TSi Power Corporation ~ Product Specifications and White Papers Book

TSi Power Corporation


Power with a Precision Attitude

Product Specifications and White Papers

October 2006

TSi Power Corporation Power with a Precision Attitude

Copyright 2006 TSi Power Corporation. All rights reserved. Please e-mail any problems with PDF loading or any errors to michael.gibson@carebase.com Thank you.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

TSi-Power-Book-Cover-2006-10-16.pdf

TSi Power Corporation

Product Specifications and White Papers


Table of Contents
TSi Power Corporation ~ Product Specifications and White Papers Book TSi Power Corporation ~ Overview ARm Series ~ Automatic Redundancy Module/UPS Bypass ATs Series ~ Automatic Transfer Switches for Redundant Power EXt Series ~ Battery Extension Units

ARm-1000 ~ 15A, 1750VA, 120vac .................................................................................. 11 ARm-1000E ~ 10A, 2300VA, 230vac ................................................................................. 13 ATs-1000 ~ 30/40A, 3.6 /4.8kVA, 120vac ......................................................................... 17 ATs-1000E ~ 30/40A, 7.2/9.6kVA, 230vac ........................................................................ 19 EXt-8000 ~ 120vac input, 24vdc output ............................................................................. 23 FLc-750/1000/1500 ~ 6.3/8.3/12A, 750VA/1/1.5kVA, 120vac........................................ 27

FLc Series ~ Ferroresonant Isolation Transformer Line Conditioners

ILc Series ~ Low-Impedance Isolation Transformer Line Conditioners

ILc-600B/1000B ~ 5/ 8.3A, 600/1kVA, 120vac.................................................................. 31 ILc-1800 / 2000 ~ 15/16A, 1.8/2kVA, 120vac.................................................................... 33 ILc-2400/3600 ~ 20/30A, 2.4 /3.6kVA, 120vac................................................................. 35 ILc-2400/3600-230V ~ 10/15A, 2.4/ 3.6kVA, 208/220/230 or 240vac............................. 37 ILc-4400/5500-230V ~ 19/24A, 4.4/5.5kVA, 208/220/230 or 240vac ............................. 39 ILc-9000/16500-0338 ~ 9/16.6kVA, 9/16.6kW, 400V delta in, 230/400V wye out.......... 41 ILc-15000-0232 ~ 15kVA, 80A, 208vac, single phase......................................................... 43 ILc-1000/1400Med4 ~ 8.3/ 11.7A, 1/ 1.4kVA, 120vac...................................................... 47

ILc-Med Series ~ Medical Isolation Transformers

Outdoor Series ~ UPS, Precision AVR and Line Conditioners

OutdoorXUPs-600-6339 ~ 600VA, 480W, 120vac, UPS+AVR, Pole-mountable................ 51 OutdoorXUPs-600A/B ~ 600VA, 420W, 120vac, UPS+AVR ............................................. 55 OutdoorXUPs-600AHV/BHV ~ 600VA, 420W, 230vac, UPS+AVR ................................... 59 OutdoorXUPs-600C ~ 600VA, 420W, 120vac, 11hrs@400W, UPS+AVR ........................ 63 OutdoorXUPs-600CHV-OEM ~ 600VA, 420W, 230vac, 11hrs@400W, UPS+AVR .......... 67 OD-XUPs-400C/600C ~ 400/600VA, 250/ 420W, 120vac, UPS+AVR ............................. 71 OutdoorXUPs-1000A/B ~ 1000VA, 700W, 120vac, UPS+AVR ......................................... 75 OutdoorXUPs-1000AHV/BHV ~ 1000VA, 700W, 230vac, UPS+AVR ............................... 79 OutdoorUPs-400Conf1-2 ~ 400VA, 250W, 120vac ........................................................... 83 Outdoor-UPs-10000-16000-21000 ~ 1 -1.6-2.1kVA, 750W-1.2kW-1.5kW, 120V .......... 85 OutdoorXUPs-1000-8024~230vac in, 400W@230vac+200W@48vdc out, UPS+AVR. 89 Outdoor-UPs-8009/8010 ~ 60 watts, 115 or 230 vac input, 12 vdc output UPS ................. 93 Outdoor-UPs-8015/8016 ~ 96 watts, 115 or 230 vac input, 12 vdc output UPS ................. 97 Outdoor-UPs-8011/8012 ~ 96 watts, 115 or 230 vac input, 24 vdc output UPS ............... 101 Outdoor-UPs-8013/8014 ~ 96 watts, 115 or 230 vac input, 48 vdc output UPS ............... 105 Outdoor-VRx-4400-0455/0460 ~ 4.4kVA, 230vac, PWM AVR+line conditioner ............. 109 Outdoor-VRp-ILc-15000/30000-5339 ~ 15/30kVA, 400 vac delta,230/400 vac wye....... 113 RMk Series ~ Rack-mounting kits for 19, 23, 24 racks, and wall-mounting.................... 119 SLc-600/1200/1800 ~ 5/10/15A, 600VA/1.2 /1.8kVA, 120vac ...................................... 123 SLc-600E/1200E /1800E ~ 2.6/5/ 7.8A, 600VA/ 1.2/1.8kVA, 230vac.............................. 125 SLc-1100B/2000B ~ 9/16A, 1.1kVA/2 kVA, 120vac........................................................ 127 SLc-1100BE/2000BE ~ 5.5 /10A, 1100/2000 VA, 230vac................................................. 129 XUPs-600/1000 ~ 600VA /1000VA, 420W/700W,120vac, UPS+AVR ........................... 133 XUPs-600HV/1000HV ~ 600VA /1000VA, 420W/700W, 230vac, UPS+AVR................ 137 UPs-400Wtb ~ 400VA, 250W, 120vac, with wide temperature battery ............................ 141 XUPs-600/1000-8022 ~ 600VA /1000VA, 420W/700W, 115vac, OEM UPS+AVR....... 143 XUPs-600/1000-8023 ~ 600VA /1000VA, 420W/700W, 230vac, OEM UPS+AVR....... 147 UPs-600 ~ 600VA, 400W, 120vac ................................................................................... 151 UPs-10000/16000/21000 ~ 1 /1.6/2.1kVA, 750/1000/1500W, 120vac......................... 153 XUPs and UPs Automatic Shutdown Instructions for Windows XP Professional ................... 157 ILc-2000-VRp-Dual-Range ~ 2kVA, 1.8kW, 120+240vac................................................ 161 VRp-3000/5000-120V ~ 3/5kVA, 3/5kW, 40/70A, 120vac............................................. 165 VRp-3000/5500-0230 ~ 3/5.5kVA, 3/5.5kW, 208/220/230/240vac .............................. 167 VRp-3500-0233 ~ 3.5kVA, 3.5kW, 208/220/230/240vac ............................................... 169 VRp-4000-0235 ~ 4kVA, 4 kW, 208/220/230 or 240vac, single phase ............................ 171 VRp-7500/10000 ~ 7.5/10kVA, 7.5/10kW, 208/220/230 or 240vac, single phase ......... 173 VRp-9000/16500 ~ 9/16.5kVA, 9/16.5kW, 220/380V or 230/400vac wye, grey............ 175 VRp-9000/16500-0338 ~ 9/16.5kVA, 9/16.5kW, 220/380vac or 230/400vac wye ........ 177 VRp-15000/20000-0230 ~ 15/20kVA, 15/20kW, 208/220/230 or 240vac, single phase 179 VRp-22500/30000-0338 ~ 22.5/ 30kVA, 22.5/30kW, 220/380V or 230/400vac wye .... 181 VRp-ILc-16500-0338 ~ 16.5kVA, 16.5kW, 400vac delta to 230/400vac wye ................... 183

RMk Series ~ Rack-mounting Kits for TSi Rack-mountable Products SLc Series ~ Automatic Voltage Stabilizing Line Conditioners

XUPs and UPs Series ~ Uninterruptible Power Systems

VRp Series ~ Precision PWM Automatic Voltage Regulators

XINv Series ~ Dc to Ac Inverters with Transformer Isolation

XINv-600/900-24V ~ 600/900VA, 600/900W, 24vdc to 115vac ................................... 189 XINv-600E/900E-24V ~ 600/900 VA, 600/900 W, 24vdc to 230vac ............................... 193 XINv-400/700/1400-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 115vac ...... 197 XINv-400E/700E/1400E-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 230vac . 201 Coordination of Telecommunications SPDs in Countries with Unstable Power ................... 207 TSi Power Case Studies ~ Mission-critical Solutions........................................................... 217 Choosing UPS Protection for Underdeveloped Countries ................................................... 221 Designing for Surge Immunity in International Markets....................................................... 225 IEC 1312 Surge Protective Device Coordination................................................................. 231 Benefits Provided by UPS and Line Conditioners with an Isolation Transformer.................. 235 The Merits of a Standby UPS with a Modified Sine Wave Output....................................... 237 Power Primer ~ A Guide to UPS and Power Terms ........................................................... 239 Why Power Supplies and Semiconductors Fail ................................................................... 243 Protection of Telecom Sites in Countries with Unstable Ac Mains....................................... 245

White Paper Series ~ TSi Power White Papers on Power Protection

This page intentionally left blank.

TSi Power Corporation ~ Overview


TSi Power Corporation Power with a Precision Attitude 7

TSi Power Corporation


Power with a Precision Attitude

Since 1987, TSis mission has been helping you solve your power protection problems, to help you satisfy your special equipment input power requirements, and to make it possible for you to relax easier, knowing your systems are protected to the best level possible.

What we manufacture and can customize for you


TSi Power makes ac line conditioners, isolation transformers, precision ac automatic voltage regulators, automatic transfer switches (ATS), indoor and outdoor uninterruptible power supplies, dc to ac inverters, and overvoltage protection devices. TSi offers a range of unique line conditioners (including a medical grade series), isolation transformers, precision and extended range automatic voltage regulators and overvoltage protection products while offering competitive automatic transfer switches (ATS), UPS and dc to ac inverters. We specialize in custom products for relatively small volumes. Customization can mean offering special wiring terminals on a standard voltage regulator product or mean the development of a hospital grade power conditioner to a unique requirement. We create our power protection products from a library of standard board designs and an extensive library of CAD designs. This combination allows us to respond quickly and economically to many varying requirements.

Examples of TSi power quality products developed include, but are not limited to:
Custom precision voltage regulators with automatic bypass and built-in isolation transformers. Custom OEM uninterruptible power supplies with special wiring harnesses. Ideal for use in control cabinets or for integration in OEM produced product. Custom UPS meeting the requirements of medical OEMs.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Custom ac power distribution units (PDU) for protection, distribution and control of ac power for medical imaging systems. Custom outdoor rated hardwired UPS (or AVR or line conditioners) with wide temperature batteries, built-in auto bypass, and a wide input voltage range. Custom line conditioners for universal input power supplies.

TSi Power Corporation Power with a Precision Attitude

How we do it
TSi strives to offer the very best value to our customers at every stage of the process. We do this by operating with a very low overhead through the utilization of appropriate technology and a cost-effective location in North-central Wisconsin. As such, we do not suffer from the productivity losses caused by big-city commuting and the high cost of living, which inevitably reduces the pool of qualified employees. Additionally, we have decided to eliminate most traditional layers of manufacturers' representatives and distributors, as they typically increase cost while in many cases not adding any significant value. We do however have a network of truly qualified and specialized distributors, representatives, retailers and OEMs that we work closely with to give you fast track service even when you are dealing with us indirectly. When you contact TSi Power we will do our best to provide technically competent and personalized service. Each customer is served by a sales engineer who understands our products down to the board level and who has at least 10 years direct experience in power protection systems. At the bottom line, Peter Nystrom, President of TSi Power, has extensive worldwide experience in developing power protection products and solutions. His background includes founding Powervar; once serving as the three phase manager for Oneac; and his working for Ericsson developing solutions to their worldwide telecommunications power quality requirements. The TSi Power sales engineer will help each customer with the best possible solution to a particular requirement.

Our commitment to you


Our commitment to customers is simple: we will serve you directly, or indirectly on a fast track, through our network of qualified and specialized distributors, representatives and OEMs.

What does this mean?


Faster communication, as information does not have to travel back and forth through many layers of people Reduced time to market and lower cost Customers can be assured that the TSi sales engineer puts them before commissions

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

TSi-Power-Overview-2006-10-16.pdf

ARm Series ~ Automatic Redundancy Module/UPS Bypass

ARm Series Automatic Redundancy Module / UPS Bypass

ARm
ARm Series Automatic redundancy module

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

10

Page For Notes ARm Series

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ARm-Series-2006-10-16.pdf

ARm-1000 ~ 15A, 1750VA, 120vac


ARm Series Automatic Redundancy Module/UPS Bypass 11

ARm
ARm model 1000
15 amps 1750 VA 1750 watts 120 volts

Two ac inputs ~ one ac output

UPS bypass switch

Compact

Automatic Redundancy Module


TSi Powers ARm-1000 redundancy module automatic bypass system is recommended when no downtime from power outage is tolerated. Internet service providers, critical servers and telecom equipment, and export markets with bad power would find this technology valuable.

Typical ARm applications


Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, export markets, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment. Note: Both power sources Must be In Phase. If cannot be guaranteed, see the ATs-1000.

Key ARm Series features


Enables redundant UPS, backup generators or other ac power sources to be used for a single load. Less than 10ms transfer time from source A to source B. Low cost LED status indicators DB9 communications interface Audible alarms with enable/disable switch
UPS #1 or other power source

Key ARm benefits


The ARm unit will provide uninterrupted ac to your load even in the event of UPS failure. ARms your critical equipment against extended power outages and catastrophic system shutdowns caused by accidental circuit breaker trips, UPS overload conditions, weak or old UPS batteries, routine and preventive maintenance of UPS, accidental UPS shutdown, loose power cords, or UPS failure. The ARM Series permits daisy chaining with any sine wave in-phase UPS, providing unlimited redundancy using any combination of independant (separate) ac circuits, UPS systems, generator-backed ac circuits, etc.

mission critical

primary feed

How the ARm works


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

automatic redundancy module


backup feed

server or

TSi Power Corporation

The ARm is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, a relay immediately switches the load over to the backup power source feed in less than 10 ms. This is fast enough to be invisible to computer switch-mode power supplies.

telecom

UPS #2 or other power Source

system

12

Specifications ARm-1000

ARm
Automatic redundancy module
Specifications

Specifications
Electrical
Capacity in VA (watts) Switching technology

ARm-1000
1750VA (1750W) Fast operating/releasing relays 120 volts ac, single phase 100 to 135 volts ac 100 to 135 volts ac 60 Hz +/-5% Both primary and backup ac are protected by fuses 15 amps Less than 10ms, primary to back-up and back-up to primary 2.5mm2 (14 AWG) recommended 1.8m(6 ft.) cords and 5-15P plugs 120 volts ac, single phase Better than 2% from no load to full load 98% or higher Four NEMA 5-15R output receptacles Green LED for primary ac presence, yellow LED for backup ac presence, flashing red LED for loss of primary or backup ac. Buzzer beeps when loss of primary or backup ac occurs. Audible alarm (buzzer) and alarm enable/disable switch A rear-mounted DB-9 connector sends loss of primary ac and loss of backup ac. (Pins 1 and 5 are used). 254mmW x 203mmD x 76 mmH (10wide x 8 deep x 3.2 high) 2.7 kg (6 lbs) Front mount kit for a 19 rack: # MK-5019A 0o to +40 oC(32o to +104o F). 10 to 90% relative humidity (non-condensing) Two year limited warranty, parts and labor.

Inputs
Nominal voltage Primary ac voltage Backup ac voltage Frequency range Over-current protection Fuse ratings Typical transfer time Input/output wire size Ac inputs (two)

Output
Nominal voltage Load regulation Power efficiency

Rear view ARm-1000

Ac receptacles Indicators Audible alarms Audible alarm switch Alarm contacts interface

Physical
Dimensions Weight Rack mount option
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Environmental
Ambient temperature

Warranty
Warranty

ARm system architecture


backup * ac input 120V hot neutral ground primary * ac input 120V hot neutral ground 15 A fuses primary ac detection 15 A fuses backup ac detection mechanical relay #1 10ms transfer time relay #2 neutral power supply logic alarm DB9 alarm signals ac output 120 V ground hot

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

* Note: Primary and back-up ac must be in phase. Otherwise, relay contacts may be damaged.

ARm-1000-120V-2006-10-16.pdf

ARm-1000E ~ 10A, 2300VA, 230vac

ARm
ARm model 1000E
10 amps 2300 VA 2300 watts 230 volts

ARm Series Automatic Redundancy Module / UPS Bypass

13

Two ac inputs ~ one ac output

Automatic redundancy

Compact

Automatic Redundancy Module~230V


TSi Powers ARm-1000 redundancy module automatic bypass system is recommended when no downtime from power outages is tolerated. Internet service providers, critical servers and telecom equipment, and export markets with bad power would find this technology valuable. The ARm Series permits daisy chaining with any UPS, providing unlimited redundancy using any combination of independant (separate) ac circuits, UPS systems, generator-backed ac circuits, and so on. Key
Note: Both power sources must be in phase. If cannot be guaranteed, see the ATs-1000E.

features of the TSi Power automatic redundancy module


Enables redundant UPS, backup generators or other ac power sources to be used for a single load. Less than a 10ms transfer time from source A to source B. Low cost LED status indicators DB9 communications interface Audible alarms with enable/disable switch

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, export markets, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key benefits
ARm will provide uninterrupted ac to your load even in the event of UPS failure.

ARms your critical equipment against extended UPS #1 or power outages and catastrophic system other power shutdowns caused by accidental circuit breaker source trips, UPS overload conditions, weak or old UPS batteries, routine & preventive maintenance of UPS, accidental UPS shut down, loose power cords, or UPS failure. primary feed ARm-1000 permits unlimited redundancy using automatic any combination of independent (separate) ac cir- redundancy module cuits, UPS systems, generator-backed ac circuits, etc.
TSi Power Corporation

mission critical

server or

How the ARm works

backup feed

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

The ARm is fed by two ac power sources. When the primary power source detector circuit UPS #2 or senses a loss of power on that circuit, a relay other power immediately switches the load over to the backup source power source feed in less than 10 ms. This is fast enough to be invisible to computer switch-mode power supplies.

telecom system

14

Specifications ARm-1000E

Automatic redundancy module


Specifications

ARm

Specification
Electrical
Capacity in VA (Watts) Switching technology

ARm-1000E
2300VA (2300W)

Fast operating/releasing relays


230 volts ac single phase 190 to 260 volts ac 190 to 260 volts ac 50 Hz +/-5% Fuses 10 amps Less than 10ms, primary to back-up and back-up to primary. 1.8m (6 ft.) 3-conductor 2.5mm2 (14 AWG) SJT cord & IEC 320 plugs. 230 volts ac, single phase Better than 2% from no load to full load 98% or higher Four IEC 320 output receptacles Green LED for primary ac presence, yellow LED for backup ac presence, flashing red LED for loss of primary or backup ac. Buzzer beeps when loss of primary or backup ac occurs. Audible alarm (buzzer) and alarm enable/disable switch. A rear-mounted DB-9 connector sends loss of primary ac and loss of backup ac signal for external power monitoring. Pins 4 and 5 are used. 254mm(10) wide x 203.2mm(8)deep x 76 mm(3.2 )high 2.7kg (6 lbs) Front mount kit: For a 19 rack: use # MK-1019A Primary and back-up ac must be sinusoidal and always be in phase. 0 o to 40o C(32o to 104o F). 10 to 90% Relative humidity (non-condensing). Two year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Input
Nominal voltage Primary ac voltage Backup ac voltage Frequency range Overcurrent protection Fuse ratings Typical transfer time Ac input

(ARm-1000 120V shown)

Rear view

Output
Nominal voltage Load regulation Power efficiency Ac receptacles Indicators Audible alarms Audible alarm switch Alarm contacts interface

Physical
Dimensions Weight Rack mount option

Special Note
In Phase Requirement

Environmental
Ambient Temperature

Warranty
Warranty

ARm system architecture


backup * ac input 230V Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi hot neutral ground primary * ac input 230V hot neutral ground 10 A fuses 10 A fuses

* Note: Primary and back-up ac must be in phase. Otherwise, relay contacts may be damaged. mechanical relay #1 backup ac detection 10ms transfer time relay #2 neutral power supply logic alarm DB9 alarm signals ground

hot ac output 230 V

TSi Power Corporation

primary ac detection

ARm-1000E-230V-2006-10-16.pdf

ATs Series ~ Automatic Transfer Switches for Redundant Power


ATs Series Automatic Transfer Switch 15

ATs
ATs Series Automatic transfer switches

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

16

ATs Series Automatic Transfer Switch

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ATs-Series-2006-10-16.pdf

ATs-1000 ~ 30/40A, 3.6 /4.8kVA, 120vac


ATs Series Automatic Transfer Switch 17

ATs
Model
ATs-1000
30 amps 3600 VA 3600 watts 120 volts

Two ac inputs ~ one ac output

Automatic transfer switch

Compact

Automatic Transfer Switch


TSi Powers ATs Series user customizable automatic transfer switches (ATS) are for enabling the use of redundant power sources, such as small uninterruptible power systems feeding industrial controls, PLC cabinets, internet servers, telecom systems, etc.

ATs-1000-40A
40 amps 4800 VA 4800 watts 120 volts

Typical ATs applications


Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, rectifiers, cell sites, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key ATs features


Enables redundant UPS, backup generators or other ac power sources to be used for a single load. Less than a 20ms transfer time from source A to source B. User selectable transfer times of 20ms, 40ms or 1 second. Built-in circuit breakers Designed to handle out-of-phase and/or asynchronous ac sources Rack-mountable LED status indicators DB9 communications interface Audible alarms with enable/disable switch
UPS #1 or other power source
mission critical

Key ATs benefits


If the ATs DIP Switch is set to Fast transfer (20ms typical transfer time) mode, then when redundant power sources are present, it can replace an expensive UPS system and battery banks for most computers, telecommunication, and industrial equipment (since switchmode power supplies used in most new electronics equipment provide a minimum of 20ms in capacitor hold-up time under full load conditions). If a positive power break is needed during the transfer, then the ATs may be set to Slow transfer (1 second) mode to ensure a full 1 second ac power outage during transfer. Also, the two ac sources do not have to be synchronized since the ATs is designed to switch between two asynchronous ac sources without damage to itself or to equipment powered by switchmode power supplies.

primary feed

How the ATs works


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

automatic transfer switch


backup feed

server or

TSi Power Corporation

The ATs is fed by two independent ac power sources. When the primary power source detector circuit senses a loss of power on the primary circuit, it immediately switches the load over to the backup power source feed in less than 20 ms. Upon restoration of primary power, the ATs will switch back in less than 20ms. This is fast enough to be invisible to computer switch-mode power supplies.

telecom

UPS #2 or other power source

system

18

ATs

ATs Series ATs-1000-30A/40A

Specification
Electrical
Capacity in VA (Watts) Switching technology

ATs-1000 (30A)
3600VA (3600W) maximum

ATs-1000-40A
4800VA (4800W) maximum

Solid-state relays (SSRs)


120 volts ac single phase 95 to 135 volts ac 95 to 135 volts ac 47 to 63 Hz User resettable circuit breaker 30 amps 40 amps 20ms, 40ms or 1000ms (user selectable) Via an internal four position DIP switch (factory set at 20ms) 10mm2 (AWG8) minimum Hardwire terminals (Optional ~ plugs and receptacles) 120 volts ac, single phase Better than 2% from no load to full load 98% or higher Hardwire terminals (plugs and receptacles optional). Hardwired units must be installed by a qualified electrician. Green LED for primary ac presence, yellow LED for backup ac presence, flashing red LED for loss of primary or backup ac. Buzzer beeps when loss of primary or backup ac occurs. Audible alarm (buzzer) and enable/disable switch. A rear-mounted DB-9 connector sends loss of primary ac and loss of backup ac signal for external power status monitoring. 406mm (16) wide x 83mm (3.25)high x 305mm(12)deep 7kg (15 lbs) Front mount kits: For a 19 Rack: use # MK-5019A For a 23 Rack: use # MK-5023A For a 24 Rack: use # MK-5024A Center mount kits: For a 19 Rack: use # MK-5019F For a 23 Rack: use # MK-5023F For a 24 Rack: use # MK-5024F Wall or Floor mount kits: use # MK-5000C
0o to 40 oC (32 to 104F). 10 to 90% relative humidity (non-condensing).

Input
Nominal voltage Primary ac voltage Backup ac voltage Frequency range Over-current protection Circuit breaker ratings Typical transfer time Transfer time selection Input /output wire size Ac input

Automatic transfer switch

Output
Nominal voltage Load regulation Power efficiency Ac distribution

ATs rear view with knockout covers off ready to hardwire

Indicators Audible alarms Audible alarm switch Alarm contacts

Physical
Dimensions Weight Rack mount options

Knockout covers and cable glands for line cords shown


TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Environmental
Ambient temperature

Warranty
Warranty
circuit breaker 30 or 40A L L ground
L1 L2

Two year limited warranty, parts and labor.


ac output

primary ac input Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

L1 L2
solid-state relay #1

TSi Power Corporation

hardwire 120 vac +/- 20% backup ac input hardwire 120 vac +/- 20%

primary ac detection backup ac detection

power supply xxms logic delay alarm

120 vac

ground

circuit breaker 30 or 40A

solid-state relay # 2 DB9 alarm signals

ground

ATs system architecture

ATs-1000-120V-2006-10-16.pdf

ATs-1000E ~ 30/40A, 7.2/9.6kVA, 230vac


ATs Series Automatic Transfer Switch 19

ATs
Model
ATs-1000E
30 amps 7200 VA 7200 watts 230 volts

Two ac inputs ~ one ac output

Automatic transfer switch

Compact

Automatic Transfer Switch


TSi Powers ATs Series user customizable automatic transfer switches (ATS) are for enabling the use of redundant power sources, such as small uninterruptible power systems feeding industrial controls, PLC cabinets, internet servers, telecom systems, etc.

ATs-1000E-40A
40 amps 7200 VA 7200 watts 230 volts

Typical ATs applications


Designed for situations where reliability and predictability matter to the enterprise. Examples: telecommunications equipment, rectifiers, cell sites, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key ATs features


Enables redundant UPS, backup generators or other ac power sources to be used for a single load. Less than a 20ms transfer time from source A to source B. User selectable transfer times of 20ms, 40ms or 1 second. Built-in circuit breakers Designed to handle out-of-phase and/or asynchronous ac sources Rack-mountable LED status indicators DB9 communications interface Audible alarms with enable/disable switch
UPS #1 or other power source
mission critical

Key ATs benefits


If the ATs DIP Switch is set to Fast transfer (20ms typical transfer time) mode, then when redundant power sources are present, it can replace an expensive UPS system and battery banks for most computers, telecommunication, and industrial equipment (since switchmode power supplies used in most new electronics equipment provide a minimum of 20ms in capacitor hold-up time under full load conditions). If a positive power break is needed during the transfer, then the ATs may be set to Slow transfer (1 second) mode to ensure a full 1 second ac power outage during transfer. Also, the two ac sources do not have to be synchronized since the ATs is designed to switch between two asynchronous ac sources without damage to itself or to equipment powered by switchmode power supplies.

primary feed

How the ATs works


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

automatic transfer switch


backup feed

server or

TSi Power Corporation

The ATs is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, it immediately switches the load over to the backup power source feed in less than 20ms. Upon restoration of primary power, the ATs will switch back in less than 20ms. This is fast enough to be invisible to computer switch-mode power supplies.

telecom

UPS #2 or other power source

system

20

ATs Series ATs-1000E-30A/40A

ATs
Automatic transfer switch
Specifications

Specification
Electrical
Capacity in VA (watts) Switching technology

ATs-1000E (30A)
7200VA (7200W) maximum

ATs-1000E-40A
9600VA (9600W) maximum

Solid-state relays (SSRs)


230 volts ac single phase 200 to 270 volts ac 190 to 270 volts ac 47 to 63 Hz User resettable circuit breaker 30 amps 40 amps 20ms, 40ms or 1000ms (user selectable) Via a four position DIP switch ~ factory set at 20ms 10mm2 (AWG8) Hardwire terminals (plugs and receptacles optional - please call) 230 volts ac, single phase Better than 2% from no load to full load 98% or higher Hardwire terminals (plugs and receptacles optional). Hardwired units must be installed by a qualified electrician. Green LED for primary ac presence, yellow LED for backup ac presence, flashing red LED for loss of primary or backup ac. Buzzer beeps when loss of primary or backup ac occurs. Audible alarm (buzzer) and enable/disable switch. A rear-mounted DB-9 connector sends loss of primary ac and loss of backup ac signal for external power status monitoring. 406mm (16) wide x 83mm (3.25)high x 305mm(12)deep 7kg (15 lbs) Front mount kits: For a 19 Rack: use # MK-5019A For a 23 Rack: use # MK-5023A For a 24 Rack: use # MK-5024A Center mount kits: For a 19 Rack: use # MK-5019F For a 23 Rack: use # MK-5023F For a 24 Rack: use # MK-5024F Wall or Floor mount kits: use # MK-5000C
0o to 40 oC (32 to 104F). 10 to 90% Relative Humidity(non-condensing).

Input
Nominal voltage Primary ac voltage Backup ac voltage Frequency range Over-current protection Circuit breaker ratings Typical transfer time Transfer time selection Input /output wire size Ac input

Output
Nominal voltage Load regulation Power efficiency

ATs rear view with knockout covers off ready to hardwire

Ac distribution Indicators Audible alarms Audible alarm switch Alarm contacts

Physical
Dimensions Weight Rack mount options

Knockout covers and cable glands for line cords shown


TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Environmental
Ambient temperature

Warranty
Warranty
circuit breaker 30 or 40A

Two year limited warranty, parts and labor.

primary ac input

L1 L2

L1 L2 primary ac
Detection power supply logic
xxms Delay

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Hardwire 230vac

solid-state relay #1

Ground

backup ac
Detection

230vac ac output

backup ac input
hardwire 230vac

L1 L2
ground
circuit breaker 30 or 40A

alarm

solid-state relay # 2 DB9 alarm signals

ground

ATs system architecture

ATs-1000E-230V-2006-10-16.pdf

EXt Series ~ Battery Extension Units


EXt Series Battery Extension Cabinets 21

EXt
EXt Series Battery extension cabinets

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

22

EXt Series Battery Extension Cabinets

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

EXt-Series-2006-10-16.pdf

EXt-8000 ~ 120vac input, 24vdc output

EXt
EXt model 8000
120vac input 24vdc ouput

EXt Series Battery Extension Cabinet

23

Built-in battery chargers

Battery extension cabinets for TSi UPs

Battery Extension Cabinet for UPs-10000/16000/21000


The modular TSI Power Battery Extension Unit is designed to provide extended back-up for use with TSI's UPs-10000, 16000 and 21000 systems.

Typical applications
Sometimes power goes out for hours and a standard five or ten minute reserve just won't do. Longer hold-up times may be needed for users that upload/download large files on the Internet, or the following applications: extensive accounting or engineering programs, point-of-sale systems, control systems, portable medical systems, inventory control systems, as well as telecom systems that need to be up all the time.

Key features of the EXt-8000


120 vac input Two or more units can be daisy-chained for back-up of 8 hours or more Rack-mountable profile Rack-mounting kits Internal battery charger provides recharge in less than 6 hours 48 vdc bus voltage Low cost Two year limited warranty

Key benefits
EXt-8000 units can be daisy-chained to provide hold-up times of eight hours or more depending on the number of EXt-8000 units and the load it powers. EXt-8000 can be rack-mounted and several different mounting kits are available. EXt-8000 can also be mounted on a movable cart together with a TSi UPS to provide long-term back-up while moving equipment from location to location.

How the EXt-8000 works


Each EXt-8000 contains its own battery charger, which keeps typical recharge time to 6 hours or less. This feature is extremely important as extension modules containing only batteries have to be recharged from the UPS's internal charger recharge can take several days for large batteries, which may result in back-up not being available when needed the most.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

A TSi UPs-16000 and EXt-8000 Battery extension unit shown mounted inside a 19 wide cabinet using MK-8019A and MK-8019B Front and Rear rack-mount kits

24

Specifications EXt-8000

EXt
Battery extension cabinet
Specifications

Specification
AC Input
Input Input cord and plug

EXt-8000 (for 120vac UPs-10000/16000/21000)


100 to 133VRMS ac, 60Hz 6 feet (1.8 m) three-conductor 14 AWG SJT cord with NEMA 5-15P plug Supplies an additional 35 to 45 minutes backup time, depending on load. 54vdc, 3A 4 to 6 hours typical recharge time( 48vdc, 14 Ah ) 48vdc Anderson PP 50 male/female low-voltage connectors 150 watts during charging 432mm(17")wide x 533mm(21")deep x 127 mm(5)high 32 kg (70 lbs)
0 to 40 oC(32 to 104F). 10 to 90% Relative humidity(non-condensing).

Battery charger/output
Back-up time Battery charger Battery recharge time Battery bus voltage Battery connectors Power consumption

Physical
Size Weight

Environment
Ambient temperature

Warranty
Warranty Two year limited warranty, parts and labor. One year battery warranty. Please call factory for assistance on rack-mount options. 120vac UPs-10000, UPs-16000 and UPs-21000
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Rack-mount options
Rack mount kits

UPS compatibility
Designed for use with:

Front view of EXt-8000

Rear view of UPs-10000

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Rear view of EXt-8000 middle unit

UPs-10000 with four EXt-8000

Rear view of EXt-8000 end unit

EXt-8000-120V-2006-10-16.pdf

FLc Series ~ Ferroresonant Isolation Transformer Line Conditioners


FLc Series Ferroresonant Transformer Line Conditioner 25

FLc
Ferroresonant transformer line conditioners

FLc Series

Power with a Precision Attitude

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

26

FLc Series Ferroresonant Line Conditioner

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

FLc-Series-2006-10-16.pdf

FLc-750/1000/1500 ~ 6.3/8.3/12A, 750VA/1/1.5kVA, 120vac

FLc
FLc model 750
6.3 amps 750 VA 750 watts 120 volts

FLc Series Ferroresonant Isolation Transformer Line Conditioner

27

Ferroresonant transformer

Voltage regulation

UL/cUL listed

Ferroresonant Constant Voltage Output Isolation Transformer Line Conditioner


To provide isolated constant output voltage and stable power, even when the incoming ac mains or generator set voltage is extremely low or high.

1000
8.3 amps 1000 VA 1000 watts 120 volts

Typical applications
FLc Series line conditioners are suitable where you want the ultimate in industrial-strength ac line protection for computers, point-of-sale terminals, copiers, data acquisition and control systems, as well as other data processing equipment. The FLc Series is recommended for use with a stable load and input frequency, and where audible noise and heat are of less concern.

1500
12.5 amps 1500 VA 1500 watts 120 volts

Key benefits
The FLc Series constant voltage regulated output protects switch-mode power supplies from failure caused by unstable ac mains. FLc provides a combination of isolation and constant output voltage transformer technology, which makes it an ideal device to replace a dedicated circuit when cost of installing same is prohibitive. Highest grade ac power can be obtained even when the mains contain high noise and/or harmonics. FLc provides three stage surge protection and significant reduction of surge voltage dV/dt rise times. The FLc internal transformer draws only sinewave current, which helps to reduce harmonics in supplied loads. The FLc line conditioner can be used between a UPS and the ac mains to provide greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.

Key features of the TSi Power ferroresonant line conditioner


Constant output voltage guaranteed Ferroresonant isolation transformer with neutral-to-ground bond. Coordinated surge protection per IEC61312.3 Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/S Front panel power switch Replaces dedicated ac circuit Reduces harmonics from non-linear loads The best surge protection available Five year warranty

How the FLc Series works


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

FLc incorporates a constant voltage output ferroresonant isolation transformer, which provides 100% isolation from the input ac line. The secondary neutral is bonded to ground thus eliminating all surge voltages between neutral and ground. Surge protection is further enhanced due to the built-in low-pass filter, which reduces fast-rise transients from 6kV/s to less than 10V/s.

Power with a Precision Attitude

28

FLc

Specifications FLc-750/1000/1500

Specification
Electrical
Capacity in VA (watts) Transformer Type

FLc-750
750VA (750W)

FLc-1000
1000VA (1000W)

FLc-1500
1500VA (1500W)

Ferroresonant line conditioner

Constant voltage output ferroresonant isolation transformer. 120 volts ac 80 to 145 volts ac 60Hz NEMA 5-15R plug NEMA 5-15R plug 120 volts ac +/-3% Output wave form: sine wave, regardless of input for 60Hz +/-3% Low-pass filter reduces noise over a wide frequency range. The measured rate of voltage rise/fall (dV/dt of the remnant waveform is less than 200V/S with input test waveform dV/dt of 6kV/S. Three-way surge protection system. Per ANSI/IEEE C62.41-1991 test pulse, Category B3, Combination Wave, 6000V, 3000A. Test pulse injection: Line-neutral, line-ground, and neutral-ground. Remnant voltage: L-N: 5V, L-G: 5V, N-G: 0.5V. 90% or higher for full load conditions. 80% typical for half load conditions. Master on/off rocker power switch control. Six (NEMA 5-15R). Optional terminal blocks for OEMs. 235mm(9.25)wide x 165mm(6.5)high x 330mm(13.0)deep 25 kg(55 lbs) 27.2 kg(60 lbs) UL and cUL 1950 Listed
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Input
Nominal voltage Operating voltage Nominal frequency Ac 6 ft. input cord with

Specifications

NEMA 5-20R plug

Output
Ac output voltage Waveform Noise filtering

Rear view FLc-1500

Surge protection Surge test conditions

Surge let-through voltages Power efficiency Power on/off switch Ac output receptacles

Physical
Dimensions Weight 27.2 kg(60 lbs)

Safety
Agency approvals

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

FLc Series system architecture


80 - 145 V

ac input

120 V +/- 3%

hot fuse ground surge protection and EMI / RFI noise filter

ac output hot

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

neutral

neutral

constant voltage output ferroresonant isolation transformer

ground

FLc-750-1000-1500-2006-10-16.pdf

ILc Series ~ Low-Impedance Isolation Transformer Line Conditioners


ILc Series Isolation Line Conditioner 29

ILc
Isolation transformer line conditioners

ILc Series

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

30

ILc Series Isolation Line Conditioner

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ILc-Series-2006-10-16.pdf

ILc-600B/1000B ~ 5/ 8.3A, 600/1kVA, 120vac

ILc
ILc model 600B
5 amps 600 VA 600 watts 120 volts

ILc Series Isolation Transformer Line Conditioner

31

Low-impedance

Isolation transformer

UL/cUL listed

Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

1000B
8.3 amps 1000 VA 1000 watts 120 volts

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key features of the TSi Power isolation line conditioner


Coordinated surge protection per IEC 61312.3 Low-impedance isolation transformer True isolation Common-mode noise elimination Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/S High efficiency Four ac outlets Low weight Quiet operation Five year warranty

Key benefits
ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.

How ILc conditioners work


The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC 61312.3

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

32

Specifications ILc-600B/1000B

ILc
Isolation line conditioner
Specifications

Specification
Electrical
Capacity in VA (Watts) Transformer type

ILc-600B
600VA (600W)

ILc-1000B
1000VA (1000W)

Low-impedance E-I core isolation transformer 120 volts ac single phase 100 to 130 volts ac 60 Hz +/-3 User resettable circuit breaker 5 amps 10 amps 6 foot long ac power cord with NEMA 5-15P plug 120 volts ac single phase 94% (typical) < 1% A three-stage surge protection system consisting of isolation transformer, capacitor and M.O.V. is included. Per ANSI/IEEE C62.41-1991 test waveforms Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. Four (NEMA 5-15R.) 152mm (6) wide x 127mm (5)high x 229mm(9)deep 11.3kg (25 lbs) UL and cUL listed
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Input
Nominal voltage Operating voltage Nominal frequency Over-current protection Circuit breaker rating Ac input cord

Output
Nominal voltage Power efficiency
Total harmonic distortion

Rear view ILc-1000B shown without 6 line cord/plug

Surge protection Surge test conditions Surge let-through voltages

Ac output receptacles

Physical
Dimensions Weight 15kg (33 lbs)

Safety
Agency approvals

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

ILc system architecture


ac input hot ground
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

isolation transformer
circuit breaker surge protection and EMI / RFI noise filter

ILc output hot neutral

TSi Power Corporation

neutral

ground

ILc-600B-1000B-2006-10-16.pdf

ILc-1800 / 2000 ~ 15/16A, 1.8/2kVA, 120vac

ILc
ILc model 1800
15 amps 1800 VA 1800 watts 120 volts

ILc Series Isolation Transformer Line Conditioner

33

Low-impedance

Isolation transformer

UL/cUL listed

Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

2000
16 amps 2000 VA 2000 watts 120 volts

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key features of the TSi Power isolation line conditioner


Coordinated surge protection per IEC61312.3 Low-impedance isolation transformer True isolation Common-mode noise elimination Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/S High efficiency Six ac outlets On/off rocker switch Low weight Quiet operation Five year warranty

Key benefits
ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.

How ILc conditioners work


The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a TSi Power Corporation capacitive element and an MOV, provide superb Represented by noise filtering, as well as coordinated multi-stage CareBase surge protection in accordance with the Michael Gibson principles of IEC-61312.3. Post Office Box 2987
Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

34

ILc Series ILc-1800/2000

ILc
Isolation line conditioner
Specifications

Specification
Electrical
Capacity in VA (watts) Transformer type

ILc-1800
1800VA (1800W)

ILc-2000
2000VA (2000W)

Low-impedance E-I core isolation transformer 120 volts ac, single phase 100 to 130 volts ac 60Hz +/-3 User resettable circuit breaker built-in 15 amps 6 foot cord with 5-15P plug 20 amps 6 foot cord with 5-20P plug

Input
Nominal voltage Operating voltage Nominal frequency Over-current protection Circuit breaker rating Ac input cord

Output
Nominal voltage Power efficiency Total harmonic distortion Surge protection Surge test conditions Surge let-through voltages 120 volts ac, single phase 95 to 97% (typical) < 1% A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Per ANSI/IEEE C62.41-1991 test waveforms Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5 V Ring wave: L-N: 20 V, L-G: 20 V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. Green LED indicates ac power is present On/off rocker style switch Six NEMA 5-15R Six NEMA 5-20R

Rear view ILc-1800

Indicators On/off switch Ac Receptacles

Physical
Dimensions Weight 216mm(8.5)wide x 165mm(6.5)high x 279mm(11.0)deep 22.7 kg(50 lbs) UL and cUL listed.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

22.7 kg(50 lbs)

Safety
Agency approvals

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

ILc system architecture


ac input TSi Power Corporation hot ground circuit breaker isolation transformer surge protection and EMI / RFI noise filter ILc output hot neutral

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

neutral

ground

ILc-1800-2000-2006-10-16.pdf

ILc-2400/3600 ~ 20/30A, 2.4 /3.6kVA, 120vac


ILc Series Isolation Transformer Line Conditioner 35

ILc
ILc model 2400
20 amps 2400 VA 2400 watts 120 volts

Low-impedance

Isolation transformer

3 stage protection

Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection/filtering devices.

3600
30 amps 3600 VA 3600 watts 120 volts

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key ILc benefits


ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.

Key features of the TSi Power isolation line conditioner


Coordinated multi-stage surge suppression Low-impedance isolation transformer True isolation
Common-mode noise elimination

How ILc conditioners work


The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.

