

P2

P2

P1

P1

P2

SG

GRP

GRP SG

SG

GRP

GRP SG

SG

GRP

GRP SG

CORE-4

P1
3

SG
METERING

CORE-4

P1
3

SG
METERING

CORE-4

P1
3

SG
METERING

CORE-4

P1
3

SG
METERING

CORE-4

P1
3

SG
METERING

NGR SG
METERING

CORE-4

P1
3

CORE-3

SG
3

CORE-3

SG
3

CORE-3

SG
3

CORE-3

SG
3

CORE-3

SG
3

CORE-3

SG
3

CORE-2 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2 CORE-1 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2

CORE-2 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2 SRP


87 OA

CORE-2 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2 SRP


87 OA

CORE-2 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2 SRP


87 OA

CORE-2 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2 SRP


87 OA

CORE-2 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2 SRP


87 OA

P2

CORE-1 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2

P2

CORE-1 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2

P2

CORE-1 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2

P2

CORE-1 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2

P2

CORE-1 2000/1A, CL. PS VK40Rct + 100V Im30mA AT Vk/2

SRP
3

87 OA

P2

11kV, 2000A, UNIT-10A, SWGR-A

11kV, 2000A, UNIT-10A, SWGR-B

11kV, 2000A, UNIT-10B, SWGR-A

11kV, 2000A, UNIT-10B, SWGR-B

11kV, 2000A, STATION-1, SWGR-A

11kV, 2000A, STATION-1, SWGR-B

FROM GEN. TRANSFORMER-1

TO UT10A 19 20 21

TO UT10B

TO STATION TRANSFORMER-1

GCB ENCLOSURE
VT-3
26kV 3 110V 110V 3 3

REFER WDG-1: CL. 0.2, 30VA WDG-2: CL. 3P, 30VA


G G 26kV 3 G 110V 110V 3 3

24

VT-2

REFER WDG-1: CL. 0.2/3P, 30VA 23 WDG-2: CL. 0.2, 30VA VT-1

26kV 3

110V 110V 3 3

REFER WDG-1: CL. 02/3P, 30VA 22 WDG-2: CL. 0.2, 30VA

GEN. CTMB
P1 X11A A111A A131A A151A TO 87G1 (GR1) 33 S2 S2 X11A A171A 7 8 1CETL1 S2 1 2 3 4 5 6

10CHA00GH001

CORE-L3 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2

S1 S1 S1

10CHA00GH002
X11B 1 2 3 4 5 6 A111B A131B A151B TO 87G2 (GR2) 38 S2 S2 S2 X11B 7 8 2CETL1 A171B

CORE-L2 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2

S1 S1

S1

CORE-L1 25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2

S1

S1

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2 S2 S2

P2

GENERATOR # 1
864MW, 960MVA, 26kV, 50Hz, 0.9PF 3000RPM, 98.94% EFFICIENCY Xd=229(UNSAT.) 207(SAT.) Xd'=35.2(UNSAT.) 32.7(SAT.) Xd"=26.5(UNSAT.) 23.6(SAT.) X0=14.5 XS=1.46

GR1 64 F2

GR2 64 F2

GR2 64 F1

G ~

STATIC EXCITATION SYSTEM CUBICLES (TOSHIBA)

TO SHEET.18

REFER SHEET. 17

GEN. CTMB
P2

S2

S2 TO TURBINE PANEL

S2

CORE-N4
25000/5A, CL. 0.2S 70VA, ISF10 S1 S1 S1

951M

S2

S2 TO METERING W951-03

S2

CORE-N3
25000/5A, CL. 0.2S 70VA, ISF10 S1 S1 S1

10CHA00GH002
2CETL2 X11B 16 15 TO GR2 X11B 38 A251B A231B A211B S1 14 13 12 11 10 9 S1 S1 A271B

S2

S2

S2

CORE-N2
25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2

10CHA00GH001
1CETL2 X11A 16 15 S2 S2 S2 TO GR1 X11A S1 S1 S1 14 13 12 11 10 9 A251A A231A A211A 33 A271A

CORE-N1
25000/5A, CL. PX VK430Rct + 800V Im15mA AT Vk/2

P1

NGT
NGR 0.054548 26kV/240V 50Hz, 400kVA FOR 10 Sec. CT-2* CT-1* 105KW FOR 10 Sec 21 22 23 24 19 20 X11A X11A E81 E82 E83 E84 A185 A186 TO 100% & 95% STATOR E/F PROTECTION CKT. IN GR1 33 TO 100% STATOR E/F PROTECTION CKT. IN GR1 33