Advanced noise and interference filter reduces dV/dt from 6kV/ S to less than 10V/ S High efficiency On/off rocker style power switch Low weight Quiet operation Five year warranty

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

36

ILc

Specifications ILc-2400-3600

Specification
Electrical
Capacity in VA (watts) Transformer type

ILc-2400
2400VA (2400W)

ILc-3600
3600VA (3600W)

Isolation line conditioner

Low-impedance E-I core isolation transformer 120 volts ac single phase 100 to 130 volts ac 60 Hz +/-3 20 amps NEMA 5-30 plug 120 volts ac, single phase 97% (typical) <1% A three-stage surge protection system consisting of isolation transformer, capacitor and M.O.V. is included. Per ANSI/IEEE C62.41-1991 test waveforms Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. On/off rocker style power switch/circuit breaker Green LED indicates ac power is present Four NEMA 5-20R and four NEMA 5-15R _ Four NEMA 5-20R and four NEMA 5-15R 30 amps ( Specify )

Input
Nominal voltage Operating voltage Nominal frequency Circuit breaker rating 6 foot ac input cord with

Specifications

Output
Nominal voltage Power efficiency

Total harmonic distortion Surge protection

Rear view

Surge test conditions Surge let-through voltages

Power on/off Indicators Ac output receptacles


(Other options available)

Physical
Dimensions Weight 254mm(10)wide x 190mm(7.5)high x 368mm(14.5)deep 27.3 kg(60 lbs) 36.3 kg(80 lbs)

Safety
Agency approvals Over-current protection Designed to meet UL, cUL and IEC standards. User resettable circuit breaker.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

ILc system architecture


ac input TSi Power Corporation hot ground circuit breaker isolation Transformer surge protection and EMI / RFI noise filter ILc output hot neutral

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

neutral

ground

ILc-2400-3600-120V-2006-10-16.pdf

ILc-2400/3600-230V ~ 10/15A, 2.4/ 3.6kVA, 208/220/230 or 240vac


ILc Series Isolation Transformer Line Conditioner 37

ILc
ILc model 2400-230V
10 amps 2400 VA 2400 watts 208/220, 230/240 volts

Low-impedance

Isolation transformer

3 stage protection

Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection/filtering devices.

3600-230V
15 amps 3600 VA 3600 watts 208/220, 230/240 volts

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key benefits
ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.

Key features of the ILc series isolation line conditioner


Coordinated multi-stage surge suppression Low-impedance isolation transformer True isolation
Common-mode noise elimination

How ILc conditioners work


The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.

Advanced noise and interference filter reduces dV/dt from 6kV/ S to less than 10V/ S High efficiency On/off rocker style power switch Low weight Quiet operation Five year warranty

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

38

Specifications ILc-2400/3600-230V

ILc

Specification
Electrical
Capacity in VA (watts) Transformer type

ILc-2400-230V
2400VA (2400W)

ILc-3600-230V
3600VA (3600W)

Isolation transformer line conditioner

Low-impedance E-I core isolation transformer 208/220/230 or 240 volts ac, single phase 190 to 250 volts ac 60Hz +/-3 15 amps 20 amps Hardwire (terminal block connector) 208/220/230 or 240 volts ac, single phase 97% (typical) <1% A three-stage surge protection system consisting of isolation transformer, capacitor and M.O.V. is included. Per ANSI/IEEE C62.41-1991 test waveforms Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. On/off rocker style power switch/circuit breaker Green LED indicates ac power is present Hardwired output terminals (L1, Neutral, and Ground) are standard. Optional ac receptacles are available. 254mm(10)wide x 190mm(7.5)high x 368mm(14.5)deep 27.3 kg(60 lbs) 36.3 kg(80 lbs)

Input
Nominal voltage Operating voltage Nominal frequency Circuit breaker rating 6 foot ac input cord with

Specifications

Output
Nominal voltage Power efficiency

Total harmonic distortion Surge protection

Rear view with optional receptacles

Surge test conditions Surge let-through voltages

Power on/off Indicators Ac output receptacles


(Other options available)

Physical
Dimensions Weight

Safety
Agency approvals Over-current protection Designed to meet UL, cUL standards User resettable circuit breaker
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

ILc system architecture


ac input TSi Power Corporation hot circuit breaker

isolation transformer
surge protection and EMI / RFI noise filter

hot

ILc output

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

ground

neutral

208, 220, 230, or 240V

208, 220, 230, 240V

neutral

ground

ILc-2400-3600-230V-2006-10-16.pdf

ILc-4400/5500-230V ~ 19/24A, 4.4/5.5kVA, 208/220/230 or 240vac

ILc
ILc model 4400-230V
19 amps 4400 VA 4400 watts 208/220, 230/240 volts

ILc Series Isolation Transformer Line Conditioner

39

Low-impedance

Isolation transformer

3 stage protection

Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line. The secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection/filtering devices.

5500-230V
24 amps 5500 VA 5500 watts 208/220, 230/240 Volts

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key benefits
ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.

Key features of the TSi Power isolation line conditioner


Coordinated multi-stage surge suppression Low-impedance isolation transformer True isolation
Common-mode noise elimination

How ILc conditioners work


The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3.

Advanced noise and interference filter reduces dV/dt from 6kV/ S to less than 10V/ S High efficiency On/off rocker style power switch Low weight Quiet operation Five year warranty

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

40

ILc

Specifications ILc-4400/5500-230V

Specifications Specification
Electrical
Capacity in VA (watts) Transformer type 4400VA (2400W) 5500VA (5500W) Low-impedance E-I core isolation transformer 208/220/230 or 240 volts ac, single phase 190 to 250 volts ac 60 Hz +/-3 25 amps 30 amps Hardwire (terminal block connector) 208/220/230 or 240 volts ac, single phase 97% (typical) <1% A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Per ANSI/IEEE C62.41-1991 test waveforms. Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. On/off rocker style power switch/circuit breaker. Green LED indicates ac power is present. Hardwired output terminals (L1, neutral, and ground) are standard. Optional ac receptacles are available. 254mm(10)wide x 190mm(7.5)high x 368mm(14.5)deep 43.56 kg(100 lbs) 54.6 kg(120 lbs)

ILc-4400

ILc-5500

Isolation transformer line conditioner

Input
Nominal voltage Operating voltage Nominal frequency Circuit breaker rating Ac input

Output
Nominal voltage Power efficiency

Total harmonic distortion Surge protection

Rear view with optional receptacles

Surge test conditions Surge let-through voltages

Power on/off Indicators Ac output

Physical
Dimensions Weight

Safety
Agency approvals Over-current protection Designed to meet UL, cUL standards. User resettable circuit breaker.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

ILc system architecture


ac input TSi Power Corporation hot circuit breaker

isolation transformer
surge protection and EMI / RFI noise filter

hot

ILc output

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

ground

neutral

208, 220, 230, or 240V

208, 220, 230, 240V

neutral

ground

ILc-4400-5500-230V-2006-10-16.pdf

ILc-9000/16500-0338 ~ 9/16.6kVA, 9/16.6kW, 400V delta in, 230/400V wye out

ILc
ILc model
9000-0338
9 kVA 9 kW 400V delta 3 phase input 230/400V wye 3 phase output

ILc Series Isolation Transformer Line Conditioner

41

International

Isolation transformer

3 stage protection

Three Phase Low-Impedance Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioners provide the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

16500-0338
16.5 kVA 16.5 kW 400V delta 3 phase input 230/400V wye 3 phase output

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: sensitive telecommunications industrial and medical equipment, and other sensitive, specialized microprocessor-based equipment.

Key benefits
ILc Series conditioners provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups. In addition, a reduction in equipment down time and service costs can be expected. TSis use of three separate transformers, one per phase, minimizes single phasing or lost phase problems associated with a common core three phase transformer.

Key features of the TSi isolation line conditioner


Coordinated surge protection per IEC61312 Three separate low-impedance isolation transformers (1 per phase) are used for maximum reliability
Common-mode noise elimination

How ILc conditioners work


The integral isolation transformers provide complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformer in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/ S Wall-fixing kit included High efficiency Quiet operation Five year warranty

42

Specifications ILc-9000-16500-0338

ILc

Specification
Electrical
Capacity in VA (watts) Transformer type

ILc-9000-0338
9 kVA (9,000W)

ILc-16500-0338
16.5 kVA (16,500W)

Specifications

Isolation line conditioner

Three separate isolation transformers are used (1 per phase) 400 volts ac three phase delta 400V(L-L), +30%,-20% 50 Hz +/-3 3 x 30 amps (ganged) 3 x 40 amps (ganged) Terminal block (L1, L2, L3 and ground wires) provided. 230/400 volts ac three phase wye 96% at 400V(L-L), (typical) 230/400 volts +30%,-20% VRp-9000-0338 VRp-16500-0338 A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Class 2 and Class 3 simulated lightning surge (Combination wave) Per ANSI/IEEE C62.41-1991, Cat.C test waveform: 6kV, 3kA, 8x20S. *Note: ILc is not a Primary (Class 1) surge arrestor - customer must provide a separate primary surge arrestor at service entry point. Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Terminal block (L1, L2, L3, neutral and ground wires) provided. 610mm(24)W x 965mm(38)H x 305mm(12)D. Rubber mounting feet. 140kg(309 lbs) 170kg (375 lbs)

Input
Nominal voltage Operating range Nominal frequency Input circuit breakers Ac connections

Output
Nominal voltage Power efficiency Operating range Matching AVR Surge protection Surge test conditions*

Left-side front view

Surge let-through voltages

Common mode filtering Normal mode filtering Ac connections

Physical
Dimensions Weight

Safety
Standards
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Designed to meet IEC 60950. Enclosure protection class: IP20.


-5 to +35C (23 to 95F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature Cooling method Fan cooled. Five year limited warranty, parts and labor.

Warranty
Warranty

ac input TSi Power Corporation

hot ground circuit breaker

isolation transformer surge protection and EMI / RFI noise filter

ILc output
(per phase)

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

hot neutral

neutral

ILc system architecture (per phase)

ground

ILc-9000-16500-0338-3Ph-2006-10-16.pdf

ILc-15000-0232 ~ 15kVA, 80A, 208vac, single phase

ILc
Model ILc-15000-0232
80 amps 15 kW 15 kVA 208 volts Single phase

ILc Series Isolation Transformer Line Conditioner

43

Low-impedance

Isolation transformer

Line conditioner

Low-Impedance Isolation Transformer Line Conditioner


TSi Powers ILc Series line conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection & filtering devices.

Typical applications
Designed for situations where reliability and predictability matter to the enterprise. Examples include: telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key benefits
ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. In addition, a reduction in equipment down time and service costs can be expected.

Key features
Coordinated surge protection per IEC 61312 Low-impedance isolation transformer True isolation
Common-mode noise elimination

How the ILc-15000 works


This ILc line conditioner utilizes a low-impedance transformer, capacitors and ultra-fast Metal Oxide Varistors (MOVs) in an optimized 3-way noise filtering and IEC 61312 compliant surge protection design to provide maximum protection of sensitive industrial and telecommunications equipment against harmful surges, spikes and noise produced by lightning strikes, utility grid switching and heavy machinery turn on and off cycles. The neutral-ground bond at the output winding of the transformer also provides maximum protection against the harmful effects of stray voltage and/or noise on the neutral conductor.

Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/S High efficiency Input circuit breaker Low weight Quiet operation Five year warranty

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

44

ILc

Specifications ILc-15000-0232

Specifications Specification
Electrical
Capacity in VA (watts) Transformer technology 15kVA (15kW) Low-impedance isolation transformer 208 volts ac, single phase 190 to 240 volts ac 47 to 63Hz 80A Two pole, 90A circuit breaker is included. 0.3 leading to 0.3 lagging 208 volts ac, single phase Better than +/-2% 95% (typical) Tightly coupled isolation transformer winding provides compatibility with switchmode power supplies and SCR controlled devices. Qualifies as a separately derived ac power source per NEC 250-5D. A three-stage surge protection system forms a hybrid filter recommended by IEC 61312 (coordination of surge protective devices). Filter consists of an isolation transformer, capacitors and MOVs. Per ANSI/IEEE C62.41-1991 single pulse, ring and combination wave. (Category C test waveforms: 6000V, 3000A, 8x20 S). Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V
The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is <10V/S w/input test waveform dV/dt of 6kV/S. (600:1 reduction ratio).

ILc-15000-0232

Input Rating
Nominal voltage Operating input voltage Nominal frequency Maximum input current Input circuit breaker Operating displacement power factor

Output Rating
Nominal output voltage Load regulation Power efficiency Load power factor Ac output quality Surge protection

Surge test conditions Surge test results (remnant voltages)


TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies. These units are for indoor use only. Note: Unit ships on a wooden pallet for ease of shipping and handling.

Reduction in rate of voltage rise/fall (dv/dt) Common mode noise filtering Normal mode noise filtering

Neutral-to-ground bond eliminates all noise or voltage on output neutral. A built-in inductor-capacitor filter attenuates EMI/RFI noise from the output. Hard-wired (terminal blocks). 610mm(24) wide x 710mm(28)high x 560mm(22)deep. Powder-painted. Weight is approx. 181kg (400 lbs).
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Mechanical
Input / output connection Dimensions Finish and weight

Environmental and Warranty


Ambient temperature Heat loss and cooling Warranty (expected life) At 80% load, heat loss is approx. 850 BTU/hr. Convection cooled. Five year limited warranty, parts and labor. (twenty years).

ILc system architecture


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ac input

L1 ground

isolation transformer surge protection and EMI / RFI noise filter

ILc output hot 208 vac ground

208 vac

L2

circuit breaker

neutral ground ILc-15000-0232-2006-10-16.pdf

ILc-Med Series ~ Medical Isolation Transformers


ILc-Med Series Medical Isolation Transformer 45

ILc-Med
ILc-Med Series Medical isolation transformers

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

46

ILc-Med Series Medical Isolation Transformer

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ILc-Med-Series-2006-10-16.pdf

ILc-1000/1400Med4 ~ 8.3/ 11.7A, 1/ 1.4kVA, 120vac


ILc-Med Series Medical Isolation Transformer 47

ILc-Med
ILc-Med model 1000Med4
8.3 amps 1000 VA 1000 watts 120 volts

Hospital-grade

Isolation transformer

UL/cUL 60601-1

Hospital Grade UL/cUL 60601-1 Medical Isolation Transformer


TSi Powers ILc-Med line conditioners provide the best all-round hospital-grade 'low-leakage current' line conditioning and surge protection for sensitive medical equipment. The integral isolation transformer provides 100% isolation from the input ac line, the secondary neutralground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

1400Med4
11.7 amps 1400 VA 1400 watts 120 volts

Key ILc-Med benefits


TSi Powers hospital- grade line conditioner reduces the need for a high quality isolated and dedicated line, while eliminating interference from adjacent sources of disturbances. ILc-Med contributes to enhanced systems operation, greater reliability, improved repeatability, fewer reboots and system lock-ups and extended operating life. Reductions in hospital equipment down time and service costs can be expected.

Key features of the TSi Power medical isolation transformer


Typical leakage current <50A UL/cUL 60601-1 listed Low-impedance isolation transformer Coordinated surge protection per IEC61312.3 Filtering and MOVs Resettable circuit breaker Eight green dot medical grade outlets/receptacles High efficiency 100% common mode noise elimination True isolation Quiet operation Five year warranty

How ILc-Med conditioners work


The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.3. In addition, ILc-Med has an extremely low input ac leakage current (typical 50A) rating which exceeds both domestic US (UL 60601-1), and international (IEC 601) medical standards for a leakage current limit of 300A maximum for non-patient connected medical equipment and instruments.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Typical ILc-Med applications


These are designed for medical systems requiring line conditioners having UL 60601-1 (formerly UL 2601 and UL 544) agency approval. Examples include: imaging systems, analyzers, patient care/ monitoring equipment, audio systems and other patient-critical applications.

48

Specifications ILc-1000Med4/1400Med4

ILc-Med

Specification
Electrical
Capacity in VA (watts) Transformer type

ILc-1000Med4
1000VA (1000W)

ILc-1400Med4
1400VA (1400W)

Hospital-grade low-leakage E-I core isolation transformer 120 volts ac, single phase 100 to 130 volts ac 60Hz +/-5% 50 A typical (300 A maximum) User resettable circuit breaker 10 amperes 15 amperes 15 foot long hospital-grade ac power cord with NEMA 5-15P plug 120 volts ac, single phase 94 to 96% < 1% A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Per ANSI/IEEE C62.41-1991 test waveforms Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5 V Ring wave: L-N: 20 V, L-G: 20 V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. Eight hospital-grade green dot NEMA 5-15R receptacles. 190mmW x 133mmH x 229mmD (7.5 W x 5.25H x 9.0D) 29 lbs (13.2kg) 216W x 165H x 229mmD (8.5 W x 6.5H x 9.0D) 49 lbs (22.3kg)

Input
Nominal voltage Operating voltage Nominal frequency Leakage current Over-current protection Circuit breaker rating Ac input cord

Rear view ILc-1000Med4

Output
Nominal voltage Power efficiency Total harmonic distortion Surge protection Surge test conditions Surge let-through voltages

Rear view ILc-1400Med4

Ac output receptacles

Physical
Dimensions Weight

Safety
Agency approvals UL/cUL 60601-1 listed (formerly UL 2601). UL control number 85EF.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

ILc-Med system architecture


ac input TSi Power Corporation hot ground circuit breaker isolation transformer surge protection and EMI / RFI noise filter ILc-Med output hot neutral

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

neutral

ground

ILc-1000-1400Med4-120V-2006-10-16.pdf

Outdoor Series ~ UPS, Precision AVR and Line Conditioners


Outdoor UPs Series Outdoor Uninterruptible Power Systems 49

Outdoor
Outdoor Series UPS, AVR and line conditioners

*Please note that the UPs-400Wtb, though it has wide temperature batteries and is often used in OEM outdoor enclosures, does not have its own outdoor enclosure, so is found in the UPS section. And, the OEM XUPS units, designed for wide temperature environments, are also suitable for use inside outdoor enclosures, and are found in the UPS section.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

50

Outdoor UPs Series Outdoor Uninterruptible Power Systems

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Outdoor-Series-2006-10-16.pdf

OutdoorXUPs-600-6339 ~ 600VA, 480W, 120vac, UPS+AVR, Pole-mountable


Outdoor XUPs Series Outdoor Uninterruptible Power System 51

Outdoor

XUPs
600 VA 480 watts 120/240V input 120V output 40 min @480W -20 to +60C; -40 to +60C with optional battery heater

Pure sine wave

Wide temperature batteries

Voltage regulation

Outdoor XUPs and EXt model

Outdoor UPS with Voltage Regulation


with extreme wide temperature batteries, and is housed in a weather protected IP44(NEMA-3R) enclosure designed to be mounted on a power pole and blend in with the environment. This unit offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with noise filtering, communications capability, maintenance bypass switch and options of automatic bypass switch, extended battery backup, and hotel capability for OEMs.

XUPs-600-6339 The XUPs-600-6339 outdoor UPS is constructed

EXt-6369
For 600 VA, or 480 watts load, adds 80 min @480W -20 to +60C; -40 to +60C with optional battery heater

Key Outdoor XUPs benefits


This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. Battery run-times for the outdoor XUPs-600-6339 are approximately 40 minutes at 480 watts load; the optional EXt-6369 provides an additional 80 minutes.

Typical applications
This heavy duty outdoor UPS is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial RTUs.

Key Outdoor XUPs features


Cabinet and color are designed for pole mounting and blending in with the environment Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Over/under-voltage protection Built-in maintenance bypass. Automatic static bypass (optional) Wide temperature batteries Surge protection and noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics Manufacturers battery warranty

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac per leg. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. Optional automatic bypass switches to bypass in case of UPS failure, and may be used to enable some maintenance without loss of power to the load. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators, a convenience outlet, maintenance bypass switch, circuit breakers, and a power on/off switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

52

Specifications XUPs-600-6339

Outdoor

Specifications
Electrical
Capacity in VA (watts) UPS topology

XUPs-600-6339
600VA (480W maximum output) High efficiency line-interactive with 15kHz PWM sine wave inverter. 120/240vac, split phase, L1, L2, N & Ground with 2 pole circuit breaker UPS: 5A @ 120vac. Convenience outlet: 15A @ 120vac. 95 to 140vac (within which UPS will not have to use batteries). 47 to 63Hz. Unit can be combined with utility type meter can if required, and internal provision for NG bond is available when used for main service. Four (4) position terminal blocks provided for four (4) x 1.5mm2 (16AWG) connections via 25mm(1) liquid-tight cable glands. 120 volts ac 115 vac +/- 8% upon changes in line or load 3:1 Pure sine wave, less than 3% THD with linear load 97%, under full load conditions On/off rocker style power switch <4 milliseconds Two 32 amp hours, 12 vdc wide temperature sealed gel-cells rated for -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 40 minutes @ 480 watts load. 2 hours @ 240 watts load. 8 hours to 90% capacity after full discharge. Optional matching size EXt-6369 extra battery cabinet available with SB50 connector. Provides extra four 12vdc, 32Ah wide temperature batteries for an extra 80 minutes of run-time @ 480W load. 24 hours to 90% capacity after full discharge. Weight: 55kg(120 lbs). Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (for TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-Neutral: Line-Ground: and Neutral-Ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LEDs for load level: 0 to 100% of rated load. 5 LEDs for battery charge level: from 0 to 100% of rated charge. 3 LEDs for: in boost, buck or normal mode. 3 LEDs for: inverter on/off, battery fault and overload. Two (2) switched UPS output circuits for a combined maximum 4A, and one (1) switched 15A convenience outlet. Includes built-in maintenance bypass switch. Optional static bypass switch (automatic redundancy module) available in case of UPS failure. 508mm(20)high x 406mm(16)wide x 203mm(8)deep 45kg(100 lbs) Full weather IP44(NEMA-3R) outdoor design in gray color. Pole mountable (steel bands optional for steel monopole mounting), pedestal (ground) or wall mountable. H style bracket included. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater.

XUPs

Input
Nominal voltage Input current maximum UPS operating voltage Frequency Main electric service connect capability Hardwire connection

Output

Outdoor lineinteractive UPS with automatic voltage regulation, maintenance bypass and wide temperature batteries

Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

Battery backup time and recharge time Optional extra battery pack(s) for longer backup time (heater optional) SNMP interface for UPS monitoring and automatic shutdown configuration (optional)
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Surge let-through voltages Status indicators

Output connections Maintenance bypass and optional ARm unit

Physical
Dimensions
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Weight Steel cabinet Mounting options

Environmental
Operating temperature, battery heater option

Outdoor XUPs Series Outdoor Uninterruptible Power System

53

bottom inside view

one size of OEM hotel area internal status LED panel

Outdoor

XUPs

top inside view

input terminal blocks

input breaker, 2 switched UPS output circuits; and one 15A convenience outlet

XUPs-600-6339 system architecture


120 / 240V split phase input 2-pole circuit breaker L1 ac surge earth ground chassis neutral L2 switch A optional heater maintenance bypass switch
+10% 0% -10%

relay 1 battery and charger dc ac

L1

protection, noise filter and overvoltage, undervoltage disconnect circuits


terminal block optional heater connect

relay 2 ARm auto bypass unit


(optional)

logic

neutral

inverter

DB9 comm port

EXt-6369 extra battery cabinet (optional)

neutral switch B switch C L1 neutral L1 115vac +/-8% regulated output

15A convenience outlet

XUPs-600-6339 at a glance
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater 40 minutes @ 480 watts load 120 minutes @ 480 watts load with the addition of an EXt-6369 115vac +/-8% output from 95 to 140vac input without going to batteries Microprocessor-controlled 15kHz PWM sine wave inverter Built-in bypass switch for UPS maintenance. Optional automatic bypass in case of UPS failure

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

54

Outdoor XUPs Series XUPs-600-6339

Outdoor

XUPs

Mounting on a pole with steel bands or bolts


Following are two pictures showing the H style mounting bracket on the rear of the Outdoor XUPs Series unit. This bracket facilitates mounting to a standard pole via the two bolt holes in the center U channel, or to a steel monopole with optional steel bands through the two sets of steel band slots in the sides of the U channel. The Outdoor XUPs cabinet (or OutdoorEXt cabinet) is mounted to the H style bracket with four (4) mounting feet at the four (4) corners. 19mm (.75) For detailed information on the optional steel bands, please call.
19mm (.75)

Mounting feet close-up drawing

508mm (20)

holes for 25mm (1) liquid-tight cable glands

19mm (.75)

steel mounting band slots

19mm (.75)

IP44(NEMA-3R) metal cabinet

center aligned bolt holes for standard pole mounting


TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

minimum height 609mm (24) above ground recommended

Outdoor-XUPs-600-6339-2006-10-16.pdf

OutdoorXUPs-600A/B ~ 600VA, 420W, 120vac, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 55

Outdoor

XUPs
600 VA 420 watts 120 vac 1 hour @420W 2.2 hrs @210W 8 hours@50W -20 to +60C; -40 to +60C with optional battery heater

Pure sine wave

Wide temperature batteries

Voltage regulation

Outdoor XUPs model 600A

Outdoor UPS with Voltage Regulation


The TSi Power Outdoor XUPs-600A/B units are constructed with extreme wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer lineinteractive automatic voltage regulation, over/ under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

Key Outdoor XUPs benefits


This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for the OutdoorXUPs-600A are approximately 1 hour at 420 watts load, 2.2 hours at 210 watts load, and 8 hours at 50W; for the OutdoorXUPs-600B, approximately 2.2 hours at 420 watts, 4.6 hours at 210 watts, and 16 hours with a 50 watts load.

600B
600 VA 420 watts 120 vac 2.2 hrs @420W 4.6 hrs @210W 16 hrs @ 50W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Over/under-voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

56

Specifications OutdoorXUPs-600A/B

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420W) High efficiency line-interactive with 15kHz PWM sine wave inverter 120 volts ac 5A maximum @ 120 vac 95 to 140 vac without using batteries 47 to 63Hz 120 volts ac 115vac +/- 8% upon changes in line or load 3:1 Pure sine wave, less than 3% THD with linear load 97%, under full load conditions On/off rocker style power switch <4 milliseconds 32 amp hours, 24 vdc 64 amp hours, 24 vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 1 hour @ 420 watts load. 2.2 hours @ 210 watts load. 8 hours @ 50 watts load. 8 hours to 90% capacity after full discharge. 2.2 hours @ 420 watts load. 4.6 hours @ 210 watts load. 16 hours @ 50 watts load. 16 hours to 90% capacity after full discharge.

Outdoor

OutdoorXUPs-600A

OutdoorXUPs-600B

XUPs

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

Outdoor lineinteractive UPS with automatic voltage regulation and extreme/wide temperature batteries

Battery backup time

Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge let-through voltages Status indicators

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (for TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-Neutral: Line-Ground: and Neutral-Ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. 3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) connections via 25mm(1) liquid-tight cable glands. 406mm(16)wide x 305mm(12)deep x 711mm(28)high 45kg(100 lbs) 68kg(150 lbs) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Thermostat controlled exhaust fan. Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Input/output connections

Physical
Dimensions Weights Steel cabinet Mounting options

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Operating temperature, battery heater option and cooling method Moisture protection (optional)

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

57

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-600A/B system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 115vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


Inverter

hot ac

logic

95 to 140 vac

neutral

chassis ground

OutdoorXUPs-600A/B at a glance
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater 24vdc battery bus
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

115vac +/-8% output from 95 to 140vac input without going to batteries Weather protected IP44/NEMA-3R painted metal cabinet SNMP compatible (optional) Less than 4ms transfer time Microprocessor-controlled 15kHz PWM sine wave inverter Thermostat controlled fan is included

TSi Power Corporation

1 hour @ 420 watts load, or 2.2 hours @ 210 watts load with the OutdoorXUPs-600A 2.2 hours @ 420 watts load, or 4.6 hours @ 210 watts load with the OutdoorXUPs-600B

58

Outdoor XUPs Series OutdoorXUPs-600A/B

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

711mm (28)

368mm (14.5) 305mm (12)

19mm (.75) 19mm (.75)

406mm (16)

thermostat controlled hot air vent for exhaust fan

711mm (28)

door hinges XUPs output door latch

IP44(NEMA-3R) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 609mm (24) above ground recommended

OutdoorXUPs-600-2006-10-16.pdf

OutdoorXUPs-600AHV/BHV ~ 600VA, 420W, 230vac, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 59

Outdoor

XUPs
600 VA 420 watts 230 vac 1 hour @420W 2.2 hrs @ 210W 8 hours @ 50W -20 to +60C; -40 to +60C with optional battery heater

Pure sine wave

Wide temperature batteries

Voltage regulation

Outdoor XUPs model 600AHV

Outdoor UPS with Voltage Regulation


The TSi Outdoor XUPs-600AHV/BHV units are constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. This series offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

Key Outdoor XUPs benefits


This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for the OutdoorXUPs-600AHV are approximately 1 hour at 420 watts load, 2.2 hours at 210 watts load, and 8 hours at 50W; for the OutdoorXUPs-600BHV, approximately 2.2 hours at 420 watts load, 4.6 hours at 210 watts and 16 hours with a 50 watts load.

600BHV
600 VA 420 watts 230 vac 2.2 hrs @420W 4.6 hrs @210W 16 hrs @ 50W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Over/under-voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 280vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

60

Specifications OutdoorXUPs-600AHV/BHV

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 230 volts ac 2.5A maximum @ 230vac 190 to 280vac without using batteries. 230 volts ac 230 vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97%, under full load conditions. On/off rocker style power switch. <4 milliseconds 32 amp hours, 24vdc 64 amp hours, 24vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 1 hour @ 420 watts load. 2.2 hours @ 210 watts load. 8 hours @ 50 watts load. 8 hours to 90% capacity after full discharge. 2.2 hours @ 420 watts load. 4.6 hours @ 210 watts load. 16 hours @ 50 watts load. 16 hours to 90% capacity after full discharge. Frequency: 47 to 63Hz.

Outdoor

OutdoorXUPs-600AHV

OutdoorXUPs-600BHV

XUPs

Input
Nominal voltage Input current Operating voltage. Freq.

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

Outdoor lineinteractive UPS with automatic voltage regulation and extreme/wide temperature batteries

Battery backup time

Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional)

Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (for TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-Neutral: Line-Ground: and Neutral-Ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. 3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) connections via liquid-tight cable glands. 406mm(16)wide x 305mm(12)deep x 711mm(28)high 45kg (100 lbs) 68kg (150 lbs) Full weather IP44(NEMA-3R) outdoor design Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. Designed to meet UL, cUL and IEC safety standards -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Thermostat controlled exhaust fan. Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Surge let-through voltages Status indicators

Input/output connections

Physical
Dimensions Weights Steel cabinet Mounting options

Safety
Agency approvals
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Operating temperature, battery heater option and cooling method Moisture protection (optional)

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

61

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-600AHV/BHV system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 230vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


inverter

hot ac

logic

190 to 280 vac

neutral

chassis ground

OutdoorXUPs-600AHV/BHV at a glance
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater 24vdc battery bus
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

230vac +/-8% output from 190 to 280vac input without going to batteries Weather protected IP44 (NEMA-3R) painted metal cabinet SNMP compatible (optional) Less than 4ms transfer time Microprocessor-controlled 15kHz PWM sine wave inverter Thermostat controlled fan is included

TSi Power Corporation

1 hour @ 420watts load, or 2.2 hours @ 210watts load with the OutdoorXUPs-600AHV 2.2 hours @ 420watts load, or 4.6 hours @ 210watts load with the OutdoorXUPs-600BHV

62

Outdoor XUPs Series OutdoorXUPs-600AHV/BHV

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

711mm (28)

368mm (14.5) 305mm (12)


19mm (.75)

406mm (16)
thermostat controlled hot air vent for exhaust fan

19mm (.75)

711mm (28)

door hinges UPS output door latch

IP44 (NEMA-3R ) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 609mm (24) above ground recommended

OutdoorXUPs-600HV-2006-10-16.pdf

OutdoorXUPs-600C ~ 600VA, 420W, 120vac, 11hrs@400W, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 63

Outdoor

XUPs
600 VA 420 watts 120vac 50/60Hz -20 to +60C; -40 to +60C with optional battery heater 11 hrs @ 400W

Pure sine wave

Wide temperature -40 to +60C UPS

Voltage regulation

Outdoor XUPs model 600C

Extreme Wide Temperature Outdoor UPS with Voltage Regulation and 11 Hours Backup Time
The TSi Power Outdoor XUPs-600C is constructed with wide temperature batteries and housed in a weather protected IP44 (NEMA-3R) enclosure. It offers line-interactive automatic voltage regulation, over/under-voltage and surge protection with heavy duty noise filtering, communications capability and extended battery backup.

Key Outdoor XUPs-600C benefits


This rugged UPS design with optional conformal coated boards and microprocessor-controlled 15kHz sinewave inverter reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs-600C extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-time for the OutdoorXUPs-600C is 11 hours with a 400 watts load.

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Automatic voltage regulation with over/under voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty surge protection and noise filtering Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs-600C provides constant voltage regulation, surge protection, including an overvoltage threshold protection of 140vac, and an undervoltage threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the Outdoor XUPs-600C will transfer to battery in less than 4 milliseconds, enabling uninterrupted operation of your telecom, surveillance systems, signaling or other outdoor systems.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

LEDs provide visual assessment of UPS status. By unlatching the two latches, the front door swings open; inside the cabinet, an array of LED status indicators and power on/off control switch are provided.

64

Specification OutdoorXUPs-600C

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420 watts) High efficiency line-interactive with 15kHz PWM sine wave inverter. 120 vac 5 A maximum @ 115vac 95 to 140vac, without using batteries. 47 to 63Hz 115 vac 115 vac +/-8% for mains ac & battery modes, all operating conditions. 3:1 Pure sine wave, less than 3% THD with linear load. 97%, under full load conditions. On/off rocker style power switch. <4 milliseconds Six wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. Eleven (11) hours @ 400 watts load. Recharge time: 48 hours to 90% capacity after full discharge. Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. Three position terminal blocks provided for 3 x 1.5mm2 (16 AWG) via 25mm(1) liquid-tight cable glands. 609mm(24)wide x 305mm(12)deep x 914mm(36)high 200kg(440 lbs) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +60C (-4 to+140F); -40 to +60C(- 40 to +140F) with optional battery heater. Includes thermostat controlled exhaust fan. Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor (depot). One year manufacturers warranty on batteries.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Outdoor

OutdoorXUPs-600C

XUPs

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries Battery backup time Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge let-through voltages Status indicators

Wide temperature outdoor lineinteractive UPS with automatic voltage regulation

Ac input and UPS output cable entry (two liquid-tight cable glands)

Input/output connections

Physical
Dimensions Weights Steel cabinet Mounting options

Environmental
Operating temperature TSi Power Corporation Moisture protection option

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

65

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-600A/B system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 115vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


inverter

hot ac

logic

95 to 140 vac

neutral

chassis ground

OutdoorXUPs-600C at a glance:
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme wide-temperature batteries 11 hours @ 400 watts with the OutdoorXUPs-600C Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater Microprocessor-controlled 15kHz PWM sine wave inverter 115vac +/-8% output from 95 to 140vac input without going to batteries Weather protected IP44 (NEMA-3R) metal cabinet SNMP compatible (optional) Less than 4ms transfer time 24vdc battery bus Thermostat controlled fan

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

66

Outdoor XUPs Series OutdoorXUPs-600C

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

914mm (36)

572mm (22.5) 305mm (12)

19mm (.75) 19mm (.75)

610mm (24)

thermostat controlled hot air vent for exhaust fan

914mm (36)

door hinges XUPs output door latch

IP44(NEMA-3R) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 610mm (24) above ground recommended

OutdoorXUPs-600C-2006-10-16.pdf

OutdoorXUPs-600CHV-OEM ~ 600VA, 420W, 230vac, 11hrs@400W, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 67

Outdoor

Pure sine wave

Wide temperature UPS (OEM version)

Voltage regulation

XUPs
Extreme Wide Temperature Outdoor UPS with Voltage Regulation, and without Batteries(OEM supplied)
The TSi Power Outdoor XUPs-600CHV-OEM is constructed for use with wide temperature batteries, and is housed in a weather protected IP44(NEMA-3R) enclosure. This unit offers line-interactive automatic voltage regulation, over/under-voltage and surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.
600 VA 420 watts 230 vac 50/60Hz *OEM version designed for use with six OEM supplied extreme/wide temperature batteries for 11 hrs @ 400W

Outdoor XUPs model 600CHV-OEM *without batteries

Key Outdoor XUPs benefits


This rugged UPS design with conformal coated boards and microprocessor-controlled 15kHz sinewave inverter reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs batteries are recommended to be special wide temperature batteries which allow operation of the UPS system over an ambient temperature range of -40 to +55C. A thermostat controlled fan exhausts hot air, if temperature exceeds a preset limit, to protect batteries and electronics. Expected battery run-time for the TSi Power OutdoorXUPs-600CHV-OEM (with six user supplied wide temperature batteries) would be approximately: 11 hours at 400 Watts load.

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Automatic voltage regulation with over/under voltage protection Remote power on/off (optional) Designed for use with user/OEM supplied wide temperature batteries Heavy-duty surge protection and noise filtering Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics

How The Outdoor XUPs Works


The Outdoor XUPs-600CHV provides constant voltage regulation, surge protection, including an overvoltage threshold protection of 280vac, and an undervoltage threshold of 180vac. Upon a brownout, overvoltage, or loss of power, the Outdoor XUPs-600CHV will transfer to battery in less than 4 milliseconds, enabling uninterrupted operation of your telecom, surveillance systems, signaling or other outdoor systems.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

LEDs provide visual assessment of UPS status. By unlatching the two latches, the front door swings open. Inside the cabinet, an array of LED status indicators and power on/off control switch are provided.

68

Specifications OutdoorXUPs-600CHV-OEM

Specifications OutdoorXUPs-600CHV-OEM (without batteries)


600VA (420 watts) High efficiency line-interactive with 15kHz PWM sine wave inverter. 230 volts ac 2.5A maximum @ 230vac 180 to 280vac without using batteries 47 to 63Hz 230 volts ac 230vac +/-8% for mains ac and battery modes, all operating conditions. 3:1 Pure sine wave, less than 3% THD with linear load. 97%, under full load conditions. On/off rocker style power switch. <4 milliseconds Recommended battery manufacturer/battery: Please call.

Outdoor

Specification
Electrical
Capacity in VA (watts) UPS topology

XUPs

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Battery recommended (User/OEM supplied) Engineering will recommend based on excellent track record and high reliability. Battery back-up time Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge let-through voltages Status indicators

Outdoor lineinteractive UPS (without batteries ) with automatic voltage regulation and designed for wide temperatures

(6) wide temperature batteries (-40o to +55oC ), 12vdc, 70AH. Each battery weighs 25kg, so six batteries will add 150kg, for a total system weight of about 200kg. Approximately 70% of the units internal space is left open for your battery placement. Batteries should be connected to provide 24vdc. 210AH battery bank.
This UPS is designed to accommodate 11 hours @ 400 watts load. Recharge time: 48 hours to 90% capacity after full discharge. Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP and SMTP protocols). Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. Terminal blocks provided for 3 x 1.5mm2 (16AWG) via cable glands. 610mm(24)wide x 305mm(12)deep x 914mm(36)high 46kg (100 lbs) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +55C (-4 to +131F) ambient air temperature. Thermostat controlled exhaust fan. (Battery heater optional). Electronic boards are conformal coated for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor (depot). (Does not include user supplied batteries).

Ac input and UPS output cable entry (two liquid-tight cable glands)
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Input/output connect.

Physical
Dimensions Weights Steel cabinet Mounting options

Environmental
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Operating temperature Moisture protection

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

69

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-600CHV-OEM(without batteries) system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 230 vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


inverter

hot ac

logic

180 to 280 vac

neutral

chassis ground

OutdoorXUPs-600CHV-OEM at a glance:
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and designed for use with extreme wide-temperature batteries Designed for a configuration of 11 hours @ 400 watts with user supplied batteries
TSi Power Corporation

230vac +/-8% output from 180 to 280vac input without going to battery Weather protected IP44 (NEMA-3R) metal cabinet SNMP compatible (optional) Less than 4ms transfer time 24vdc battery bus Comes without batteries

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

We recommend the use of wide ambient temperature range sealed gel-cell batteries: -40 to +60C (-40 to +140F) Thermostat controlled fan Microprocessor-controlled 15kHz PWM sine wave inverter

70

Outdoor XUPs Series OutdoorXUPs-600CHV-OEM

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

914mm (36)

572mm (22.5) 305mm (12)

19mm (.75) 19mm (.75)

610mm (24)

thermostat controlled hot air vent for exhaust fan

914mm (36)

door hinges XUPs output door latch

IP44(NEMA-3R) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 610mm (24) above ground recommended

OutdoorXUPs-600CHV-OEM-2006-10-16.pdf

OD-XUPs-400C/600C ~ 400/600VA, 250/ 420W, 120vac, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 71

Outdoor
Od-XUPs Models model OD-XUPs-400C 400C

XUPs

Pure sine wave

Wide temperature batteries

Voltage regulation

Outdoor UPS with Voltage Regulation


The TSi Power Outdoor Od-XUPs-400C/600C UPS are constructed with extreme wide/low temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. This unit offers line-interactive automatic voltage regulation, over/under-voltage and surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

400VA, 250W 400 VA 120vac 250 watts 15 Min @250W 120vac 30 Min @125W 15 min @250W -20 to +60C; 30 min @125W -40 to +60C -20 to +60C; w/ Optional -40 to +60C Battery Heater with optional battery heater OD-XUPs-600C

Key benefits
This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for the Od-UPs-400C are approximately 15 minutes at 250 watts load, and 30 minutes with a 125 watts load; and for the Od-XUPs-600C, approximately 1.2 hours at 420 watts load, and 3 hours at 210 watts load.

600C

600 VA 420 watts 120 vac 1.2 hrs @ 420W 3 hrs @ 210W -20 to +60C; -40 to +60C with optional battery heater

Sample photo only, enclosure size may vary per custom application

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance & security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Over/under-voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty ac surge protection and ac noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

72

Specifications Od-XUPs-400C/600C

Outdoor

Specification
Electrical
Capacity in VA (watts) UPS topology

Od-XUPs-400C

Od-XUPs-600C

XUPs

600VA (420 watts) High efficiency line-interactive with 15kHz PWM sine wave inverter. 120 volts ac 5A maximum @ 120 vac 95 to 140 vac without using batteries 47 to 63Hz 120 volts ac 115 vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97%, under full load conditions. On/off rocker style power switch. <4 milliseconds 5 amp hours, 24 vdc 32 amp hours, 24 vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 15 minutes @ 250 watts load. 30 minutes @ 125 watts load. 1.2 hours @ 420 watts load. 3 hours @ 210 watts load.

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

Outdoor UPS with automatic voltage regulation and wide temperature batteries

Battery backup time Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge let-through voltages Status indicators

Specifications

Recharge time: 4 to 6 hours to 95% capacity after full discharge. Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 4 status LEDs: Inverter on indicator, ac present indicator, battery fault indicator, and overload indicator. Three position terminal blocks provided for 3 x 1.5mm2 (16AWG) via 25mm(1) liquid-tight cable glands. 507mm(20)wide x 305mm(12)deep x 609mm(24)high 22.7 kg(50 lbs) 36.3 kg(80 lbs) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Thermostat controlled exhaust fan. Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Input/output connections

Physical
Dimensions Weights Steel cabinet Mounting options

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Operating temperature, battery heater option, and cooling method Moisture protection option

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

73

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

Od-XUPs-400C/600C system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 115vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


Inverter

hot ac

logic

95 to 140 vac

neutral

chassis ground

Od-XUPs-400C/600C at a glance
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme wide-temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater 24vdc battery bus
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

115vac +/-8% output from 95 to140vac input without going to batteries Weather protected IP44 (NEMA-3R) metal cabinet SNMP compatible (optional) Less than 4ms transfer time 15kHz microprocessor-controlled PWM sinewave inverter Thermostat controlled fan is included

TSi Power Corporation

15 minutes @ 250 watts load 30 minutes @ 125 watts with the Od-XUPs-400C 1.2 hours @ 420 watts load 3 hours @ 210 watts with the Od-XUPs-600C

74

Outdoor XUPs Series Od-XUPs-400C/600C

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The Outdoor XUPs cabinet (or Outdoor EXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

19mm (.75)

Mounting feet close-up drawing

470mm (18.5) 305mm (12)


19mm (.75)

610mm (24)

508mm (20)
thermostat controlled hot air vent for exhaust fan

19mm (.75)

610mm (24)

door hinges XUPs output door latch

IP44(NEMA-3R) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 609mm (24) above ground recommended

Od-XUPs-400C-600C-2006-10-16.pdf

OutdoorXUPs-1000A/B ~ 1000VA, 700W, 120vac, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 75

Outdoor

XUPs
1000 VA 700 watts 120 vac 30 min @700W 1.1 hrs @350W -20 to +60C; -40 to +60C with optional battery heater

Pure sine wave

Wide temperature batteries

Voltage regulation

Outdoor XUPs model 1000A

Outdoor UPS with Voltage Regulation


The TSi Outdoor XUPs-1000A/B units are constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer lineinteractive automatic voltage regulation, over/ under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

Key Outdoor XUPs benefits


This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for the OutdoorXUPs-1000A are approximately 30 minutes at 700 watts load, and 1.1 hours with a 350 watts load; for the OutdoorXUPs-1000B, approximately 1.1 hours at 700 watts load, and 2.3 hours at 350 watts.

1000B
1000 VA 700 watts 120 vac 1.1 hrs @700W 2.3 hrs @350W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Pure sine wave output Over/under-voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

76

Specifications OutdoorXUPs-1000A/B

Specifications Specifications
Electrical
Capacity in VA (watts) UPS topology 1000VA (700W) High efficiency line-interactive with 15kHz PWM sine wave inverter 120 volts ac 8.3A maximum @ 120vac 95 to 140vac without using batteries 47 to 63Hz 120 volts ac 115 vac +/-8% upon changes in line or load 3:1 Pure sinewave, less than 3%THD with linear load 97%, under full load conditions On/off rocker style power switch <4 milliseconds 32 amp hours, 24vdc 64 amp hours, 24vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 30 minutes @ 700 watts load. 1.1 hours @ 350 watts load. 8 hours to 90% capacity after full discharge. 1.1 hours @ 700 watts load. 2.3 hours @ 350 watts load. 16 hours to 90% capacity after full discharge.

Outdoor

OutdoorXUPs-1000A

OutdoorXUPs-1000B

XUPs

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

Outdoor lineinteractive UPS with automatic voltage regulation and extreme/wide temperature batteries

Battery backup time Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge let-through voltages Status indicators

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination Wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. 3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) connections via 25mm(1) liquid-tight cable glands. 406mm(16)wide x 305mm(12)deep x 711mm(28)high 50kg(110 lbs) 73kg(160 lbs) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Thermostat controlled exhaust fan. Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Input/output connections

Physical
Dimensions Weights Steel cabinet Mounting options

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Operating temperature, battery heater option and cooling method Moisture protection (optional)

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

77

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-1000A/B system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 115vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


inverter

hot ac

logic

95 140 vac

neutral

chassis ground

OutdoorXUPs-1000A/B at a glance
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater 24vdc battery bus
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

115vac +/-8% output from 95 to 140vac input without going to batteries Weather protected IP44 (NEMA-3R) metal cabinet SNMP compatible (optional) Less than 4ms transfer time Microprocessor-controlled 15kHz PWM sine wave inverter Thermostat controlled fan is included

TSi Power Corporation

30 minutes @ 700 watts, or 1.1 hours @ 350watts with the OutdoorXUPs-1000A 1.1 hours @ 700 watts, or 2.3 hours @ 350 watts with the OutdoorXUPs-1000B

78

Outdoor XUPs Series OutdoorXUPs-1000A/B

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

711mm (28)

368mm (14.5) 305mm (12)


19mm (.75)

406mm (16)
thermostat controlled hot air vent for exhaust fan

19mm (.75)

711mm (28)

door hinges UPS output door latch

IP44 /NEMA-3R metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 609mm (24) above ground recommended

OutdoorXUPs-1000-2006-10-16.pdf

OutdoorXUPs-1000AHV/BHV ~ 1000VA, 700W, 230vac, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 79

Outdoor

XUPs
1000 VA 700 watts 230vac 30 min @700W 1.1 hrs @350W -20 to +60C; -40 to +60C with optional battery heater

Pure sine wave

Wide temperature batteries

Voltage regulation

OutdoorXUPs model 1000AHV

Outdoor UPS with Voltage Regulation


The TSi Outdoor XUPs-1000AHV/BHV are constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These units offer line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy-duty noise filtering, communications capability and optional extended battery backup.

Key Outdoor XUPs benefits


This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-times for: OutdoorXUPs-1000AHV are 30 minutes at 700 watts load, and 1.1 hours with a 350 watts load; battery run-times for the OutdoorXUPs-1000BHV are 1.1 hrs at 700 watts load, and 2.3 hours with a 350 watts load.

1000BHV
1000 VA 700 watts 230vac 1.1 hrs @700W 2.3 hrs @350W 20 to +60C; -40 to +60C with optional battery heater

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44 (NEMA-3R) metal cabinet Pure sine wave output Over/under-voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 280vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

80

Specifications OutdoorXUPs-1000AHV/BHV

Specifications OutdoorXUPs-1000AHV OutdoorXUPs-1000BHV

Outdoor

Specification
Electrical
Capacity in VA (watts) UPS topology

XUPs

1000VA (700W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 230 volts ac 4.2A maximum @ 230vac 190 to 280 vac without using batteries 47 to 63Hz 230 volts ac 230vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97%, under full load conditions. On/off rocker style power switch. <4 milliseconds 32 amp hours, 24 vdc 64 amp hours, 24 vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 30 minutes @ 700 watts load. 1.1 hours @ 350 watts load. 8 hours to 90% capacity after full discharge. 1.1 hours @ 700 watts load. 2.3 hours @ 350 watts load. 16 hours to 90% capacity after full discharge.

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

Outdoor lineinteractive UPS with automatic voltage regulation and extreme/wide temperature batteries

Battery backup time Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge let-through voltages Status indicators

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. 3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) connections via 25 mm (1) liquid-tight cable glands. 406mm(16)wide x 305mm(12)deep x 711mm(28)high 50kg(110 lbs.) 73kg(160 lbs.) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Thermostat controlled exhaust fan. Optional conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Input/output connections

Physical
Dimensions Weights Steel cabinet Mounting options

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Operating temperature, battery heater option and cooling method Moisture protection (optional)

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

81

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-1000AHV/BHV system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 230vac +/-8% relay 2

hot earth ground


chassis

relay 1 battery and charger dc neutral


inverter

hot ac

logic

190 to 280 vac

neutral

chassis ground

OutdoorXUPs-1000AHV/BHV at a glance
Heavy-duty outdoor UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater 24vdc battery bus
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

230vac +/-8% output from 190 to 280vac input without going to batteries Weather protected IP44 (NEMA-3R) painted metal cabinet SNMP compatible (optional) Less Than 4ms transfer time Microprocessor-controlled 15kHz PWM sine wave inverter Thermostat controlled fan is included

TSi Power Corporation

30 minutes @ 700watts, or 1.1 hours @ 350 watts with The OutdoorXUPs-1000AHV 1.1 hours @ 700 watts, or 2.3 hours @ 350 watts with the OutdoorXUPs-1000BHV

82

Outdoor XUPs Series OutdoorXUPs-1000AHV/BHV

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

711mm (28)

368mm (14.5) 305mm (12)


19mm (.75)

406mm (16)
thermostat controlled hot air vent for exhaust fan

19mm (.75)

711mm (28)

door hinges UPS output door latch

IP44 (NEMA-3R ) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 609mm (24) above ground recommended

OutdoorXUPs-1000HV-2006-10-16.pdf

OutdoorUPs-400Conf1-2 ~ 400VA, 250W, 120vac


Outdoor UPs Series Outdoor Uninterruptible Power System 83

UPs
Outdoor UPs model
400Conf1

Outdoor

Outdoor UPS

Wide temperature batteries

IP44/NEMA-3R enclosure

Outdoor Uninterruptible Power System


These TSi Power Outdoor Series UPS are constructed with extreme wide/low temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. This series offers exterior battery backup with good surge protection and communications capability.

400 VA 250 watts 120 vac 1 hour@250W 2 hrs @ 125W 4 hours @ 50W -20 to +60C; -40 to +60C with optional battery heater

Key benefits
This rugged outdoor UPS design, is the ideal UPS for exterior computer or telecommunications equipment in extreme wide temperature -20o to +60oC(-4 o to +140 oF) environments where ac power delivery is unreliable and long battery backup times may be necessary. It is suitable where power outages are a regular occurrence, or in areas where utilities need to conduct rolling blackouts. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Battery run-times for the OutdoorUPs-400Conf1 are approximately 1 hour at 250 watts load, and 2 hours at a 125 watts load; the OutdoorConf2, 2 hours at 250 watts, and 4 hours at 125 watts.

400Conf2
400 VA 250 watts 120 vac 2 hrs @ 250W 4 hrs @ 125W 8 hours @ 50W -20 to +60C; -40 to +60C with optional battery heater

Sample photo only, enclosure size may vary per custom application

Key features
Cabinet can be pedestal(ground), pole, or wall mounted Full weather protection IP44(NEMA 3R) metal cabinet Wide temperature batteries Conformal coated boards for moisture ingress protection Undervoltage protection Enhanced surge protection Two year warranty on electronics One year warranty on batteries Status and alarm signals available through DB9 connector

How the OutdoorUPs-400 works


Upon brownout, or loss of power, the OutdoorUPs-400Conf unit will transfer to battery in <8ms, enabling uninterrupted operation of your telecom, surveillance systems, signaling or other outdoor systems. One LED provides visual assessment of UPS status. Front panel rocker switches control UPS functions. Audible alarms activate upon power outage and low-battery conditions.

Typical applications
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

These outdoor extreme wide temperature rated UPS are ideal for surveillance cameras, cellular repeater sites, mission-critical 911 and telecommunications equipment, and other areas where reliability and/or extended battery backup time is required, or ac power is unpredictable.

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands

84

Specifications OutdoorUPs-400Conf1/2

UPs

Outdoor

Specification
Electrical
Capacity in VA (watts) UPS type

OutdoorUPs-400Conf1

OutdoorUPs-400Conf2

400VA (250W) Single conversion UPS with less than 8 ms transfer time. 120 volts ac single phase 100 to130 volts ac Terminal block via through-wall watertight fittings 57 to 63Hz 120 volts ac, single phase, sine wave during normal operation. 57 to 63Hz >98% for normal operation, 80% or higher during battery inverter operation. Less than 8ms typical between ac and inverter, phase-locked to the ac mains voltage. 105 to 130V RMS, 60Hz +/-1%, pulse-width-modulated, modified square wave. Brown-out threshold: 97+/-2V RMS The line voltage has to stabilize to between 100 and 130V RMS for at least 2 seconds in order to transfer back to ac mains. Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 30Ah, 12 volts 60Ah, 12 volts 1 hour @ 250 watts load. 2 hours @ 250 watts load. 2 hours @ 125 watts load. 4 hours @ 125 watts load. 4 hours @ 50 watts load. 8 hours @ 50 watts load. LED indicator and audible signals for ac, inverter, and battery status. DB-9 connector provides RS-232 compatible alarm signals. Terminal block via through-wall 25mm(1) cable glands (water-tight fittings). 406mm(16)high x 305mm(12)wide x 203mm(8)deep 27 kg(60 lbs) 39 kg(85 lbs) IP44 (NEMA-3R) fully weather protected metal cabinet. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. Internal fuses protect all ac and dc circuits. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Conformal coating of electronic boards for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Input
Nominal voltage Operating voltage Ac input (hardwire) Operating frequency

Output
Nominal voltage Nominal frequency Power efficiency Transfer time

Outdoor UPS
Specifications

UPS inverter output Transfer: ac to inverter Transfer: inverter to ac Batteries Battery backup time

optional bandable or boltable monopole mounting brackets

Indicators and alarm Communications Ac output (hardwire)

Physical
Dimensions Weight Cabinet Mounting options

Safety
TSis ongoing product improvement process makes specifications subject to change without notice. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Overload protection

Environmental
Operating temperature, battery heater option Moisture protection

Warranty
Warranty

Outdoor-UPs -400Conf1/2 system architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

hot fuse ground surge protection and noise filter battery and charger

external battery connector

UPS output relay hot

dc to ac inverter

neutral

neutral

ground Outdoor-UPs-400Conf1-2-2006-10-16.pdf

Outdoor-UPs-10000-16000-21000 ~ 1 -1.6-2.1kVA, 750W-1.2kW-1.5kW, 120V


Outdoor UPs Series Outdoor Uninterruptible Power System 85

UPs
Outdoor UPs models
10000-4871
750 watts 120vac

Outdoor

Pure sinewave

Ferroresonant voltage regulation

Transformer isolated

Outdoor UPS with Ferroresonant Constant Voltage Transformer, Extreme Wide Temperature Batteries and Failsafe Automatic Bypass
TSi Powers Outdoor Series UPS are constructed with a rugged, ferroresonant no-break design and a fully isolated sine wave output with neutral-to-ground bond. They are housed in a weather protected (NEMA 3R rated design) enclosure. This series offers the best surge protection available, with excellent noise filtering, long battery back-up time built-in automatic bypass.

16000-4871
1200 watts 120vac

21000-4871
1500 watts 120vac

Power with a Precision Attitude

Key -4871 benefits


This rugged industrial-strength ferroresonant design reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor UPS batteries are special wide temperature batteries which allow operation of the UPS system over an ambient temperature range of -40 to +55 C. Built-in battery run-time is approximately 90 minutes under a typical 600 watts load.

Typical outdoor applications


These heavy-duty outdoor rated UPS are ideal for cell sites, critical 911 and telecom equipment, LED traffic signal systems, and other areas where reliability is a must, extended back-up might be necessary, or the power source is unpredictable.

How the -4871works


The constant output isolation transformer provides 100% isolation from the input ac line. The regulated output protects switchmode power supplies from failure caused by unstable ac mains. The secondary neutral is bonded to ground, thus eliminating all surge voltages between neutral and ground. This type of surge protection is superior to all other technologies and is further enhanced with a built-in low-pass filter, which takes the edge off fast transients. UPS status is monitored by LED indicators, LED bargraph displays and audible signals for ac status, inverter status, output voltage, load, and battery status. Alarm interface: Upon loss of power, the audible alarm will beep. Because the Outdoor Series is a continuous sinewave no-break UPS system, power to equipment loads will be completely unaffected. As the battery level drops until only a few minutes of holdup time remains, the audible alarm will change, warning of impending shutdown.

Key -4871 features


Cabinet can be pedestal (ground), pole, or wall mounted Full weather protection (NEMA 3R rated design) No-break, pure sine wave output Wide temperature batteries Best surge protection available Constant voltage regulation and ferroresonant isolation transformer Reduces harmonics from non-linear loads Built-in failsafe automatic bypass Comprehensive array of status bargraphs for voltage, load and battery levels 2 yr. warranty on electronic parts, mfgrs warranty on batteries

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

86

UPs Outdoor Series Outdoor-UPs-10000-16000-21000-4871

UPs

Outdoor

Specification
Electrical
Capacity in VA (watts) Transformer type Isolation

UPs-10000-4871
1000VA (750watts)

UPs-16000-4871
1600VA (1200watts)

UPs-21000-4871
2100VA (1500 watts)

Ferroresonant constant voltage output isolation transformer. 100% input/output isolation & output neutral-ground bonding qualifies the UPS output as a separately derived ac power source via NEC 250-5D. 120 volts ac 90 to 140 volts ac without using batteries 60Hz sinusoidal +/- 5% Hardwire (14AWG) terminal block 120 volts ac +/-3% upon changes in line or load 3:1 Pure sine wave, less than 3% THD with linear load 90%, under full load conditions On/Off rocker style power switch Zero (continuous no-break) Wide temperature -40 to +55 C, maintenance-free sealed gel-cells. 2 hours 1.5 hours 1 hour Recharge time: 48 hours to return to 90% capacity after full discharge. Built-in for continued operation even if UPS failure occurs. Low-pass filter reduces noise over a wide frequency range. Built-in multi-stage, coordinated surge protection system. ANSI/IEEE C62.41-1991 test pulse. Category B3, Combination Wave, 6000 volts, 3000 amps. Test pulse injection: Line-neutral, Line-ground and Neutral-ground. Combination Wave: L-N: 35V, L-G: 35V, N-G: 0.5V 10 LED bar-graph indicators: output voltage, battery voltage, and show the output load from 0 to 100% of rated power. 4 status LEDs indicating - ac power present; inverter status; output mode; ac load, and battery status. 3 separately fused (15A fuses) terminal blocks. 24 wide x 12 deep x 36 high (609mmW x 304mmD x 914mmH) 73kgs(160 lbs) 77kgs(170 lbs) 82kgs(180 lbs) Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. Durable, all-steel NEMA 3R enclosure withstands transport in hostile environments and operation in severe outdoor applications. Designed to meet UL, cUL and IEC safety standards. FET inverter circuit ensures efficiency and reliability. -40 to +55C. (-40 to +131F ) Conformal coated boards are moisture resistant. 2 Year limited warranty, parts & labor. Manufacturers battery warranty.

Input
Nominal voltage Operating voltage Nominal frequency Ac input

Output
Nominal voltage Voltage regulation

Outdoor NEMA 3R heavy-duty UPS with ferroresonant voltage regulating isolation transformer

Crest ratio Output wave form Power efficiency Power on/off switch Transfer time Batteries Back-up time @ 50% load Recharge time Automatic bypass Noise filtering Surge protection Surge test conditions Surge let-through voltages Indicators

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Ac output

Physical
Dimensions Weight Mounting options

Enclosure

Safety
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Agency approvals FET inverter circuit

Environmental
Operating temperature Moisture protection

Warranty
Warranty

Outdoor UPs Series Outdoor Uninterruptible Power System

87

UPs
ac input

Outdoor

Outdoor-UPs -10000/16000/21000-4871 system architecture


ferroresonant transformer solid-state relay resonant capacitor

hot fuse ground

3 - way MOV surge protection EMI / RFI noise filter

neutral +48 vdc battery hot neutral UPS output

inverter

battery charger * automatic bypass not shown

ground

Heavy-duty outdoor NEMA 3R rated UPS with ferroresonant constant voltage regulating isolation transformer
No-break zero transfer time
Ferroresonant constant voltage-regulating isolation transformer
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Wide temperature batteries -40 to +55 C ambient temperature range 1000VA / 750 watts rating 1600VA / 1200 watts rating 2100VA / 1500 watts rating Thermostat controlled battery heater is included Thermostat controlled fan is included

TSi Power Corporation

Weather protected NEMA 3R rated cabinet 48vdc battery bus Failsafe automatic bypass

88

UPs Outdoor Series Outdoor-UPs-10000-16000-21000-4871

UPs

Outdoor

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-UPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The Outdoor-UPs cabinet is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html 0.75 0.75

Outdoor-UPs pad mounted


Optional bandable or boltable monopole mounting brackets

hole to hole

mounting feet close-up drawing

36

22.5 12 24
thermostatically controlled hot air vent for exhaust fan 0.75 0.75

36

door hinges outputs 1,2 & 3

NEMA 3R Enclosure Input Hole For A 1 Liquid-Tight Connector output holes for 1 liquid-tight connectors input

door latches

intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad

Outdoor-UPs-10000-16000-21000-4871-2006-10-16.pdf

OutdoorXUPs-1000-8024~230vac in, 400W@230vac+200W@48vdc out, UPS+AVR


Outdoor XUPs Series Outdoor Uninterruptible Power System 89

Outdoor

XUPs
230vac output 400 watts 1.74 amps 48vdc output 200 watts 4.2 amps 2 hours @ 600W 20 to +60C; -40 to +60C with optional battery heater

Ac + dc output

Wide temperature batteries

Voltage regulation

OutdoorXUPs model 1000-8024

Outdoor UPS with Voltage Regulation


The TSi Power Outdoor XUPs-1000-8024 is constructed with extreme/wide temperature batteries, and are housed in a weather protected IP44(NEMA-3R) enclosure. These units offer both ac and dc outputs, line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy-duty noise filtering, communications capability and optional extended battery backup.

Key Outdoor XUPs benefits


This rugged UPS design, with microprocessorcontrolled 15kHz sine wave inverter, and optional conformal coated boards, reduces the number of solid-state devices required for power conversion and is suitable for use in severe outdoor environments. Outdoor XUPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. Built-in automatic voltage regulation enables a wide input voltage window within which power is delivered without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Battery run-time for OutdoorXUPs-1000-8024 is 2 hours at 600 watts load (based on a total output of 400 watts of ac and 200 watts of dc).

Typical applications
This heavy duty outdoor UPS system is ideal for protection of WiFi/GSM/CDMA/satellite base stations, wireless communications/ perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key Outdoor XUPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44 (NEMA-3R) metal cabinet Provides both ac and dc output Pure ac sine wave Over/under-voltage protection Remote power on/off (optional) Wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation Comprehensive array of status bargraphs for voltage, load and battery levels Two year warranty on electronics One year warranty on batteries

How the Outdoor XUPs works


The Outdoor XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, as well as overvoltage protection with a threshold of 280vac, and under-voltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other systems. +/-48vdc output is also provided. LEDs provide visual assessment of UPS status. By unlatching, the front door swings open; inside the cabinet is an array of LED status indicators and a power on/off control switch.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

90

Specifications OutdoorXUPs-1000-8024

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 1000VA (600W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 230 volts ac 6A maximum @ 230vac. 190 to 280 vac without using batteries. 47 to 63Hz Ac: 230 volts, 1.74 amps, 400 watts. Dc: +/-48 volts, 4.2 amps, 200 watts. 230vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97%, under full load conditions. On/off rocker style power switch. <4 milliseconds 74 amp hours, 24vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 2 hours @ 600 watts load. (with total output of 400 watts at 230 vac, and 200 watts at 48 dc). 16 hours to 90% capacity after full discharge. Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Test pulse injection: Line-neutral: Line-ground: and Neutral-ground. Combination wave: L-N: 450V, L-G: 300 V, N-G: 300V 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. 3 position terminal blocks provided for 3 x 1.5mm2 (16AWG) ac connections via 25 mm (1) liquid-tight cable glands. 2 position terminal blocks provided for 48vdc output connections. 610mm(24)wide x 203mm(8)deep x 762mm(30)high 100kg(220 lbs) Full weather IP44(NEMA-3R) outdoor design. Bolting or banding mountable to monopole via optional H style bracket (steel mounting bands not included), pedestal (ground) or wall mountable. Four wall mounting feet are included. -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Thermostat controlled exhaust fan. Conformal coating of electronic boards is available for moisture resistance to protect against high humidity environments. Two year limited warranty, parts and labor. One year battery warranty.

Outdoor

Outdoor XUPs-1000-8024

XUPs

Input
Nominal voltage Input current Operating voltage Operating frequency

Output
Nominal voltage, amps and watts Ac voltage regulation Crest ratio Ac output wave form Power efficiency Power on/off switch Transfer time Batteries

Outdoor lineinteractive UPS with automatic voltage regulation, wide temperature batteries, and both ac and dc output

Backup time Recharge time SNMP interface for UPS monitoring and automatic shutdown configuration (optional)

Ac input and UPS output cable entry via two 25mm (1) liquid-tight cable glands
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Surge let-through voltages Status indicators

Input/output connections

Physical
Dimensions Weight Steel cabinet Mounting options

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Operating temperature, battery heater option and cooling method Moisture protection (optional)

Warranty
Warranty

Outdoor XUPs Series Outdoor Uninterruptible Power System

91

optional bandable or boltable monopole mounting brackets

Outdoor

XUPs

OutdoorXUPs-1000-8024 system architecture


utility ac input
ac circuit breaker

external battery (optional) heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

regulated XUPs output 230vac +/-8% relay 2

hot

relay 1 battery and charger dc neutral


inverter

earth ground
chassis

hot ac

logic

190 to 280 vac

neutral

dc circuit breaker

chassis ground 48 vdc output terminal block

OutdoorXUPs-1000-8024 at a glance
Heavy-duty outdoor ac and dc output UPS with line-interactive automatic voltage regulation and extreme/wide temperature batteries 400 watts, 230vac +/-8% output from 190 to 280vac input without going to batteries 200 watts, +/-48vdc output 2 hours @ 600watts, at a total of 400 watts at 230vac and 200 watts at 48vdc
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Less than 4ms transfer time Weather protected IP44 (NEMA-3R) painted metal cabinet SNMP compatible (optional) 24vdc battery bus Microprocessor-controlled 15kHz PWM sine wave inverter Thermostat controlled fan is included Optional conformal coated boards for moisture protection

TSi Power Corporation

Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater

92

Outdoor XUPs Series OutdoorXUPs-1000-8024

Outdoor

XUPs

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor-XUPs Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The OutdoorXUPs cabinet (or OutdoorEXt cabinet) is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html
19mm (.75) 19mm (.75)

Outdoor XUPs pad mounted


hole to hole

Mounting feet close-up drawing

762mm (30)

572mm (22.5) 203mm (8)


19mm (.75)

610mm (24)
thermostat controlled hot air vent for exhaust fan

19mm (.75)

762mm (30)

door hinges UPS output door latch

IP44 (NEMA-3R ) metal cabinet holes for 25mm (1) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 610mm (24) above ground recommended

OutdoorXUPs-1000-8024-2006-10-16.pdf

Outdoor-UPs-8009/8010 ~ 60 watts, 115 or 230 vac input, 12 vdc output UPS


Outdoor UPs Series Outdoor Uninterruptible Power System 93

UPs
Outdoor UPs model 8009

Outdoor

Dc output

Wide temperature batteries

Wide ac input voltage window

Outdoor On-line UPS with Dc Output


The TSi Power Outdoor-UPs-8009/8010 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 12 vdc output, with heavy duty surge protection and noise filtering.

60 watts input can be 115 or 230 vac output is 12 vdc 1.3 hrs @60W 2.5 hrs @36W -20 to +60C; -40 to +60C with optional battery heater

Key Outdoor UPs benefits


This rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life. Battery run-times for the Outdoor-UPs-8009 are approximately 1.3 hours at 60 watts load, and 2.5 hours at a 36 watts load. For the Outdoor-UPs-8010, approximately 5 hours at 60 watts load, and 8 hours with a 36 watts load.

8010
60 watts input can be 115 or 230 vac output is 12 vdc 5 hours @60W 8 hours @36W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
These heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

How the Outdoor UPs works


The outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 12 vdc (10 to 14 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small hotel space is provided inside the unit for your equipment to reside.

Key Outdoor UPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Dc output with low ripple Wide temperature batteries Heavy-duty surge protection and noise filtering Wide ac input voltage window lengthens battery life Two year warranty on electronics One year warranty on batteries

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

94

Specifications Outdoor-UPs-8009/8010

Specifications Specification
Electrical
Capacity in watts UPS topology 60 watts Ac to dc rectifier, battery charger and sealed gel-cell batteries 115 or 230 volts ac 88 to 264 vac without using batteries 1A maximum @ 115 vac, or 0.5A maximum @ 230 vac 50 or 60Hz (47 to 63Hz) 12 volts dc 10 to 14 volts dc (depending on battery charge status) 5A maximum @ 12vdc Less than 200 millivolts peak to peak 84% (typical) On/off rocker style power switch Zero transfer time 1.3 hours @ 60 watts(5A) load, 2.5 hours @ 36 watts(2.5A) load. 4 hours to 90% capacity after full discharge. 5 hours @ 60 watts(5A) load, 8 hours @ 36 watts(2.5A) load. 16 hours to 90% capacity after full discharge.

UPs

Outdoor

Outdoor-UPs-8009

Outdoor-UPs-8010

Input
Nominal voltage Operating voltage Input current Operating frequency

Output
Nominal voltage Operating voltage Output current Dc ripple voltage Power efficiency Power on/off switch Transfer time to backup Battery backup time Recharge time Batteries

Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries

10 amp hours, 12vdc 30 amp hours, 12vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2) diameter liquid-tight cable glands. 2 position terminal block provided for dc output wires connection via 19mm(3/4) diameter liquid-tight cable glands. 254mm(10)wide x 305mm(12)high x 152mm(6)deep 14kg(30 lbs) 21kg(45 lbs) Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Pole mountable to monopole via optional H style bracket (mounting bands not included). Wall mountable via enclosures top+bottom brackets. Also, optional pedestal (ground) brackets are available. Approximately 254mm(10)wide x 76mm(3)high x 152mm(6)deep, (if more space is needed, unit can be built with a larger enclosure). -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Two year limited warranty, parts and labor. One year battery warranty.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Ac connections Dc connections

Physical
Dimensions Weights Steel cabinet Mounting options

Hotel space for OEM option

Environmental
Operating temperature, battery heater option

Warranty
Warranty TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Outdoor UPs Series Outdoor Uninterruptible Power System

95

optional bandable or boltable monopole mounting brackets

UPs

Outdoor

Outdoor-UPs-8009/8010 at a glance
Heavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater Low dc output ripple 12vdc battery bus 1.3 hours @ 60 watts load, or 2.5 hours @ 36 watts load with the Outdoor-UPs-8009 5 hours @ 60 watts load, or 8 hours @ 36 watts load with the Outdoor-UPs-8010 Nominal 12 volts dc (10 to 14vdc) output from 88 to 264vac input without going to batteries Weather protected IP44/NEMA-3R, UL50 painted metal cabinet Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order. Larger OEM hotel space is available, please call if more space is necessary.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ac input is via a 12mm (1/2) diameter liquid-tight cable gland, and dc output is via a 19mm (3/4) diameter liquid-tight cable gland

Outdoor-UPs-8009-8010-115or230vac-12vdc-60W-2006-10-16.pdf

96

Outdoor UPs Series Outdoor Uninterruptible Power System

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Outdoor-UPs-8015/8016 ~ 96 watts, 115 or 230 vac input, 12 vdc output UPS


Outdoor UPs Series Outdoor Uninterruptible Power System 97

UPs
Outdoor UPs model 8015

Outdoor

Dc output

Wide temperature batteries

Wide ac input voltage window

Outdoor On-line UPS with Dc Output


The TSi Power Outdoor-UPs-8015/8016 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 12 vdc output, with heavy duty surge protection and noise filtering.

96 watts input can be 115 or 230 vac output is 12 vdc 0.4 hour @ 96W 1 hour @ 48W -20 to +60C; -40 to +60C with optional battery heater

Key Outdoor UPs benefits


This rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life. Battery run-times for the Outdoor-UPs-8015 are approximately 0.4 hour at 96 watts load, and 1 hour at a 48 watts load. For the Outdoor-UPs-8016, approximately 1 hour at 96 watts load, and 2 hours with a 48 watts load.

8016
96 watts input can be 115 or 230 vac output is 12 vdc 1 hour @ 96W 2 hours @ 48W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
These heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

How the Outdoor UPs works


The outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 12 vdc (10 to 14 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small hotel space is provided inside the unit for your equipment to reside.

Key Outdoor UPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Dc output with low ripple Wide temperature batteries Heavy-duty surge protection and noise filtering Wide ac input voltage window lengthens battery life Two year warranty on electronics One year warranty on batteries

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

98

Specifications Outdoor-UPs-8015/8016

Specifications Specification
Electrical
Capacity in watts UPS topology 96 watts Ac to dc rectifier, battery charger and sealed gel-cell batteries 115 or 230 volts ac 88 to 264 vac without using batteries 2A maximum @ 115vac, or 1A maximum @ 230 vac 50 or 60Hz (47 to 63Hz) 12 volts dc 10 to 14 volts dc (depending on battery charge status) 8A maximum @ 12vdc Less than 200 millivolts peak to peak 84% (typical) On/off rocker style power switch Zero transfer time 0.4 hour @ 96 watts(8A) load, 1 hour @ 48 watts(4A) load. 4 hours to 90% capacity after full discharge. 1 hour @ 96 watts(8A) load, 2 hours @ 48 watts(4A) load. 8 hours to 90% capacity after full discharge.

UPs

Outdoor

Outdoor-UPs-8015

Outdoor-UPs-8016

Input
Nominal voltage Operating voltage Input current Operating frequency

Output
Nominal voltage Operating voltage Output current Dc ripple voltage Power efficiency Power on/off switch Transfer time to backup Battery backup time Recharge time Batteries

Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries

5 amp hours, 12vdc 10 amp hours, 12vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2) diameter liquid-tight cable glands. 2 position terminal block provided for dc output wires connection via 19mm(3/4) diameter liquid-tight cable glands. 254mm(10)wide x 305mm(12)high x 152mm(6)deep 14kg(30 lbs) 21kg(45 lbs) Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Pole mountable to monopole via optional H style bracket (mounting bands not included). Wall mountable via enclosures top+bottom brackets. Also, optional pedestal (ground) brackets are available. Approximately 254mm(10)wide x 76mm(3)high x 152mm(6)deep, (if more space is needed, unit can be built with a larger enclosure). -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Two year limited warranty, parts and labor. One year battery warranty.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Ac connections Dc connections

Physical
Dimensions Weights Steel cabinet Mounting options

Hotel space for OEM option

Environmental
Operating temperature, battery heater option

Warranty
Warranty TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Outdoor UPs Series Outdoor Uninterruptible Power System

99

optional bandable or boltable monopole mounting brackets

UPs

Outdoor

Outdoor-UPs-8015/8016 at a glance
Heavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater Low dc output ripple 12vdc battery bus 0.4 hour @ 96 watts load, or 1 hour @ 48 watts load with the Outdoor-UPs-8015 1 hour @ 96 watts load, or 2 hours @ 48 watts load with the Outdoor-UPs-8016 Nominal 12 volts dc (10 to 14vdc) output from 88 to 264vac input without going to batteries Weather protected IP44/NEMA-3R, UL50 painted metal cabinet Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order. Larger OEM hotel space is available, please call if more space is necessary.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ac input is via a 12mm (1/2) diameter liquid-tight cable gland, and dc output is via a 19mm (3/4) diameter liquid-tight cable gland

Outdoor-UPs-8015-8016-115or230vac-12vdc-96W-2006-10-16.pdf

100 Outdoor UPs Series Outdoor Uninterruptible Power System

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Outdoor-UPs-8011/8012 ~ 96 watts, 115 or 230 vac input, 24 vdc output UPS


Outdoor UPs Series 101 Outdoor Uninterruptible Power System

UPs
Outdoor UPs model 8011

Outdoor

Dc output

Wide temperature batteries

Wide ac input voltage window

Outdoor On-line UPS with Dc Output


The TSi Power Outdoor-UPs-8011/8012 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 24 vdc output, with heavy duty surge protection and noise filtering.

96 watts input can be 115 or 230 vac output is 24 vdc 1 hour @ 96W 2 hours @ 48W -20 to +60C; -40 to +60C with optional battery heater

Key Outdoor UPs benefits


This rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life. Battery run-times for the Outdoor-UPs-8011 are approximately 1 hour at 96 watts load, and 2 hours at a 48 watts load. For the Outdoor-UPs-8012, approximately 2 hours at 96 watts load, and 4 hours with a 48 watts load.

8012
96 watts input can be 115 or 230 vac output is 24 vdc 2 hours @ 96W 4 hours @ 48W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
These heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

How the Outdoor UPs works


The outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 24 vdc (20 to 28 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small hotel space is provided inside the unit for your equipment to reside.

Key Outdoor UPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Dc output with low ripple Wide temperature batteries Heavy-duty surge protection and noise filtering Wide ac input voltage window lengthens battery life Two year warranty on electronics One year warranty on batteries

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

102 Specifications Outdoor-UPs-8011/8012

Specifications Specification
Electrical
Capacity in watts UPS topology 96 watts Ac to dc rectifier, battery charger and sealed gel-cell batteries 115 or 230 volts ac 88 to 264 vac without using batteries 2A maximum @ 115vac, or 1A maximum @ 230 vac 50 or 60Hz (47 to 63Hz) 24 volts dc 20 to 28 volts dc (depending on battery charge status) 4A maximum @ 24vdc Less than 200 millivolts peak to peak 84% (typical) On/off rocker style power switch Zero transfer time 1 hour @ 96 watts (4A) load, 2 hours @ 48 watts(2A) load. 4 hours to 90% capacity after full discharge. 2 hours @ 96 watts(4A) load, 4 hours @ 48 watts(2A) load. 16 hours to 90% capacity after full discharge.

UPs

Outdoor

Outdoor-UPs-8011

Outdoor-UPs-8012

Input
Nominal voltage Operating voltage Input current Operating frequency

Output
Nominal voltage Operating voltage Output current Dc ripple voltage Power efficiency Power on/off switch Transfer time to backup Battery backup time Recharge time Batteries

Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries

5 amp hours, 24vdc 10 amp hours, 24vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2) diameter liquid-tight cable glands. 2 position terminal block provided for dc output wires connection via 19mm(3/4) diameter liquid-tight cable glands. 254mm(10)wide x 305mm(12)high x 152mm(6)deep 14kg(30 lbs) 21kg(45 lbs) Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Pole mountable to monopole via optional H style bracket (mounting bands not included). Wall mountable via enclosures top+bottom brackets. Also, optional pedestal (ground) brackets are available. Approximately 254mm(10)wide x 76mm(3)high x 152mm(6)deep, (if more space is needed, unit can be built with a larger enclosure). -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Two year limited warranty, parts and labor. One year battery warranty.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Ac connections Dc connections

Physical
Dimensions Weights Steel cabinet Mounting options

Hotel space for OEM option

Environmental
Operating temperature, battery heater option

Warranty
Warranty TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Outdoor UPs Series 103 Outdoor Uninterruptible Power System

optional bandable or boltable monopole mounting brackets

UPs

Outdoor

Outdoor-UPs-8011/8012 at a glance
Heavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater Low dc output ripple 24vdc battery bus 1 hour @ 96 watts load, or 2 hours @ 48 watts load with the Outdoor-UPs-8011 2 hours @ 96 watts load, or 4 hours @ 48 watts load with the Outdoor-UPs-8012 Nominal 24 volts dc (20 to 28vdc) output from 88 to 264vac input without going to batteries Weather protected IP44/NEMA-3R, UL50 painted metal cabinet Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order. Larger OEM hotel space is available, please call if more space is necessary.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ac input is via a 12mm (1/2) diameter liquid-tight cable gland, and dc output is via a 19mm (3/4) diameter liquid-tight cable gland

Outdoor-UPs-8011-8012-115or230vac-24vdc-96W-2006-10-16.pdf

104 Outdoor UPs Series Outdoor Uninterruptible Power System

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Outdoor-UPs-8013/8014 ~ 96 watts, 115 or 230 vac input, 48 vdc output UPS


Outdoor UPs Series 105 Outdoor Uninterruptible Power System

UPs
Outdoor UPs model 8013

Outdoor

Dc output

Wide temperature batteries

Wide ac input voltage window

Outdoor On-line UPS with Dc Output


The TSi Power Outdoor-UPs-8013/8014 with dc output are for dc powered applications needing backup power in extreme weather conditions. They are constructed with wide temperature batteries and are housed in a weather protected IP44(NEMA-3R) enclosure. These offer a wide input voltage window (88 to 264 vac) and low ripple 48 vdc output, with heavy duty surge protection and noise filtering.

96 watts input can be 115 or 230 vac output is 48 vdc 2 hour @ 96W 4 hours @ 48W -20 to +60C; -40 to +60C with optional battery heater

Key Outdoor UPs benefits


This rugged outdoor dc output UPS design is suitable for use in severe outdoor environments. Outdoor UPs extreme/wide temperature batteries allow operation of the UPS system over an ambient temperature range of -20to +60C (- 4 to +140F); - 40 to +60C (-40 to +140F) with optional battery heater. The wide input voltage window enables dc output without having to drain or exercise the batteries, thereby ensuring long battery life. Battery run-times for the Outdoor-UPs-8013 are approximately 2 hours at 96 watts load, and 4 hours at a 48 watts load. For the Outdoor-UPs-8014, approximately 4 hours at 96 watts load, and 8 hours with a 48 watts load.

8014
96 watts input can be 115 or 230 vac output is 48 vdc 4 hours @ 96W 8 hours @ 48W -20 to +60C; -40 to +60C with optional battery heater

Typical applications
These heavy duty outdoor UPS systems are designed to power wireless communications, perimeter surveillance cameras (CCTV), security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

How the Outdoor UPs works


The outdoor UPs with dc output provides extended battery backup through a system which takes nominal 115 or 230 vac input (from 88 to 264 vac), converts it to dc, charges the batteries, and delivers a nominal 48 vdc (40 to 56 vdc) with a less than 200 millivolts peak to peak ripple. The heavy duty surge protection and noise filtering on the ac input helps protect the unit and load from transient surges on the line. Because the unit is already delivering dc power, upon a deep brownout or loss of power, the Outdoor UPs with dc output has a zero transfer time to the reserve power in the batteries. For OEMs, a small hotel space is provided inside the unit for your equipment to reside.

Key Outdoor UPs features


Cabinet can be pedestal(ground), pole, or wall mounted Full weather outdoor protection IP44(NEMA-3R) metal cabinet Dc output with low ripple Wide temperature batteries Heavy-duty surge protection and noise filtering Wide ac input voltage window lengthens battery life Two year warranty on electronics One year warranty on batteries

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

106 Specifications Outdoor-UPs-8013/8014

Specifications Specification
Electrical
Capacity in watts UPS topology 96 watts Ac to dc rectifier, battery charger and sealed gel-cell batteries 115 or 230 volts ac 88 to 264 vac without using batteries 2A maximum @ 115vac, or 1A maximum @ 230 vac 50 or 60Hz (47 to 63Hz) 48 volts dc 40 to 56 volts dc (depending on battery charge status) 2A maximum @ 48vdc Less than 200 millivolts peak to peak 84% (typical) On/off rocker style power switch Zero transfer time 2 hour @ 96 watts (2A) load, 4 hours @ 48 watts (1A) load. 8 hours to 90% capacity after full discharge. 4 hours @ 96 watts (2A) load, 8 hours @ 48 watts (1A) load. 16 hours to 90% capacity after full discharge.

UPs

Outdoor

Outdoor-UPs-8013

Outdoor-UPs-8014

Input
Nominal voltage Operating voltage Input current Operating frequency

Output
Nominal voltage Operating voltage Output current Dc ripple voltage Power efficiency Power on/off switch Transfer time to backup Battery backup time Recharge time Batteries

Outdoor dc output UPS with a wide ac input voltage window and extreme/wide temperature batteries

5 amp hours, 48vdc 10 amp hours, 48vdc Wide temperature sealed gel-cells -20 to +60C (-4 to+140F); -40 to +60C (-40 to+140F) with optional battery heater. 3 position terminal block provided for 3 x 1mm2 (18AWG), L1, L2 and Ground connections via 12mm(1/2) diameter liquid-tight cable glands. 2 position terminal block provided for dc output wires connection via 19mm(3/4) diameter liquid-tight cable glands. 254mmWx305mmHx152mmD (10wide x 12high x 6deep) 14kg(30 lbs) 406mmWx406mmHx152mmD (16wide x 16high x 6deep) 23kg(50 lbs)

Ac connections Dc connections

Physical
Dimensions Weights Steel cabinet Mounting options

Full weather IP44(NEMA 3R) UL50 outdoor padlockable enclosure. Pole mountable to monopole via optional H style bracket (mounting bands not included). Wall mountable via enclosures top+bottom brackets. Also, optional pedestal (ground) brackets are available. Approximately 254mm(10)wide x 76mm(3)high x 152mm(6)deep, (if more space is needed, unit can be built with a larger enclosure). -20 to +60C (-4 to+140F) ambient air temperature. -40 to +60C (-40 to+140F) with optional battery heater. Two year limited warranty, parts and labor. One year battery warranty.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Hotel space for OEM option

Environmental
Operating temperature, battery heater option

Warranty
Warranty
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Outdoor UPs Series 107 Outdoor Uninterruptible Power System

optional bandable or boltable monopole mounting brackets

UPs

Outdoor

Outdoor-UPs-8013/8014 at a glance
Heavy-duty outdoor on-line UPS with dc output, wide ac input voltage window, and wide temperature batteries Wide ambient temperature range sealed gel-cell batteries: -20 to +60C (-4 to +140F); or -40 to +60C (-40 to +140F) with optional thermostat controlled battery heater Low dc output ripple 48vdc battery bus 2 hours @ 96 watts load, or 4 hours @ 48 watts load with the Outdoor-UPs-8013 4 hours @ 96 watts load, or 8 hours @ 48 watts load with the Outdoor-UPs-8014 Nominal 48 volts dc (40 to 56 vdc) output from 88 to 264 vac input without going to batteries Weather protected IP44/NEMA-3R, UL50 painted metal cabinet Optional pole, wall or floor mounting brackets available. Must be specified/ordered at time of purchase order. Larger OEM hotel space is available, please call if more space is necessary.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ac input is via a 12mm (1/2) diameter liquid-tight cable gland, and dc output is via a 19mm (3/4) diameter liquid-tight cable gland

Outdoor-UPs-8013-8014-115or230vac-48vdc-96W-2006-10-16.pdf

108 Outdoor UPs Series Outdoor Uninterruptible Power System

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Outdoor-VRx-4400-0455/0460 ~ 4.4kVA, 230vac, PWM AVR+line conditioner


Outdoor VRx Series 109 Outdoor PWM Automatic Voltage Regulator Line Conditioner

Outdoor

VRx

International

Precision voltage regulator

Isolation transformer

Od-VRx model
4400-0455
19 amps 4.4kVA 4.4 kW 230vac -20 to +52C

Outdoor Precision PWM Automatic Voltage Regulator with optional Low-impedance Isolation Transformer
TSi Powers Outdoor VRx precision PWM automatic voltage regulator with optional built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a wide mains ac voltage range of 172 to 276V found in many developing countries.
There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer primary winding. VRx is also designed with a fail-safe automatic bypass which enables the VRx to provide power to the load even in the event of internal failure that may otherwise result in a disruption of power to the load. VRx with optional isolation transformer provides complete isolation from the ac line, with a neutral-to-ground bond to eliminate all surge voltages between neutral and ground.