10CHA00GH002
X11B 17 18 NOTE: * - CT-1 & CT-2 TO BE SUPPLIED BY SIEMENS AS LOOSE ITEM. THE SAME SHALL BE MOUNTED IN NGT BY 'CGPL'. SIZE : 64x48x85.5 MODEL NO : 4NC5225-2CE20 A285 A286 TO 100% STATOR E/F PROTECTION CKT. IN GR2 38

SITE1

FROM 17

UT-10A CTMB 10CHA00GH004


X11DA A111D A131D A151D TO 87/51-UT10A 77 A190D A171D TO METERING(MWH) W951-04 S2 S2 S2 C111D C131D C151D TO 50 - UT10A 84 C190D C171D TO WTI (DCS) TO 64-2-UT10A 88 TO METERING (SG) S2 S2 S2 TO SG 1 2 3 4 5 6 X11DA 7 8 4CETL1

P1

CORE-3 UT10A
1600/1A, CL. PS VK31Rct + 100V Im30mA AT Vk/2 S2 S2 S2

S1

S1

S1

10CFA00
S1 S1 S1

CORE-2 UT10A
1600/1A, CL. 0.2S ISF5, 5VA

10CHA00GH004
X11DA 9 10 11 12 13 14 X11DA P2 4CETL2 15 16

CORE-1 UT10A
6000/1A, CL. 5P20 Rct23, 30VA S2 S2 S2

S1

S1

S1

UNIT TRF-10A
63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 P1 S1 X4 17 X11DA A375D A371D P2 NGR S2 800A For 10 Sec. 18 10CHA00GH004 19 20 NGR 800A For 10 Sec. S2 X4 14 13 S1 10CHA00GH004 TO 64-1-UT10A 86 A275D X11DA A271D 17 18 P2 P1

11kV UNIT-10 SWGR.


P1 S1 TO METERING (SG) S1 S1 S1 P1 S1

11kV UNIT-10 SWGR.


S1

CORE-4
S2 S2 S2

CORE-4

S1 TO SG

S1

S1

S1

S1

S1

CORE-3
S2 S2 S2

CORE-3
S2 S2 S2

10CHA00GH004
4CETL3 X11DA A271D 28 27 A290D S1 X11DA S2 S2 S2 S2 S2 S2 S1 S1 4CETL4 X11DA 36 35

10CHA00GH004

A371D

CORE-2

CORE-2

S1

S1

S1 X11DA 34 33 32 31 30 29

A390D A351D A331D A311D

77

A251D 26 25 A231D 24 23 A211D 22 21

77

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2

S1

S1

CORE-1
S2 S2 P2

CORE-1

S1

S1

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2 P2 S2 S2

11kV, 2000A, UNIT-10A, SWGR-A

11kV, 2000A, UNIT-10A, SWGR-B

FROM 17

UT-10B CTMB 10CHA00GH004


X11DB A411D A431D A451D TO 87/51-UT10B 93 A490D A471D TO METERING(MWH) W951-05 S2 S2 S2 C211D C231D C251D TO 50 - UT10B 100 C290D C271D TO WTI (DCS) TO 64-2-UT10B 104 TO METERING (SG) S2 S2 S2 TO SG 1 2 3 4 5 6 X11DB 7 8 4CETL5

P1

CORE-3 UT10A
1600/1A, CL. PS VK31Rct + 100V Im30mA AT Vk/2 S2 S2 S2

S1

S1

S1

10CFA00
S1 S1 S1

CORE-2 UT10A
1600/1A, CL. 0.2S ISF5, 5VA

10CHA00GH004
X11DB 9 10 11 12 13 14 X11DB P2 4CETL6 15 16

CORE-1 UT10A
6000/1A, CL. 5P20 Rct23, 30VA S2 S2 S2

S1

S1

S1

UNIT TRF-10B
63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 P1 S1 X4 17 X11DB A675D A671D P2 NGR S2 800A For 10 Sec. 18 10CHA00GH004 19 20 NGR 800A For 10 Sec. S2 X4 14 13 S1 10CHA00GH004 TO 64-1-UT10B 102 A575D X11DB A571D 17 18 P2 P1

11kV UNIT-10 SWGR.