4400-0460
19 amps 4.4kVA 4.4 kW 230vac with isolation transformer -20 to +52C

Key features of the VRx-4400


Accepts continuous 172 to 276vac at 50/60Hz input PWM automatic voltage regulation Built-in over-voltage (OVP) and under-voltage (UVP) protection Automatic fail-safe bypass Fail-safe design ensures OVP functions even if voltage regulation circuits fail and unit transfers to bypass Coordinated surge protection in accordance with IEC 61312 EFT and noise protection withlow dv/dt True isolation and neutral-ground bond with optional isolation transformer Low weight and high efficiency Quiet operation 2 year warranty

Typical applications
Designed for critical outdoor systems where Power with a Precision Attitude reliability and predictability matter, such as remote transceiver base stations, fixed wireless applications, as well as for other outdoor equipment requiring additional protection. They are also for mission-critical applications such as telecom applications in remote environments where consistent voltage levels cannot be trusted, and where service calls are expensive.

Copyright 2006 TSi

VRx provides highly available regulated power and protection from mains voltages outside of the design limits for RBS power plants, typically 172 to 276vac. A low input voltage can result in TSi Power Corporation inadequately charged batteries as the ac to dc Represented by power system is unable to draw the power CareBase Michael Gibson required. An input voltage in excess of 276V, Post Office Box 2987 even for a short time, can cause the destruction Glenwood Springs, CO of ac to dc power systems. In summary, VRx is 81602-2987 USA Phone +1 970 945 2770 designed to protect equipment even in the most 800 430 2770 (USA.CAN) challenging worldwide electrical, mechanical michaelg@carebase.com and environmental conditions. www.carebase.com

110 Outdoor VRx Series Od-VRx-4400-0455-0460

Outdoor

VRx

Key VRx Series benefits


The lightweight, high efficiency Outdoor VRx is easy to install in severe weather exposed environments. The unit comes in a specially designed IP44 (NEMA-3R) outdoor rated enclosure and has removable lifting eyes to enable use of lifting equipment. The automatic bypass assures that connected equipment will not shut down, even if VRx fails. VRx is compatible with all loads as it does not switch any components in the power path. VRxs ultra-low impedance assures stability even with the most demanding loads. The automatic over-voltage / under-voltage cutoff with automatic restart ensures that operation is off-line during serious over-voltage or under-voltage situations that could damage the system and/or load, and then restarts without intervention when the ac mains voltage becomes within the operating range. The optional isolation line conditioner provides maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups, a reduction in equipment down time and service costs can be expected.

Outdoor VRx system architecture


input
172 to 276 vac

circuit breaker
surge prot. and noise filter

buck-boost transformer

automatic bypass
over / under voltage cutoff
noise filter

VRx output 230 vac +/-3%

L1 ground

ac

dc ground

microprocessor control

N G

L2

isolation transformer (optional)

How the VRx Series works


Power with a Precision Attitude
The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230 +/-3% vac output. The automatic bypass will be activated when there is a fault condition. Two green LEDs indicate Normal (regulating protected mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition. The over-voltage and under-voltage cutoff is activated whenever the ac mains voltage becomes dangerously high or low (outside 172 to 276 vac). It automatically restarts whenever ac mains voltage is restored within 172 to 276 vac. An optional low-impedance isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformer, in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Specifications

Specifications 111 OD-VRx-4400/0455-0460

Outdoor

VRx

Specification
Electrical
Capacity in VA (watts) Regulator engine Transformer type

Od-VRx-4400-0455

Od-VRx-4400-0460

4400VA (4400W) High frequency 20kHz IGBT driven voltage regulation converter PWM buck-boost transformer PWM buck-boost transformer plus isolation transformer

Outdoor rated wide voltage range precision automatic voltage regulator

Input
Operating voltage Nominal frequency Circuit breaker rating
VRx circuit breaker rating

172 to 276 vac 47 to 63Hz Upstream two-pole, 50A is recommended (to be supplied by customer). Internal two-pole, 32A. 10mm (AWG 8) for both power and earth conductors. Stranded copper wire with min. 105o C insulation system recommended. 230 vac, single phase. Combined 3% maximum under 0 to 100% load and input of 172~276V. OVP removes power to protected load if output voltage exceeds 264V. Automatic reset returns power when voltage levels are back in tolerance. 96% (typical) 90% (typical) Automatic bypass will be activated when there is a fault condition. System status LEDs provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down). A coordinated surge protection system consisting of buck-boost transformer, filter and MOV. (Plus isolation transformer on -0460). Class 2 and Class 3 simulated lightning surge (Combination wave) Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV, 3kA, 8x20S L-N L-G Single pulse: 50 V 50 V Ring wave: 20 V 20 V Comb. wave: 250 V 250 V Singlepulse: Ring wave: Comb. wave: L-N L-G N-G 50V 50V 0.5V 20V 20V 0.5V 250V 250V 0.5V
2

Input wire size (two wires plus ground)

Output
Nominal voltage Voltage regulation Over-voltage protection

VRx-4400 with isolation transformer option

Power efficiency Automatic bypass System status indicators

Surge protection Surge test conditions Surge let-through Voltage

VRx-4400 liquid-tight cable glands

Ac connection

Terminal block connectors via 19mm(3/4) liquid-tight cable glands. 406mm(16)wide x 711mm(28)high x 305mm(12)deep 36.3kg(80 lbs) 72.6kg(160 lbs) Pole mountable with optional pole mounting kit, pedestal(ground), or wall-mountable, four wall-mounting feet included. System is built in a weather tight IP44 (NEMA 3R) metal enclosure. Designed to meet UL, cUL and IEC standards. - 20o to +52 oC. (- 40o to +52 oC with optional built-in heater), - 4o to +125 oF. (- 40o to +125oF with optional built-in heater). From sea level to 10,000 feet (3000m) above sea level. Two year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Physical
Dimensions Weight Mounting options Enclosure

Safety
Agency approvals

Environmental
Ambient temperature TSi Power Corporation Altitude

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Warranty
Warranty

112 Outdoor VRx Series Od-VRx-4400-0455-0460

Outdoor

VRx

Mounting on a concrete pad with Unistrut (or similar)


Following is a drawing of a recommended pedestal/concrete pad mounted installation of an Outdoor VRx Series unit bolted to vertical Unistrut members, which are bolted to horizontal Unistrut members that are bolted to a concrete pad. The Outdoor VRx cabinet is provided with four (4) mounting feet at the four (4) corners. For detailed information on Unistrut, go to: http://www.unistrut.com/product/mframe.html 19mm (.75) 19mm (.75)

Outdoor VRx pad mounted


hole to hole

Mounting feet close-up drawing

711mm (28)

368mm (14.5) 305mm (12)


19mm (.75)

406mm (16)
thermostat controlled hot air vent for exhaust fan

19mm (.75)

711mm (28)

door hinges VRx output door latch

IP44(NEMA-3R) metal cabinet holes for 19mm (3/4) liquid-tight cable glands

ac input intake air vent underneath

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

concrete pad 609mm (24) above ground recommended

Od-VRx-4400-0455-0460-2006-10-16.pdf

Outdoor-VRp-ILc-15000/30000-5339 ~ 15/30kVA, 400 vac delta,230/400 vac wye


Outdoor VRp-ILc Series 113 Precision Voltage Regulator + Isolation Transformer

VRp-ILc
Outdoor VRp-ILc models

Outdoor

International

Precision voltage regulator

Isolation transformer

15000-5339
15 kVA 15 kW input 400Vdelta output 230/400V wye three phase

Precision PWM Automatic Voltage Regulator with Isolation Transformer, Automatic Bypass and Automatic Cutoff
TSi Powers Outdoor VRp-ILc automatic precision voltage regulator with built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a very wide mains ac voltage range of 400V+/-20% found in many developing countries. There is no switching of taps nor any break in the power path thanks to continuous pulse width modulation (PWM) switching of a buck-boost transformer primary winding.

30000-5339
30 kVA 30 kW input 400Vdelta output 230/400V wye three phase

Typical applications
Designed for applications where absolutely safe and precisely regulated ac power is required, such as radio base stations (RBS), telecommunication transmission sites for backhaul (including microwave links), TV/ radio broadcasting, industrial equipment and end-of-line utility equipment.

Key Outdoor VRp-ILc features


Power with a Precision Attitude
Outstanding voltage regulation performance: output is within 230/400vac+/-3% under a normal input range of 400vac +/-20% No switching of power path and unit always starts up on sine wave zero crossing
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

VRp-ILc provides continuous, fast, no-break voltage regulation

A three phase low-impedance isolation transformer is used for maximum reliability Coordinated surge protection per IEC61312 Advanced noise and interference filter reduces dV/dt from 6kV/s to less than 10V/ s Pedestal-mountable cabinet Common-mode noise elimination IP23 outer enclosure with sensitive components housed in an IP55 inner case (overall equivalent to IP44/NEMA-3R) Two year warranty

TSi Power Corporation

Over-voltage cutoff, with automatic restart when ac mains voltage returns to normal (safe) condition Failsafe: automatic bypass (even during bypass, the over-voltage protection is active) Lightweight design

114 Outdoor VRp-ILc Series Outdoor-VRp-ILc-15000/30000-5339

VRp-ILc

Outdoor

Key Outdoor VRp-ILc benefits


The lightweight, high efficiency Outdoor VRp-ILc is easy to install in outdoor environments. The unit comes in a specially designed outdoor rated enclosure with multiple air exhaust fans. To maximize cooling, the isolation transformer is housed in an IP23 outer enclosure. Sensitive components are housed in an IP55 inner case. Overall equivalent is to an IP44(NEMA-3R) enclosure. The automatic bypass assures that connected equipment will not shut down, even if VRp-ILc fails. VRp-ILc is compatible with all loads as it does not switch any components in the power path. VRp-ILcs ultra-low impedance assures stability even with the most demanding loads.

Outdoor rated precision PWM voltage regulator with isolation transformer

The automatic over-voltage cutoff with automatic restart ensures that operation is off-line during serious over-voltage situations that could damage the system and/or load, and then restarts without intervention when the ac mains voltage returns to the normal operating range. The ILc isolation line conditioner components provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, the VRp-ILc offers improved repeatability, fewer reboots or system lock-ups. A reduction in equipment down time and service costs can also be expected.

How the Outdoor VRp-ILc works


Power with a Precision Attitude
The high frequency insulated gate bi-polar transistor (IGBT) driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230/400 vac three phase output. The Automatic Bypass will be activated when there is a fault condition. A green LED indicates normal regulated protected mode operation. The over-voltage cutoff is activated whenever the ac mains voltage becomes dangerously high (over 475vac). It automatically restarts whenever ac mains voltage is restored to a safe level. At extremely low ac input conditions it can be operated at limited duty cycle. A low-impedance isolation transformer provides complete isolation between the primary and secondary, and permits bonding between output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformer, in combination with capacitive elements and metal oxide varistors (MOVs), provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312. Multiple cooling fans control the units internal temperature, with intakes at the bottom of the unit and exhaust through the top rear of the unit, protected with a rain guard/sunshield.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Specifications 115 Precision Voltage Regulator + Isolation Transformer

VRp-ILc

Outdoor

Specification
Electrical
Capacity in VA (watts) Regulator technology Transformer type

15000-5339
15kVA (15kW)

30000-5339
30kVA (30kW)

High frequency IGBT driven voltage regulation converter Three phase isolation transformer used Three phase delta: 400 volts ac 400 volts ac +/-25% at limited duty cycle 47 to 63 Hz Input circuit breaker with limited inrush current capability. Over-voltage cutoff activated when >475vac with automatic restart when voltage returns to normal. 40A 10mm2 (AWG 8) 60A 15mm2 (AWG 6)

Input
Nominal voltage Normal operating range Nominal frequency Input circuit breaker Over-voltage cutoff with auto-restart

Outdoor precision Input wire size PWM voltage Ac connection regulator with isolation transformer Output

Circuit breaker rating

Terminal block (L1, L2, L3 and ground wires) provided. Three phase wye: 230/400 volts ac 95% maximum Better than +/-3% Automatic bypass will be activated when there is a fault condition. Output circuit breaker provides protection against overload conditions. A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Green LED indicates Normal (regulating) mode operation. Class 2 and Class 3 Simulated lightning surge (Combination wave) Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV,3kA,8x20s. Optional Class 1 surge arrester available for primary protection. Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V Measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/s with input test waveform dV/dt of 6kV/s. Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. 30A 6mm (AWG 10)
2

Nominal voltage Power efficiency Voltage regulation Automatic bypass

Specifications

Overload protection Surge protection System status indicator Surge test conditions

Power with a Precision Attitude

Surge let-through voltages

Common mode filtering


TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Normal mode filtering Circuit breaker rating Output wire size Ac connection

50A 15mm2 (AWG 6)

Terminal block (L1, L2, L3, neutral and ground wires) provided. 1040mm(40.9)wide 450mm(17.7)deep 1170mm(46.1)high 250kg (550 lbs) 1150mm(45.3)wide 600mm(23.6)deep 1300mm(51.2) high 450kg(990 lbs)

Physical
Dimensions Weight

Safety
Standards
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Designed to meet IEC 60950 standards. -20o to +40 oC(-4o to +104 oF). Multiple air exhaust fans are used. IP23 outer enclosure with sensitive components housed in an IP55 inner case (overall equivalent to IP44/NEMA-3R). Two year limited warranty, parts and labor.

TSi Power Corporation

Environmental
Ambient temperature Cooling method Weather protection

Warranty
Warranty

116 Outdoor VRp-ILc Series Outdoor-VRp-ILc-15000/30000-5339

VRp-ILc
1040 mm (40.9)

Outdoor

model -15000
450 mm (17.7)

model -30000
600 mm (23.6)

the Outdoor VRp-ILc provides excellent protection, superior thermal management and ease of installation

1150 m (45.3 m )

1170mm (46.1)

front panel is a hinged door with locks ventilated base

input/output cable glands openings

Right side rear view

Front right side view

Outdoor VRp-ILc system architecture (per phase)


input 400 vac + / - 20 %
L1

3 phase circuit breaker


surge prot. and noise filter

buck - boost transformer

automatic bypass over-voltage cutoff


microprocessor control

VRp- ILc output 230 vac +/-3%


L

ground

ac

dc ground

noise filter
N G

L2

isolation transformer

three separate buck-boost transformers delta to wye transformer


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

hot air exhaust via multiple fans (not shown) VRp electronic module with fans ac input/output connection terminals ac input/output via cable glands

TSi Power Corporation

ac surge protection and filter module cold air entry through mesh

Inside view
Outdoor-VRp-ILc-15000-30000-5339-2006-10-16.pdf

1300 mm (51.2)

hot air exhaust

RMk Series ~ Rack-mounting Kits for TSi Rack-mountable Products


RMk Series 117 Rack-Mounting Kits

RMk
RMk Series Rack-mounting kits

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

118 RMk Series Rack-Mounting Kits

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

RMk-Series-2006-10-16.pdf

RMk Series ~ Rack-mounting kits for 19, 23, 24 racks, and wall-mounting
RMk ~ Rack-Mounting Kits 119

RMk
Models
MK-5019A MK-8019A
19 Front

For 19, 23 or 24 racks

Rackmount kits for XUPs/UPs, XINv and ATs

Rack/ floor/wall Mounting Kits for XUPs/UPs, XINv, and ATs Series
All of TSi's products can be placed virtually anywhere that fits your space considerations. This includes desktop and floor mount options. If a rackmount configuration is what you require, TSi's XINv, INv, ATs, XUPs and most UPs systems are designed to accommodate most standard component rack/cabinet enclosures.

MK-5023A MK-8023A
23 Front

MK-5024A
24 Front

MK-8024A & MK-8024B


24 Front and Rear

Key benefits
With one of these simple rack mount kit options, you can place your rack-mountable UPs (uninterruptible power system), XINv/INv (inverter) ARm (automatic redundancy module), or ATs (automatic transfer switch) in either a 19". 23", or 24" rack and facilitate the space requirements of your systems, not the UPS or transfer switch. TSi offers a range of different brackets allowing you to mount our products on the rack of your choice. We can help you to choose the most suitable set for your specific product and rack size. Also, please see the back of this page for a table of standard kits.

MK-5019F MK-8019F
19 Center

MK-5023F MK-8023F
23 Center

MK-5024F MK-8024F
24 Center

MK-8019B
19 Rear

MK-8023B
23 Rear

MK-5000C MK-5019C
Wall/floor

A TSi UPs-7200 & EXt-5000 battery extension unit shown mounted inside a 19 wide cabinet using an MK-5019A (Front rack-mount kit).

Shown mounted inside a standard telco-style 19 wide, 40 tall rack, are: An ARm-1000FAA automatic redundancy module (automatic transfer switch), using an MK-5019F Center-mounting kit. A TSi Power UPs-10000, and two EXt-8000 battery extension units, using MK-8019F A TSi UPs-16000 and EXt-8000 Battery Center-mounting kits. Extension Unit shown mounted inside a 19 wide cabinet using an MK-8019A & MK-8019B (Front and Rear rack-mount kits).

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

120 Specifications Rack-mounting Kits

RMk
Rackmount kits

by Kit part numbers


For 19 racks Mk-5019A MK-5019F Mk-8019A Mk-8019B MK-8019F For 23 racks MK-5023A MK-5023F MK-8023A MK-8023B MK-8023F For 24 racks MK-5024A MK-5024F MK-8024A And MK-8024B MK-8024F Wall / floor mount MK-5000C MK-5019C

Rackmount kit description


19 Front mounting kit 19 Center mounting kit 19 Front mounting kit 19 Rear mounting kit 19 Center mounting kit 23 Front mounting kit 23 Center mounting kit 23 Front mounting kit 23 Rear mounting kit 23 Center mounting kit 24 Front mounting kit 24 Center mounting kit 24 Front And Rear mounting kit 24 Center mounting kit Wall / floor mounting kit Wall / floor mounting kit

Specifications

By Specific Product by Specific product

rack-mount Kit Choices Rackmount kit choices

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

For XUPs-600/1000/600E/1000E, XINv-400/700/1400/400E/700E/1400E Rackmount options Front-mount kits: For a 19 rack: use # MK-5019A For a 23 rack: use # MK-5023A For a 24 rack: use # MK-5024A Center-mount kits: For a 19 rack: use # MK-5019F For a 23 rack: use # MK-5023F For a 24 rack: use # MK-5024F Wall/floor-mount kits: use # MK-5000C For VRp-3000/5000/5500 Wall/floor-mount Wall/floor-mount kits: Use # MK-5019C For ARm-1000 Rackmount option Front-mount kit: For a 19 rack: use # MK-1019A For ARm-1000FAA, Rackmount options Front-mount kits: For a 19 rack: use # MK-5019A For a 23 rack: use # MK-5023A For a 24 rack: use # MK-5024A Center-mount kits: For a 19 rack: use # MK-5019F For a 23 rack: use # MK-5023F For a 24 rack: use # MK-5024F Wall/floor-mount kits: Use # MK-5000C For ATs-1000/1000E Rackmount options Front-mount kits: For a 19 rack: use # MK-5019A For a 23 rack: use # MK-5023A For a 24 rack: use # MK-5024A Center-mount kits: For a 19 rack: use # MK-5019F For a 23 rack: use # MK-5023F For a 24 rack: use # MK-5024F Wall /floor-mount kits: use # MK-5000C For INv-750/1000/1500, UPs-10000/16000/21000, and EXt-8000 Rackmount options For 19 cabinet: use Front Pair # MK-8019A (Heavy units should have and Rear Pair # MK-8019B both front & rear) For telecom center-mount rack: use Center pair # MK-8019F RMk-2006-10-16.pdf

SLc Series ~ Automatic Voltage Stabilizing Line Conditioners


SLc Series 121 Stabilizing Line Conditioners

SLc
Voltage stabilizing line conditioners

SLc Series

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

122 SLc Series Stabilizing Line Conditioners

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

SLc-Series-2006-10-16.pdf

SLc-600/1200/1800 ~ 5/10/15A, 600VA/1.2 /1.8kVA, 120vac


SLc Series 123 Stabilizing Line Conditioner

SLc
SLc model 600
5 amps 600 VA 600 watts 120 volts

Auto-transformer

Automatic voltage regulator

UL/cUL listed

Four- stage Auto-transformer Voltage Regulator Line Conditioner


This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.

1200
10 amps 1200 VA 1200 watts 120 volts

Typical applications
SLc Series conditioners provide low-cost ac line protection for computers, point-of-sale terminals, copiers, data acquisition and control systems, as well as other data processing equipment. SLcs can also be used to protect low-cost stand-by UPS to prevent discharge of UPS batteries due to low- or high-voltage transfer to inverter.

1800
15 amps 1800 VA 1800 watts 120 volts

Key benefits
TSi Powers SLc Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc provides three-way surge protection and reduction of surge voltage. The SLc line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.

Key features of the SLc Series stabilizing line conditioner


Four stages of regulated output voltages Wide input range Multi-mode surge protection Quiet operation Four ac outlets Front panel power switch Four status LED display indicators High efficiency Low cost Two year warranty

How the SLc Series works


The SLc Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 75 to 150V, the output is regulated to within 105 and 130V, well within the range of most equipment. SLc operation is monitored by four status LEDs, indicating normal, boost 1, boost 2 and buck stages of voltage regulation. The front panel power switch turns the SLc unit on and supplies power to the equipment.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

124 Specifications SLc-600-1200-1800

SLc
Four stage auto-transformer voltage regulator

Specification
Electrical
Capacity in VA (watts) Transformer type

SLc-600
600VA (600W)

SLc-1200
1200VA (1200W)

SLc-1800
1800VA (1800W)

Four winding auto-transformer. 120 volts ac 75 to 150 volts ac 60 Hz 6 foot long ac power cord with NEMA 5-15P plug. 105 to 130 volts ac Three-way surge protection system. Per ANSI/IEEE C62.41-1991 test pulse, Category A3, Ring wave, 6000V, 200A. Test pulse injection: Line-neutral, Line-ground, and Neutral-ground. Remnant voltage: L-N: 15V, L-G: 15V, N-G: 400V. > 97% at full load. On/off rocker power switch. Transfers to new stage within 20 cycles of new ac input voltage. Less than 4ms between stages. 6V minimum. Prevents unnecessary switch-overs due to momentary ac sags and brownouts. Four status LEDs indicating normal, boost 1, boost 2, and buck stages of voltage regulation. Four (NEMA 5-15R) 152mm(6)wide x 102mm(4.0)high x 203mm(8.0)deep 3.6 kg(8 lbs) 5.0 kg(11 lbs) UL and cUL listed
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Input
Nominal voltage Operating voltage Nominal frequency Ac input cord

Output
Ac output voltage Surge protection Surge test conditions

Rear view
Specifications

Surge let-through voltages Power efficiency Power on/off switch Response time Transfer time Hysteresis Indicators Ac output receptacles

Physical
Dimensions Weight 6.8 kg(15 lbs)

Safety
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Agency approvals

Environmental
Ambient temperature

Warranty
Warranty Two year limited warranty, parts and labor.

SLc Series system architecture


ac input
hot fuse surge protection and noise filter

four tap voltage regulator


+40% +20% 0% -15%

ac output 105 to 130 vac


hot

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

ground

75 to 150 vac

power supply logic

neutral

SLc output
ground

neutral

SLc-600-1200-1800-120V-2006-10-16.pdf

SLc-600E/1200E /1800E ~ 2.6/5/ 7.8A, 600VA/ 1.2/1.8kVA, 230vac


SLc Series 125 Stabilizing Line Conditioner

SLc
SLc model 600E
2.6 amps 600 VA 600 watts 230 volts

Auto-transformer

Automatic voltage regulator

UL/cUL listed

Four stage Auto-transformer Voltage Regulator Line Conditioner


This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.

1200E
5 amps 1200 VA 1200 watts 230 volts

Typical applications
SLc Series conditioners provide low-cost ac line protection for computers, point-of-sale terminals, copiers, data acquisition and control systems, as well as other data processing equipment. SLcs can also be used to protect low-cost stand-by UPS to prevent discharge of UPS batteries due to low- or high-voltage transfer to inverter.

Key benefits
TSi Powers SLc Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc provides three-way surge protection and reduction of surge voltage. The SLc line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.

Key features of the SLc Series stabilizing line conditioner


Four stages of regulated output voltages Wide input range Multi-mode surge protection Quiet operation Four ac outlets Front panel power switch Four status LED display indicators High efficiency Low cost Two year warranty

How the SLc Series works


The SLc Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 75 to 150V, the output is regulated to within 105 and 130V, well within the range of most equipment. SLc operation is monitored by four status LEDs, indicating normal, boost 1, boost 2 and buck stages of voltage regulation. The front panel power switch turns the SLc unit on and supplies power to the equipment.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

126 Specifications SLc-600E-1200E-1800E

SLc
Four stage 230V auto-transformer voltage regulator
Specifications

Specification
Electrical
Capacity in VA (watts) Transformer type

SLc-600E
600VA (600W)

SLc-1200E
1200VA (1200W)

SLc-1800E
1800VA (1800W)

Four winding auto-transformer. 230 volts ac 150 to 280 Volts ac 50/60 Hz 6 foot long ac power cord with IEC-320 plug. 200 to 250 volts ac Three-way surge protection system. Per ANSI/IEEE C62.41-1991 test pulse, Category A3, Ring wave, 6000V, 200A. Test pulse injection: Line-neutral, Line-ground, and Neutral-ground. Remnant Voltage: L-N: 15V, L-G: 15V, N-G: 400V. > 97% at full load. On/off rocker power switch. Transfers to new stage within 20 cycles of new ac input voltage. Less than 4 mS between stages. 6V minimum. Prevents unnecessary switch-overs due to momentary ac sags and brownouts. Four status LEDs indicating normal, boost 1, boost 2, and buck stages of voltage regulation. Four IEC-320, (E Option) or two Schuko (EC Option) 152mm(6)wide x 102mm(4.0)high x 203mm(8.0)deep 3.6 kg(8 lbs) 5.0 kg(11 lbs) 6.8 kg(15 lbs)

Input
Nominal voltage Operating voltage Nominal frequency Ac input cord

Output
Ac output voltage Surge protection Surge test conditions

Surge let-through voltages Power efficiency Power on/off switch Response time Transfer time Hysteresis Indicators Ac output receptacles

Physical
Dimensions Weight

Safety
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Safety Standards

Designed to meet UL, cUL and IEC standards.


0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient Temperature

Warranty
Warranty Two year limited warranty, parts and labor.

SLc system architecture


ac input
hot fuse
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

four tap voltage regulator


+40% +20% 0% -15%

SLc output 200 to 250 vac


hot

TSi Power Corporation

ground

surge protection and noise filter

150 to 280vac

power supply logic

neutral

SLc output
ground

neutral

SLc-600E-1200E-1800E-230V-2006-10-16.pdf

SLc-1100B/2000B ~ 9/16A, 1.1kVA/2 kVA, 120vac


SLc-B Series 127 Wide Voltage Input ~ Stabilizing Line Conditioner

SLc-B
SLc model 1100B
9 amps 1100VA 1100 watts 120 volts

Auto-transformer

Automatic voltage regulator

Wide input range

Four stage Auto-transformer Voltage Regulator Line Conditioner


This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.

2000B
16 amps 2000VA 2000 watts 120 volts

Typical applications
SLc-B Series conditioners provide low-cost ac line protection for copiers, digital printers, fax, data acquisition and control systems, as well as other data processing equipment. SLc-Bs can also be used to protect low-cost stand-by UPS to prevent discharge of UPS batteries due to low- or high-voltage transfer to inverter.

Key SLc-B benefits


TSi Powers SLc-B Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc-B provides three-way surge protection and reduction of surge voltage. The SLc-B line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.

Key SLc-B Series features


Four stages of regulated output voltages Wide input voltage range Three-stage surge protection Quiet operation Four NEMA 5-15R outlet receptacles Front panel power switch High efficiency Low cost Five year warranty

How The SLc-B Series works


The SLc-B Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 80 to 150V, the output is regulated to within 104 and 126V, well within the range of most equipment. A rocker style power switch/circuit breaker turns the unit on and supplies power to the equipment.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

128 Specifications SLc-1100B/2000B

SLc-B

Specification
Electrical
Capacity in VA (Watts) Transformer type

SLc-1100B
1100VA (1100W)

SLc-2000B
2000VA (2000W)

Four winding auto-transformer. 120 volts ac+/-33% 80 to 150 volts ac 50/60 Hz (47 to 63Hz) 6 foot cord with NEMA 5-15P plug 9 amps @ 120vac 6 foot cord with NEMA 5-20P plug 16 amps @ 120vac

Input
Nominal voltage Operating voltage Nominal frequency Ac input

Four stage 120V auto-transformer voltage regulator


Specifications

Maximum input current

Output
Ac output voltage Maximum output Surge protection Power efficiency Power on/off switch Response time Transfer time Hysteresis Ac output receptacles Audible noise 115 volts+/-10% ac (104 to 126 vac) 9 amps 16 amps Three-stage surge protection system. 97% or higher under all conditions. On/off rocker power switch. Transfers to new stage within 20 cycles of new ac input voltage. Less than 4 mS between stages. 6V minimum. Prevents unnecessary switch-overs due to momentary ac sags and brownouts. Four standard NEMA 5-15R Less than 45 dBA (at 1 meter) 152mm(6) wide x 127mm(5.0)high x 229mm(9)deep 8.2kgs(18 lbs) 9kgs(20 lbs)

Physical
Dimensions Weight

Safety
Safety standards Designed to meet UL, cUL and IEC standards.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty. (Replacement boards will be provided free of charge upon failure ~ board is the only part that can fail and can be easily replaced by the user).
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

SLc-B system architecture


ac input hot fuse
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

four tap voltage regulator


+40% +20% 0% -15%

SLc - B output 115 vac + / - 10 %

TSi Power Corporation

ground

surge protection and noise filter

hot
power supply logic

neutral

80 to 150vac

neutral

ground

SLc-1100B-2000B-2006-10-16.pdf

SLc-1100BE/2000BE ~ 5.5 /10A, 1100/2000 VA, 230vac


SLc-Be Series 129 Wide Voltage Input ~ Stabilizing Line Conditioner

SLc-Be
SLc model 1100BE
5.5 amps 1100VA 1100 watts 230 volts

Auto-transformer

Automatic voltage regulator

Wide input range

Four stage Auto-transformer Voltage Regulator Line Conditioner


This automatic voltage regulator provides stable power even when the ac mains or back-up generator voltage is extremely low or high.

2000BE
10 amps 2000VA 2000 watts 230 volts

Typical applications
SLc-Be Series conditioners provide low-cost ac line protection for copiers, digital printers, fax, data acquisition and control systems, as well as other data processing equipment. SLc-Bes can also be used to protect low-cost stand-by UPS to prevent discharge of UPS batteries due to low- or high-voltage transfer to inverter.

Key SLc-Be benefits


TSi Powers SLc-Be Series regulated output protects switch-mode power supplies from failure caused by unstable ac mains. SLc-Be provides three-way surge protection and reduction of surge voltage. The SLc-Be line conditioner can be used between a UPS and the ac mains to provide even greater protection for the connected equipment, while saving the UPS's internal batteries for true black-outs.

Key SLc-Be Series features


Four stages of regulated output voltages Wide input voltage range Three-stage surge protection Quiet operation Four IEC320 ac outlet receptacles Front panel power switch High efficiency Low cost Five year warranty

How the SLc-Be Series works


The SLc-Be Series incorporates a four-winding auto-transformer, which provides four levels of line regulation: two boost-stage and one buck-stage. Even when the input voltage varies between 154 to 306V, the output is regulated to within 207 and 253V, well within the range of most equipment.
TSi Power Corporation

A rocker style power switch/circuit breaker turns the unit on and supplies power to the equipment.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

130 Specifications SLc-1100BE/2000BE

SLc-Be

Specification
Electrical
Capacity in VA (watts) Transformer type

SLc-1100BE
1100VA (1100W)

SLc-2000BE
2000VA (2000W)

Four winding auto-transformer. 230 volts ac+/-33% 154 to 306 volts ac 50/60 Hz (47 to 63Hz) IEC320 inlet (ac input cord plug provided by customer per country spec) 6 amps @ 200vac 11 amps @ 200vac

Input
Nominal voltage Operating voltage Nominal frequency Ac input Maximum input current

Four stage 230V auto-transformer voltage regulator


Specifications

Output
Ac output voltage Maximum output Surge protection Power efficiency Power on/off switch Response time Transfer time Hysteresis Ac output receptacles Audible noise 230 volts+/-10% ac(207 to 253 vac) 5.5 amps 10 amps Three-stage surge protection system. 97% or higher under all conditions. On/off rocker power switch. Transfers to new stage within 20 cycles of new ac input voltage. Less than 4 mS between stages. 6V minimum. Prevents unnecessary switch-overs due to momentary ac sags and brownouts. Four IEC-320 Less than 45 dBA (at 1 meter) 152mm(6) wide x 127mm(5.0)high x 229mm(9)deep 8.2kgs(18 lbs) 9kgs(20 lbs)

Physical
Dimensions Weight

Safety
Safety standards Designed to meet UL, cUL and IEC standards.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Ambient temperature

Warranty
Warranty Five year limited warranty . (Replacement boards will be provided free of charge upon failure ~ board is the only part that can fail and can be easily replaced by the user).
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

SLc-Be system architecture


ac input hot fuse
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

four tap voltage regulator


+40% +20% 0% -15%

SLc - Be output 230 vac + / - 10 %

TSi Power Corporation

ground

surge protection and noise filter

hot
power supply logic

neutral

154 to 306 vac

neutral

ground

SLc-1100BE-2000BE-2006-10-16.pdf

XUPs and UPs Series ~ Uninterruptible Power Systems


UPs and XUPs Series ~ Indoor 131 Uninterruptible Power Systems

UPs and XUPs


UPs and XUPs Series Uninterruptible power systems

Note: This section also includes some wide temperature UPS suitable for use in outdoor enclosures. For self-contained Outdoor XUPs/ UPs, please see the Outdoor section.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

132 UPs and XUPs Series ~ Indoor Uninterruptible Power Systems

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

UPs-XUPs-Series-2006-10-16.pdf

XUPs-600/1000 ~ 600VA /1000VA, 420W/700W,120vac, UPS+AVR


XUPs Series 133 Rack-mountable Uninterruptible Power System

XUPs
XUPs model 600
5 amps 600 VA 420 watts 120 volts 10 min @420W 25 min @ 210W

Pure sine wave

Wide input voltage window

Voltage regulation

Rack-mountable Sine Wave UPS with AVR and a Wide Input Voltage Window
These heavy-duty XUPs Series UPS are housed in a rugged steel rack-mountable enclosure. The XUPs offers line-interactive automatic voltage regulation, over/undervoltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

1000
8.3 amps 1000 VA 700 watts 120 volts 5 min @ 700W 12 min @ 350W

Key XUPs benefits


The XUPs design, with its microprocessorcontrolled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Standard battery run-times for the XUPs-600 are approximately 10 minutes at a 420 watts load, and 25 minutes with a 210 watts load; and for the XUPs-1000, approximately 5 minutes at a 700 watts load, and 12 minutes at a 350 watts load. A built-in Anderson SB50 connector enables adding extra battery cabinets for longer times.

Typical XUPs applications


This heavy duty UPS system is ideal for protection of computers, WiFi/GSM/ CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key XUPs features


Pure sine wave inverter output Over/under-voltage protection Rack or wall mountable with optional rack/wall-mount kit Heavy-duty surge protection and noise filtering Automatic voltage regulation with wide voltage input window enhances long battery life Comprehensive array of status bargraphs for voltage, load and battery levels SNMP compatible via RS-232 port with optional SNMP adapter Both RS-232 (via DB9)and relay contact signals are provided Two year warranty on electronics One year warranty on batteries

How the XUPs works


The XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 135vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems. A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals. The power on/off switch is recessed to prevent accidental turn on or off.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

134 Specifications XUPs-600/1000

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420W) 1000VA (700W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 120 volts ac (95135vac without using batteries) 5A maximum @ 120 vac 8.3A maximum @ 120 vac 47 to 63Hz. 95 to 140 vac without using batteries.

XUPs
Rack-mountable heavy-duty line-interactive UPS with automatic voltage regulation

XUPs-600

XUPs-1000

Input
Nominal voltage Input current Operating voltage. Freq. Input receptacle/plug

IEC320 input receptacle. Line cord with NEMA 5-15P plug. 120 volts ac 115vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97 %, under full load conditions. Recessed on/off rocker style power switch. <4 milliseconds 7 amp hours, 24vdc maintenance-free sealed lead-acid batteries. 10 minutes @ 420 watts load. 25 minutes @ 210 watts load. 5 minutes @ 700 watts load. 12 minutes @ 350 watts load.

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries Battery backup time Recharge time Optional extra battery pack(s) for longer backup time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge protection Status indicators

Four hours to 95% capacity after full discharge. Matching extra battery pack(s) available with SB50 connector, and separate battery charger for enabling faster recharge times. Please call for sizing assistance. Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Ac input surge/noise filter (using inductor, capacitor and MOV). 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault and overload. Eight standard NEMA 5-15R receptacles. For others please call. 406mm(16)wide x 381mm(15)deep x 89mm(3.5)high (2U high) 15kg(32 lbs) Front pair rack-mount kit: For a 19 rack: # MK-5019A For a 23 rack: #MK-5023A 17kg(37 lbs) Center pair rack-mount kit: For a 19 rack: # MK-5019F For a 23 rack: #MK=5023F Painted steel enclosure with rubber feet.

Output receptacles

Physical
Dimensions Weights Housing Rack or wall mounting kits (optional)

Wall or floor mount kit: use # MK-5000C


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Environmental
Operating temperature

Warranty
Warranty Two year limited warranty, parts and labor. One year battery warranty.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

XUPs Series 135 Rack-mountable Uninterruptible Power System

XUPs
Front-right view

recessed on/off switch output current: three of five LEDs showing XUPs 60% loaded

- ac input on LED lit - buck mode - boost mode - overload - inverter on/off - battery failure

battery voltage level: four of five LEDs showing batteries at 80% charge status

Rear view

dc circuit breaker DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)

output ac via eight NEMA 5-15R receptacles dc Anderson SB-50 battery connector

input ac circuit breaker input ac IEC 320 receptacle for 6 foot cord with NEMA 5-15P plug (also accepts other cord/plug sets)

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

136 XUPs Series XUPs-600/1000

XUPs
XUPs-600/1000 system architecture
utility ac input
ac circuit breaker

regulated XUPs output 115vac +/-8% heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits
+10% 0% -10%

hot

relay 1 battery and charger dc neutral


inverter

relay 2 hot ac

earth ground
chassis

logic

95 135 vac

neutral

dc circuit breaker

chassis ground Anderson SB50 connector

XUPs-600/1000 at a glance
Rack or wall-mountable heavy-duty UPS with line-interactive automatic voltage regulation and wide input voltage window 10 minutes @ 420 watts load 25 minutes @ 210 watts load with XUPs-600 5 minutes @ 700 watts load 12 minutes @ 350 watts load with XUPs-1000 A built-in Anderson SB50 connector enables adding extra battery packs for longer times Less than 4ms transfer time 24vdc battery bus
TSi Power Corporation

115vac +/-8% output from 95 to 135vac input without going to batteries Microprocessor-controlled 15kHz PWM sine wave inverter Rack-mountable metal cabinet allows for rack or wall mounting using optional mounting kits SNMP compatible with optional SNMP adapter

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

XUPs-600-1000-2006-10-16.pdf

XUPs-600HV/1000HV ~ 600VA /1000VA, 420W/700W, 230vac, UPS+AVR


XUPs Series 137 Rack-mountable Uninterruptible Power System

XUPs
XUPs model 600HV
2.5 amps 600 VA 420 watts 230 volts 10 min @420W 25 min @ 210W

Pure sine wave

Wide input voltage window

Voltage regulation

Rack-mountable Sine Wave UPS with AVR and a Wide Input Voltage Window
These heavy-duty XUPs Series UPS are housed in a rugged steel rack-mountable enclosure. The XUPs offers line-interactive automatic voltage regulation, over/undervoltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

1000HV
4.2 amps 1000 VA 700 watts 230 volts 5 min @ 700W 12 min @ 350W

Key XUPs Benefits


The XUPs design, with its microprocessorcontrolled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect batteries and electronics. Standard battery run-times for the 600HV are approximately 10 minutes at a 420 watts load, and 25 minutes with a 210 watts load; and for the 1000HV, approximately 5 minutes at a 700 watts load, and 12 minutes at a 350 watts load. A built-in Anderson SB50 connector enables adding extra battery cabinets for longer times.

Typical XUPs applications


This heavy duty UPS system is ideal for protection of computers, WiFi/GSM/ CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key XUPs features


Pure sine wave inverter output Over/under-voltage protection Rack or wall mountable with optional rack/wall-mount kit Heavy-duty surge protection and noise filtering Automatic voltage regulation with wide voltage input window enhances long battery life Comprehensive array of status bargraphs for voltage, load and battery levels SNMP compatible via RS-232 port with optional SNMP adapter Both RS-232 and relay contact signals are provided Two year warranty on electronics One year warranty on batteries

How the XUPs Works


The XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 270vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems. A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals. The power on/off switch is recessed to prevent accidental turn on or off.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

138 Specifications XUPs-600HV/1000HV

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420W) 1000VA (700W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 230 volts ac (190270vac without going to batteries) 2.5A maximum @ 230vac 4.2A maximum @ 230vac 190 to 270vac without using batteries. 47 to 63Hz. IEC320 input receptacle. Line cord with IEC320P plug. 230 volts ac 230vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97 %, under full load conditions. Recessed on/off rocker style power switch. <4 milliseconds 7 amp hours, 24vdc maintenance-free sealed lead-acid batteries. 10 minutes @ 420 watts load. 25 minutes @ 210 watts load. 5 minutes @ 700 watts load. 12 minutes @ 350 watts load.

XUPs
Rack-mountable heavy-duty line-interactive UPS with automatic voltage regulation

XUPs-600HV

XUPs-1000HV

Input
Nominal voltage Input current Operating voltage. Freq. Input receptacle/plug

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries Battery backup time Recharge time Optional extra battery pack(s) for longer backup time SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Surge protection Status indicators

Four hours to 95% capacity after full discharge. Matching extra battery pack(s) available with SB50 connector, and separate battery charger for enabling faster recharge times. Please call for sizing assistance. Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). Ac input surge/noise filter (using inductor, capacitor and MOV). 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. Six standard IEC320 female outlets (receptacles). Others, please call. 406mm(16)wide x 381mm(15)deep x 89mm(3.5)high (2U high) 15kg(32 lbs) Front pair rack-mount kit: For a 19 rack: # MK-5019A For a 23 rack: #MK-5023A 17kg(37 lbs) Center pair rack-mount kit: For a 19 rack: # MK-5019F For a 23 rack: #MK=5023F Painted steel enclosure with rubber feet.

Output receptacles

Physical
Dimensions Weights Housing Rack or wall mounting kits (optional)

Wall or floor mount kit: use # MK-5000C


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Safety
Agency approvals Designed to meet UL, cUL and IEC safety standards. 0o to 40 oC (32 to 104F). 10 to 90% relative humidity(non-condensing). Two year limited warranty, parts and labor. One year battery warranty.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Environmental
Operating temperature

Warranty
Warranty

XUPs Series 139 Rack-mountable Uninterruptible Power System

XUPs
Front-right view

recessed on/off switch output current: three of five LEDs showing XUPs 60% loaded

- ac input on LED lit - buck mode - boost mode - overload - inverter on/off - battery failure

battery voltage level: four of five LEDs showing batteries at 80% charge status

Rear view

dc circuit breaker DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)

output ac via six IEC320 female outlets (receptacles) (NEMA 5-15R shown) dc Anderson SB-50 battery connector

input ac circuit breaker input ac IEC 320 male inlet for 6 foot cord with IEC320 female plug (also accepts other cord/plug sets)

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

140 XUPs Series XUPs-600HV/1000HV

XUPs
XUPs-600HV/1000HV system architecture
utility ac input regulated XUPs output 230vac +/-8% hot fuse earth ground
chassis

190 to 270 vac

neutral

heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits

+10% 0% -10%

relay 1 battery and charger dc neutral


inverter

relay 2 hot ac

logic

chassis ground Anderson SB50 connector

XUPs-600HV/1000HV at a glance
Rack or wall-mountable heavy-duty UPS with line-interactive automatic voltage regulation and wide input voltage window 10 minutes @ 420 watts load 25 minutes @ 210 watts load with XUPs-600HV 5 minutes @ 700 watts load 12 minutes @ 350 watts load with XUPs-1000HV A built-in Anderson SB50 connector enables adding extra battery packs for longer times Less than 4ms transfer time 24vdc battery bus
TSi Power Corporation

230vac +/-8% output from 190 to 270vac input without going to batteries Six IEC320 female outlets Microprocessor-controlled 15kHz PWM sine wave inverter Rack-mountable metal cabinet allows for rack or wall mounting using optional mounting kits SNMP compatible with optional SNMP adapter

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

XUPs-600HV-1000HV-2006-10-16.pdf

UPs-400Wtb ~ 400VA, 250W, 120vac, with wide temperature battery


UPs Flexible Series 141 Uninterruptible Power System

UPs
UPs model 400Wtb
400 VA 250 watts 120 volts 8 min @ 250W 20 min@ 125W

Flexible

Wide temperature battery

Flexibility of adding extra battery cabinets

Wide Temperature Battery UPS with the Flexibility of Adding Extra Battery Cabinets
TSi Power's Flexible Series wide temperature battery UPS is an excellent choice for those applications that require battery backup with good surge protection, a wide temperature battery for usage in more extreme environments, and the flexibility of being able to add additional battery cabinets for extended run-time.

Typical applications
UPs-400Wtb is the ideal UPS for computer or telecommunications equipment in extreme wide temperature -20o to +60oC(-4 o to +140 oF) environments where ac power delivery is unreliable and long battery backup times may be necessary. The UPs-400Wtb is suitable where power outages are a regular occurrence, or in areas where utilities need to conduct rolling blackouts.

Key features
Wide temperature battery -20o to +60oC (-4o to +140 oF) Add-on battery cabinet flexibility User-selectable 50/60Hz frequency Electronics ~ Two year warranty Batteries ~ One year warranty

Key benefits
The UPs-400Wtb protects connected equipment from: power supply failure, erroring, system lockups and re-boots. It contributes to enhanced systems operation, greater reliability, improved repeatability, and extended operating life. Typical back-up time fully loaded is 8 minutes, but 20 minutes can be obtained when the unit is loaded to 50% of its capacity. Thus, an application requiring 200VA can be provided with 20 minutes of hold-up. The capability of adding extra EXt-400Wtb external battery packs also makes this a very cost-effective choice for enabling nearly unlimited holdup times.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

How the UPs-400WTB works


The UPs-400Wtb continually provides surge protection with a capacitive element, and coordinated MOV surge protection. Upon loss of power, the audible alarm beeps about once a second, as the battery inverter kicks in within 8ms, which means equipment will continue to operate without interruption. When the battery level drops until only a few minutes of holdup time remain, the alarm will beep, and the LED will flash more rapidly, alerting of impending shutdown. A DB-9 female connector provides communications capability with monitoring software which can safely save open files and automatically shutdown your systems.

TSi Power Corporation

Custom Settings: DIP switches in the rear panel allow the user to set brownout sensitivity, inverter operating frequency, or alarm mode, for complete flexibility and control of the UPS.

142 Specifications UPs-400Wtb

Specifications Specification
Electrical Capacity in VA (watts) UPS type Input Nominal voltage Operating voltage Ac input cord Output Nominal voltage Nominal frequency Power efficiency Transfer time UPS inverter output Battery backup time

UPs

Flexible

UPs-400Wtb
400VA (250 watts) Single conversion standby with 4 to 8ms transfer time. 120 volts ac, single phase. 95 to 135 volts ac. 47 to 63Hz, sinusoidal. 6 foot cord with 5-15P plug 120 volts ac, single phase, sine wave during normal operation. 50/60Hz +/-3% (user-selectable) 98% or higher during ac operation, 80% or higher during battery inverter operation. 4 to 8ms typical between ac and inverter. 105 to 130V RMS, 50/60Hz +/-1%, pulse-width-modulated, modified square wave. 8 minutes @ full load (250 watts) 20 minutes @ half load (125 watts) 8 hours to return to 90% capacity after full discharge. A matching extra battery cabinet with separate charger, supplying an additional 40 minutes @ full load, 90 minutes @ half load. With a weight of 15.9kg(35 lbs), and same size as the UPs-400Wtb. EXt-400Wtbs battery recharge time is 12 hours to 90% capacity. MOV spike/surge suppression. ANSI/IEEE C62.41-1991 test pulse, Category A3, ring wave, 6000V, 200A. LEDs and audible signals for ac, inverter, and battery status. DB-9 female connector provides communications capability with optional monitoring and automatic shutdown software. Two NEMA 5-15R 125mm(5)wide x 178mm(7)high x 394mm(16)deep 10.7 kg (23.5 lbs) Designed to meet UL and cUL 1778 standards External fuse protects all ac circuits. Internal fuses protect all dc circuits. Durable, all-steel chassis withstands transport in hostile environments and operation in any indoor application.
-20o to +60oC(-4o to +140 oF). 90% relative humidity, non-condensing at 25 oC.

UPs-400Wtb with wide temperature battery and add-on battery cabinet flexibility

(for more time see below)

Recharge time Optional # EXt-400Wtb Extra battery pack for longer back-up time w/Anderson SB50conn. Surge protection Surge test conditions Indicators and alarms Communications interface Ac output receptacles Physical Dimensions Weight Safety Safety standards Safety and reliability

Rear view
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Environmental Ambient temperature Warranty Warranty

Two year limited warranty, parts and labor. One year battery warranty.

UPs-400Wtb system architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Anderson SB50 external battery connector hot fuse ground surge protection wide temp. battery and charger relay hot dc to ac inverter neutral

TSi Power Corporation

UPS output
ground

neutral

UPs-400Wtb-2006-10-16.pdf

XUPs-600/1000-8022 ~ 600VA /1000VA, 420W/700W, 115vac, OEM UPS+AVR


XUPs Series 143 Modular OEM Uninterruptible Power System

XUPs
XUPs model 600-8022
3.6 amps 600 VA 420 watts 115 volts (OEM version, no batteries)

Pure sine wave

Wide input voltage window

Voltage regulation

Modular OEM Sine Wave UPS with AVR and a Wide Temperature Design
These heavy-duty XUPs Series UPS are housed in a rugged aluminum enclosure and designed for OEMs wanting a modular UPS with wide temperature capabilities and suitable for use in existing OEM outdoor enclosures. The XUPs offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

1000-8022
6 amps 1000 VA 700 watts 115 volts (OEM version, no batteries)

Key modular XUPs OEM benefits


The XUPs design, with its microprocessorcontrolled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect the electronics. This OEM system is designed for use with OEM supplied wide temperature batteries and includes a built-in battery charger for a recommended external battery bank size of from 50 to 280 Ah.

Typical OEM applications


This heavy duty UPS system is ideal for protection of telecommunications systems, WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key XUPs 8022 features


Pure sine wave inverter output Over/under-voltage protection Suitable for use in outdoor rated enclosures with OEM provided wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation with wide voltage input window enhances long battery life Comprehensive array of status bargraphs for voltage, load and battery levels SNMP compatible via RS-232 port with optional SNMP adapter RS-232 and relay contact signals Temperature-compensated battery charger maximizes battery lifetime Two year warranty

How the XUPs works


The XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 140vac, and undervoltage protection with a threshold of 95vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems. A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

144 Specifications XUPs-600/1000-8022

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420W) 1000VA (700W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 115 volts ac (95 to 140vac without going to batteries) 7A maximum @ 115vac 10A maximum @ 115vac 95 to 140vac without using batteries. 47 to 63Hz. Male IEC320-C14 inlet. 115 volts ac 115vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97 %, under full load conditions. On/off rocker style power switch. <4 milliseconds Ac input surge/noise filter (using inductor, capacitor and MOV). Designed for 24 vdc gel-cell wide temperature gel-cell battery bank consisting of multiples of two 12V batteries. e.g. Two 12V batteries in series, or four batteries if two 24V battery banks are paralleled; or six batteries if three 24V battery banks are paralleled. 50 to 280Ah. Temperature compensated battery charger. 27V, 5A. Temperature compensated battery charger. 27V, 10A.

XUPs

XUPs-600-8022

XUPs-1000-8022

Input
Nominal voltage Input circuit breaker Operating voltage. Freq.

Modular UPS designed for use in outdoor enclosures with OEM supplied wide temperature batteries

Input inlet

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Surge protection Designed for wide temperature batteries *batteries not included Battery charger Recharge time Dc breaker SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Status indicators

After full discharge, 24V, 30Ah battery will be recharged within 8 hours to 95% capacity, and a 24V, 100Ah battery bank within 24 hours. 30A 40A Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. Relay contact signals for: ac good/ ac fail and battery ok/battery low. Low voltage alarm sounds when battery voltage drops below 22vdc, and low voltage disconnect will occur at 21vdc. Two NEMA 5-15R receptacles/outlets. For HW or other, please call. 300mm(12)wide x 250mm(10)deep x 150mm(6)high 8kg(18 lbs) 13kg(28 lbs) Aluminum enclosure with rubber feet. Designed to meet UL, cUL and IEC safety standards. -20o to 60 oC (-4 to 140F). 10 to 90% relative humidity (non-condensing). Two year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Alarm signals

Output receptacles

Physical
Dimensions Weights Housing
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Safety
Agency approvals

Environmental
Operating temperature

Warranty
Warranty

XUPs Series 145 Modular OEM Uninterruptible Power System

front view

XUPs

on/off switch output current: three of five LEDs showing XUPs 60% loaded

- ac input on LED lit - buck mode - boost mode - overload - inverter on/off - battery failure

battery voltage level: four of five LEDs showing batteries at 80% charge status

rear view

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

dc circuit breaker shielded hardwire terminals for battery connection

input ac circuit breaker IEC320- C14 ac inlet *for OEM provided line cord and typical NEMA 5-15P plug

DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter) output ac via two NEMA 5-15R receptacles

146 XUPs Series XUPs-600/1000-8022

XUPs
XUPs-600/1000-8022 system architecture
utility ac input hot
ac circuit breaker

earth ground
chassis

neutral
95 to 140 vac

heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits

+10% 0% -10%

relay 1 temperature compensated charger


dc circuit breaker

regulated XUPs output 115vac +/-8% relay 2 dc neutral


inverter

hot ac

logic

chassis ground external 24 vdc battery connector

XUPs-600/1000-8022 at a glance
OEM design heavy-duty wide-temperature UPS with line-interactive automatic voltage regulation and wide input voltage window Temperature compensated battery charging voltage maximizes battery lifetime
battery charging voltage
29V 28V 27V 26V -20 -10

115vac +/-8% output from 95 to 140vac input without going to batteries Two 5-15R receptacles/outlets Wide temperature design Microprocessor-controlled 15kHz PWM sine wave inverter Less than 4ms transfer time Rugged aluminum enclosure

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

operating temperature (oC)

10 20 30 40 50 60

SNMP compatible with optional SNMP adapter

XUPs-600-1000-8022-OEM-115V-2006-10-16.pdf

XUPs-600/1000-8023 ~ 600VA /1000VA, 420W/700W, 230vac, OEM UPS+AVR


XUPs Series 147 Modular OEM Uninterruptible Power System

XUPs
XUPs model 600-8023
1.8 amps 600 VA 420 watts 230 volts (OEM version, no batteries)

Pure sine wave

Wide input voltage window

Voltage regulation

Modular OEM Sine Wave UPS with AVR and a Wide Temperature Design
These heavy-duty XUPs Series UPS are housed in a rugged aluminum enclosure and designed for OEMs wanting a modular UPS with wide temperature capabilities and suitable for use in existing OEM outdoor enclosures. The XUPs offers line-interactive automatic voltage regulation, over/under-voltage protection, surge protection with heavy duty noise filtering, communications capability and optional extended battery backup.

1000-8023
3.0 amps 1000 VA 700 watts 230 volts (OEM version, no batteries)

Key modular XUPs OEM benefits


The XUPs design, with its microprocessorcontrolled 15kHz sine wave inverter, reduces the number of solid-state devices required for power conversion, thereby yielding a high level of reliability. Built-in automatic voltage regulation enables a wide input voltage window within which the XUPs can deliver power without having to drain or exercise the batteries, thereby ensuring long battery life. A fan exhausts hot air to protect the electronics. This OEM system is designed for use with OEM supplied wide temperature batteries and includes a built-in battery charger for a recommended external battery bank size of from 50 to 280 Ah.

Typical OEM applications


This heavy duty UPS system is ideal for protection of telecommunications systems, WiFi/GSM/CDMA/satellite base stations, wireless communications/perimeter surveillance and security/gate control systems, LED traffic light/roadway display systems and industrial remote terminal units (RTUs).

Key XUPs 8023 features


Pure sine wave inverter output Over/under-voltage protection Suitable for use in outdoor rated enclosures with OEM provided wide temperature batteries Heavy-duty surge protection and noise filtering Automatic voltage regulation with wide voltage input window enhances long battery life Comprehensive array of status bargraphs for voltage, load and battery levels SNMP compatible via RS-232 port with optional SNMP adapter RS-232 and relay contact signals Temperature-compensated battery charger maximizes battery lifetime Two year warranty

How the XUPs works


The XUPs Series UPS provides automatic voltage regulation with surge protection and noise filtering, and also overvoltage protection with a threshold of 280vac, and undervoltage protection with a threshold of 190vac. Upon a brownout, overvoltage, or loss of power, the XUPs will transfer to battery power in less than 4 milliseconds, enabling uninterrupted operation of computer, telecom, surveillance, signaling or other electronic systems. A comprehensive array of power, battery level, voltage level, and inverter status LED indicators is provided for visual assessment of UPS status. A DB-9 port is provided for communication using RS-232 or relay dry contact signals.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

148 Specifications XUPs-600/1000-8023

Specifications Specification
Electrical
Capacity in VA (watts) UPS topology 600VA (420W) 1000VA (700W) High efficiency line-interactive with 15kHz PWM sine wave inverter. 230 volts ac (190 to 280vac without going to batteries) 4A maximum @ 230vac 5A maximum @ 230vac 190 to 280vac without using batteries. 47 to 63Hz. Male IEC320-C14 inlet. 230 volts ac 230vac +/-8% upon changes in line or load. 3:1 Pure sine wave, less than 3% THD with linear load. 97 %, under full load conditions. On/off rocker style power switch. <4 milliseconds Ac input surge/noise filter (using inductor, capacitor and MOV). Designed for 24 vdc gel-cell wide temperature gel-cell battery bank consisting of multiples of two 12V batteries. e.g. Two 12V batteries in series, or four batteries if two 24V battery banks are paralleled; or six batteries if three 48V battery banks are paralleled. 50 to 280Ah. Temperature compensated battery charger. 27V, 5A. Temperature compensated battery charger. 27V, 10A.

XUPs

XUPs-600-8023

XUPs-1000-8023

Input
Nominal voltage Input circuit breaker Operating voltage. Freq.

Modular UPS designed for use in outdoor enclosures with OEM supplied wide temperature batteries

Input inlet

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Surge protection Designed for wide temperature batteries *batteries not included Battery charger Recharge time Dc breaker SNMP interface for UPS monitoring and automatic shutdown configuration (optional) Status indicators

After full discharge, 24V, 30Ah battery will be recharged within 8 hours to 95% capacity, and a 24V, 100Ah battery bank within 24 hours. 30A 40A Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the UPS can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external UPS monitoring/ configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols). 5 LED load level indicator: 0 to 100% of rated load. 5 LED battery charge level indicator from 0 to 100% of rated charge. 3 LED indicators for: in boost, buck or normal mode. 3 LED indicators for: inverter on/off, battery fault, and overload. Relay contact signals for: ac good/ ac fail and battery ok/battery low. Low voltage alarm sounds when battery voltage drops below 22vdc, and low voltage disconnect will occur at 21vdc. Two standard IEC320-C13 female outlets. For HW/other, please call. 300mm(12)wide x 250mm(10)deep x 150mm(6)high 8kg(18 lbs) 13kg(28 lbs) Aluminum enclosure with rubber feet. Designed to meet UL, cUL and IEC safety standards. -20o to 60 oC (-4 to 140F). 10 to 90% relative humidity (non-condensing). Two year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Alarm Signals

Output receptacles

Physical
Dimensions Weights Housing
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Safety
Agency approvals

Environmental
Operating temperature

Warranty
Warranty

XUPs Series 149 Modular OEM Uninterruptible Power System

front view

XUPs

on/off switch output current: three of five LEDs showing XUPs 60% loaded

- ac input on LED lit - buck mode - boost mode - overload - inverter on/off - battery failure

battery voltage level: four of five LEDs showing batteries at 80% charge status

rear view

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

dc circuit breaker shielded hardwire terminals for battery connection

input ac circuit breaker IEC320-C14 ac inlet *for OEM provided line cord and plug

DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter) output ac via two standard IEC320-C13 female outlets

150 XUPs Series XUPs-600/1000-8023

XUPs
XUPs-600/1000-8023 system architecture
utility ac input hot
ac circuit breaker

earth ground
chassis

neutral
190 to 280 vac

heavy - duty ac surge protection, noise filter and overvoltage, undervoltage disconnect circuits

+10% 0% -10%

relay 1 temperature compensated charger


dc circuit breaker

regulated XUPs output 230vac +/-8% relay 2 dc neutral


inverter

hot ac

logic

chassis ground external 24 vdc battery connector

XUPs-600/1000-8023 at a glance
OEM design heavy-duty wide-temperature UPS with line-interactive automatic voltage regulation and wide input voltage window Temperature compensated battery charging voltage maximizes battery lifetime
battery charging voltage
29V 28V 27V 26V -20 -10

230vac +/-8% output from 190 to 280vac input without going to batteries Two IEC320-C13 female outlets Wide temperature design Microprocessor-controlled 15kHz PWM sine wave inverter Less than 4ms transfer time Rugged aluminum enclosure

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

operating temperature (oC)

10 20 30 40 50 60

SNMP compatible with optional SNMP adapter

XUPs-600-1000-8023-OEM-230V-2006-10-16.pdf

UPs-600 ~ 600VA, 400W, 120vac


UPs Flexible Series 151 Uninterruptible Power System

UPs
Model UPs-600
600 VA 400 watts 120 volts 8 min @ 400W 20 min@ 200W

Flexible

Wide temperature battery

Flexibility of adding extra battery cabinets

Basic UPS plus theFlexibility of Adding Extra Battery Cabinets


TSi Power's Flexible Series UPS is an excellent choice for those applications that require battery backup with good surge protection, And the flexibility of being able to add additional battery cabinets for extended run-time.

Typical applications
UPs-600 is the ideal UPS for computer or telecommunications equipment in environments where ac power delivery is unreliable and several hours of backup time are necessary.

Key benefits
The UPs-600 protects connected equipment from power supply failure, erroring, system lockups and re-boots. It contributes to enhanced systems operation, greater reliability, improved repeatability, and extended operating life. Typical back-up time fully loaded is 8 minutes, but 20 minutes can be obtained when the unit is loaded to 50% of its capacity. Thus, an application requiring 300VA can be provided with 20 minutes of hold-up. The capability of adding extra EXt-400 external battery packs also makes this a very cost-effective choice for enabling nearly unlimited battery backup times. Custom settings: DIP switches in the rear panel allow the user to set brownout sensitivity, inverter operating frequency, or alarm mode, for complete flexibility and control of the UPS.

Key features of the UPs-600


Add-on battery cabinet flexibility Surge protection is included DB-9 female connector provides communications capability with optional monitoring and automatic shutdown software Customizable brownout sensitivity User-selectable 50 or 60Hz 2 year warranty on electronic parts 1 year warranty on batteries

How the UPs-600 works


The UPs-600 continually provides power protection with a capacitive element and a fast-acting MOV (metal oxide varistor).
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation the unit transfers to the battery inverter in less

Upon loss of power, the audible alarm beeps as than 8ms. When the battery level drops until only a few minutes of holdup time remain, the alarm will beep, and the LED will flash more rapidly, alerting of impending shutdown. A DB-9 connector provides communications with monitoring software which can safely save open files and automatically shut down your systems.

152 Specifications UPs-600

Specification
Electrical
Capacity in VA (watts) UPS type

UPs-600
600VA (400 watts) Single conversion standby with 4-8ms transfer time. 120 volts ac single phase 95 to 135 volts ac. 47 to 63Hz, sinusoidal 6 foot long ac cord with 5-15P plug 120 volts ac, single phase, sine wave during normal operation. 50/60Hz +/-3% (user-selectable) 98% or higher during ac operation, 80% or higher/battery inverter oper. 4 to 8ms typical between ac and inverter. 105 to 130 vac RMS. 50/60 Hz+/-1% Pulse-width-modulated, modified square wave. 8 minutes @ full load (400 watts) 20 minutes @ 1/2 load (200 watts) 8 hours to return to 90% capacity after full discharge. A matching extra battery cabinet with separate charger, supplying an additional 45 minutes @ full load, 110 minutes @ half load. With a weight of 35 lbs (15.9kg), and same size as the UPs-600. EXt-400s battery recharge time is 12 hours to 90% capacity. MOV spike/surge suppression. ANSI/IEEE C62.41-1991 test pulse, Category A3 ring wave, 6000V, 200A. LED indicators and audible signals for ac, inverter, and battery status. DB-9 female connector provides communications capability with optional monitoring and automatic shutdown software. Two (NEMA 5-15R) 125mm(5)wide x 178mm(7)high x 394mm(16)deep 9.1 kg(22 lbs) Durable, all-steel chassis designed for indoor applications. Designed to meet UL and cUL 1778 standards External fuse protects all ac circuits. Internal fuses protect all dc circuits.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Input
Nominal voltage Operating voltage Ac input cord

UPs-600 with add-on battery cabinet flexibility

Output
Nominal voltage Nominal frequency Power efficiency Transfer time Inverter output Battery backup time Recharge time Optional # EXt-400 extra battery pack for longer backup time w/Anderson SB50 conn Surge protection Surge test conditions Indicators and alarms Communications interface

(for more time see below)

Rear view
Specifications
TSis ongoing product improvement process makes these specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Ac output receptacles

Physical
Dimensions Weight Enclosure

Safety
Safety standards Safety and reliability

Environmental
Ambient temperature

Warranty
Warranty Two year limited warranty, parts and labor. One year battery warranty.

ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

UPs-600 system architecture


hot fuse ground surge protection wide temp. battery and charger

Anderson SB50 external battery connector relay hot dc to ac inverter neutral

TSi Power Corporation

UPs output
ground

neutral

UPs-600-2006-10-16.pdf

UPs-10000/16000/21000 ~ 1 /1.6/2.1kVA, 750/1000/1500W, 120vac


UPs Premium Series 153 Uninterruptible Power System

UPs
Models UPs-10000

Premium

Pure sine wave

Ferroresonant voltage regulation

Transformer isolated

Heavy-duty UPS with Ferroresonant Isolation Transformer Voltage Regulation


TSi Powers Premium Series UPS are
constructed with a rugged, ferroresonant no-break design and a fully isolated sinewave output with neutral-to-ground bond. This series offers the best surge protection available, with excellent noise filtering, remote on/off control, and optional extended battery back-up.

1000 VA 750 watts 120 vac 10 min@ 750W 30 min@375W

UPs-16000
1600 VA 1200 watts 120 vac 10min@1200W 30 min@ 600W

Key benefits
This rugged industrial-strength ferroresonant design reduces the number of solid-state devices required for power conversion and is suitable for use in severe environments. All models can be rack-mounted in 19, 23, or 24" racks. Standard battery run-time is about 30 minutes under typical 50% load. If additional battery runtime is required, EXt-8000 Battery Extension Units can be daisy-chained to the UPS unit to provide hours of battery runtime.

Typical applications
These heavy-duty UPS are ideal for backing up critical servers, routers, hubs, networks, factory/industrial process controls, systems going to export markets, critical telecom equipment, ISPs and other areas where reliability is a must, extended back-up might be necessary, or the power source is unpredictable.

UPs-21000
2100 VA 1500 watts 120 vac 10min@1500W 30 min@ 750W

How the Premium Series works


The constant output isolation transformer provides 100% isolation from the input ac line. The regulated output protects switchmode power supplies from failure caused by unstable ac mains. The secondary neutral is bonded to ground, thus eliminating all surge voltages between neutral and ground. This type of surge protection is superior to all other technologies and is further enhanced thanks to the built-in low-pass filter, which takes the edge off even very fast transients. UPS status is monitored by LED indicators, LED bargraph displays and audible signals for ac status, inverter status, output voltage, load, and battery status. Alarm interface: Upon loss of power, the audible alarm will beep. Because the Premium Series is a continuous sinewave No-break UPS system, power to equipment loads will be completely unaffected. As the TSi Power Corporation battery level drops until only a few minutes Represented by of holdup time remains, the audible alarm will CareBase change, warning of impending shutdown. Michael Gibson Post Office Box 2987 Communications: A DB-9 female connector Glenwood Springs, CO in the rear panel provides communications 81602-2987 USA capability with most network operating systems Phone +1 970 945 2770 800 430 2770 (USA.CAN) such as Novell, Unix, Solaris, Windows, Linux, michaelg@carebase.com etc. Optional monitoring software may be www.carebase.com Copyright 2006 TSi needed for some operating systems.

Key features of the TSi Power Premium Series UPS


Pure sine wave output No-break UPS Best surge protection available Voltage regulation and integral isolation transformer Reduces harmonics from Non-linear loads Extended back-up modules available Rack-mount kits available Remote shutdown, auto-restart and alarm interface Comprehensive array of status bargraphs for voltage, load and battery levels Network compatible Two year warranty on electronic parts One year warranty on batteries

154 Specifications UPs-10000/16000/21000

Specifications Specification
Electrical
Capacity in VA (watts) Transformer type Isolation 1000VA (750watts) 1600VA (1200watts) 2100VA (1500 watts) Ferroresonant constant voltage output isolation transformer. 100% input/output isolation & output neutral-ground bonding qualifies the UPS output as a separately derived ac power source via NEC 250-5D. 120 volts ac 90 to 140 volts ac without using batteries 60Hz sinusoidal +/- 5% 6 foot line cord, 2.5mm2 (14AWG) SJT with NEMA 5-15P plug 120volts +/-3 vac +/-3% upon changes in line or load 3:1 Pure sine wave, less than 3% THD with linear load 90%, under full load conditions On/off rocker style power switch Zero (continuous no-break) Maintenance-free sealed lead-acid batteries 10 - 15 minutes of backup time @ full load (30min. under typical 1/2 load) 8 hours to return to 90% capacity after full discharge. A matching extra battery cabinet with separate charger, supplying an additional 35 to 45 minutes backup time (details - see EXt specs). Weight is 70 lbs (32kg), size is the same as the UPs-10000. EXt-8000s battery recharge time is 8 hours to 90% capacity. Low-pass filter reduces noise over a wide frequency range. A three-stage surge protection system consisting of ferroresonant isolation transformer, capacitor and M.O.V. is included. ANSI/IEEE C62.41-1991 test pulse. Category B3, Combination wave, 6000volts, 3000amps. Test pulse injection: Line-Neutral, Line-Ground and Neutral-Ground. Combination wave: L-N: 35V, L-G: 35V, N-G: 0.5V 10 LED bar-graph indicators: output voltage, battery voltage, and show the output load from 0 to 100% of rated power. 4 status LEDs indicating - ac power present; inverter status; output mode; ac load, and battery status. Four NEMA 5-15R 431.8x533.4x127mm (17Wx21Dx5H) 31.8 kg(70 lbs) Six NEMA 5-15R 431.8x533.4x165mm (17Wx21Dx6.5H) 49.9 kg(110 lbs) Six NEMA 5-15R 431.8x533.4x165mm (17Wx21Dx6.5H) 59 kg(130 lbs)

UPs

Premium

UPs-10000

UPs-16000

UPs-21000

Heavy-duty UPS with ferroresonant voltage regulating isolation transformer and add- on battery cabinet flexibility

Input
Nominal voltage Operating voltage Nominal frequency Ac input cord

Output
Nominal voltage Voltage regulation Crest ratio Output waveform Power efficiency Power on/off switch Transfer time Batteries

UPs-10000

Rear view UPs-10000

Battery backup time Recharge time Optional # EXt-8000 extra battery pack for longer backup time w/Anderson SB50 conn Noise filtering Surge protection

UPs-16000/ 21000

Surge test conditions Surge let-through voltages Indicators

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Ac receptacles

Physical
Dimensions Weight Rack mount options Steel housing

Please call for factory assistance on rack-mount kit options. Durable, all-steel chassis withstands transport in hostile environments and operation in any indoor application. Designed to meet UL, cUL and IEC safety standards. FET inverter circuit ensures efficiency and reliability.
0 to 40C (32 to 104F). 10 to 90% relative humidity(non-condensing).

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Safety
Agency approvals FET inverter circuit

Environmental
Ambient temperature Cooling method Forced air (fan cooled). Two year limited warranty, parts and labor. One year battery warranty.

Warranty
Warranty

UPs

Premium

UPs Premium Series 155 Uninterruptible Power System

Heavy-duty UPS with ferroresonant voltage regulating isolation transformer and add- on battery cabinet flexibility

UPS-10000

UPS-16000/ 21000

UPs Premium Series system architecture


ac Input hot fuse ground 3 - way MOV surge protection EMI / RFI noise filter solid-state relay resonant capacitor ferroresonant transformer

neutral +48vdc
to optional EXt-8000 extra battery cabinet

hot battery

fuse inverter neutral UPS output

via Anderson SB-50 connector

logic ground

battery charger

ground

48vdc battery bus Anderson SB50 battery connector: for optional single/multiple extra battery cabinets, or external 48vdc battery bank
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

No-break zero transfer time Ferroresonant constant voltage-regulating isolation transformer Rack-mountable

TSi Power Corporation

1000VA / 750 watts rating 1600VA / 1200 watts rating 2100VA / 1500 watts rating

UPs-10000-16000-21000-2006-10-16.pdf

156 UPs Premium Series Uninterruptible Power System

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

XUPs and UPs Automatic Shutdown Instructions for Windows XP Professional


UPs Series 157 UPs Shutdown Instructions for Windows XP

UPs
Configuring Windows XP For TSi UPs

Automatic Shutdown

Auto-shutdown

UPS signal polarities

Hibernation

Instructions for Configuring System AutoShutdown in Windows XP Professional


Windows XP Professional now has UPS based computer system automatic shutdown built-in.

Preparing for UPS configuration


Before you start the configuration in Windows XP, make sure your UPS communication cable is properly plugged into a COM port on your computer. To help prevent any possible damage, do this while both the computer and UPS are turned off, and both units have their plugs inserted into properly grounded outlets.

4. Under Select model, click on Custom.

Setting up UPS power options


Please Note: These instructions are for configuring Windows XP Pro for TSi Power UPS. Other software may require different instructions, but the Power Fail, Low-Battery and UPS Shutdown signal polarities being positive will remain the same.

1. Click Windows- Start > Control Panel > Power Options, then the UPS tab.

5. Check that the Default Port Setting is correct (probably COM 1). If your UPS is plugged into a different port, change it accordingly. 6. Click on the Next button.

UPs interface configuration


7. Checkmark all three boxes for: Power Fail/On Battery, Low Battery, and UPS Shutdown.

2. Then, click on the Select button. This will open up the UPS selection dialog box. 3. Under Select Manufacturer, click on the drop-down menu button, and click on Generic.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

8. Select Positive polarity for all three. 9. Then, click on the Finish button. This will then open up the Power Options Properties dialog box again.

TSi Power Corporation

158 UPs Series UPs Shutdown Instructions for Windows XP

UPs

Automatic Defining UPS power options Shutdown 10. Click on the Hibernation tab.

14. Checkmark the Enable all notifications box, and set for 30 seconds, or other time, depending on your needs. Generally, electric utilities have automatic reclosure operations which attempt to restore power up to 3 times, each time taking about 10 seconds. If power hasnt been restored after 30 seconds, you usually are in a hard down situation, and most likely will be out of power for at least 30 minutes. 15. In the Critical alarm area, checkmark the Minutes on battery before critical alarm. To preserve battery life, once you are past 30 seconds during an outage, it is usually advisable to start hibernation/shutdown, or shutdown, as soon as possible. Two minutes is the fastest setting. 16. Checkmark the Finally turn off the UPS. With this checked, the system will then automatically turn off the UPS, and it will automatically come back up when the AC power is restored. 17. Click on the Okay button. This will return the Power Options Properties dialog box with UPS tab.

11. Checkmark Enable hibernation if you want the system to be able to save your open files and conduct an orderly shutdown after a certain amount of time. Except for certain unusual situations, this is usually the preferred choice. 12. Next, click on the UPS tab again. Then,click on the Configure button.

Setting up your UPS configuration


13. Now, set up the UPS Configuration.

18. Click on either OK or Apply to finish. 19. Save any files you may have open.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

20. Open some test files. 21. Test the system with some outages a few times to ensure correct operation. Note: Use a circuit breaker or some other safe means to simulate the outages. Do not just unplug the UPS, as doing so disconnects the safety ground.
UPs-Shutdown-Instructions-Win-XP-2006-10-16.pdf

VRp Series ~ Precision PWM Automatic Voltage Regulators


VRp Series - Indoor 159 Precision Automatic Voltage Regulators

VRp
Precision Automatic Voltage Regulators

VRp Series

Power with a Precision Attitude

Note: For Outdoor VRp/VRp-ILc units please see Outdoor Series section

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

160 VRp Series - Indoor Precision Automatic Voltage Regulators

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

VRp-Series-2006-10-16.pdf

ILc-2000-VRp-Dual-Range ~ 2kVA, 1.8kW, 120+240vac


ILc-VRp Series 161 Isolation Transformer Line Conditioner + Precision Voltage Regulator

ILc-VRp
ILc-VRp model
ILc-2000-VRpDual Range
2000VA 2000 watts input: 120 or 240vac output: 115 &/or 230vac

Dual Range

International

Precision voltage regulator

Isolation transformer

Isolation Line Conditioner with Precision PWM Automatic Voltage Regulation and 120vac or 240vac Input Capability
Continuous fast and no-break PWM voltage regulation
isolation transformer allows trouble-free operation of electronic equipment over a very wide ac voltage range of 120 or 240vac +/-20% found in many developing countries. Output regulation responds in less than one line cycle and corrects output voltage to +/-2.5% with 20,000 corrections per second. There is no switching of taps or otherwise a break in the power path as continuous PWM (pulse-widthmodulation) switching of the primary winding of a buck-boost transformer leaves the secondary power path intact.

The ILc-VRp dual range automatic precision Power with a Precision Attitude voltage regulator with built-in low-impedance

Typical ILc-VRp applications


Designed for applications where absolutely safe and precisely regulated ac power is required, such as mobile telecommunications, wireless, satellite and carrier equipment.

Key features of the ILc-VRp Series dual range isolation line conditioner with precision PWM automatic voltage regulation
Dual voltage input enables use with either 120vac or 240vac power Dual voltage output enables 115vac via two NEMA 5-15R receptacles, and/or 230vac via one BS1362 socket Outstanding voltage regulation under normal input range of: +/- 20% of 120 or 240vac, output voltage will be a precision 115 or 230vac +/-2.5% (47~ 63Hz)
TSi Power Corporation

Failsafe: automatic bypass Coordinated surge protection per IEC61312 Common-mode noise elimination Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/ S Lightweight design Two year warranty

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

No switching of power path and unit always starts up on sine wave zero crossing, reducing inrush currents

162 ILc-VRp Series ILc-2000-VRp-Dual Range

ILc-VRp

Dual Range

Key ILc-2000-VRp -Dual Range system benefits


The lightweight, high efficiency dual voltage range ILc-VRp is easy to install in indoor environments. The unit comes in a rack-mountable enclosure and has the ability to accept either 120vac or 240vac +/-20% input via either a IEC320 C-20 input connector for the 120vac, or an IEC320C-13 inlet connector for the 240vac. Power output is up to 1800watts, and can be drawn from Either/or Both 115vac and 230vac +/-2.5%, as long as total output power is not exceeded. 115vac and 230vac outputs are provided via two standard NEMA 5-15R receptacles for the 115vac, and one UK BS1363 outlet connector for the 230vac.

Dual voltage range isolation transformer with precision PWM automatic voltage regulator

The automatic bypass assures that connected equipment will not shut down, even if the ILc-VRp unit were to fail. The ILc-VRp is compatible with all loads as it does not switch any components in the power path. ILc-VRps ultra-low impedance assures stability even with the most demanding loads. The isolation line conditioner components provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups. Also, a reduction in equipment down time and service costs can be expected. Maximum transformer and regulator performance, reliability and lifetime is achieved by a design with no moving mechanical parts other than a thermostatically controlled high reliability cooling fan to control the units internal temperature.

How the ILc-VRp 2000VA Dual Range system works


The ILc-VRp unit is comprised of an automatic precision voltage regulator, and an isolation line conditioner. Unit has a front panel key switch to select either 120vac or 240vac, with a safety interlock to prevent voltage from appearing on unused terminals.

Power with a Precision Attitude

The high frequency IGBT driven converter microprocessor takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230 or 120vac output, cycle by cycle. Voltage correction times do not exceed 1 cycle, or 20 milliseconds for all mains ac voltage changes, even for instantaneous voltage changes from 96 to 144vac (when at the 120vac input setting) or from 192 to 288vac (when at the 240vac input setting). The ILc-VRp starts on sine wave zero voltage crossing point upon turn-on. This reduces potentially damaging inrush currents into difficult loads. The automatic bypass will be activated when there is a fault condition, and makes operation possible without regulation. Three LEDs display unit status, the Green LED indicates Normal (regulating protected mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition. (If Green LED is off, it means internal circuit board needs replacement). A low-impedance isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

The leakage inductance of the isolation transformers, in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312.

Specifications

Specifications 163 Isolation Transformer Line Conditioner + Precision Voltage Regulator

ILc-VRp

Dual Range

Specification
Electrical
Capacity in VA (watts) Transformer type Regulator engine

ILc-2000-VRp-Dual Range
2kVA (2kW) Isolation transformer with key-switched taps for dual range capability. High frequency 20kHz IGBT driven voltage regulation converter. Pulse-width-modulated (PWM) ac to dc converter and dc to ac topology. 120 or 240 volts ac (User selectable via key switch with safety interlock to prevent voltage from appearing on the unused terminals). 120 or 240vac +/-20%. Short duration (less than 5 minutes) operation +/-30%. 47 to 63Hz Input circuit breaker (150% overload capability for heavy start load). 20 amps@120vac or 10 amps@240vac. 120vac IEC320C-20 inlet. 240vac IEC320C-13 inlet. 115vac and/or 230vac Better than 96% 115vac+/-2.5%, or 230vac+/-2.5% Automatic bypass will be activated when there is a fault condition. Unit starts on sine wave zero voltage crossing point upon turn-on. Unit is fully functional/regulated within 5 seconds of mains restoration. System status LEDs provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down). A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Class 2 & Class 3 simulated lightning surge (Combination wave) per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV, 3kA, 8x20S Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt) of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S. Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Two NEMA 5-15R 120vac, and One UK BS1363 230vac socket. 436mm(17.2)wide x 127mm(5)high x 381mm(15) deep 22.7 kg(50 lbs) For 19 Front mounting: MK-8019A. For 19 Rear mounting: MK-8019B. Design ready to meet UL, CUL and EMC standards. -5o to +35o C(23o to 95 o F) Fan cooled. Two year limited warranty, parts and labor.
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Input
Nominal voltage Normal operating range

Dual voltage range isolation transformer with precision PWM automatic voltage regulator

Nominal frequency Input circuit breaker Circuit breaker rating Input

Output
Nominal voltage Power efficiency Voltage regulation Automatic bypass Safe start System status indicators (per phase)

Surge protection Surge test conditions Surge let-through voltages (system will continue to operate without interruption under these conditions) Common mode filtering Normal mode filtering Output receptacles

Physical
Dimensions Weight Rack-mountng (optional)

Safety
Standards TSi Power Corporation

Environmental
Ambient temperature Cooling method

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Warranty
Warranty

164 ILc-VRp Series ILc-2000-VRp-Dual Range

ILc-VRp

Dual Range

Power with a Precision Attitude

ILc-2000-VRp-Dual Range system architecture


dual range ac Input circuit breaker
line ground surge prot. and noise filter

buck-boost transformer

automatic bypass

ILc-VRp ac output 115 vac and / or 230 vac + / - 2.5 %

L ac
noise filter

dc

microprocessor control

N ground ground

120 or 240 vac + / - 20 %

neutral

isolation transformer

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Dual voltage range input: 120vac Or 240vac Dual voltage range output: 115vac And/Or 230vac Precision PWM automatic voltage regulator with low-impedance isolation transformer

ILc-2000-VRp-Dual-Range-2006-10-16.pdf

VRp-3000/5000-120V ~ 3/5kVA, 3/5kW, 40/70A, 120vac


VRp Series 165 Precision Automatic Voltage Regulator

VRp
VRp model 3000-120V
3 kVA 3 kW 120 volts

Failsafe

Automatic voltage regulator

With precision

Precision PWM Automatic Voltage Regulator with Automatic Bypass


Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 95 to 145vac.

5000-120V
5 kVA 5 kW 120 volts

Power with a There is no switching of taps or otherwise a Precision Attitude break in the power path thanks to continuous
PWM switching of a buck-boost transformer.