P1 S1 TO METERING (SG) S1 S1 S1 P1 S1

11kV UNIT-10 SWGR.


S1

CORE-4
S2 S2 S2

CORE-4

S1 TO SG

S1

S1

S1

S1

S1

CORE-3
S2 S2 S2

CORE-3
S2 S2 S2

10CHA00GH004
4CETL7 X11DB A571D 28 27 A590D S1 X11DB S2 S2 S2 S2 S2 S2 S1 S1 4CETL8 X11DB 36 35

10CHA00GH004

A671D

CORE-2

CORE-2

S1

S1

S1 X11DB 34 33 32 31 30 29

A690D A651D A631D A611D

93

A551D 26 25 A531D 24 23 A511D 22 21

93

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2

S1

S1

CORE-1
S2 S2 P2

CORE-1

S1

S1

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2 P2 S2 S2

11kV, 2000A, UNIT-10B, SWGR-A

11kV, 2000A, UNIT-10B, SWGR-B

FROM 17

ST1 CTMB
X11E A111E A131E A151E TO 87/51-ST1 108 A190E A171E TO METERING(MWH) W951-06 S2 S2 S2 C111E C131E C151E TO 50 - ST1 115 C190E C171E TO WTI (DCS) TO 64-2-ST1 119 TO METERING (SG) S2 S2 S2 TO SG 1 2 3 4 5 6 X11E 7 8 5CETL1

10CHA00GH005

P1

CORE-3 ST1
1600/1A, CL. PS VK31Rct + 100V Im30mA AT Vk/2 S2 S2 S2

S1

S1

S1

951M
S1 S1 S1

CORE-2 ST1
1600/1A, CL. 0.2S ISF5, 5VA

10CHA00GH005
X11E 9 10 11 12 13 14 X11E P2 5CETL2 15 16

CORE-1 ST1
6000/1A, CL. 5P20 Rct23, 30VA S2 S2 S2

S1

S1

S1

STATION TRF-1
63/31.5/31.5 MVA, ONAN/ONAF, 26/11.5/11.5kV Dyn11yn11, Z(HV)-Z(LV1)/Z(HV)-Z(LV2)=10% Z(LV1)-Z(LV2)=20% OFF CIRCUIT TAPS IN THE RANGE OF IN STEPS OF 2.5% 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 2000/1A, CL. PS VK37Rct + 100V Im30mA AT Vk/2 P1 S1 X4 17 X11E A375E A371E P2 NGR S2 800A For 10 Sec. 18 10CHA00GH005 19 20 P1 S1 TO METERING (SG) S1 S1 S1 P1 S1 S1 NGR 800A For 10 Sec. S2 X4 14 13 S1 10CHA00GH005 TO 64-1-ST1 117 X11E A275E A271E 17 18 P2 P1

11kV ST1 SWGR.

11kV ST1 SWGR.