Typical applications
Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
(VRp-7500 shown)

Key features
Outstanding voltage regulation. under normal input range of: 95 to 145V (47 to 63Hz), output regulation will be: 120V+/ -3%. No switching of the power path Fast regulation Failsafe automatic bypass Low impedance Low weight Quiet operation Two year warranty

Key benefits
The low weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve the nominal output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

166 Specifications VRp-3000/5000-120V

Specifications Specification
Electrical
Capacity in VA (watts) Regulator engine 3 kVA (3000W) 5 kVA (5000W) High frequency 20kHz IGBT driven voltage regulation converter 120 volts ac single phase 95 to 145 volts ac 47 to 63 Hz Single pole circuit breaker 1 x 40 amps 10mm (AWG 8)
2

VRp

VRp-3000-120V

VRp-5000-120V

Input
Nominal voltage Operating voltage Nominal frequency Overcurrent protection Circuit breaker rating Input wire size

Precision automatic voltage regulator

1 x 70 amps 15mm 2 (AWG 6)

Output
Nominal voltage Power efficiency Voltage regulation Automatic bypass Status indicators 120 volts ac, single phase 96% (typical) Combined 3% maximum under 0 to 100% load and input of 95 to 45V. Automatic bypass will be activated when there is a fault condition. System status LEDs provided as follows: Green LED indicates Normal (regulating mode operation); Yellow LED indicates Bypass (non-regulated output); Red LED indicates Fault. Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Category A3, Ring wave, 200A: L-N: 30V Cat. B3, Combination wave, 3000A: L-N: 200V
Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond.

Surge test conditions Surge let-through voltages

Ac output connection

Hardwired output terminals (hot, neutral and ground) are standard. Optional input cord and output receptacles are available. 270mm(10.6)wide x 159mm(6.25)high x 368mm(14.5)deep 18.2kg(40 lbs) MK-5019C (optional) Designed to meet UL1950 and cUL1950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited depot warranty, parts and labor. 22.7kg(50 lbs)

Physical
Dimensions Weight Wall/Floor mounting kit

Safety
TSi Powers ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Agency approvals

Environmental
Ambient temperature

Warranty
Warranty

VRp system architecture


ac input TSi Power Corporation
95 to 145 V

hot ground

L1
single pole circuit breaker

buck- boost transformer surge protection and noise filter

automatic bypass

ac output L1 hot
120 V +/- 3%

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

ac

dc

microprocessor control neutral

noise filter L2

L2 neutral

ground

VRp-3000-5000-120V-2006-10-16.pdf

VRp-3000/5500-0230 ~ 3/5.5kVA, 3/5.5kW, 208/220/230/240vac


VRp Series 167 Precision Automatic Voltage Regulator

VRp
VRp model 3000-0230
3 kVA 3 kW 208/220/ 230/240 volts

Failsafe

Automatic voltage regulator

With precision

Precision PWM Automatic Voltage Regulator with Automatic Bypass


Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 184 to 264vac.
There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.

5500-0230
5.5 kVA 5.5 kW 208/220/ 230/240 volts

Power with a Precision Attitude

Typical applications
Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.
(VRp-7500 shown)

Key features of the VRp Series


Outstanding voltage regulation: under normal input range of 184 to 264V (47 to 63Hz), output regulation will be 208/220/230 or 240V+/ -3%. Failsafe: no switching of power path Fast regulation Automatic bypass Low- impedance Low weight Quiet operation 2 Year warranty

Key benefits
The low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve the nominal output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), yellow LED indicates Bypass (non-regulated output), and the red LED indicates a Fault condition.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

168 Specifications VRp-3000/5500-0230

VRp

Specification
Electrical
Capacity in VA (watts) Regulator engine

VRp-3000-0230
3 kVA (3000W)

VRp-5500-0230
5.5 kVA (5500W)

High frequency 20kHz IGBT driven voltage regulation converter 208/220/230 or 240 volts ac, single phase 184 to 264 volts ac 47 to 63Hz Circuit breaker 2 x 20 amps 6mm (AWG 10)
2

Input
Nominal voltage Operating voltage Nominal frequency Over-current protection Circuit breaker rating Input wire size

Specifications
(VRp-7500 shown)

2 x 40 amps 10mm2 (AWG 8)

Precision automatic voltage regulator

Output
Nominal voltage Power efficiency Voltage regulation Automatic bypass Status indicators 208/220/230 or 240 volts ac, single phase 96% (typical) Combined 3% maximum under 0 to 100% load and input of 184 to 264V Automatic bypass will be activated when there is a fault condition. System status LEDs provided as follows: Green LED indicates Normal (regulating mode operation); Yellow LED indicates Bypass (nonregulated output); Red LED indicates Fault. Per ANSI/IEEE C62.41-1991 6kV normal-mode injection. Category A3, Ring wave, 200A: L-N: 30V Cat. B3, Combination wave, 3000A: L-N: 200V Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. Hardwired output terminals (L1, L2, and ground) are standard. Optional ac socket option is available(for slight extra charge). 270mm(10.6)wide x 159mm(6.25)high x 368mm(14.5)deep 18.2kg(40 lbs) MK-5019C (optional) Designed to meet UL1950 and cUL1950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited depot warranty, parts and labor. 22.7kg(50 lbs)

Surge test conditions Surge let-through voltages

Ac output connection

Physical
Dimensions Weight Wall/Floor mounting kit
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Safety
Agency approvals

Environmental
Ambient temperature

Warranty
Warranty

VRp system architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi two pole circuit breaker

TSi Power Corporation

L1 ground surge protection 184 to and 264 V noise filter

buck- boost transformer

automatic bypass

208, 220, 230,240 V L1 + / - 3 %

ac output ac dc microprocessor control noise filter L2


ground

L2

VRp-3000-5500-230V-2006-10-16.pdf

VRp-3500-0233 ~ 3.5kVA, 3.5kW, 208/220/230/240vac


VRp Series 169 Precision Automatic Voltage Regulator

VRp
VRp model 3500-0233
3500 VA 3500 watts input: 208/220/ 230/240vac output: 230vac +/-3%

Failsafe

Automatic voltage Regulator

With precision

Precision PWM Automatic Voltage Regulator for MacDermid Colorspan Inkjet Printers
Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator
line conditioner provides output voltage within

Power with a plus/minus 3% of nominal, for input voltage that varies plus/minus 20%. Precision Attitude

There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.

Typical applications
Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: MacDermid Colorspan high-performance color wide format digital Inkjet printers, and copiers, analytical equipment, radio/TV broadcast equipment, and mobile broadcast vans, and other 230vac loads that are 3500VA or under.

Key features of the VRp Series


Outstanding voltage regulation: under normal input range of nominal 184 to 276vac, output regulation will be 230vac+/ -3% Failsafe: no switching of the power path Fast regulation Automatic bypass Low-impedance Low weight Quiet operation Two year warranty

Key VRp-3500-0233 benefits


The light-weight, high efficiency VRp-3500-0233 is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve the nominal output voltage +/-3%. The Automatic Bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), and the Red LED indicates a Fault condition.

170 Specifications VRp-3500-0233

Specifications

VRp
Precision automatic voltage regulator

Specification
Electrical
Capacity in VA (watts) Regulator engine

VRp-3500-0233
3.5 kVA (3500W) maximum High frequency 20kHz IGBT driven voltage regulation converter 230 volts ac, single phase 184 to 276 volts ac 47 to 63Hz magnetic circuit breaker two pole - 20 amps 8 foot long cord with IEC60320 C-20 inlet- connector, and NEMA L6 -20P plug. (May be ordered configured with hardwired input terminals L1, L2, and ground. Extra charge will apply). 230 vac 16A (maximum) ~ 96% efficiency (typical) Combined 3% maximum under to 100% load and input of 184 to 276V Automatic bypass will be activated when there is a fault condition. System status LEDs provided as follows: Green LED indicates Normal (regulating mode operation); Red LED indicates Fault. Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Category A3, Ring wave, 200A: L-N: 30V Cat. B3, Combination wave, 3000A: L-N: 200V Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. One NEMA #L6-20R Receptacle (May be ordered configured with hardwired output terminals L1, L2, and ground. Extra charge will apply). 282mm(11.125) wide x 162mm(6.375)high x 377mm(14.875)deep 21.8 kg(48 lbs) MK-5019C (optional) Designed to meet UL1950 and cUL1950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited warranty, parts and labor.

Input
Nominal voltage Operating voltage Nominal frequency Over-current protection Circuit breaker rating Inlet line, cord-plug

Output

Front-right view
(VRp-4000 shown)

Nominal voltage Current and efficiency Voltage regulation Automatic bypass Status indicators Surge test conditions Surge let-through voltages

Rear view*
(VRp-4000 shown) *Future models for the EU will be painted steel AC output connection

Physical
Dimensions Weight Wall/floor mounting kit

Safety
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Agency approvals

Environmental
Ambient temperature

Warranty
Warranty

VRp system architecture


ac input hot
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi two pole circuit breaker

L1 surge protection 184 to and 276 V noise filter

buck - boost transformer

automatic bypass L1

230 V +/- 3% ac output

TSi Power Corporation

ground

ac

dc

microprocessor control

noise filter L2
ground

L2 neutral

VRp-3500-0233-230vac-2006-10-16.pdf

VRp-4000-0235 ~ 4kVA, 4 kW, 208/220/230 or 240vac, single phase


VRp Series 171 Precision Automatic Voltage Regulator

VRp
VRp model 4000-0235
4000 VA (max.) 4000 watts input: 208/220/ 230 or 240 vac output: 208/220/230 or 240 vac +/-3%

Fail-safe

Automatic voltage regulator

with PWM precision

Precision PWM Automatic Voltage Regulator for Copiers and Printers


Precision fast-PWM mains voltage correction
TSi Powers VRp automatic precision regulator
line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies plus/minus 15%. There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.

Power with a Precision Attitude

Typical applications
Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: high-throughput color printers and copiers, analytical equipment, radio/TV broadcast equipment, and mobile broadcast vans.

Key features of the VRp Series


Outstanding voltage regulation: under normal input range of nominal 184 to 264vac (60Hz), output regulation will be 208/220/ 230 or 240 vac+/ -3%. Failsafe: no switching of power path Fast regulation Automatic bypass Low-impedance Low weight Quiet operation Two year warranty

Key VRp-4000-0235 benefits


This light-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 10,000 times per second, to achieve the nominal output voltage +/-3%.
TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), and the Red LED indicates a Fault condition.

172 Specifications VRp-4000-0235

Specifications Specification
Electrical
Capacity in VA (watts) Regulator engine 4 kVA (4000W) maximum High frequency 10kHz IGBT driven voltage regulation converter 208 volts ac single phase (220/230 or 240vac optional) 184 to 264 volts ac 47 to 63Hz Magnetic circuit breaker Two - 20 amps 6 foot long cord with NEMA 6-20P plug. (May be ordered configured with hardwired input terminals L1, L2, and ground. Extra charge will apply). 208/220/230 or 240vac (Please specify at time of order). 16A (maximum) ~ 96% efficiency (typical) Combined 3% maximum under 0 to 100% load and input of 184 to 264V Automatic bypass will be activated when there is a fault condition. System status LEDs provided as follows: Green LED indicates Normal (regulating mode operation); Red LED indicates Fault. Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Category A3, Ring wave, 200A: L-N: 30V Category B3, Combination wave, 3000A: L-N: 200V Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. One NEMA #6-20R Receptacle. (May be ordered configured with hardwired output terminals L1, L2, and Ground.Extra charge will apply). 282mm(11.125)wide x 162mm(6.375)high x 377mm(14.875)deep 12 kg(27 lbs) MK-5019C (optional) Designed to meet UL1950 and cUL1950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited warranty, parts and labor.

VRp
Precision automatic voltage regulator

VRp-4000-0235

Input
Nominal voltage Operating voltage Nominal frequency Over-current protection Circuit breaker rating Input line cord/plug

Output

Front-right view

Nominal voltage Current and efficiency Voltage regulation Automatic bypass Status indicators Surge test conditions Surge let-through voltages

Rear view*
*Future models for the EU will be painted steel Ac output connection

Physical
Dimensions
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Weight Wall/Floor mounting kit

Safety
Agency approvals

Environmental
Ambient temperature

Warranty
Warranty

VRp system architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi two pole circuit breaker

TSi Power Corporation

L1 ground surge protection 184 to and 264 V noise filter

buck - boost transformer

automatic bypass

208, 220, 230,240 V L1 + / - 3 % ac output

ac

dc

microprocessor control

noise filter L2
ground

L2

VRp-4000-0235-208vac-2006-10-16.pdf

VRp-7500/10000 ~ 7.5/10kVA, 7.5/10kW, 208/220/230 or 240vac, single phase


VRp Series 173 Precision Automatic Voltage Regulator

VRp
VRp model 7500
7.5 kVA 7.5 kW input: 208/220/ 230 or 240 vac output: 208/220/230 or 240 vac +/-3%

Fail-safe

Automatic voltage regulator

with PWM precision

Precision, Light-weight, No-break PWM Automatic Voltage Regulator Line Conditioner with Automatic Bypass
Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 185 to 265VAC.
There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.

10000
10 kVA input: 208/220/ 230 or 240 vac output: 208/220/230 or 240 vac +/-3%

Typical applications
Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.

Power with a Precision Attitude

Key features of the VRp Series


Outstanding voltage regulation: under normal input range of 185 to 265V (47 to 63Hz), output regulation will be: single phase 208/220/230 or 240V +/-3%. Failsafe: no switching of power path Fast regulation Automatic bypass Low-impedance Low weight Quiet operation Two year warranty

Key benefits
The low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per cycle, to achieve the nominal output voltage +/-3%. The Automatic Bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.

174 VRp Series VRp-7500-10000

VRp
Voltage regulation with precision

Specification
Electrical
Capacity in VA (watts) Regulator engine

VRp-7500
7.5kVA (7.5 kW)

VRp-10000
10kVA (10kW)

High frequency 20kHz IGBT driven voltage regulation converter 208/220/230 or 240 volts ac, single phase 185 to 265 volts ac 160 to 300 volts ac (with reduced capacity, wider output regulation) 47 to 63 Hz Input circuit breaker 40 amps AWG 8 (8 square mm) 60 amps AWG 6 (13 square mm)

Input
Nominal voltage Operating voltage
Maximum operating range

Nominal frequency Overcurrent protection Circuit breaker rating Input wire size Ac connection

Terminal block (for L1, L2, and ground wires) is provided. 208/220/230 or 240 volts ac, single phase. (factory adjusted) Better than 96% (under all load conditions) Nominal +/-3% maximum under 0 to 100% load and 185 to 265 vac input 192 to 240 volts ac over wider input range of 160 to 300 vac Automatic bypass will be activated when there is a fault condition System status LEDs provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Fault condition. Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Category A3, Ring wave, 200A: L-N: 30V. L-G: 30V Category B3, Combination wave, 3000A: L-N: 200V,L-G: 200V
Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer (ILc) is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. (customized built-in ILc option is available).

Output
Nominal voltage Power efficiency Voltage regulation
Relaxed voltage regulation

Specifications

Automatic bypass System status indicators

Surge test conditions Surge let-through voltages

Ac connection

Terminal block (for L1, L2, and ground wires) is provided. 330mm(13)wide x 216mm(8.5)high x508mm(20)deep 36.3 kg(80 lbs) 40.8kg(90 lbs)

Physical
Dimensions
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Weight

Safety
Agency approvals Designed to meet UL/cUL1950 and IEC 60950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited warranty, parts and labor.

Environmental
Ambient temperature

Warranty
Warranty

ac input L1
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

VRp system architecture


surge 185 protection to and 265 noise vac Filter

buck - boost transformer

automatic bypass L1 microprocessor control noise filter L2

ac output
208/220/ 230/240V +/- 3%

TSi Power Corporation

ground

ac

dc

L2

two pole circuit breaker

ground

VRp-7500-10000-230V-2006-10-16.pdf

VRp-9000/16500 ~ 9/16.5kVA, 9/16.5kW, 220/380V or 230/400vac wye, grey

VRp
VRp model 9000
9 kVA 9 kW 220/380 or 230/400 volts 3 phase wye

VRp Series 175 Precision Automatic Voltage Regulator

Fail-safe

Automatic voltage regulator

with PWM precision

Precision PWM Automatic Voltage Regulator with Automatic Bypass


Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 185 to 265 vac, per phase.
There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.

16500
16.5 kVA 16.5 kW 220/380 or 230/400 volts 3 phase wye

Typical VRp applications


Power with a Precision Attitude stable, high-reliability power, without switching
components in the power path. Designed for applications that require absolutely

Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.

Key features of the VRp Series precision voltage regulator


Outstanding voltage regulation: under normal input range of 185 to 265V(47 to 63Hz) per phase, output regulation will be: nominal +/-3% Failsafe: no switching of power path Fast regulation Automatic bypass Low- impedance Low weight Quiet operation Two year warranty

Key VRp benefits


The low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, TSi Power Corporation 10,000 times per second, to achieve the nominal Represented by output voltage +/-3%. The automatic bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.

CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

176 Specifications VRp-9000/16500

VRp

Specification
Electrical
Capacity in VA (watts) Regulator engine

VRp-9000
9kVA (9 kW)

VRp-16500
16.5kVA (16.5kW)

High frequency 10kHz IGBT driven voltage regulation converter 220/380V or 230/400 volts ac, three phase wye Range: 185 to 265 volts ac 160 to 300 volts ac (with reduced output capacity and wider regulation). 47 to 63Hz Input circuit breaker 3 x 20 amps (ganged) AWG 12 (3.3 square mm) 3 x 40 amps (ganged) AWG 8 (8 square mm)

Input
Nominal voltage Normal operating voltage Maximum operating range Nominal frequency Over-current protection Circuit breaker rating Input wire size Ac connection

Voltage regulator with precision


Power with a Precision Attitude

Terminal block (L1, L2, L3, neutral and ground wires) provided. 220/380V or 230/400 volts ac (specify with PO), three phase wye. Better than 96% (under all load conditions)
Nominal +/-3% maximum under 0 to 100% load and input of 185 to 265 vac

Output
Nominal voltage Power efficiency Voltage regulation Relaxed voltage regulation Automatic bypass System status indicators Surge test conditions Surge let-through voltages

Specifications

192 to 240 volts ac over wider input range of 160 to 300 vac Automatic bypass will be activated when there is a fault condition.
System status LEDs provided as follows: Green LED (blinking) indicates normal (regulating mode operation); Yellow LED (blinking) indicates bypass (non-regulated output); Red LED indicates fault condition.

Per ANSI/IEEE C62.41-1991 6kV normal-mode injection. Category A3, Ring wave, 200A: L-N: 30V. L-G: 30V Category B3, Combination wave, 3000A: L-N: 200V,L-G: 200V Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer(ILc) is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. (Customized built-in ILc option is available). Terminal block (L1, L2, L3, neutral and ground wires) provided. 610mm(24)wide x 710mm(28)high x 560mm(22)deep 73 kg(160 lbs) 86 kg(190 lbs)

Ac connection

Physical
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Dimensions Weight

Safety
Agency approvals Designed to meet UL/cUL1950 and IEC 60950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited warranty, parts and labor.

Environmental
Ambient temperature

Warranty
Warranty

VRp system (per phase) architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi three phase circuit breaker

TSi Power Corporation

hot

L1

buck - boost transformer

automatic bypass

ac output
L1
220 V or 230 V per ph. +/- 3%

ground

surge 185V to protection 265 V and per noise phase filter

ac

dc

microprocessor control

noise filter
neut

neutral

ground

VRp-9000-16500-3ph-Gray-2006-10-16.pdf

VRp-9000/16500-0338 ~ 9/16.5kVA, 9/16.5kW, 220/380vac or 230/400vac wye

VRp
VRp model 9000-0338
9 kVA 9 kW 230/400 volts 3 phase wye

VRp Series 177 Precision Automatic Voltage Regulator

Fail-safe

Automatic voltage regulator

with PWM precision

Precision PWM Automatic Voltage Regulator with Automatic Bypass


Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator allows trouble-free operation of electronic equipment over a very wide mains ac voltage range of 160 to 300V found in many developing countries.
break in the power path thanks to continuous PWM switching of a buck-boost transformer.

16500-0338
16.5 kVA 16.5 kW 230/400 volts 3 phase wye

Power with a Precision Attitude There is no switching of taps or otherwise a

Typical applications
Designed for applications where absolutely safe and precisely regulated ac power is required, such as mobile communication (GSM/satellite/ wireless broadband), radio/TV broadcasting, industrial process controller (PLC), medical (mobile MRI, CT) and laboratory or analytical measurement equipment.

Key benefits
VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads. The automatic bypass assures that connected equipment will not shut down, even if VRp fails.

Key features of the VRp Series precision voltage regulator


Outstanding voltage regulation: under voltage input range of 185 to 265V (47 to 63Hz) per phase, output regulation will be: within +/-1%. No switching of power path and unit always starts up on sinewave zero crossing. Over-under voltage cutoff, with automatic restart when mains voltage decreases back to below 275 vac, or above 160 vac. Failsafe: automatic bypass Low- impedance Lightweight Wall fixing kit is included Quiet operation Two year warranty

How the VRp Series works


The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 10,000 times per second, to achieve precisely regulated 230vac output. The automatic bypass will be activated when there is a fault condition. Green LED indicates TSi Power Corporation Normal (regulating mode operation), Yellow LED Represented by indicates Bypass (non-regulated output), and the CareBase Michael Gibson Red LED indicates a Fault condition.

Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

178 Specifications VRp-9000/16500-0338

Specifications Specification
Electrical
Capacity in VA (watts) Regulator engine 9kVA (9 kW) 16.5kVA (16.5kW) High frequency 10kHz IGBT driven voltage regulation converter 230/400 volts ac, three phase wye Range: 160 to 300 volts ac 160 to 300 volts ac(with reduced output capacity and wider regulation) 47 to 63Hz Input circuit breaker and over-under voltage cutoff (>300vac or <160vac) 3 x 20 amps (ganged) AWG 10 (4 square mm) 3 x 30 amps (ganged) AWG 8 (8 square mm)

VRp

VRp-9000-0338

VRp-16500-0338

Voltage regulator with precision

Input
Nominal voltage Normal operating voltage Maximum operating range Nominal frequency Overcurrent protection Circuit breaker rating Input wire size Ac connection

Terminal block (L1, L2, L3, Neutral and ground wires) provided. 230/400 volts ac, three phase wye Better than 96% (with 20-100% load conditions) Factory set at 1%, long-term stability: <2%. 192 to 240 volts ac over wider input range of 160 to 300 volts ac Automatic bypass will be activated when there is a fault condition.
Status LEDs provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (nonregulated output); Red LED indicates Overload (system may shut down).

Output

Left side - front view

Nominal voltage Power efficiency Voltage regulation Relaxed voltage regulation Automatic bypass System status indicators Surge test conditions Surge let-through voltages

Power with a Precision Attitude

Per Class 2 and Class 3 simulated lightning surge (Combination wave)


Class 2 and 3, 4000V, 3000A: L-N: 200V, L-G: 200V Note: For maximum protection of the VRp and connected load equipment, TSi Power recommends that a matching isolation power conditioner (ILc) be placed adjacent to the VRp.

Matching ILc (mandatory) Ac connection

ILc-9000-0338

ILc-16500-0338

Terminal block (L1, L2, L3, neutral and ground wires) provided. 610mm(24)wide x 610mm(24)high x 305mm(12)deep 80 kg(176 lbs) 100 kg(220 lbs)

Physical
Dimensions Weight
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Safety
Agency approvals Designed to meet IEC 60950 standards. Protection class IP20. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Fan cooled. Two year limited warranty, parts and labor.

Environmental
Ambient temperature Cooling method

Warranty
Warranty

VRp system (per phase) architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

three phase circuit breaker hot


L1

TSi Power Corporation

buck - boost transformer

automatic bypass

ac output
L1
230 V per ph. +/- 1%

ground

surge 185V to 265 V protection and per noise phase filter

ac

dc

microprocessor control

noise filter
neut

neutral

ground

VRp-9000-16500-0338-3ph-2006-10-16.pdf

VRp-15000/20000-0230 ~ 15/20kVA, 15/20kW, 208/220/230 or 240vac, single phase

VRp Series 179 Precision Automatic Voltage Regulator

VRp
VRp model 15000-0230
15 kVA 15 kW 208/220/230 or 240 volts single phase

Fail-safe

Automatic voltage regulator

with PWM precision

Precision, Light-weight, No-break PWM Automatic Voltage Regulator Line Conditioner with Automatic Bypass
Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator line conditioner provides output voltage within plus/minus 3% of nominal, for input voltage that varies between 185 to 265VAC.
There is no switching of taps or otherwise a break in the power path thanks to continuous PWM switching of a buck-boost transformer.

20000-0230
20 kVA 20 kW 208/220/230 or 240 volts single phase

Typical applications
Power with a Precision Attitude
Designed for applications that require absolutely stable, high-reliability power, without switching components in the power path. Applications include, but are not limited to: analytical equipment, radio and TV broadcast equipment, mobile broadcast vans, industrial controllers (PLC), milking machines, lithographic equipment, recording studio equipment and electrolysis equipment.

Key features of the VRp Series


Outstanding voltage regulation: under normal input range of 185 to 265V (47 to 63Hz), output regulation will be: single phase 208/220/230 or 240V +/-3%. Failsafe: no switching of power path Fast regulation Automatic bypass Low-impedance Low weight Quiet operation Two year warranty

Key benefits
The low-weight, high efficiency VRp is easy to install in any environment. The automatic bypass assures that connected equipment will not shut down, even if VRp fails. VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads.

How the VRp Series works


TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

The high frequency IGBT driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per cycle, to achieve the nominal output voltage +/-3%. The Automatic Bypass will be activated when there is a fault condition. Green LED indicates Normal (regulating mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition.

180 Specifications VRp-15000/20000-0230

VRp

Specification
Electrical
Capacity in VA (watts) Regulator Engine

VRp-15000-0230
15kVA (15 kW)

VRp-20000-0230
20kVA (20kW)

High frequency 20kHz IGBT driven voltage regulation converter 208/220/230 or 240 volts ac, single phase 185 to 265 volts ac 160 to 300 volts ac (with reduced capacity, wider output regulation) 47 to 63 Hz Input circuit breaker 80 amps AWG 4 100 amps AWG 2

Input
Nominal Voltage Operating Voltage Maximum Operating Range Nominal Frequency Overcurrent Protection Circuit Breaker Rating

Voltage regulator with precision


Power with a Precision Attitude

Input Wire Size AC Connection

Input wire terminal block (L1, L2, and ground wires) is provided. 208/220/230 or 240 volts ac, single phase. (factory adjusted) Better than 96% (under all load conditions) Nominal +/-3% maximum under 0 to 100% load and 185 to 265 vac input 192 to 240 volts ac over wider input range of 160 to 300 vac Automatic bypass will be activated when there is a fault condition System status LEDs provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Fault condition. Per ANSI/IEEE C62.41-1991 6kV normal-mode injection Category A3, Ring wave, 200A: L-N: 30V. L-G: 30V Category B3, Combination wave, 3000A: L-N: 200V,L-G: 200V
Note: Unit should be installed as close as possible (within 30) of the neutral-to-ground bond at the service entrance, in order to minimize potential difference between neutral and ground. A separate isolation transformer (ILc) is recommended for installations where distance exceeds above, or for grounding systems without a neutral-to-ground bond. (customized built-in ILc option is available).

Output
Nominal voltage Power efficiency Voltage regulation Relaxed voltage regulation Automatic bypass System status indicators

Specifications

Surge test conditions Surge let-through voltages

Ac connection

Terminal block (for L1, L2, and ground wires) is provided. 610mm(24)wide x 710mm(28)high x 560mm(22)deep 82 kg(180 lbs) 91 kg (200 lbs)

Physical
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Dimensions Weight

Safety
Agency approvals Designed to meet UL/cUL1950 and IEC 60950 standards. 0o to +40 oC(32o to +104 oF). 10 to 90% RH non-condensing. Two year limited warranty, parts and labor.

Environmental
Ambient temperature

Warranty
Warranty ac input L1
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

VRp system architecture


surge 185 protection to and 265 noise vac Filter

buck - boost transformer

automatic bypass L1 microprocessor control noise filter L2

ac output
208/220/ 230/240V +/- 3%

TSi Power Corporation

ground

ac

dc

L2

two pole circuit breaker

ground

VRp-15000-20000-230V-2006-10-16.pdf

VRp-22500/30000-0338 ~ 22.5/ 30kVA, 22.5/30kW, 220/380V or 230/400vac wye


VRp Series 181 Precision Automatic Voltage Regulator

VRp
VRp model 22500-0338
22.5 kVA 22.5 kW 230/400 volts 3 phase wye

Fail-safe

Automatic voltage regulator

with PWM precision

Precision PWM Automatic Voltage Regulator with Automatic Bypass


Precision fast-PWM ac mains voltage correction
TSi Powers VRp automatic precision regulator allows trouble-free operation of electronic equipment over a very wide mains ac voltage range of 160 to 300V found in many developing countries.
There is no switching of taps or otherwise a break in the power path thanks to continuous pulsed-width-modulation (PWM) switching of a buck-boost transformer.

30000-0338
30 kVA 30 kW 230/400 volts 3 phase wye

Typical applications
Designed for applications where absolutely safe and precisely regulated ac power is required, such as mobile communications (GSM/satellite/ wireless broadband), radio base stations (RBS)/ base transmitter stations (BTS), radio/TV broadcasting, transmission sites for backhaul (including microwave links) industrial process controller (PLC), medical (mobile MRI, CT) and laboratory or analytical measurement equipment.

VRp-22500

Key features of the VRp Series precision voltage regulator


Outstanding voltage regulation: under voltage input range of 185 to 265V (47 to 63Hz) per phase, output regulation will be: within +/-1%. No switching of power path and unit always starts up on sine wave zero crossing. Over-under voltage cutoff, with automatic restart when mains voltage decreases back to below 275 vac, or above 160 vac. Failsafe: automatic bypass Low- impedance Lightweight Wall fixing kit is included Quiet operation Two year warranty

Key benefits
VRp is compatible with all loads as it does not switch any components in the power path. VRps ultra-low impedance assures stability even with the most demanding loads. The automatic bypass assures that connected equipment will not shut down, even if VRp fails.

How the VRp Series works


The high frequency insulated gate bi-polar transistor (IGBT) driven converter takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230vac output. The automatic bypass will be activated when there is a fault condition. Green LEDs are used to indicate Normal (regulating mode) operation).

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

182 Specifications VRp-22500/30000-0338

VRp

Specifications

Specification
Electrical
Capacity in VA (watts) Regulator engine

VRp-22500-0338
22.5kVA (22.5 kW)

VRp-30000-0338
30kVA (30kW)

High frequency 20kHz IGBT driven voltage regulation converter 230/400 volts ac, three phase wye Range: 160 to 300 volts ac 160 to 300 volts ac (with reduced output capacity and wider regulation) 47 to 63Hz Input circuit breaker (with limited inrush current capability) and over-under voltage cutoff (at greater than 300vac or less than160vac) 3 x 40 amps (ganged) 10mm2 (AWG 8) 3 x 60 amps (ganged) 15mm2 (AWG 6)

Input
Nominal voltage Normal operating voltage Maximum operating range Nominal frequency Input circuit breaker and overcurrent protection

Precision PWM automatic voltage regulator


Power with a Precision Attitude

Circuit breaker rating Input wire size Ac connection

Terminal block (L1, L2, L3, neutral and ground wires) provided. 230/400 volts ac, three phase wye Better than 96% (with 20-100% load conditions) Factory set at 1%, long-term stability: <2%. 192 to 240 volts ac over wider input range of 160 to 300 volts ac Automatic bypass will be activated when there is a fault condition.
Green LED (ON) indicates Normal (regulating mode) operation.

Output
Nominal voltage Power efficiency Voltage regulation Relaxed voltage regulation Automatic bypass System status indicator Surge test conditions Surge let-through voltages

Per Class 2 and Class 3 simulated lightning surge (Combination wave)


Class 2 and 3, 4000V, 3000A: L-N: 200V, L-G: 200V Note: For maximum protection of the VRp and connected load equipment, TSi Power recommends that a matching isolation power conditioner (ILc) be placed adjacent to the VRp.

Matching ILc (mandatory) Ac connection

ILc-22500-0338

ILc-30000-0338

Terminal block (L1, L2, L3, neutral and ground wires) provided. 610mmW x 610mmH x 305mmD 24wide x 24high x 12deep 89kg(196 lbs) 610mm W x 863mm H x 305mm 24wide x 34high x 12deep 110kg(243 lbs)

Physical

Lifting ears shown

Dimensions Weight

Safety
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Standards

Designed to meet IEC 60950 standards. Protection class IP20.


-5 to +35C (23 to 95F). 10 to 90% RH non-condensing.

Environmental
Ambient temperature Cooling method Fan cooled. Two year limited warranty, parts and labor.

Warranty
Warranty

VRp system (per phase) architecture


ac input
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi three phase circuit breaker

TSi Power Corporation

hot

L1

buck - boost transformer

automatic bypass

ac output
L1
230 V per ph. +/- 1%

ground

surge 185V to protection 265 V and per noise phase filter

ac

dc

microprocessor control

noise filter
neut

neutral

ground

VRp-22500-30000-0338-3ph-2006-10-16.pdf

VRp-ILc-16500-0338 ~ 16.5kVA, 16.5kW, 400vac delta to 230/400vac wye


VRp-ILc Series 183 Precision Voltage Regulator + Isolation Transformer Line Conditioner

VRp-ILc
VRp-ILc model

International

Precision voltage regulator

Isolation transformer

16500-0338
16.5 kVA 16.5 kW input - 4 wires 400vac delta output - 5 wires 230/400vac wye three phase

Precision PWM Automatic Voltage Regulator with Isolation Transformer, Automatic Bypass and Automatic Cutoff
Continuous fast and no-break PWM regulation
TSi Powers VRp-ILc automatic precision voltage regulator with built-in low-impedance isolation transformer allows trouble-free operation of electronic equipment over a very wide mains ac voltage range of 400V +/-20% (+/-30% for short durations) found in many developing countries.

Power with a There is no switching of taps or otherwise a Precision Attitude break in the power path thanks to continuous
PWM (Pulse-Width-Modulation) switching of a buck-boost transformer primary winding.

Typical VRp-ILc applications


Designed for applications where absolutely safe and precisely regulated ac power is required, such as outdoor mobile telecommunication, TV/radio broadcasting or industrial equipment.

Key features of the VRp-ILc Series precision automatic voltage regulator with isolation transformer
Outstanding voltage regulation: under normal input range of 400vac +/- 20%, output voltage will be 230vac +/-1% (47 to 63Hz) No switching of power path and unit always starts up on sine wave zero crossing Over and under voltage cutoff, with automatic restart when ac mains voltage returns to normal (safe) condition Failsafe: automatic bypass (even during bypass, the over/under voltage protection is active) Lightweight design Three separate low-impedance isolation transformers (one per phase) are used for maximum reliability Coordinated surge protection per IEC61312 Common-mode noise elimination Advanced noise and interference filter reduces dV/dt from 6kV/S to less than 10V/ S IP20 rated enclosure with two separate compartments Two year warranty

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

184 VRp-ILc Series VRp-ILc-16500-0338

VRp-ILc
Key VRp-ILc benefits
The lightweight, high efficiency VRp-ILc is easy to install in indoor environments. The unit comes in a specially designed IP20 rated enclosure with thermostatically controlled fans and has removable lifting eyes to enable use of lifting equipment. The automatic bypass assures that connected equipment will not shut down, even if VRp-ILc fails. VRp-ILc is compatible with all loads as it does not switch any components in the power path. VRp-ILcs ultra-low impedance assures stability even with the most demanding loads. The automatic over-voltage/under-voltage cutoff with automatic restart ensures that operation is off-line during serious over-voltage or under-voltage situations that could damage the system and/or load, and then restarts without intervention when the ac mains voltage becomes within the operating range.

Precision PWM voltage regulator with isolation transformer

The ILc isolation line conditioner components provide maximum equipment protection against surges, spikes and transients, for higher equipment reliability and maximum equipment operating life. In addition, improved repeatability, fewer reboots or system lock-ups. In addition, a reduction in equipment down time and service costs can be expected. TSis use of three separate transformers, one per phase, minimizes the dangers associated with single phasing or lost phase problems associated with a three phase transformer built on a common (single) core. Maximum transformer and regulator performance, reliability and lifetime is achieved by a design with no moving mechanical parts other than cooling fans.

How the VRp-ILc Series works


The VRp-ILc unit is comprised of a VRp section - an automatic precision voltage regulator, and an ILc section - an isolation line conditioner, each in its own separate compartment.

Power with a Precision Attitude

The high frequency IGBT driven converter microprocessor takes the incoming ac power, measures against the nominal voltage and adds or subtracts voltage, 20,000 times per second, to achieve precisely regulated 230/400 vac three phase output, cycle by cycle. Voltage correction times do not exceed 1 cycle, or 20 milliseconds for all mains ac voltage changes, even for instantaneous voltage changes from 160 to 300vac or from 300 to 160vac. The automatic bypass will be activated when there is a fault condition. Three LEDs display unit status, the Green LED indicates Normal (regulating protected mode operation), Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition. The over-voltage and under-voltage cutoff is activated whenever the ac mains input voltage becomes dangerously high or low (>300vac or <160vac). It automatically restarts whenever ac mains voltage is restored within <300vac and >160vac. Three separate low-impedance isolation transformers provide complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground. The leakage inductance of the isolation transformers, in combination with capacitive elements and MOVs, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC-61312. High reliability cooling fans control the units internal temperature, with intake and exhaust through vents on sides of the unit.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Specifications

Specifications 185 Precision Voltage Regulator + Isolation Transformer Line Conditioner

VRp-ILc

Specification
Electrical
Capacity in VA (watts) Regulator technology Transformer type

VRp-ILc-16500-0338
16.5kVA (16.5kW) High frequency 20kHz IGBT driven voltage regulation converter. Pulse width modulated (PWM) ac to dc converter and dc to ac topology. Three separate isolation transformers are used (one per phase). Three phase delta: 400 volts ac Range: 400 vac, +/-20%. Short duration (less than 5 minutes) operation 400vac, +/-30%. 47 to 63 Hz Input circuit breaker (150% overload capability for heavy start load). Over-under voltage cutoff activated when >300vac or <160vac, with automatic restart when voltage becomes <300vac and >160vac. 3 x 40 amps (ganged) 10mm2 (8AWG) Terminal block (L1, L2, L3 and ground wires) provided. Three phase wye: 230/400 volts ac Better than 93% (at 400V input) Factory set at 1%, long-term stability: <2%. 230/400vac +/-10% (over input range of 400vac +/- 30%) Automatic bypass will be activated when there is a fault condition. Unit starts on sine wave zero voltage crossing point upon turn-on. Unit is fully functional/regulated within 5 seconds of mains restoration. System status LEDs provided as follows: Green LED (blinking) indicates Normal (regulating mode operation); Yellow LED (blinking) indicates Bypass (non-regulated output); Red LED indicates Overload (system may shut down). A three-stage surge protection system consisting of isolation transformer, capacitor and MOV is included. Class 2 and Class 3 simulated lightning surge (Combination wave) Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV, 3kA, 8x20S Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V The measured rate of voltage rise/fall (dV/dt of the remnant waveform is less than 10V/S with input test waveform dV/dt of 6kV/S Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V) A built-in inductor-capacitor filter attenuates EMI/RFI noise from output. Terminal block (L1, L2, L3, neutral and round wires) provided. 800mm(32)wide x 1300mm(51)high x 300mm(12)deep 276 kg(242 lbs) IP20. Painted metal. Design ready to meet EMC standards. -5o to +35o C(23o to 95o F) (Air conditioned). Fan cooled (Ball bearing). Two year limited warranty, parts and labor.

Input
Nominal voltage Normal operating range Nominal frequency Input circuit breaker Over-under voltage cutoff with auto-restart Circuit breaker rating Front-right side view Input wire size Ac connection

Output
Nominal voltage Power efficiency

Power with a Precision Attitude

Voltage regulation Relaxed voltage regulation Automatic bypass Safe start System status indicators (per phase)

Surge protection Surge test conditions Surge let-through voltages (system will continue to operate without interruption under these conditions) Common mode filtering Normal mode filtering Ac connection

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Physical
Dimensions Weight Enclosure
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Safety
Standards

Environmental
Ambient temperature Cooling method

Warranty
Warranty

186 VRp-ILc Series VRp-ILc-16500-0338

VRp-ILc

Precision PWM automatic voltage regulator with low-impedance isolation transformer

VRp-ILc-16500-0338 system architecture (per phase)


Input
400 vac - 20 % + 30%

3 phase circuit breaker


surge prot. and noise filter

buck-boost transformer

automatic bypass
over / under voltage cutoff
noise filter

VRp-ILc output 230 vac +/-2%

L1 ground

ac

dc ground

microprocessor control

N G

L2

isolation transformer

Power with a Precision Attitude

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

VRp-ILc-16500-0338-2006-10-16.pdf

XINv Series ~ Rack-mountable PWM Dc to Ac Inverters with Transformer Isolation


XINv Series 187 Dc to Ac Inverters

XINv
XINv Series Dc to Ac Inverters
Power with a Precision Attitude

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

188 XINv Series Dc to Ac Inverters

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

XINv-Series-2006-10-16.pdf

XINv-600/900-24V ~ 600/900VA, 600/900W, 24vdc to 115vac


XINv Series 189 Rack-mountable 24vdc to 115vac Inverter

XINv
XINv model 600-24V
600 VA 600 watts +/-24 vdc input 115 vac output

Pure sine wave

PWM dc to ac inverter

Voltage regulation + isolation

Rack-mountable Dc to Ac Inverter
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 115 volts ac from 24volts dc.

900-24V
900 VA 900 watts +/-24 vdc input 115 vac output

Key XINv benefits


XINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation: of 115vac +/-3% and less than 5% THD. XINvs 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 24vdc battery banks.

Typical XINv applications


Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 24vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.

Power with a Precision Attitude

Key XINv features


Pure sine wave inverter output Eight NEMA 5-15R receptacles Rack or wall mountable with optional rack/wall-mount kits Unipolar PWM inverter Ac output is isolated from dc +/-3% voltage regulation Comprehensive array of status LEDs/bargraphs SNMP compatible via RS-232 port with optional SNMP adapter Both RS-232 and relay contact signals are provided Very low audible noise Rugged construction supports mobile and portable applications Two year limited warranty parts and labor

How the XINv works


A rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 60Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. When the input dc voltage drops below 21volts, a DB9 connector in the rear of the inverter sends signals for inverter output failure and low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

190 Specifications XINv-600/900-24vdc-115vac

Specifications Specification
Electrical
Capacity in VA (watts) Inverter type 600VA (600W) 900VA (900W) Pulse-width-modulated (PWM) with isolation transformer. -24 volts dc or +24 volts dc 21 to 29 volts dc 35 amps 10mm2 (8 AWG) 50 amps 15mm2 (6 AWG) 3 screw terminal block for earth ground, (+), (-) dc Inputs.

XINv
Rack-mountable heavy-duty PWM dc to ac inverter
Power with a Precision Attitude

XINv-600-24V

XINv-900-24V

Input
Nominal voltage Operating voltage Maximum input current Dc input connector Recommended wire

Output
Ac output voltage Frequency stability Output waveform Load compatibility 115 volts +/-3% ac (factory settable to 100, 110 or 120 vac) 60Hz +/- 0.5% Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging) power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies. Up to 3:1 crest factor loads can be powered by the inverter. Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles. 1 minute @ 120% overcurrent. Greater than 85% under all load and dc input voltage conditions. Recessed on/off rocker style power switch. Rear-mounted DB-9 female signal port. Dc input voltage indicator: 5 green LEDs (20% per each LED). Ac output current: 5 green LEDs (20% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists. Eight standard NEMA 5-15R female receptacles. <45dBA @ 1m under all operating conditions. 100% isolation between input dc and output ac (isolation transformer included). Metal enclosure is bonded to dc input terminal block earth ground input. 406mm(16)wide x 381mm(15)deep x 89mm(3.5)high (2U high) 12 kg(26 lbs) 18 kg(38 lbs) 19 Inch Front rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C Designed to meet IEC 60950 safety standards. Protection against shorts or misapplication of inverter current. Inverter turns off automatically if input dc voltage drops below 21vdc. Inverter turns off automatically if overload is >120% for over 1 minute. -20o to +40 oC(-4o to +104 oF). 10 to 95% relative humidity (non-condensing). Storage temp. -20o to +60 oC(-4o to +140 oF). Forced air (internal hot air exhaust fan is included). 0 to 4000 meters (0 to 12,400 feet) above sea level. Two year limited depot warranty, parts and labor.

Load crest factor Surge current capability Overload capability Power efficiency Power on/off switch Communications Status indicators

Ac receptacles Audible noise Isolation and grounding

Physical
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Dimensions Weight Rack or wall mounting kits (optional), 23/24 also available

Safety
Agency approvals Dc breaker Low voltage disconnect Overload shutdown
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Ambient temperature Cooling method Elevation

Warranty
Warranty

XINv Series 191 Rack-mountable 24vdc to 115vac Inverter

XINv

recessed on/off switch output current level: 20% per LED

inverter On overload condition

front-right view
dc input voltage level: 20% per LED

XINv-600/900-24V system architecture


dc input 21 29 vdc dc circuit breaker microprocessor DB9 port for communications
gnd

dc to ac inverter dc

isolation transformer

XINv output 115 vac + / - 3 %


L

ac

ground chassis ground neutral-ground bond on transformer output

earth ground

rear view

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

dc input circuit breaker

dc input terminal block connector

output ac via eight standard NEMA 5-15R receptacles

DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)

192 XINv Series XINv-600/900-24vdc-115vac

XINv
Rack-mountable heavy-duty PWM dc to ac inverter

Specification
DB9 port function
Remote shutdown

Connector pin
1 For Remote Shutdown

Switching condition
A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart. RS-232 signal line RS-232 signal line For future use. Logic ground for pins 1 through 4. Closed when inverter is On, Open when inverter is Off. Open when dc is okay. Closed when input source (battery voltage) drops below 21.5vdc.

(Please note: relay contact is rated for 48vac/vdc, 1A maximum).

Transmit data Receive data Custom or future use Ground Inverter On Low battery alarm

2 TXD RS-232 Signal 3 RXD RS-232 Signal 4 Unused 5 Ground 6 + 7 Inverter On/Off (Relay contact) 8 + 9 Low Battery Alarm (Relay contact)

RS-232C serial communication for inverter status communication compatible with MEGATEC Communication Protocol, Part 1
Baud rate Data length Stop bit Parity SNMP interface for inverter monitoring and automatic shutdown configuration (Optional) 2400bps 8 bits 1 bit None Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).

SNMP interface (optional)

XINv-600/900-24V at a glance
Rack or wall-mountable heavy-duty PWM dc to ac inverter with isolation transformer and 115vac +/- 3% voltage regulation

Power with a Precision Attitude

High performance microprocessor-controlled PWM sine wave output +/-24vdc to 115vac inverter Pure sine wave output Isolation transformer Rack-mountable 2U high metal cabinet allows for rack or wall mounting using optional mounting kits

115vac +/-3% standard output can be set to a 100, 110 or 120vac output at the factory Eight NEMA 5-15R receptacles +/-24vdc terminal block connection with dc circuit breaker DB-9 signal port with RS-232 and relay contact signals SNMP compatible with optional SNMP adapter

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

XINv-600-900-24vdc-115vac-Inverter-2006-10-16.pdf

XINv-600E/900E-24V ~ 600/900 VA, 600/900 W, 24vdc to 230vac


XINv Series 193 Rack-mountable 24vdc to 230vac Inverter

XINv
XINv model 600E-24V
600 VA 600 watts +/-24 vdc input 230 vac output

Pure sine wave

PWM dc to ac inverter

Voltage regulation + isolation

Rack-mountable Dc to Ac Inverter
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 230 volts ac from 24volts dc.

900E-24V
900 VA 900 watts +/-24 vdc input 230 vac output

Key XINv benefits


XINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation of: 230vac +/-3% and less than 5% THD. XINvs 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 24vdc battery banks.

Typical XINv applications


Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 24vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.

Power with a Precision Attitude

Key XINv features


Pure sine wave inverter output Four IEC320-C13 receptacles Rack or wall mountable with optional rack/wall-mount kits Unipolar PWM inverter Ac output is isolated from dc +/-3% voltage regulation Comprehensive array of status LEDs/bargraphs SNMP compatible via RS-232 port with optional SNMP adapter Both RS-232 and relay contact signals are provided Very low audible noise Rugged construction supports mobile and portable applications Two year limited warranty parts and labor

How the XINv works


A rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 50Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. When the input dc voltage drops below 21volts, a DB9 connector in the rear of the inverter sends signals for inverter output failure and low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

194 Specifications XINv-600E/900E-24V

Specifications Specification
Electrical
Capacity in VA (watts) Inverter type 600VA (600W) 900VA (900W) Pulsed-width-modulated (PWM) with isolation transformer. -24 volts dc / +24 volts dc 21 to 29 volts dc 35 amps 10mm2 (8 AWG) 50 amps 15mm2 (6 AWG) 3 screw terminal block for earth ground, (+), (-) dc Inputs.

XINv
Rack-mountable heavy-duty PWM dc to ac inverter
Power with a Precision Attitude

XINv-600E-24V

XINv-900E-24V

Input
Nominal voltage Operating voltage Maximum input current Dc input connector Recommended wire

Output
Ac output voltage Frequency stability Output waveform Load compatibility 230volts +/-3% ac (factory settable to 200, 220 or 240vac) 50Hz +/- 0.5% Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging) power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies. Up to 3:1 crest factor loads can be powered by the inverter. Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles. 1 minute @ 120% overcurrent. Greater than 85% under all load and dc input voltage conditions. Recessed on/off rocker style power switch. Rear-mounted DB-9 female signal port. Dc input voltage indicator: 5 green LEDs (20% per each LED). Ac output current: 5 green LEDs (20% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists. Four standard IEC320-C13 female outlets (receptacles). <45dBA @ 1m under all operating conditions. 100% isolation between input dc and output ac (isolation transformer included). Metal enclosure is bonded to dc input terminal block Earth Ground input. 406mm(16)wide x 381mm(15)deep x 89mm(3.5)high (2U high) 12 kg(26 lbs) 18 kg(38 lbs) 19 Inch Front rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C Designed to meet IEC 60950 safety standards. Protection against shorts or misapplication of inverter current. Inverter turns off automatically if input dc voltage drops below 21vdc. Inverter turns off automatically if overload is >120% for over 1 minute. -20o to +40 oC(-4o to +104 oF). 10 to 95% relative humidity (non-condensing). Storage temp. -20o to +60 oC(-4o to +140 oF). Forced air (internal hot air exhaust fan is included). 0 to 4,000 meters (0 to 12,400 feet) above sea level. Two year limited depot warranty, parts and labor.

Load crest factor Surge current capability Overload capability Power efficiency Power on/off switch Communications Status indicators

Ac receptacles Audible noise Isolation and grounding

Physical
TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Dimensions Weight Rack or wall mounting kits (optional), 23/24 also available

Safety
Agency approvals Dc breaker Low voltage disconnect Overload shutdown
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Ambient temperature Cooling method Elevation

Warranty
Warranty

XINv Series 195 Rack-mountable 24vdc to 230vac Inverter

XINv

recessed on/off switch output current level: 20% per LED

inverter On overload condition

front-right view
dc input voltage level: 20% per LED

XINv-600E/900E-24V system architecture


dc input 21 29 vdc dc circuit breaker microprocessor DB 9 port for communications
gnd

dc to ac inverter dc

isolation transformer

XINv output 230 vac + / - 3%


L

ac

ground chassis ground neutral ground bond on transformer output

earth ground

rear view

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

dc input circuit breaker

dc input terminal block connector

DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)

(115V NEMA 5-15R receptacles shown)

output ac via four standard IEC320-C13 female outlets (receptacles)

196 XINv Series XINv-600E/900E-24vdc-230vac

XINv
Rack-mountable heavy-duty PWM dc to ac inverter

Specification
DB9 port function
Remote shutdown

Connector pin
1 For remote shutdown

Switching condition
A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart. RS-232 signal line RS-232 signal line For future use. Logic ground for pins 1 through 4. Closed when inverter is on, Open when inverter is off. Open when dc is okay. Closed when input source (battery voltage) drops below 21.5vdc.

(Please note: relay contact is rated for 48vac/vdc, 1A maximum).

Transmit data Receive data Custom or future use Ground Inverter On Low battery alarm

2 TXD RS-232 signal 3 RXD RS-232 signal 4 Unused 5 Ground 6 + 7 Inverter on/off (Relay Contact) 8 + 9 Low battery alarm (relay contact)

RS-232C serial communication for inverter status communication compatible with MEGATEC Communication Protocol, Part 1
Baud rate Data length Stop bit Parity SNMP interface for inverter monitoring and automatic shutdown configuration (optional) 2400bps 8 bits 1 bit None Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).

SNMP interface (optional)

XINv-600E/900E-24V at a glance
Rack or wall-mountable heavy-duty PWM dc to ac inverter with isolation transformer and +/- 3% voltage regulation

Power with a Precision Attitude

High performance microprocessor-controlled PWM sine wave output 24vdc to 230vac inverter Pure sine wave output Isolation transformer Rack-mountable 2U high metal cabinet allows for rack or wall mounting using optional mounting kits

230vac +/-3% standard output can be set to a 200, 220 or 240vac output at the factory Four IEC320-C13 female outlets +/-24vdc terminal block connection with dc circuit breaker DB-9 signal port with RS-232 and relay contact signals SNMP compatible with optional SNMP adapter

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

XINv-600E-900E-24vdc-230vac-Inverter-2006-10-16.pdf

XINv-400/700/1400-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 115vac


XINv Series 197 Rack-mountable 48vdc to 115vac Inverter

XINv
XINv model 400-48V
400 VA 400 watts +/-48 vdc input 115 vac output

Pure sine wave

PWM dc to ac inverter

Voltage regulation + isolation

Rack-mountable Dc to Ac Inverter
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 115 volts ac from 48 volts dc.

700-48V
700 VA 700 watts +/-48 vdc input 115 vac output

Key XINv benefits


XINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation with 115vac +/-3% and less than 5% THD. XINvs 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 48vdc battery banks.

Typical XINv applications


Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 48vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.

1400-48V
1400 VA 1400 watts +/-48 vdc input 115 vac output

Power with a Precision Attitude

Key XINv features


Pure sine wave inverter output Eight NEMA 5-15R receptacles Rack or wall mountable with optional rack/wall-mount kits Unipolar PWM inverter Ac output is isolated from dc +/-3% voltage regulation Comprehensive array of status LEDs/bargraphs SNMP compatible via RS-232 port with optional SNMP adapter Both RS-232 and relay contact signals are provided Very low audible noise Rugged construction supports mobile and portable applications Two year limited warranty parts and labor

How the XINv Works


A rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 60Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. If the input dc voltage drops below 42vdc, a DB9 connector in the rear of the inverter sends signals for inverter output failure & low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

198 Specifications XINv-400/700/1400-48vdc-115vac

Specifications XINv-400-48V
400VA (400W)

XINv
Rack-mountable heavy-duty PWM dc to ac inverter
Power with a Precision Attitude

Specification
Electrical
Capacity in VA (watts) Inverter type

XINv-700-48V
700VA (700W)

XINv-1400-48V
1400VA (1400W)

Pulsed-width-modulated (PWM) with isolation transformer. -48 volts dc or +48 volts dc 42 to 56 volts dc 25 amps 10mm2 (8 AWG) 40 amps 15mm2 (6 AWG) 75 amps 25mm2 (4 AWG) 3 screw terminal block for earth ground, (+), (-) dc Inputs.

Input
Nominal voltage Operating voltage Maximum input current Dc input connector Recommended wire

Output
Ac output voltage Frequency stability Output waveform Load compatibility 115 volts +/-3% ac (factory settable to 100, 110 or 120vac) 60Hz +/- 0.5% Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging) power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies. Up to 3:1 crest factor loads can be powered by the inverter. Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles. 1 minute @ 120% overcurrent. Greater than 85% under all load and dc input voltage conditions. Recessed on/off rocker style power switch. Rear-mounted DB-9 female signal port. Dc input voltage indicator: 5 green LEDs (25% per each LED). Ac output current: 5 green LEDs (25% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists. Eight standard NEMA 5-15R female receptacles. <45dBA @ 1m under all operating conditions. 100% isolation between input dc and output ac (isolation transformer included). Metal enclosure is bonded to dc input terminal block earth ground input. 406mm(16)wide x 381mm(15)deep x 89mm(3.5)high (2U high) 10 kg(22 lbs.) 12 kg(26 lbs.) 18 kg(38 lbs.) 19 Inch Front or Rear rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C Designed to meet IEC 60950 Safety Standards. Protection against shorts or misapplication of inverter current. Inverter turns off automatically if input dc voltage drops below 42vdc. Inverter turns off automatically if overload is >120% for over 1 minute.
0o to +40 oC(32o to +104 oF). 5 to 95% RH non-condensing. Storage temp. -20o to +60 oC(-4o to +140 oF).

Load crest factor Surge current capability Overload capability Power efficiency Power on/off switch Communications Status indicators

Ac receptacles Audible noise Isolation and grounding

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Physical
Dimensions Weight Rack or wall mounting kits (optional)

Safety
Agency approvals Dc breaker Low voltage disconnect Overload shutdown
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Ambient temperature Cooling method Elevation

Forced air (internal hot air exhaust fan is included). -200 to 3000 meters (-656 to 9842) with respect to sea level. Two year limited depot warranty, parts and labor.

Warranty
Warranty

XINv Series 199 Rack-mountable 48vdc to 115vac Inverter

XINv

recessed on/off switch output current level: 20% per LED

inverter On overload condition

front-right view
dc input voltage level: 20% per LED

XINv-400/700/1400-48v system architecture


dc input 42 56 vdc dc circuit breaker microprocessor DB9 port for communications
gnd

dc to ac inverter dc

isolation transformer

XINv output 115 vac + / - 3 %


L

ac

ground chassis ground neutral-ground bond on transformer output

earth ground

rear view

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

dc input circuit breaker

dc input terminal block connector

output ac via eight standard NEMA 5-15R receptacles

DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)

200 XINv Series XINv-400/700/1400-48vdc-115vac

XINv
Rack-mountable heavy-duty PWM dc to ac inverter

Specification
DB9 Port Function
Remote shutdown

Connector pin
1 For remote shutdown

Switching condition
A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart. RS-232 signal line RS-232 signal line For future use. Logic ground for pins 1 through 4. Closed when inverter is On, Open when inverter is Off. Open when dc is okay. Closed when input source (battery voltage) drops below 43vdc.

(Please note: relay contact is rated for 48vac/vdc, 1A maximum).

Transmit data Receive data Custom or future use Ground Inverter On Low battery alarm

2 TXD RS-232 signal 3 RXD RS-232 signal 4 Unused 5 Ground 6 + 7 Inverter On/Off (Relay contact) 8 + 9 Low battery alarm (Relay contact)

RS-232C serial communication for inverter status communication compatible with MEGATEC Communication Protocol, Part 1
Baud rate Data length Stop bit Parity SNMP interface for inverter monitoring and automatic shutdown configuration (optional) 2400bps 8 bits 1 bit None Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).

SNMP interface (optional)

XINv-400-700-1400-48V at a glance
Rack or wall-mountable heavy-duty PWM dc to ac inverter with isolation transformer and 115vac +/- 3% voltage regulation

Power with a Precision Attitude

High performance microprocessor-controlled PWM sine wave output +/-48vdc to 115vac inverter Pure sine wave output Isolation transformer Rack-mountable 2U high metal cabinet allows for rack or wall mounting using optional mounting kits

115vac +/-3% standard output can be set to a 100, 110 or 120vac output at the factory Eight NEMA 5-15R receptacles +/-48vdc terminal block connection with dc circuit breaker DB-9 signal port with RS-232 and relay contact signals SNMP compatible with optional SNMP adapter

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

XINv-400-700-1400-48vdc-115vac-Inverter-2006-10-16.pdf

XINv-400E/700E/1400E-48V ~ 400/700/1400VA, 400/700/1400W, 48vdc to 230vac


XINv Series 201 Rack-mountable 48vdc to 230vac Inverter

XINv
XINv model 400E-48V
400 VA 400 watts +/-48 vdc input 230 vac output

Pure sine wave

PWM dc to ac inverter

Voltage regulation + isolation

Rack-mountable Dc to Ac Inverter
These heavy-duty XINv Series dc to ac inverters are housed in a 2U rack-mountable enclosure. XINv PWM inverters feature a transformer isolated sine wave output. They are designed for all applications requiring continuous pure sine wave power. They produce 230 volts ac from 48volts dc.

700E-48V
700 VA 700 watts +/-48 vdc input 230 vac output

Key XINv benefits


XINv uses high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuits for high efficiency and low input dc ripple currents. They also feature high dc to ac power conversion efficiency, pure sine wave output and long MTBF. XINv also provides precision automatic voltage regulation: of 230vac +/-3% and less than 5% THD. XINvs 2U high construction with optional wall or rack-mounting kits provides maximum flexibility for telecom and industrial users. XINv offers a hardwire terminal block battery connection with a dc circuit breaker for external 48vdc battery banks.

Typical XINv applications


Applications include all waveshape sensitive equipment such as telecommunications systems, industrial, measurement and other mission-critical, harmonic-sensitive electronics. They are also ideal for use in facilities with 48vdc rectifier/battery power plants, where the inverter can be used to provide the function of a double-conversion on-line UPS.

1400E-48V
1400 VA 1400 watts +/-48 vdc input 230 vac output

Power with a Precision Attitude

Key XINv features


Pure sine wave inverter output Eight IEC320 receptacles Rack or wall mountable with optional rack/wall-mount kits Unipolar PWM inverter Ac output is isolated from dc +/-3% voltage regulation Comprehensive array of status LEDs/bargraphs SNMP compatible via RS-232 port with optional SNMP adapter Both RS-232 and relay contact signals are provided Very low audible noise Rugged construction supports mobile and portable applications Two year limited warranty parts and labor

How the XINv works


A rugged, high-performance microprocessor and unipolar pulse-width-modulated (PWM) power conversion circuit takes the dc input and converts it into a pure sine wave. The circuitry automatically adjusts the duty cycle of the output for all loads and inputs. XINv delivers a stable 50Hz +/-0.5% frequency. A dc circuit breaker protects all dc circuits, and an overload shutdown feature protects the inverter from overload. If the input dc voltage drops below 42vdc, a DB9 connector in the rear of the inverter sends signals for inverter output failure and low dc input voltage. A comprehensive array of output current, battery charge levels, and status LED indicators are provided for visual assessment of inverter status. A DB-9 port is provided for communication using RS-232 or dry relay contact signals.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

202 Specifications XINv-400E/700E/1400E-48vdc-230vac

Specifications XINv-400E-48V
400VA (400W)

XINv
Rack-mountable heavy-duty PWM dc to ac inverter
Power with a Precision Attitude

Specification
Electrical
Capacity in VA (watts) Inverter type

XINv-700E-48V
700VA (700W)

XINv-1400E-48V
1400VA (1400W)

Pulse-width-modulated (PWM) with isolation transformer. -48 volts dc / +48 volts dc 42 to 56 volts dc 25 amps 10mm2 (8 AWG) 40 amps 15mm2 (6 AWG) 75 amps 25mm2 (4 AWG) 3 Screw Terminal Block for Earth Ground, (+), (-) dc Inputs.

Input
Nominal voltage Operating voltage Maximum input current Dc input connector Recommended wire

Output
Ac output voltage Frequency stability Output waveform Load compatibility 230 volts +/-3% ac (Factory settable to 200, 220 or 240vac) 50 Hz +/- 0.5% Pure sine wave. Less than 5% maximum THD for 0 to 100% loads. All linear and non-linear loads from -0.6 (leading) to +0.6 (lagging) power factor, including new power-factor corrected switchmode power supplies and older non-power-factor corrected power supplies. Up to 3:1 crest factor loads can be powered by the inverter. Up to 300% surge power is available from the inverter to power load equipment with high starting/stopping surge currents for a few ac cycles. 1 minute @ 120% overcurrent. Greater than 85% under all load and dc input voltage conditions. Recessed On/off rocker style power switch. Rear-mounted DB-9 female signal port. Dc input voltage indicator: 5 green LEDs (25% per each LED). Ac output current: 5 green LEDs (25% per each LED). Inverter On: 1 yellow LED illuminates during normal inverter operation. Overload: 1 red LED illuminates if overload condition exists. Four standard IEC320-C13 female outlets (receptacles). <45dBA @ 1m under all operating conditions. 100% isolation between input dc and output ac (isolation transformer included). Metal enclosure is bonded to dc input terminal block Earth Ground input. 406mm(16)wide x 381mm(15)deep x 89mm(3.5)high (2U high) 10 kg(22 lbs.) 12 kg(26 lbs.) 18 kg(38 lbs.) 19 Inch Front or Rear rack-mount kit: MK-5019A 19 Inch Center rack-mount kit: MK-5019F Wall or Floor mount kit: MK-5000C Designed to meet IEC 60950 Safety Standards. Protection against shorts or misapplication of inverter current. Inverter turns off automatically if input dc voltage drops below 42vdc. Inverter turns off automatically if overload is >120% for over 1 minute.
0o to +40 oC(32o to +104 oF). 5 to 95% RH non-condensing. Storage temp. -20o to +60 oC(-4o to +140 oF).

Load crest factor Surge current capability Overload capability Power efficiency Power On/Off switch Communications Status indicators

Ac receptacles Audible noise Isolation and grounding

TSis ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies.

Physical
Dimensions Weight Rack or wall mounting kits (optional)

Safety
Agency approvals dc breaker Low voltage disconnect Overload shutdown
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Environmental
Ambient temperature Cooling method Elevation

Forced air (internal hot air exhaust fan is included). -200 to 3000 meters (-656 to 9842) with respect to sea level. Two year limited depot warranty, parts and labor.

Warranty
Warranty

XINv Series 203 Rack-mountable 48vdc to 230vac Inverter

XINv

recessed on/off switch output current level: 20% per LED

inverter On overload condition

front-right view
dc input voltage level: 20% per LED

XINv-400E/700E/1400E-48V system architecture


dc input 42 56 vdc dc circuit breaker microprocessor DB 9 port for communications
gnd

dc to ac inverter dc

isolation transformer

XINv output 230 vac + / - 3%


L

ac

ground chassis ground neutral ground bond on transformer output

earth ground

rear view

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

dc input circuit breaker

dc input terminal block connector

DB-9 communication port provides both RS-232 and relay alarm contact signals (or SNMP using optional SNMP adapter)

(115V NEMA 5-15R receptacles shown)

output ac via four standard IEC320- C13 female outlets (receptacles)

204 XINv Series XINv-400E/700E/1400E-48vdc-230vac

XINv
Rack-mountable heavy-duty PWM dc to ac inverter

Specification
DB9 port function
Remote shutdown

Connector pin
1 For remote shutdown

Switching condition
A +5vdc to +12vdc signal sent to pin#1 for three full seconds will shut down the inverter remotely. Note: this operation requires manual restart. RS-232 signal line RS-232 signal line For future use. Logic ground for pins 1 through 4. Closed when inverter is On, Open when inverter is Off. Open when dc is okay. Closed when input source (battery voltage) drops below 43vdc.

(Please note: relay contact is rated for 48vac/vdc, 1A maximum).

Transmit data Receive data Custom or future use Ground Inverter on Low battery alarm

2 TXD RS-232 signal 3 RXD RS-232 signal 4 Unused 5 Ground 6 + 7 Inverter On/Off (Relay Contact) 8 + 9 Low battery alarm (Relay contact)

RS-232C serial communication for inverter status communication compatible with MEGATEC Communication Protocol, Part 1
Baud rate Data length Stop bit Parity SNMP interface for inverter monitoring and automatic shutdown configuration (optional) 2400bps 8 bits 1 bit None Using an external SNMP adapter, the RS-232 signals (from the DB-9 female connector) from the inverter can be converted to 10M/100M fast Ethernet signals (and RJ-45 connection) for external inverter monitoring/configuration capability using Telnet, web browsers, or NMS (most such external devices support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP & SMTP protocols).

SNMP interface (optional)

XINv-400E/700E/1400E-48V at a glance
Rack or wall-mountable heavy-duty PWM dc to ac inverter with isolation transformer and +/- 3% voltage regulation

Power with a Precision Attitude

High performance microprocessor-controlled PWM sine wave output +/-48vdc to 230vac inverter Pure sine wave output Isolation transformer Rack-mountable 2U high metal cabinet allows for rack or wall mounting using optional mounting kits

230vac +/-3% standard output can be set to a 200, 220 or 240vac output at the factory Four IEC 320-C13 female outlets +/-48vdc terminal block connection with dc circuit breaker DB-9 signal port with RS-232 and relay contact signals SNMP compatible with optional SNMP adapter

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

XINv-400E-700E-1400E-48vdc-230vac-Inverter-2006-10-16.pdf

White Paper Series ~ TSi Power White Papers on Power Protection


White Paper Series 205 TSi Power White Papers On Power Protection

White Paper
White Paper Series

TSi White Papers on Power Protection

Power with a Precision Attitude

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

206 White Paper Series TSi Power White Papers On Power Protection

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

WP-White-Paper-Series-2006-10-16.pdf

Coordination of Telecommunications SPDs in Countries with Unstable Power


White Paper Series 207 Coordination of Telecommunications Surge Protective Devices In Countries With

White Paper
Author Peter Nystrom President TSi Power Corp

Power Protection in Countries with Unstable Ac Mains Voltages

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable Ac Power

ZONED PROTECTION STRATEGY

Abstract
The rapid growth of the world market for telecommunications equipment will continue for the next several years. Manufacturers of radio infrastructure and switching equipment are based in the USA, Europe and Japan with some minor exceptions. Yet, these manufacturers are often not familiar with power quality in places far away from their home countries. The needs for surge protective devices vary from market to market and are especially challenging in the emerging countries. Why? Surge protection in the USA and Europe is based on the assumption that the ac power-line voltage is relatively stable. Developing countries, however, often have inadequate infrastructures for the generation and distribution of electric power. The lack of stable ac power complicates the selection and coordination of surge protective devices considerably. This paper will review the new IEC surge protection standards and discuss how to achieve coordination of surge protective devices in accordance with IEC 1312 principles.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

208 White Paper Series Coordination of Telecom Surge Protective Devices In Countries With

Introduction
IEC standards are used throughout Europe and in many other parts of the world. CE marking is based on such IEC standards. CE marking involves both equipment safety and electromagnetic compatibility while UL only involves safety. Thus, all electronic equipment that carry the CE label should have been tested to withstand static electricity, electric fast transients and surge voltages. This paper will focus on the surge voltage aspects. IEC 1000-4-5 is a Combination Wave consisting of a voltage waveform of 1.2/50 s with an amplitude of 2000 V in normal mode and 4000 V in common mode, and a current wave form of 8/20 s at 2000 A. The Combination Wave is identical to the U.S. ANSI/IEEE C62.41-1991 Combination Wave with the following exceptions: the ANSI/IEEE voltage is 6000 V and the current is 3000 A. In the IEC standard, the equipment that is tested for surge immunity is referred to as the "vulnerable equipment." Hence, the term "vulnerable equipment" will be used in this paper. All "vulnerable equipment" must be able to withstand IEC 1000-4-5 without upset, thus guaranteeing a certain level of surge immunity, which will be sufficient for most office environments. IEC has developed a series of standards that apply to enhanced surge protection of equipment and structures in cases where built-in equipment surge immunity is not sufficient. Telecom installations in outdoor shelters and enclosures are good examples of when enhanced surge immunity is required. This paper will review key aspects of the following IEC standards: IEC 1024-1: 1990 Protection of Structures Against Lightning -Part 1: General Principles IEC 1312-3: Protection Against Electromagnetic Impulse -Part 3: Requirements of Surge Protective Devices.

SPECIAL PROBLEMS IN DEVELOPING COUNTRIES


Fluctuating power line voltage
Causes
Overloaded, inadequate power generation and distribution systems, particularly when large step load changes are present, result in large voltage sags and surges. Voltage fluctuations between 155V to more than 310V have been observed in the field. Differences between day- and night-time voltage of 40V have also been observed. Such conditions are common in Africa, India, Pakistan and China, but can be found in many other areas. Additional power plants and distribution infrastructure is needed in many developing countries. Timely power plant expansion is prevented by political and economic issues, which means the problem is here to stay for the foreseeable future.

Effects
Sags and undervoltages can cause component overheating or destruction, which reduces the life and deteriorates the real reliability as opposed to the estimated reliability, based on steady-state conditions of the power supply Swells and overvoltages can cause component overheating and destruction of MOVs, SCRs and input capacitors that are rated too close to the line voltage. It is fairly common for power supply and telecom rectifier manufacturers to rate

White Paper Series 209 Coordination of Telecom Surge Protective Devices In Countries With Unstable Ac

input MOVs at 275Vrms with the apparent objective of reducing the surge remnant voltage, thus providing better surge immunity of the power supply. The author of this paper has observed still-functioning telecom rectifiers where the input MOVs had been completely destroyed by high line voltage. Boost converters can be destroyed by voltage swells that cause increased energy storage in the input filter, which charges the output capacitor to an unsafe level. The charge level is dependent on the value of the output capacitor and the load levels for the dc to dc converter connected to the output of the boost converter. Poorly damped EMI filters can dramatically magnify the effects of voltage disturbances. The result can be oscillations inside the EMI filter during transitional conditions. Severe voltage surges may result from energy released when saturated inductors are looking for a path to release energy.

Frequent lightning conditions


Review of IEC 1024-01
This standard relates to the protection of structures against lightning. A structure can be anything from a high rise building to an outdoor shelter containing telecommunications equipment. IEC 1024 introduces the concept of Lightning Protection Zones (LPZ). Figure 1 below illustrates the basic zone concept.

Figure 1

The purpose of LPZs is to divert the surge energy from lightning and other disturbances away from the "vulnerable equipment." The majority of the energy should be diverted at the lowest zone boundaries. The number of required zones is determined by the physical properties of the structure and the sensitivity of the "vulnerable equipment."

210 White Paper Series Coordination of Telecom Surge Protective Devices In Countries With

Sensitive equipment installed in outdoor shelters, particularly when a poor physical ground is present, require a higher number of zones. Basic Lightning Protection Zones and surge current waveforms are explained below:

LPZ 0A
This zone is subject to direct lightning strokes and may have to carry the full lightning current. The unattenuated electromagnetic field occurs here. 100 kA, 10/350 s 200 A, 0.5 s 25 kA, 0.25/100 s Figure 2 shows a comparison between the 10 x 350 s test waveform and lower-energy Combination Wave.

Figure 2

LPZ 0B
This zone is not subject to direct lightning strokes. The unattenuated electromagnetic field occurs here. 10 kV, 1.2/50 s 5 kA, 8/20 s

LPZ 1
This zone is not subject to direct lightning strokes and currents on all conductive parts within this zone are further reduced from previous zones. The electromagnetic field may also be attenuated depending on the screening measures.

White Paper Series 211 Coordination of Telecom Surge Protective Devices In Countries With Unstable Ac

LPZ 2
When a further reduction of conducted currents and/or magnetic field is required, subsequent zones can be introduced. In general, the higher the number of zones, the lower the electromagnetic environment parameters.

LPZ 3
According to the authors interpretation of IEC standards, this zone should contain the protected equipment. The requirement for Zone 3 is that the remnant surge voltage does not exceed the test levels specified in IEC 1000-4-5: Combination Wave, 1.2/50 s, 8/20 s 2000 A Normal-Mode Voltage: 2000 V Common-Mode Voltage: 4000 V

Review of IEC 1312-3


Lightning surges contain significant amounts of energy which needs to be diverted away from the "vulnerable equipment." Electronic equipment, if CE marked, is designed with a certain built-in surge voltage immunity in accordance with IEC 10004-5 this level of immunity will be sufficient for the majority of office buildings when the "vulnerable equipment" is located far away from the electric service entrance. Thus, equipment that carries the CE mark will work well without surge protection in many environments. However, when the "vulnerable equipment" is installed close to the electric service entrance, or in an outdoor enclosure, particularly in areas with a poor physical ground (dry sand, rock, etc.), it is often necessary to add external surge protective devices (SPDs). IEC recommends (IEC 1024) that lightning protection zones (LPZ) be established to successively reduce lightning currents, in stages, down to the built-in immunity of the "vulnerable equipment." The number of zones required depends on the structure containing the installation and the "vulnerable equipment." IEC 1024 requires that an SPD be installed at each zone boundary. The surge current and voltage ratings of individual SPDs must not be exceeded.

Purpose of coordination
To progressively reduce the lightning threat, in stages (SPD 1, 2 & 3) down to the surge withstand capability of the "vulnerable equipment," without exceeding surge current and voltage ratings of individual SPDs.

Coordination concepts
IEC 1312 defines four coordination "variants." The first three utilize individual single-port SPDs while the fourth variant is a two-port hybrid design.

Variant I
Shown in figure 3, the rated voltage of SPDs is identical and coordination is achieved by separating each SPD by means of series impedance.

212 White Paper Series Coordination of Telecom Surge Protective Devices In Countries With

Figure 3

Variant I is not recommended by the IEC, probably because it would require approximately 30 (10 m) of wire or separate inductors between each SPD, which is not practical when installing equipment close to the electric service entrance or in outdoor enclosures.

Variant II
Shown in figure 4, the rated voltages of SPD's are stepped so that the SPD in the "vulnerable equipment" has the highest rated voltage and SPD 3, 2 & 1 have progressively lower rated voltages, thus assuring that each upstream SPD would divert progressively higher currents.

Figure 4

Variant II is difficult to implement as most power supplies, uninterruptible power systems and telecom rectifiers, rated for 230 Vac, use input SPDs with a 275 Vrms rating. Thus, stepping down rated voltage, would cause SPD 1 and 2 to be destroyed by normal line voltage fluctuations-experience has shown that fluctuations of plus 10% resulting in 250V is not unusual.

White Paper Series 213 Coordination of Telecom Surge Protective Devices In Countries With Unstable Ac

Variant III
Shown in figure 5, includes a component with a non-linear current/voltage characteristic, such as a spark gap. The SPD 1 spark gap would divert the majority of the surge current and output a Combined Wave, similar to ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000 A, 6000 V, to downstream SPDs 2 and 3. The voltage ratings of SPD 2 and 3 are identical, but each device will handle considerably less current due to the much higher energy handling capability of spark gap SPD 1.

Figure 5

Variant III is a better choice than I or II as the spark gap is insensitive to fluctuations in line voltage. However, spark gap follow-on, short-circuit current may be an issue, and MOVs will still be sensitive to line voltage fluctuations.

Variant IV
Figure 6

Figure 6 shows a two-port hybrid device that incorporates cascaded stages of SPDs internally coordinated with series impedance.

214 White Paper Series Coordination of Telecom Surge Protective Devices In Countries With

A hybrid device can be designed to maximize performance while reducing the undesirable characteristics of spark gaps and SPDs based on varistor or silicon-avalanche-diode technology. The use of a hybrid device eliminates the need to coordinate surge protective devices, but does not eliminate sensitivity to prolonged ac overvoltage.

Proposed hybrid device in accordance with Variant IV


The purpose of the circuit shown in figure 7 below is to provide, in a condensed space, the critical functions required for a universal ac power interface used in outdoor shelters for cellular, fixed wireless and other telecom equipment. The major functions required are outlined below: Surge protective device coordination for successive reduction of surge currents, High energy handling capability, Tolerance against high line voltage, Adjustment for local nominal voltage variation, Low dv/dt rise time, Function not dependent on performance of internal protection of "vulnerable equipment."

Figure 7

Discussion of circuit features shown in figure 7


The protection scheme is designed to work with an outdoor equipment shelter even when "vulnerable equipment" uses 275V MOVs as internal protection. In this case it is impossible to provide coordination in accordance with Variant II and Variant I is not practical, because the required wiring distances of 30 between SPD's are too short in an outdoor equipment shelter. The spark gap is designed to provide primary protection within LPZ 0 and ignites when the surge voltage reaches approximately 2000V. The series inductance provided introduces the necessary coordination and reliable ignition of the spark gap. The output of the spark gap is a Combination Wave and is easily handled by the circuits in LPZ 1 and 2. Spark gaps can handle considerably more energy than MOV or SAD arrays and are not sensitive to line voltage fluctuations and are also more cost effective. The major disadvantage of a spark gap is the follow-on current which can cause tripping of upstream circuit protection devices. However, new-technology spark gaps based on the arc-chopping principle provide significant performance improvements.

White Paper Series 215 Coordination of Telecom Surge Protective Devices In Countries With Unstable Ac

The new spark gap technology shown in figure 8 consists of two electrodes positioned opposite each other, held in place by a barrier and separated by a baffle. This arrangement and spacing of electrodes is called "arc chopping" and provides reliable ignition of the arc, which is then chopped by the baffle into several smaller arcs. Special versions with reduced follow-on current are available for branch circuits and services up to 75 kVA. The neutral-to-ground bond provided at the service entrance or by a separate isolation transformer eliminates all surge voltages between neutral and ground and the requirement for SPD's between power carrying conductors and ground. The series inductor with primary buck-boost windings provides static adjustment for different nominal voltages that can range from 200 to 250 V. The buck-boost windings can also be controlled automatically if the line voltage is chronically unstable. The series inductor also forms a two-pole filter together with the shunt capacitor. The filter reduces the surge voltage rise time (dv/dt) from 6 kV/s to 10 V/s thus providing considerable relief for the "vulnerable equipment." The filter which starts conduction well before MOV 1 also provides protection against electric fast transients and other line noise. MOV 1, located within LPZ 2, is a 40-mm device rated for 275 Vrms, which is made possible due to the voltage adjustment provided by the buck-boost windings on the primary of the series inductor. In other words, MOV 1 is well-protected against premature failure caused by high nominal voltages. Now available in attractive packaging, easy-toreplace MOVs provide thermal disconnect and alarms in case of failure.

Figure 8

216 White Paper Series Coordination of Telecom Surge Protective Devices In Countries With

Summary
This paper has reviewed IEC 1024 and 1312 standards for protection of structures against lightning and for coordination of surge protective devices (SPDs). Line voltage fluctuations outside of the typical regulation window of most power supplies have been observed in many developing countries. Methods for designing an economical power interface which provides hybrid surge protection for demanding international applications have been discussed. The hybrid circuit provides full coordination of SPDs while being tolerant to line voltage fluctuations.

About the Author:


Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in the state of Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, automatic transfer switches and dc to ac inverter systems designed to meet the challenging international power conditions.
Copyright held by Intertec International, Inc. Originally published in the Power Quality 97/Power Value 97 Proceeding for the POWER SYSTEMS WORLD 97 Conference held in Baltimore, MD September 1997.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

WP-Coordination-Telecom-SPDs-Unstable-Power-2006-10-16.pdf

TSi Power Case Studies ~ Mission-critical Solutions

White Paper
Author Nam Paik TSi Power Corp

White Paper 217 TSi Power Case Studies: Mission-Critical Solutions

TSi Power ~ Case Studies Of Mission-Critical Solutions

TSi Power Case Studies


Mission- critical solutions

TSi Power supplies Federal Aviation Administration with UPS


TSi UPS systems back-up signal transmitters that send critical flight information to all airplanes approaching any airport for landing.
Since 1991, TSi Power has been providing the Federal Aviation Administration (FAA) with UPS systems designed to provide 6 to 8 hours of battery back-up time in hostile environments. The TSi UPS systems back-up signal transmitters that send critical flight information to all airplanes approaching any airport for landing. The transmitters & UPS systems are housed in unmanned and non- air-conditioned equipment huts that are subject to extreme temperature swings between winter and summer. Several hundred systems were installed nationwide and have been operational since 1991 with minimal field problems. The FAA was so impressed with their performance that they have continued to install our UPS systems at hundreds of sites. So if you have a system that is exposed to harsh conditions, then a rugged TSi UPS is your solution!

TSi Power backs up White House telecommunications system with UPS and ARm-1000 automatic transfer switches
There is no more mission critical communications system than the Presidential telecommunications system run by the State Department. It is responsible for routing and tracking all telecommunications between the White House and the world. This system is backed up with both a TSi Power UPS system and a large generator UPS system to provide back-up power redundancy. In case of a problem with the primary ac source, TSi Powers ARM-1000 Automatic Redundancy Module automatically detects the failed ac line and seamlessly transfers to another ac source without interruption. In the most unlikely event that even the back-up ac source is also defective, a second ARM-1000 can automatically select the second back-up ac source. There is no limit to the levels of redundancy that can be applied to these mission critical systems. By using multiple ARM-1000 units, as many layers of independent power back-up can be achieved as there are power sources available. Independent power sources include battery back-up, alternate utility circuit (from a different power grid), and emergency ac generator sets to name a few. If your system is truly mission critical, then TSi Power has the solution!

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

218 White Paper TSi Power Case Studies: Mission-Critical Solutions

The United States Army relies on TSi Power ac line conditioners for demanding international applications in the field
Having access to accurate and timely information is the key to success in any field in the world, and the Armed Forces are no exception. In 1997, the U.S. Army was dispatched to Bosnia to serve as part of a peacekeeping force to help end the brutal conflict engulfing that region. Army Intelligence, which was responsible for gathering, disseminating and forwarding vast quantities of information to the peacekeeping forces, ran into some problems. During much of their operation, utility power was unavailable. They also found that their UPS technology was not capable of handling the large numbers of spikes, surges, sags and brownouts that were present on the AC line. As a result, the back-up UPS systems they relied on to maintain their computer networks were actually burning out. When all their UPS were gone, they hooked their computers directly into the field generators set up in their camps. This caused catastrophic computer failure. Since an army with no information is no army at all, the U.S. Army turned to TSi Power to create a quick solution. Within a few weeks, the U.S. Army Intelligence was up and running without fear of burning up their UPS systems or their computers after installation of rugged, generator compatible line conditioners from TSi Power.

Major drug store chain powers through an earthquake with TSi UPS
The drugs stores point-of-sale (POS) computers equipped with these UPS systems continued to operate and record unprecedented sales because all the other drug stores were shut down.
In 1989, a significant earthquake hit the San Francisco area causing millions of dollars in damage and interrupting the basic utilities for the area residents. Panic gripped many of the residents who immediately went to buy emergency food supplies, candles, flashlights, batteries, etc. TSi Powers UPS systems were backing up three drug stores in San Francisco at the time of the earthquake. These drug stores were open a full eight hour business day entirely on TSi back-up power. The drugs stores point-of-sale (POS) computers equipped with these UPS systems continued to operate and record unprecedented sales because all the other drug stores were shut down. This incident convinced the drug stores corporate executives that extended battery UPS systems were a necessity for uninterrupted operation of retail stores during emergency situations. TSi has the solution for all retail and service industry power protection and back-up power problems!

Medical equipment manufacturer utilizes TSi Power UPS and battery extension units for patient respirators
A leading manufacturer of medical technologies for critical care patients. Since 1990, a leading intensive patient care respirator manufacturer has been using a customized version of TSi Powers UPS and Battery Extension Units to provide continuous ac power to respirators of critically ill patients. The respirator and UPS system are attached to the patients portable bed and moved around inside the hospital (e.g. from the operating room to the recovery room) by simply unplugging the UPS from the ac socket. In order to meet the stringent European medical equipment safety standards, TSi Powers engineers worked closely with manufacturers engineers to implement the necessary modifications to the existing models.

Applied Energy Concepts, a partner of TSi Power, solves telecommunication problems in emerging markets
In January 1998, TSi Power joined with Applied Energy Concepts to increase its range of power quality products and applications on the market today. Applied Energy Concepts develops solutions that control electrical surges and regulate voltage for mission-critical electronic systems.