CORE-4
S2 S2 S2

CORE-4

S1 TO SG

S1

S1

S1

S1

S1

CORE-3
S2 S2 S2

CORE-3
S2 S2 S2

10CHA00GH005
5CETL3 X11E A271E 28 27 A290E S1 X11E S2 S2 S2 S2 S2 S2 S1 S1 5CETL4 X11E 36 35

10CHA00GH005

A371E

CORE-2

CORE-2

S1

S1

S1 X11E 34 33 32 31 30 29

A390E A351E A331E A311E

108

A251E 26 25 A231E 24 23 A211E 22 21

108

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2

S1

S1

CORE-1
S2 S2 P2

CORE-1

S1

S1

S1 TO OVERALL DIFF. PROTN. 87OA(SRP) S2 P2 S2 S2

11kV, 2000A, STATION-1, SWGR-A

11kV, 2000A, STATION-1, SWGR-B

10CHA00GH002
GCB -X83 E113 x 46 1 2 1 R E111

2PTMCB1-2A
X13B R

E133 x 47 3 4 2

BURDEN: 30VA CL-0.2/3P

TO GR-2 38 E131 Y E153 x 48 5 6 3 E151 B E173 x 43 7 8 4 2ETL1 1S473 A2 TO RTU 76P 1S101 A1 E171 N X43B

WDG - 1

Y B

2PTMCB2-2A
E213 x 1 2 5 E231 4 6 E211 X13B

1 X43B E233 x 3 X43B 2

TO AVR E253 x 5 6 E271 x 7 1S101 A1 8 1S473 A2 8 X43B E273 TO RTU 76P E251 7

10CFA00
-X83 E911 1 X13M R 40

3 4 E931 TO METERING W951-03 E951 E971

2ETL2

VT-1

26kV 110V 110V 3 3 3

Y 41 2 Y

WDG - 2

BURDEN: 30VA. CL-0.2

B 42 3 N 37 4 1ETL1 B

10CHA00GH001
GCB -X83 E313 x 16 1 2 1 R

1PTMCB1-2A
E311 X13A R

E333 x 17 3 4 2

BURDEN: 30VA CL-0.2/3P

TO GR-1 33 E331 Y E353 x 18 5 6 3 E351 B E373 x 13 7 8 4 1ETL1 1S475 A2 TO RTU 76P 1S101 A1 E371 N X43A

WDG - 1

Y B

1PTMCB2-2A
E413 x 1 2 5 E431 4 6 E411 X13A

1 X43A E433 x 3 X43A 2

TO AVR E453 x 5 6 E471 x 7 1S101 A1 8 1S475 A2 8 X43A E473 4 TO RTU 76P X43A 5 X43A 6 E533 3 TO GCP E553 7 8 TO RTU 76P 5 E573 7 1S101 A1 x 8 1S477 A2 X43A X43A E513 1 x 2 x 4 x 6 E571 12 E451 7 3

1ETL2

VT-2

26kV 110V 110V 3 3 3

-X83

1PTMCB3-2A
E511 9

X13A

R 10

E531 10

Y 11 Y B E551 11 N 07 12 B

WDG - 2

BURDEN: 30VA. CL-0.2/3P

1ETL3

10CHA00GH003
GCB -X82 E613 x 10 1 2 1 R

3PTMCB1-2A
E611 X13C R

E633 x 11 3 4 2 Y

BURDEN: 30VA CL-0.2

TO 87GT/64GT/99GT 61 E631 Y E653 x 12 5 6 3 E651 B B E673 x 13 7 8 4 3PETL1 1S479 A2 TO RTU 76K 1S101 A1 E671 N X43C E713 x 1 2 5 E731 4 6 X43C E733 x 3 X43C E753 x 5 6 7 E771 8 1S479 A2 8 3PETL2 X43C E773 x 7 1S101 A1 E751 3 2 E711

WDG - 1

3PTMCB2-2A
X13C

TO EXTERNAL METERS FOR PERFORMANCE TESTING 4 TO RTU 76P X43C E813 1 X43C 2 E833 3 X43C 1

3PTMCB3-2A
x 2 E831 x 4 10 E811 9

X13C

VT-3

26kV 110V 110V 3 3 3

TO GCP

E853 3 X43C 4 TO RTU 76P E913 TO 59N CKT 43 E973 3 TO RTU 76P 1S101 A1 E873 7 1S101 A1 5

x 6

E851 11 E871 x 8 1S479 A2 12 3PETL2

10CHA00GH002
-X82

2PTMCB3-2A
x 1 2

E911 9

X13B

R 01

WDG - 2

BURDEN: 30VA. CL-3P Y B

x 4

E971 10 1S481 A2 2ETL3

N 02

10CFA00
X79 240V AC SUPPLY TO METERING PANEL W951-02 1 2

ACDB
240V A.C. SUPPLY

10CHA00GH001
X61 *1 X79 1

10CHA00GH002
X79 1

10CHA00GH003
X79 1

10CHA00GH004
X79 1

10CHA00GH005
X79 H1 1

Ph

H1

H1

H1

H1

N *2 AMCB91-16A

H2 2 AMCB92-16A 4 2

H2 2 AMCB93-16A 4

H2 2 AMCB94-16A 4 2 2

H2 2 4 2 AMCB95-16A

H2

A2

4 CFL H5 HTS H7 TH H8 PS HT H10 H4 3 A1 A2

A2

A2

A1

A1

A1

A1

A2

H4

H4

H4

H3

H3

H3

H3

H4

CFL CILS H5

CFL CILS H5

CFL CILS H5

CFL CILS H5

H3 CILS PSS

HTS H7 TH

H8 PS

HT

HTS H7 TH

H8 PS

HT

HTS H7 TH

H8 PS

HT

HTS H7 TH

H8 PS

HT

PSS

H10

PSS

H10

PSS

H10

PSS

H10

NOTE: *

THUS MARKED TERMINAL NUMBER SHALL BE SUITABLE FOR 2 x 6 Sq mm WIRE.

10CHA00GH001 80A (MVAAM11)


13 K401 5 1 6 X51A U101 1 2 7 8 4 9 10 DC1 IND DC2 J5 1 J4 3 A1 A2 4 S179 TO RTU 76J 3 5 7 9 4 6 8 J15 10 J16 11 13 15 3 4 DCSS 12 14 16 134 X77 3 4 5 6 26A TO GR-1 TO 60G11 CKT. TO 60G12 CKT. TO 60G13 CKT. TO 186A1, A2, B & C 27 5 6 2 J6 X77 26A 1 U102X51A SPARE 2 3 K483 63 14 NOTE: * THUS MARKED TERMINAL NUMBER SHALL BE SUITABLE FOR 2 x 6 Sq mm WIRE.

SL01

J3A

DCDB1
+VE DC-1 X62 J1 *1 -VE *2 J2 S101

80 20 MS. TDDO

DMCB111-32A
J3 1 2

DMCB113-10A

DMCB114-10A

DMCB121-10A

DMCB112-4A

2 1 3 4
K2T

TO RTU 76J

TO RTU 76J

3 TO RTU 76J

A2

A2

A2

K101

K102

A1

A1

A1

K1T

K11

K12

K1

K2

TO GCB TC-1 69

TO GCP 69

TO TC-1 CIRCUIT SUPERVISION 69

X77

X77

10CHA00GH002
X77

DCDB2 DMCB213-10A DMCB214-10A


3 3 3 TO RTU 76K TO RTU 76K TO RTU 76K +VE DC-2 X63 J11 *1 -VE *2 J12 S101 3 A1 A2 4 J13 13 J14 S179 TO RTU 76A X51B U201 1 K301 5 1 6 2 7 8 4 9 10 U202X51B SPARE 2 J13A TO GR-2 TO 60G21 CKT. TO 60G22 CKT. TO 60G23 CKT. TO 286A1, A2, B & C 30 3 K341 TO 51NGT 68 14 TO RTU 76K 2 4
K52T

DMCB211-32A
1 2

A2

A2

A2

3 A1 A2

80B (MVAAM11)

A1

A1

TO GCB TC-2 69A

A1

TO GCP 69

TO TC-2 CIRCUIT SUPERVISION 69A

80 20 MS. TDDO

K51T

K201

K202

K15

K17

K51

K52

SL02

DMCB220-10A

DMCB212-4A

A1

A2

TO RTU 76J

10CHA00GH003

10CHA00GH004

10CHA00GH005

10CFA00

J5 FROM 26

X77 1

X77 1

X77 1

X77 1 220V DC SUPPLY TO METERING PANEL W951-03A

J6

DMCB115-4A

DMCB116-4A

DMCB117-4A

DMCB118-4A

DMCB119-4A

DMCB120-4A

2 3 1 TO RTU 76J

2 3 1 TO RTU 76J

2 1 3 4
K1302

TO RTU 76J

TO RTU 76J

3 TO RTU 76J

A2

A2

A2

A2

A2

K1101

A1

A1

A1

A1

K1102

A1

K1301

K301

K302

K701

K702

K801

K802

K901

K902

TO 51NGT CKT. TO GCB MULT. CKT. 68

TO TM1703 72

TO ETHERNET SWITCH SITE1 137

TO 50-UT10A CKT. TO 186D-UT10A CKT. 85

TO 50-UT10B CKT. TO 186D-UT10B CKT. 101

TO 50-ST1 CKT. TO 186D-ST1 CKT. 116

J15 FROM 26

X77 5

X77 5

X77 5

J16

DMCB215-4A

DMCB216-4A

DMCB217-4A

DMCB218-4A

DMCB219-4A

6 3 1 TO RTU 76K

6 3 1 TO RTU 76K

TO RTU 76K

TO RTU 76B

3 4
K1402

A2

A2

A2

A2

K1001

K1002

K1201

K1202

A1

A1

A1

A1

K1401

K401

K402

K601

K602

TO 87GT/64GT/99GT TO 59N CKT. 44

TO ETHERNET SWITCH 137

TO 87/51-UT10A TO 64-1-UT10A TO 64-2-UT10A TO 286D-UT10A 79

TO 87/51-UT10B TO 64-1-UT10B TO 64-2-UT10B TO 286D-UT10B 95

TO 87/51-ST1 TO 64-1-ST1 TO 64-2-ST1 TO 286D-ST1 110

A1

A2

TO RTU 76K

A1

A2

TO RTU 76J

10CHA00GH001

60G11
FROM GR-1, VT-2 WDG-1 33 E355 27 E315 E335 25 23 Vr

(MVAPM32)

Vy Vb

10CHA00GH002
26 C K131 13 K101 K101 3 C1 1 14 K141 X71 1 X71 1 17 TO GR-1 34 30 60G21 15 26 X71 2 X71 2 K102 28 5

5 C2 4 2

C3 7 K101 8 K231 17 B1 C4

6 9 K157 10 K202 15 TO GR1 35

(SCADA ALARM) TO 60G21 30

19 X51A U103 3 28 20 18 B2 16 U105 U104 X51A 4 SPARE

10CHA00GH001

60G12
X13A FROM AVR, VT-2 WDG-1 14 15 16 E415 E435 25 E455 27 23 Vr

(MVAPM32)

Vy Vb

10CHA00GH002
27 C K133 13 K101 C1 3 1 14 X71 3 X71 3 17 31 60G22 15 27 X71 4 X71 4 K102 5 C2 4 2 K509 X43A TO AVR (VT-2 Wdg-1 UNHEALTHY) 10 6 9 C4 8 K233 17 B1 15 10 K202 TO 60G22 31 K159 TO SCADA ALARM 35 19 X51A U106 6 29 20 18 B2 16 U108 8 U107 X51A 7 SPARE 29

X43A K507 9

C3 7 K101

10CHA00GH001

60G13
X13A FROM GCP, VT-2 WDG-2 17 18 19 E515 E535 25 E555 27 23 Vr

(MVAPM32)

Vy Vb

10CHA00GH002
28 C K135 13 K101 C1 3 1 14 X71 5 X71 5 17 32 60G23 15 28 X71 6 X71 6 K102 5 C2 4 2 6 9 C4 8 K235 17 B1 15 10 K202 TO 60G23 32 K161 TO SCADA ALARM 35 19 X51A U109 9 34 20 18 B2 16 U111 11 U110 X51A 10 SPARE 34

C3 7 K101

10CHA00GH002

60G21
FROM GR-2, VT-1 WDG-1 38 E155 27 E115 E135 25 23 Vr

(MVAPM32)

Vy Vb

10CHA00GH001
26 C K231 13 K201 K201 3 C1 1 14 K241 X71 7 X71 7 17 39 27 60G11 15 26 X71 8 X71 8 K202 27 31 5

TO GR2

5 C2 4 2

C3 7 K201 8 K131 17 B1 C4

6 9 K257 10 K102 15 40 TO GR2 (SCADA ALARM) TO 60G11

19 X51B U203 3 31 20 18 B2 16 U205 U204 X51B 4 SPARE

10CHA00GH002

60G22
X13B FROM AVR, VT-1 WDG-1 11 12 13 E711 E731 25 E751 27 23 Vr

(MVAPM32)

Vy Vb

10CHA00GH001
30 C K233 13 K201 C1 3 1 14 X71 9 X71 9 17 28 60G12 15 30 X71 10 X71 10 K202 5 C2 4 2 K509 X43BTO AVR (VT-1 Wdg-1 UNHEALTHY) 6 6 9 C4 8 K133 17 B1 15 10 K102 K259 TO GR2 (SCADA ALARM) TO 60G12 28 40 19 X51B U206 6 32 20 18 B2 16 U208 8 U207 X51B 7 SPARE 32

X43B K507 5

C3 7 K201

10CHA00GH002

10CFA00
X13B FROM VT-1 WDG-2 W951-07 14 15 16 X13B 14 15 16 E811 E831

60G23
23 25 E851 27 Vr

(MVAPM32)

Vy Vb

10CHA00GH001
31 C K235 13 K201 C1 3 1 14 X71 11 X71 11 17 29 60G13 15 31 X71 12 X71 12 K202 5 C2 4 2 6 9 C4 8 K135 17 B1 15 10 K102 TO 60G13 29 K261 TO SCADA ALARM 40 19 X51B U209 9 39 20 18 B2 16 U211 11 U210 X51B 10 SPARE 39

C3 7 K201

10CHA00GH001 GR1
A111A GEN. LINE SIDE CT CORE-L3 17 A131A A151A A171A

(7UM62)
IL1S1 J2 J4 J6 LED NO. GR1 DIFF. PROTN. OPTD. 95% & 100% STATOR EARTH FAULT PROTN. OPTD. POLE SLIPPING PROTN. OPTD. LOSS OF EXCITATION PROTN. OPTD. NEG. PHASE SEQ. PROTN. OPTD. B/U. IMPEDANCE PROTN. OPTD. REVERSE POWER PROTN. OPTD. LOW FORWARD POWER PROTN. OPTD. UNDER FREQUENCY PROTN. OPTD. OVER VOLTAGE PROTN. OPTD. DEAD MACHINE PROTN. OPTD. OVER FLUX PROTN. OPTD. LBB PROTN. OPTD. ROTOR E/F PROTN. OPTD. LED MARSHALLING DETAILS:

BLK-GR1A
S3 S4 S5 S6 R3 R4 R5 R6

A112A A132A A152A A172A J1 J3 J5

IL2S1 IL3S1

A211A GEN. NEUTRAL SIDE CT CORE-N1 18 A231A A251A A271A S7 S8 S9 S10 131 R7 R8 R9 R10

A212A A232A A252A A272A Q1 Q3 Q5

IL1S2 IL2S2 IL3S2 Q2 Q4 Q6

1 2 3 4 5 6

20Hz GENERATOR G20HZ(7XT33)


X43A 230V AC UPS SUPPLY FROM STATION 11 -G20HZ *E775 2 3 12 12 -EBAR *E715 1 11 *E715A

20Hz BANDPASS FILTER FGR1 (7XT34)


1A1 1B4 330 50H 330 50H 1B1 330 1A4 50H 330 50H 330 50H E771 1A2 E773

BLK-GR1C
E781 S7 S8 131 1A3 TO GR2 FOR 100% & 95% STATOR E/F 38 131 A185 A186 S4 J76 R4 J96 K14 J97 S4 J78 S5 J79 S6 131 R6 J85 K17 J87 TO 60G11 27 E313 E333 E353 E373 K18 SITE1 E315 E335 R15 R17 E355 E375 R18 R16 UL1 UL2 UL3 TD3(EXCITATION VOLTAGE) (FOR ROTOR E/F) R5 J99 K15 R4 J98 K16 TD2(ROTOR E/F) K13 TD1(ROTOR E/F) R7 E783 R8 R13 UE R14 100% STATOR E/F / 95% STATOR E/F PROTN.

7 8 9 10 11

10CHA00GH002
X71 X71 13 14 13 14 FROM NGT TRF 18 TO ROTOR EARTH FAULT RELAY 38

SITE1

12 13

BLK-GR1B
S3 R3

FROM NGR CUBICLE FOR 100% STATOR E/F - CT-1 18

A187 J7 A189 J8 IEE1 100% STATOR E/F PROTN.

14

BLK-GR1C
S3 R3

*E81 *E82 *E83 *E84

J77

FROM GR2 FOR ROTOR E/F 38 1. * MARKED CABLES SHOULD BE 5Sq mm SCREENED CABLES (IN SIEMENS SCOPE).

NOTE :

2. ROTOR E/F PROTECTION: THE RESISTOR & CAPACITOR IS PROVIDED IN THE EXCITATORY CIRCUIT TO MONITOR UNDER EXCITATION VOLTAGE MONITORING(VOLTAGE SUPERVSION). TO OPERATE UNDER EXCITATION PROTECTION, ALL THE THREE TERMINAL PHASE CURRENT AND ALL THE TERMINAL VOLTAGE IS REQUIRED. THE SAME IS ALREADY PROVIDED. IN ADDITIONN TO THIS WE HAVE PROVIDED UNDER EXCITAITON VOLTAGE MONITORING THROUGH TRANSDUCER OF 7UM62 RELAY TD3 TO GET FAST TRIP. PLEASE REFER CHAPTER 2.16 OF 7UM62 MANUAL FOR FURTHER DETAILS. FROM VT-2, CORE-1 SUPPLY RATIO: 26KV 110V 110V 3 3 23 3

BLK-GR1B
S7 S8 S9 S10 131 R7 R8 R9 R10

10CHA00GH001
29 K101 60G11 3 1 (VT2 CORE-1 SUPPLY FAILURE) 27 K141 F5 F10 BI1 21G1 B/U IMP, 27G1U/V 37 BLOCK, 40G1 BLOCK, 78

GR1

7UM62

29 K102

SRP-403
X41A 1 GT CB-R GT CB-Y GT CB-B X41A K143 2 F6 BI2 GT-1 ON GRID/BUS CB SITE1 X43A 14 K145 F7 BI3 EXCITER FIELD CB CLOSED

EXCITER CB
X43A 13

SRP-402
X41A 3 TIE CB-R TIE CB-Y TIE CB-B X41A K147 4 F8 BI4 GT-1 ON GRID/MIDDLE CB

SITE1

186A1 17 186A2-1 17 19 47 X43A 16 19 46

K149 F9 BI5 GCB 50LBB

EXCITATION TR-MB
X43A 15 K151 K9 BI6 # TRIP K10

TURBINE
X43A 17 X43A 18 K153 K11

SITE1

K12 BI7 TURBINE TRIP CHANNEL-1 K155

19

P17 P18 BI8 TURBINE TRIP CHANNEL-2

# EXCITATION TRANSFORMER WINDING TEMPERATURE VERY HIGH . THIS SIGNAL SHALL BE MADE AVAILABLE TO DCS THROUGH SOFT LINK 35

35

10CHA00GH001 GR1 (7UM62)

34 K101

34 K102

60G11 8 27 60G12 8 28 60G13 8 10CHA00GH003 X71 15 X71 15 13 71 GCB 1 2 17 17 29 GCB 14 X71 16 X71 16 10 10 10

K157 N5 BI09 GEN VT-2 CORE-1 FUSE FAILURE-60G11 ALARM N3 K159 N3 BI10 N5 GEN VT-2 CORE-1 FUSE FAILURE-60G12 ALARM K161 N4 BI11 GEN VT-2 CORE-2 FUSE FAILURE-60G13 ALARM K163 N6 BI12 GCB OPEN

K165 N7 N8 BI13 GCB CLOSE

IN OUT K167 1 2 N9 N10 BI14 GCB LBB IN

K169 4 3 LBBSW1 134 K101 F1 46 N11 N12 BI15 GCB LBB OUT

= = F2 46

POWER SUPPLY