White Paper 219 TSi Power Case Studies: Mission-Critical Solutions

These international applications have included protection for switchmode rectifiers, power supplies and uninterruptible power systems. A major cellular infrastructure suppliers experience has revealed that conventional surge protection devices have little impact on equipment failures and often fail themselves as a result of inadequate power generation and distribution infrastructures. In thousands of installations worldwide, AEC equipment has proven to consistently reduce high failure rates of telecom rectifiers, UPS, and other equipment connected to the power line. Critical loads such as base transceiver stations (BTS) and nodes for wireless-in-the-local-loop applications as well as other outdoor enclosure installations often require this additional protection.

Constant voltage and isolation of TSi Premium Series UPS key to smooth manufacturing control systems
In 1996, TSi Power was asked to assist a large farming product manufacturer in the middle of Georgia. Nearly one hundred cabinets that control the automated manufacturing equipment had to be manually reset after each power outage (even though they were protected by a well-known, national brand UPS). Each manual reset operation meant a down-time of over one hour for the entire plant and financial losses were piling up quickly, especially during summer months when a number of power outages can occur in a week. After careful analysis of the problem, TSi engineers concluded that the problem was caused by a lack of voltage regulation, lack of isolation, power conditioning, and long transfer time (to 8 milliseconds) of existing standby UPS units. They recommended the Premium Series UPS-16000 with built in CVT (constant voltage transformer with 100% input/output isolation) and zero transfer time. The result was spectacular. The controller cabinet protected by the TSi Power Premium Series no longer required a manual reset after a power outage while the identical control cabinet powered by the original standby UPS needed a manual reset after each power outage. By the middle of 1997, the manufacturing plant management decided to replace all of their existing UPS units with TSi Power Premium Series UPS-16000 units. TSi Power is also helping in the disposal of the old standby UPS units that are being replaced since the lead-acid batteries inside the old UPS units must be recycled properly.

Internet service provider keeps the world connected with TSi Power rack-mounted UPS and battery extension units backing them up
In 1996, a leading Internet Service Provider (ISP) began to realize that with increasing frequency of power outages and transients damaging the sensitive equipment in one of their Cisco 7513 routers and other critical communications equipment, it was time to take action. After careful evaluation, they chose TSi Powers Premium Series rack-mounted UPS, Battery Extension Unit and Automatic/Manual Bypass Unit. In 1998, the ISP is in the process of installing several hundred Premium Series UPS systems in equipment rooms located in all of the major cities in the U.S. This again proves that for Premium Power Protection, customers turn to TSi Power.

About the author


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Nam Paik ~ Director of Engineering, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.
WP-Case-Studies-TSi-Rev1-2006-10-16.pdf

220 White Paper TSi Power Case Studies: Mission-Critical Solutions

This page intentionally left blank.

Choosing UPS Protection for Underdeveloped Countries


White Paper Series 221 Choosing UPS Protection For Underdeveloped Countries

White Paper
Author Nam Paik Director of Engineering TSi Power

Choosing UPS Protection for Underdeveloped Countries

Choosing UPS Protection for Underdeveloped Countries


Facing Unusual Challenges
I. INTRODUCTION
Problems include: Frequent blackouts & ac mains voltages frequently fluctuate beyond the IEC assumed standard of a 184 to 264vac input range.
All electrical and electronic equipment users in underdeveloped countries face unusual difficulties in trying to cope with ac power problems. Among the problems are: 1. Frequent blackouts due to inadequate generation capacity; 2. Wide ac mains voltage variation due to inadequate distribution infrastructure; 3. Generally poor quality of the power, in areas such as distortion, spike/noise, frequency, sags/surges and dropouts, especially when generators are used to supplement utility power. Of course, these problems also exist in developed countries. However, in underdeveloped countries in Africa, South America and Asia, such power problems can occur so often as to cause unacceptable levels of system down time and catastrophic equipment failures. Also, uninterruptible power supply (UPS) systems, which are installed to mitigate the above-mentioned ac power problems, often exhibit unacceptably high failure rates. Standard UPS systems are designed to meet IEC specifications for a mains ac voltage window of 184 to 264vac, while actual mains voltages quite often vary between 160 to 330vac in many developing countries.
TSi Power Corporation

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Operating a UPS system outside of its specified ac mains voltage window is one of the primary reasons for premature UPS failure. When the other common power quality problems such as surges, spikes, noise, sags, and frequency problems are also considered, designing a reliable UPS system for underdeveloped countries poses a special challenge to UPS manufacturers.

222 White Paper Series Choosing UPS Protection For Underdeveloped Countries

II. DIFFERENCES IN UPS REQUIREMENTS


A standard UPS designed for use in a developed country (such as in the USA) might encounter the following difficulties when installed in underdeveloped countries: 1. Because of frequent blackouts, the batteries in the UPS, whether online or standby, will be discharged and charged very often. Furthermore, because the duration of the blackout is usually longer than in developed countries, the batteries will be more deeply discharged. These two factors combine to drastically reduce the expected lifetime of the battery. For example, a typical lead-acid battery will last for about 1,200 discharge/charge cycles when the depth discharge is 30% of battery capacity. However, when the depth of discharge is 50%, this number is reduced to 450. And when the depth of discharge is 100%, the number is reduced to below 200. A UPS in the U.S. may experience a 100% discharge/charge cycle about 5 to 10 times a year. In underdeveloped countries, this may occur almost every day, reducing the expected life of the UPS to less than a year. 2. Because of the frequency of power disturbances, the power electronic circuitry in the UPS must work far more often and under greater stress. This is especially true for standby UPS systems, which must make the transfer to battery backup every time there is a power disturbance. Even in doubleconversion online UPS systems (where transfer to battery is not required), the power transistors and transformers must operate at higher current and voltage levels during brownout and overvoltage conditions, resulting in a shorter-than-normal operating lifetime of the UPS. 3. The batteries cannot be charged fully when the power disturbances occur so frequently. Consequently, the UPS cannot provide the rated backup time during each power disturbance. This can cause severe problems with mission-critical computers or telecommunications equipment that depend on the UPS to provide the 99.99% (or higher) system availability. 4. Small emergency power generators can cause special problems for when they are used to power a UPS system. They are known to produce wide frequency/voltage fluctuations, surges/spikes, and highly distorted (often nonsinusoidal) outputs which can cause continuous mains/inverter transfer operations, shutdowns, and even catastrophic UPS failure. 5. For sites subject to frequent lightning strikes, absence of a coordinated surge protection system based on IEC Technical Specification 61312-3 "Requirement of Surge Protective Devices" may cause premature failure of UPS due to unmitigated surges and spikes induced on incoming ac power line(s). 6. If the ambient temperature is outside of the optimum 10 to 25 degree C range, standard sealed lead-acid batteries cannot be used. Standard batteries are rated to work only when temperature is above 0 degree C, and sudden battery failure can occur when operating temperature goes above 40 degree C. Even at 30 degrees C, expected battery lifetime is reduced by 50% compared to the expected battery lifetime at 20 degrees C.

Challenges include: Deep and numerous battery discharges, frequency of power disturbances, small generator aberrant output, wide temperature swings, and non-coordinated systems unable to handle lightning.

White Paper Series 223 Choosing UPS Protection For Underdeveloped Countries

III. SOLUTIONS FOR RELIABLE AND COST-EFFECTIVE UPS PROTECTION


The above-mentioned international power quality problems provide UPS manufacturers with a difficult challenge in trying to design UPS systems for underdeveloped countries. It must be recognized that no UPS system can provide foolproof protection against all types of power problems, especially at a reasonable cost. To provide the best solution to power problems in underdeveloped countries requires an intelligent application of technology, coupled with an intimate familiarity with the nature of the problems. Involved in international ac power protection since 1990, TSi Power has developed a family of UPS systems which are particularly useful in underdeveloped countries, with the following features: 1. A Voltage Range Extended UPS (VRe-UPs) provides an input voltage range of 160 to 330vac for a nominal 230vac in/output UPS system. Battery lifetime is maximized since battery discharge takes place during blackouts only (and not for brownout or overvoltage periods). The up-time percentage of a VReUPS is significantly higher than a standard UPS since the battery is always kept fully charged even during deep brownouts or overvoltage conditions. 2. Since only regulated 230vac is supplied to transistors and transformers in a VRe-UPs, they are not subjected to excessive voltage, current, or heat even during brownouts or overvoltage periods. Thus, the maximum lifetime of transistors and transformers can be expected, thus increasing the reliability (and up-time percentage) of the VRe-UPS and the connected equipment. 3. When a small emergency power generator is used to power a UPS, the Precision Voltage Regulated UPS (VRp-UPs) should be used. The VRp circuit constantly regenerates a clean sine wave even from a highly distorted and non-sinusoidal output typical of a small power generator. By providing only high-quality, regulated sinewave input to the UPS, the VRp-UPs provides maximum UPS up-time percentage as well as maximum UPS and connected equipment lifetime. 4. When a site is subject to frequent and severe lightning strikes, an Isolation Line Conditioned (ILc-UPs) should be used. By providing transformer isolation, a new neutral-to-ground bond, surge protection at the output side of isolation transformer, and excellent noise filtering between incoming ac and the UPS, a coordinated protection system based on IEC Technical Specification 61312-3 is included. Therefore, the maximum level of surge protection for the mission-critical equipment is provided by the ILc-UPs. 5. If the ambient temperature is expected to be outside of the recommended 10 to 25 degree C window, a special class of wide-temperature rated batteries (which are guaranteed to work from -20 to +55 degrees C) must be used in order to obtain 5 years (or longer) of battery lifetime.

TSi Power has developed 4 distinct UPS topologies to handle the challenging problem of reliability in underdeveloped countries.

224 White Paper Series Choosing UPS Protection For Underdeveloped Countries

IV. CONCLUSION
There are special challenges in designing a UPS system which can provide the requisite ac power protection and backup in underdeveloped countries. A UPS manufacturer must be knowledgeable in handling all the possible power quality problems in the country where the UPS must be installed. Armed with this knowledge of actual conditions in underdeveloped countries, it is possible to provide an enhanced-performance, yet cost-effective UPS system that can withstand hostile conditions and fully protect the connected equipment against the following problems: 1. Wide ac mains voltage variation from 160 to 330vac. 2. Distortion, spike/noise, frequency, sags/surges and dropouts produced by small emergency power generators in wide use in underdeveloped countries due to the shortage of adequate power generation and distribution infrastructures. 3. Surges and spikes caused by frequent lightning strikes nearby. 4. Ambient temperature outside of the 10 to 25 degree C range. Since 1992, TSi Power has developed several special optional modules, which can be added to the standard UPS, which extend the operating voltage range significantly and maximize the equipment protection level, up-time percentage and the lifetime of the UPS. In order to ensure reliable UPS operation in an underdeveloped country, a specially modified UPS might be required. TSi Powers experienced technical staff can work with customers to arrive at the best UPS design for underdeveloped countries.

A UPS manufacturer must be knowledgeable in handling all the possible power quality problems in the country where the UPS must be installed.

ABOUT THE AUTHOR


Nam Paik ~ Director of Technology, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Choosing-UPS-Underdeveloped-Countries-2006-10-16.pdf

Designing for Surge Immunity in International Markets


White Paper Series 225 Designing For Surge Immunity In International Markets

White Paper
Author Peter Nystrom President TSi Power Corp

Designing for Surge Immunity in International Markets

Designing for Surge Immunity in International Markets


Facing Hostile Environments
BACKGROUND
Surge immunity means the ability of electronic equipment to operate properly, with a low rate of failure, in the presence of abnormal line voltages and surge voltages from load switching and lightning.
Systems integrators in telecommunications and other industries that export to markets all over the world have to design equipment that will operate in electrical environments that may be more hostile than those found in North America or most parts of Western Europe. Power supplies, uninterruptible power systems and telecommunications rectifiers, for international applications, are typically designed to accept an input voltage window of 170 to 270 Vac. In addition, the equipment will have built-in surge withstand capability in accordance with IEC 1000-4-5, if CE marked. It is fairly safe to assume that power supplies and electronic equipment, designed in accordance with IEC standards, will be reasonably reliable in markets with stable power and minor lightning activity. However, conditions encountered in parts of Latin America, Asia, Africa and eastern Europe are often severe enough to cause power supply and sometimes system malfunction. The principals of TSi Power have identified three factors that drastically reduce system reliability:
TSi Power Corporation

Inadequate infrastructure for the generation and distribution of electricity, causing frequent power outages and large voltage fluctuations. Inconsistent wiring and installation practices, locations without TN-S grounding systems (TN-S is the international term for three-phase with grounded neutral). Frequent lightning activity, especially when combined with a poor ground, thus causing lightning currents to find a path to ground through the power lines.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

Designing for surge immunity requires careful attention to a number of factors that may be more or less difficult to control. Surge immunity, in the context of this paper, means the ability of electronic equipment to operate properly, with a low rate of failure, in the presence of abnormal line voltages and surge voltages from load switching and lightning. This paper will discuss factors that may necessitate enhanced surge immunity.

226 White Paper Series Designing For Surge Immunity In International Markets

FACTORS AFFECTING EQUIPMENT IMMUNITY


Fluctuating power line voltage
Causes
Overloaded , inadequate power generation and distribution systems, particularly when large step load changes are present, result in large voltage sags and surges. Voltage fluctuations between 155 to more than 310 V have been observed in the field. Differences between day and night-time voltage of 40 V have also been observed. Such conditions are common in Africa, India, Pakistan and China, but can be found in many other areas. Additional power plants and distribution infrastructure is needed in many developing countries. Timely power plant expansion is prevented by political and economic issues, which means the problem is here to stay for the foreseeable future.

Effects
Power supplies can fail for a variety of reasons related to voltage fluctuations, the most common ones are listed below: Sags and undervoltages can cause component overheating or destruction, which reduces the life and deteriorates the real reliability as opposed to the estimated reliability, based on steady-state conditions of the power supply. Swells and overvoltages can cause component overheating and destruction of MOVs, SCR's and input capacitors that are rated too close to the line voltage. It is fairly common for power supply and telecom rectifier manufacturers to rate input MOVs at 275 Vrms with the apparent objective of reducing the surge remnant voltage, thus providing better surge immunity of the power supply. The author of this paper has observed still-functioning telecom rectifiers where the input MOVs had been completely destroyed by high line voltage. Typical EMI filters are not well damped, which can dramatically magnify the effects of voltage disturbances. The result can be oscillations inside the EMI filter during transitional conditions. Severe voltage surges may result from energy release where saturated inductors are looking for a path to release energy. Boost converters can be destroyed by voltage swells that cause increased energy storage in input filter, which charges the output capacitor to an unsafe level. The charge level is dependent on the value of the output capacitor and the load levels for the DC/DC converter connected to the output of the boost converter.

Most power supplies, telecom rectifiers and UPS for international applications are designed for a nominal voltage of 230V with an input range of 176 to 270V

Remedies
Most power supplies, telecom rectifiers and UPS for international applications are designed for a nominal voltage of 230V with an input range of 176 to 270V. As previously mentioned, input MOVs are typically rated for 275Vrms to reduce surge remnant voltage. Experience suggests that the standard specifications for 230V power supplies are adequate for the majority of installations in major industrial countries. What to do if the supply voltage falls outside of the standard parameters? One possible solution is to specify telecom rectifiers and UPS that can withstand an expanded input range. The drawback is increased cost for the enhanced equipment and limited competitive selection, thus resulting in higher cost. Specifying equipment with enhanced input voltage range is only economical for new installations, not for retrofitting existing sites.

White Paper Series 227 Designing For Surge Immunity In International Markets

Another possibility is to add external voltage regulation devices, which can be cost-effective if the regulation device is sized and installed correctly. Modern voltage regulators can be both cost-effective and reliable, if applied properly. The use of an external voltage regulator makes it possible for the user to specify the best possible equipment without worrying about input voltage range specifications. This approach might be more cost-effective, particularly for existing installations.

Look for the following when specifying voltage regulators:


Dynamic stability with all kinds of loads including power-factor-corrected, Input voltage range should be at least 160 to 300 V, Over voltage cut-off circuit, Low heat loss, Low wave form distortion, By-pass switch to be used when unit fails, Internal MOVs and capacitors should be sized to withstand 400 Vrms.

Lightning surges
Causes
There are a number of areas in the world that experience a higher-than-average number of lightning days. Such areas are easily identified from an isokeraunic map.

Electrical installations are affected by both direct and indirect lightning. A direct hit to a structure may produce 100 kA or more of a 10 x 350 s wave form according to IEC 1024

Electrical installations are affected by both direct and indirect lightning. A direct hit to a structure may produce 100 kA or more of a 10 x 350 s wave form according to IEC 1024. Equipment installed close to the electric service entrance is exposed to considerably higher amounts of energy and may be subjected to the IEC 1024 wave shape above. Equipment installed more than 30 (10 m) from the service entrance is subjected to the much milder ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000A, 6000V, as the energy has dissipated somewhat before reaching the equipment.A poor physical ground such as rock or dry sand causes lightning current to divert to the power line in order to find a path to ground. Incorrectly implemented site grounding may result in lightning current seeking a path to ground through equipment frames and power supplies. Use of non-TN-S grounding systems (TN-S is equivalent to three-phase with grounded neutral) can contribute to excessive surge voltages between power carrying conductors and ground.

Effects
Power supplies and the semiconductors used in electronic equipment can fail for a variety of reasons related to surge voltages from lightning and load switchingthe most common threats are listed below: Destruction of power supply front end including EMI filter, MOVs, fuse holders and other components. Damage to chassis components and equipment frames that carried lightning current. The damaged equipment is usually located close to the electric service entrance and is installed in a region with a high number of lightning days. Typical wave shapes and currents are defined in the IEC 1024 standard. Surge voltages can cause damage or destruction to power semiconductors in the power supply. Surge voltages can cause false triggering of power supply SCRs and other components, thus causing short circuits that destroy components.

228 White Paper Series Designing For Surge Immunity In International Markets

Nuisance alarm tripping can result from surge voltages triggering detection circuits in the power supply. Semiconductor damage can occur as a result of surge voltages getting past the power supply, on to the logic board. The majority of semiconductor devices are intolerant to surge voltages that exceed their voltage ratings. Semiconductor damage occurs when a high reverse voltage is applied to a PN junction that is in the non-conducting state. Semiconductor junctions may avalanche at small points because of the non-uniformity of the electric field. Thermal runaway may result due to localized heat build up, thus causing the melt-through that leads to the destruction of the junction. Note, even a fast surge of a few microseconds may cause a semiconductor to fail catastrophically or cause degradation that shortens its useful life. System malfunctions including error messages, reboots, lock-ups, disk drive read/ write errors are well known symptoms of surge voltage disturbances. A higher-than-average number of service calls and circuit board replacements is the definite confirmation that a system may be exposed to surge voltages that exceed the built-in system immunity.

Remedies
Power supplies, telecommunications rectifiers, UPS and other electronic equipment carrying the CE label have a certain built in level of surge immunity. What factors indicate the need for enhanced surge immunity? The presence of one or all of the following factors should warrant external surge protection in order to strengthen system immunity: Critical loads such as base transceiver stations (BTS) and nodes for wireless-inthe-local-loop applications as well as other outdoor enclosure installations often require additional protection, Inadequate infrastructure for the generation and distribution of power causing frequent power interruptions and unstable line voltages, High nominal line voltage, Non-TN-S grounding systems, High number of lightning days, Poor physical grounding conditions, Geographic locations where service calls are very expensive.

Look for the following when specifying external surge protection devices:
A primary protection device is required to handle the primary lightning threat that is defined by IEC 1024. A secondary protection device is required to divert the remnant of the primary device. Surge protective devices (SPD's) need to be coordinated in accordance with the requirements of IEC 1312. Coordination is essential for proper performance of SPD's. Incorrect coordination can result in the "vulnerable equipment" absorbing most of the energy created by the surge. The clamping voltages of SPD's must not be rated too close to the power line voltage. This is especially important in locations with large voltage fluctuations. SPD's should have an internal disconnect to take them off line in case of failure. Failure conditions should generate an alarm. SPD's should be easy to replace in the field. Protection should be provided between line and neutral as well as neutral to ground.

White Paper Series 229 Designing For Surge Immunity In International Markets

An isolation transformer should be added for non-TN-S systems in order to provide the neutral-to-ground bond that is essential for good surge protection. Spark-gap and gas-discharge-tube devices cause follow-on short-circuit current, which requires careful control not to cause problems. Careful attention should be given to ensure that follow-on currents do not cause disruption of the "vulnerable equipment." Proper down-stream inductance is required to ensure that spark gaps fire at the correct voltage level. A hybrid SPD may be used if it meets the above requirements.

Installation and wiring practices


Causes
The U.S. and Canada have consistent rules for grounding and bonding at the service entrance, but these vary between countries throughout the world. Some grounding systems actually contribute to surge voltage problems.
Installation and wiring practices are very important to ensure a reliable installation. Electrical installations in the U.S. have to conform to the National Electric Code and local inspectors enforce these and, in some cases, additional local requirements before approving a particular installation. It is often difficult, even in the U.S. and Western Europe where similar requirements exist, to ensure consistent quality practices. The U.S. and Canada have consistent rules for grounding and bonding at the service entrance, but these vary between countries throughout the world. Some grounding systems actually contribute to surge voltage problems. Some common problems are listed below: Inadequate wire size or type, Long overloaded wire runs, Too many loads on a branch circuit, Incorrect circuit breakers, Poor connections, Ground currents due to incorrect wiring, Poor ground and conduit connections, Systems that do not have a clear path to ground for fault currents have to rely on ground fault detection that sometimes malfunctions, Mixing electrical equipment that is designed for different standards, Incorrect grounding of distribution/isolation transformers, Overloaded utility transformers, Incorrectly applied surge protection devices.

Effects
The effects on the "vulnerable equipment" can vary from insignificant to major, sometimes intermittent malfunction. It can be very time consuming and costly to diagnose and correct problems, especially when the installation is far away in a country with different languages and customs. Those with experience from solving similar problems in North America will attest that fixing electrical problems can be a challenge even where one is familiar with language and customs. Some typical effects are listed below: Load induced voltage changes can cause equipment lock ups, Load induced over voltage can cause failure of surge protective devices, Incorrect grounding can cause excessive surge voltages, particularly from lightning, Poor wiring connections can create surge voltages that damage or upset equipment.

230 White Paper Series Designing For Surge Immunity In International Markets

Remedies
The following is suggested when planning site power: Develop universal wire size recommendations in both AWG and square mm, Develop one set of recommendations for countries that do not use North-American-style metallic conduits, Do not use conduit as ground, Provide dedicated circuits to the "vulnerable equipment," Use breakers that are rated for universal use (UL, CSA and IEC), Make sure that terminations and connections are properly checked before approving the installation, Establish a TN-S grounding system. Ideally, design and build a power distribution module that can be used anywhere in the world and that is approved by the major safety agencies. Develop simple installation instructions in the appropriate languages.

SUMMARY
Many equipment malfunctions can be traced back to inadequate infrastructure for power generation and distribution, inadequate installation practices and significant lightning activity coupled with poor grounding systems. Installation and grounding practices vary from country to country and are not always enforced. Surge-immunity enhancement is often required for installations per above. The selection and coordination of surge protective devices require careful attention and planning. A standardized approach is the best way to ensure consistent system performance.

About the Author:


Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, and dc to ac inverter systems designed to meet the challenging international power conditions.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

WP-Designing-Surge-Immunity-Intl-Markets-2006-10-16.pdf

IEC 1312 Surge Protective Device Coordination


White Paper Series 231 IEC 1312 Surge Protective Device Coordination

White Paper
Author Peter Nystrom President TSi Power Corp

IEC 1312 Surge Protective Device Coordination

IEC 1312 Surge Protective Device Coordination


FOUR COORDINATION VARIANTS

Background
The purpose of SPD coordination is to successively reduce the lightning threat, in stages (SPD 1, 2 & 3) down to the surge withstand capability of the "vulnerable equipment," without exceeding surge current and voltage ratings of individual SPDs.
Lightning surges contain significant amounts of energy that needs to be diverted away from the "vulnerable equipment" (system that is to be protected from surges). Electronic equipment, if CE marked, is designed with a certain built-in surge voltage immunity in accordance with IEC 1000-4-5this level of immunity will be sufficient for the majority of office buildings where the "vulnerable equipment" is located far away from the electric service entrance. Thus, equipment that carries the CE mark will work well without surge protection in many environments.However, when the "vulnerable equipment" is installed close to the electric service entrance, or in an outdoor enclosure, particularly in areas with a poor physical ground (dry sand, rock, etc.), it is often necessary to add external surge protective devices (SPDs). IEC recommends (IEC 1024) that lightning protection zones (LPZ) are established to successively reduce lightning currents, in stages, down to the built-in immunity of the "vulnerable equipment." The number of zones required depends on the structure containing the installation and the "vulnerable equipment." IEC 1024 requires that an SPD is installed at each zone boundary? the surge current and voltage ratings of individual SPDs must not be exceeded. This paper explains the purpose and concept of surge protective device (SPD) coordination in accordance with the IEC 1312 standard.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Purpose of coordination
To successively reduce the lightning threat, in stages (SPD 1, 2 & 3) down to the surge withstand capability of the "vulnerable equipment," without exceeding surge current and voltage ratings of individual SPDs.

232 White Paper Series IEC 1312 Surge Protective Device Coordination

Variant I

Figure 1

Coordination concepts
Variants I, II & III utilize individual single-port SPDs. Variant IV is a two-port hybrid design.
IEC 1312 defines four coordination "variants." The first three utilize individual single-port SPDs while the fourth variant is a two-port hybrid design.

Variant I
Shown in Figure 1, the rated voltage of SPDs is identical and coordination is achieved by separating each SPD by means of series impedance. Variant I is not recommended by the IEC, probably because it would require approximately 30 (10 m) of wire or separate inductors between each SPD, which is not practical when installing equipment close to the electric service entrance, or in outdoor enclosures.

Variant II
Shown in Figure 2, the rated voltages of SPDs are stepped so that the SPD in the "vulnerable equipment" has the highest rated voltage and SPD 3, 2 & 1 have progressively lower rated voltages, thus assuring that each upstream SPD would divert progressively higher currents. Variant II is difficult to implement as most power supplies, uninterruptible power systems and telecom rectifiers, rated for 230vac, use input SPDs with a 275Vrms rating. Thus, stepping down rated voltage, would cause SPD 1 and 2 to be destroyed by normal line voltage fluctuationsexperience has shown that fluctuations of plus 10% resulting in 250V is not unusual.

White Paper Series 233 IEC 1312 Surge Protective Device Coordination

Variant II

Figure 2

Variant III is a better choice than I or II as the spark gap is insensitive to fluctuations in line voltage.

Variant III
Shown in Figure 3, includes a component with a non-linear current/voltage characteristic, such as a spark gap. The SPD 1 spark gap would divert the majority of the surge current and output a combined wave, similar to ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000A, 6000V, to downstream SPDs 2 and 3. The voltage ratings of SPD 2 and 3 are identical, but each device will handle considerably less current thanks to the much higher energy handling capability of spark gap SPD 1. Variant III is a better choice than I or II as the spark gap is insensitive to fluctuations in line voltage. However, spark gap follow-on, short-circuit current may be an issue, and MOVs will still be sensitive to line voltage fluctuations.

Figure 3

234 White Paper Series IEC 1312 Surge Protective Device Coordination

Variant IV
Figure 4 shows a two-port hybrid device that incorporates cascaded stages of SPDs internally coordinated with series impedances. A hybrid device can be designed to maximize performance while reducing the undesirable characteristics of spark gaps and SPDs based on varistor or silicon-avalanche-diode technology. The use of a hybrid device eliminates the need to coordinate surge protective devices, but does not eliminate sensitivity to prolonged line over voltage.

Figure 4

Summary
Equipment designed to conform to CE requirements has a built-in surge immunity level that is sufficient in most office applications. However, equipment installed close to the electric service entrance or in an outdoor enclosure, particularly in areas with a large number of lightning days, requires additional protectionespecially if the physical ground is poor. Surge protective devices require coordination to perform well. The remnant voltage of the SPD closest to the "vulnerable equipment," shall not exceed its built-in immunity level. Coordination of surge protective devices is not always easy and the best solution may be a two-port, hybrid device, which will simplify the planning and installation process. High line voltage will destroy varistor and silicon-avalanche devices that are rated too close to the line voltage and must be considered when planning for protection in areas with unstable power lines.

About the Author


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, and dc to ac inverter systems designed to meet the challenging international power conditions.

WP-IEC-1312-SPD-Coordination-2006-10-16.pdf

Benefits Provided by UPS and Line Conditioners with an Isolation Transformer


White Paper Series 235 The Benefits of UPS and Line Conditioners with an Isolation Transformer

White Paper
Author Nam Paik Director of Engineering TSi Power

Benefits Provided by UPS/Line Conditioners with Isolation Transformers

The Benefits Provided by UPS and Line Conditioners with an Isolation Transformer DEDICATION AND ISOLATION
With the recent proliferation of low-cost standby UPS products which claim to "solve all the ac power problems", a false sense of security seems to exist among users who purchased and installed these basic non-isolated UPS for their PCs, fileservers, network/telecommunication equipment, point-of-sale terminals, etc. Such a false sense of security and confidence is often rudely challenged by equipment glitches, crashes, and malfunctions that persist even after installation of these non-isolated UPS products. The answer to this unexplainable failure of UPS to provide 100% protection against ac power problems can be found in an "Isolation Transformer" based UPS or Line Conditioner. Experienced electrical engineers have known this limitation of non-isolated UPS, line conditioners, surge protection devices and EMI/RFI noise filters for a long time - and their answer has been a "dedicated circuit" which is a separate ac wire run all the way to the main electrical panel located next to the buildings power transformer. Since the high neutral line voltage and high levels of spikes and transients are caused by devices such as air conditioners, heaters, elevators, copiers, laser printers, etc., bypassing all the sub-panels that feed these "dirty" devices by installing and using a "dedicated circuit" usually solved the problems.However, installation of a dedicated circuit can be very expensive and time-consuming, especially when it is a large or high-rise building. Installation of a dedicated circuit also requires an approval and permit from a licensed professional engineer (PE.), the building wiring diagram and the final drawing and work must be inspected and approved by a local county or city electrical inspector. The cost of a single dedicated circuit can be several thousand dollars and may require several weeks (or months) from start to finish.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

The high cost and long installation time of installing a dedicated circuit can be eliminated by using an isolation line conditioner or isolation UPS system, however. Because of the integral isolation transformer, each isolation line conditioner or UPS qualifies as a "Separately derived power source" under National Electrical Code 250-5D. Isolation conditioner and UPS also complies with the U.S. federal governments FIPS Publication 94 requirement of neutral and ground bonding for elimination of any problems caused by the presence of neutral voltage or commonmode noise/transients.

236 White Paper Series The Benefits of UPS and Line Conditioners with an Isolation Transformer

Additional benefits provided by an isolation line conditioner (or UPS with isolation transformer):
1. Regeneration of power using the isolation transformer at the point of use means that it is a truly ideal power source (It is like moving the building transformer to within a few feet of sensitive equipment). The power from an isolation transformer is both DEDICATED and ISOLATED. 2. Multi-stage surge protectors and EMI/RFI noise filters are also built-in. 3. Isolation conditioner sizes ranging from 90 VA to 5.5 kVA allows optimized performance vs. cost product selection. UPS size ranges from 400VA to 2100 VA. 4. Installation is immediate and no permit or approval is required. (Conditioners are also available in sizes up to 36 kVA, and it is recommended they be installed by a licensed electrician). 5. Cost of the unit is only a small fraction of a dedicated circuit installation cost.

About the author


Nam Paik ~ Director of Engineering, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

WP-Isolation-Transformer-Benefits-2006-10-16.pdf

The Merits of a Standby UPS with a Modified Sine Wave Output

White Paper Series 237 The Merits of a Standby UPS with a Modified Sinewave Output

White Paper
Author Nam Paik Director of Engineering TSi Power

The Merits of a Standby UPS with a Modified Sine Wave Output

The Merits of a Standby UPS with a Modified Sinewave Output


Of the 3 major UPS architectures (e.g. Standby, Ferroresonant On-Line, and Double-Conversion On-Line), the Standby UPS features the following advantages:

Features
1. Extremely high power efficiency, typically above 97%. Air exhaust fan is normally off since very little heat is generated. The inverter circuit is normally off.

Benefits
Lowest operating cost in terms of electric use only 1/10 of double-conversion on-line UPS. Quiet operation. Does not add to air conditioning loads. Very quiet operation and the highest MTBF (mean-time-between failure) due to the lowest voltage, current and temperature of its internal parts. Battery lifetime is approximately twice that of an on-line type UPS. The pulse-width-modified and optimized peak-voltage modified square waveform is actually more beneficial for switchmode power supplies. Simple design with the lowest parts count. Means lowest purchase price and maintenance costs. Repair procedures are quick and easy. The ride-through of a typical switchmode power supply is 10 to 20 ms. A fast 1 ms switchover time guarantees glitch-free transfers.

2. 3.

4. 5.

Cooler internal operating temperature. Output waveform is normally a sinewave. The inverter waveform is a modified square-wave, generated only during power outages. Simplest and most economical UPS design.

6.

7.

The switchover time of some high-quality Standby UPS is less than 1ms.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

About the Author


Nam Paik ~ Director of Engineering, TSi Power Corporation Mr. Paik has over 15 years experience in the power electronics industry. He was with Northern Telecom (now Nortel Networks) for 4 years prior to joining TSi Power in 1988. Nam has focused on UPS, Line Conditioner and dc to ac inverter products and most recently has developed a number of customized power protection and conversion systems for several U.S. government agencies and international applications.
WP-Merits-of-Standby-UPS-2006-10-16.pdf

238 White Paper Series The Benefits of UPS and Line Conditioners with an Isolation Transformer

This page intentionally left blank.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Power Primer ~ A Guide to UPS and Power Terms


White Paper Series 239 Power Primer ~ A Guide to UPS and Power Terms

White Paper
Author Peter Nystrom President TSi Power Corp

Power Primer and Guide to UPS Terms

Power Primer
A Guide to Power and UPS Terms

The reliability of PCs and the Internet comes nowhere near the telephone system.

Power quality is an issue that all serious computer users should be concerned with. Why? The world is becoming more dependent on computers than ever before. The Internet is changing everything in ways that could not have been imagined just a few years ago. We are now using the Web to make travel reservations, buy and sell stocks, upload and download large files and to purchase many different products. Yet the reliability of PCs and the Internet comes nowhere near the telephone system. We are always expecting dial tone when we pick up the receiver to make a telephone call, and we would be quite surprised if the telephone company would have to reboot the digital switch used in the central office. We certainly would not accept if the telephone didnt work when there was a power outage. Somehow we seem to accept much less when we log on to the Web. In time the computer industry will figure out how to design reliable software, computers and data communications equipment. The good news is that it is quite inexpensive to do something about computer crashes caused by power interruptions. Most PCs can be adequately protected for less than $285.00 with a Flexible Series UPS from TSi Power Corporation. The purpose of the Power Primer is to provide some basic information about the quality of utility power and how it affects the average computer user. First, a list of power anomalies and their effect on computers: Power outage (also known as blackout or power failure)a complete loss of power, which causes the computer to crash and shut down. Surge voltage (also known as spike, transient or impulse)a short-duration overvoltage, which can cause computer malfunction or failure, depending on the severity of the surge. Sag (also known as brownout or undervoltage)a longer-term abnormal deviation from the nominal voltage of 120V (230V in many countries outside North-America), which can cause the computer to shut down or cause overheating of its internal power supply if the sag continues for a long time. Swell (also known as overvoltage)a longer-term overvoltage, which can cause failure of the computers internal power supply or possible shut down for some computers.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

240 White Paper Series Power Primer ~ A Guide to UPS and Power Terms

What is the cause of the above problems? The power provided by the local Power Company has to be generated and distributed to the user. This process and natural events like lightning cause most problems. Using generators that are powered by hydro, fossil fuel or nuclear fission generates power. Future supply of power will be affected by the lack of available sources of hydro and concerns over pollution caused by the burning of fossil fuelthe situation will worsen because of the lack of enthusiasm for any expansion of nuclear plants. A number of US nuclear plants are being decommissioned while countries like Sweden have decided to decommission most of its nuclear plants. Thus, it is possible that there will not be enough power to satisfy future demand in the US. Many developing countries are already experiencing severe shortages of power and have been unable to arrange the financing necessary to build more power plants. A shortage of power will cause all of the above problems, as some users will be subject to momentary power outages when there is not enough power to satisfy demand. Power is distributed over long distances using high-voltage overhead power lines distribution voltages can be as high as one million volts. Power is distributed locally via lower voltages provided through a series of step-down transformers. Some local distribution networks are unable to provide the power required when many users demand power at the same time, which may cause local distribution transformers to fail and hence cause power outages. Many local distribution systems in the US use overhead power lines that are very sensitive to tree branches falling and thus causing power interruptions. Additionally, surge voltages will occur when power fails as the rapid interruption of power results in a surge voltage. The deregulation trend may compound power interruptions and stability problems in the future as switching between different power grids becomes more frequent as sellers and buyers exchange power. Power problems can also be caused by thunderstorms when surge voltages from lightning strikes are delivered via the power line to the computer. Additionally, lightning arresters on utility distribution lines can cause brief power interruptions as the momentarily short the power while diverting lightning voltages to ground.

Surge voltages can result as electrical equipment turns on and off inside buildings.

Helpful terminology when selecting a UPS


All computers and telecommunications key systems and PBXs have a voltage and current rating and requirement. Typically, such information is printed on the back planes of equipment (near serial number and product model information) and is also included in the Users Manual. Uninterruptible Power Systems are rated in Volt Amperes or "VA." It is a simple task to determine what size UPS a particular system requires just: (Note, the information provided applies to equipment connected to a regular 120V or 230V outlet) Determine required VA rating for each piece of equipment to be connected to the UPS (e.g. computer, monitor, modem, etc). Multiply volts (V) and amps (A) for each piece of equipment and obtain VA per device. Then add the total and obtain total VA rating. Example: Computer 120V x 2A = 240 VA; Monitor 120V x 1A = 120 VA; Modem 120V x 0.1A = 12 VA. Thus, total VA is 240VA + 120VA + 12VA = 372 VA. Note, if only watts are given: multiply watts by 1.35 to obtain VA rating. Select a UPS that is the same rating or larger than the above calculated load. For example, a UPs-400 provides 400 VA of power and would provide at least 8 minutes of backup. If more backup is required or if more equipment will be connected to the UPS in the future, a larger UPS should be selected. A UPs-600 would provide longer backup than a UPs-400, typically 15 minutes or more. TSi Power Quality Products can provide longer backup times.

White Paper Series 241 Power Primer ~ A Guide to UPS and Power Terms

A Guide to UPS Terms


Transfer time
This describes the amount of time it takes from the initial loss of ac power to the time the UPS takes over the load. The importance of time for the computer translates into the computer locking up or freezing and thereby losing any unsaved information. Instantaneous transfer time means that the computer would not even notice that its power source had switched from one input to another.

Isolation from line


A characteristic of a UPS in which the output is completely electrically disconnected from the input. Power is coupled from input to output by magnetic fields in a transformer. Because there is no connection from input to output, transients cannot cross the magnetics thereby eliminating any transients in the ac output.

Neutral to ground bond


The neutral to ground bond provides protection from transients on the neutral line which could feedback into sensitive electronic equipment.

EMI/RFI noise filtering


EMI refers to electro-magnetic interference which is unwanted electrical noise present on the power line. This noise may "leak" from the power lines and affect equipment that is not even connected to the power line. Such "leakage" is called a magnetic field. Magnetic fields are formed when unwanted noise voltages give rise to noise currents. Such noise may adversely affect electronic equipment and cause intermittent data problems. EMI protection is provided by noise filters placed on the ac power line. The filter reduces the noise voltage on the protected line, and by doing so eliminates the magnetic fields of noise generated by the protected line. Noise signals that act over a significant distance are called Radio Frequency Interference (RFI). Equipment power cords and building wiring often act as antennas to receive RFI and convert it to EMI.

Surge/spike protection
This category is fairly self explanatory. The higher your protection, the better your equipment is insulated from momentary increases in voltage on the ac line.

Output voltage regulation


Voltage regulation, especially in areas where the power quality is low, is essential to equipment performance. Computer equipment will identify if the voltage is within the operating parameters and if it falls below those parameters, the computer will shut down and will lose any unsaved information. Furthermore, with a constant voltage, the internal components in the computer will run more efficiently and will extend the life of the computers hardware substantially.

Inverter Waveform
Sine wave inverter waveform is the best. Pseudo-sine wave (typically modified square wave) is suitable for computers and other switchmode power supply driven equipment, but not motors or fans.

Energy efficiency
The ratio of output power to input power as expressed as a percent. For example, if a UPS has an efficiency of 80%, then 20% of the input energy in lost as heat.

Source impedance
Small engine generators (1kW to 10kW range) have very high source impedance, which means output voltage will drop as more load is connected to the output. This is the reason for oversizing a generator.

242 White Paper Series Power Primer ~ A Guide to UPS and Power Terms

Operating environment
An overall description of the ac environment which includes in its definition frequency of transients (i.e. surges, spikes, sags), blackouts, and voltage fluctuations to name a few. Often contributing factors can be industrial growth, poor utility maintenance, poor power management or erratic weather. The areas in which your computers are operating are easily described as poor ac environments.

Unit surge voltage withstand


This denotes the amount of voltage surge the UPS itself can handle before damage and failure of the unit. If the UPS fails, the computer equipment becomes vulnerable to the transients on the ac line.

Price
The range of prices, as youve discovered, is widely disparate because the standby UPS is using the cheapest but least reliable technology, whereas the ferroresonant, and online technologies are very high quality and durable.

About the Author


Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of indoor and outdoor UPS, isolation transformer line conditioners, precision automatic voltage regulators, and dc to ac inverter systems designed to meet the challenging international power conditions.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

WP-Power-Primer-UPS-Terms-2006-10-16.pdf

Why Power Supplies and Semiconductors Fail


White Paper Series 243 Why Power Supplies and Semiconductors Fail

White Paper
Author Peter Nystrom President TSi Power Corp

Why Power Supplies and Semiconductors Fail

Why Power Supplies and Semiconductors Fail


Causes and results of power disturbances

Comments regarding power disturbances


A power disturbance can be defined as unwanted excess energy that is presented to the load.
Power quality varies significantly from one area to another. Some countries have very stable power grids while others are extremely short on capacity. Power disturbances are caused by the generation, distribution and use of power; and lightning. A power disturbance can be defined as unwanted excess energy that is presented to the load.

Causes of power disturbances


Power disturbance originate both outside and inside customer facilities. Load switching causes surges because of collapsing fields (-e = l * di/dt). Over loaded power distribution systems can cause significant voltage variations between peak and off-peak hours. Significant momentary load changes, such as heavy inrush currents can cause severe voltage variations. Black-outs can cause severe voltage surges both on loss and return of power. Circuit-breaker tripping and fuse blowing can cause severe surge voltages. Large ups and variable-speed drives can cause various surge voltages inside buildings.

Results of power disturbances



Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Sags and under voltages can cause component overheating or destruction. Surges and over voltages can cause component overheating, destruction or can trigger other electronic components such as SCR's. Component overheating reduces the life and deteriorates the real reliability as opposed to the estimated reliability based on steady-state conditions of the product. False triggering of other components can create nuisance alarm tripping or, worse, can cause overheating or destruction of other electronic components.

244 White Paper Series Why Power Supplies and Semiconductors Fail

Why semiconductors fail


Most semiconductor devices are intolerant to surge voltages in excess of their voltage ratings. Even a fast surge of a few microseconds can cause the semiconductor to fail catastrophically or may degrade it so as to shorten its useful life. Damage occurs when a high reverse voltage is applied to a non-conducting pn junction. The junction may avalanche at a small point due to the non-uniformity of the electric field. In this case, thermal runaway can occur because of localized heat build up and cause a melt-through which destroys the junction.

Problems with current solutions


Common-mode voltage disturbances can be amplified in non-tn-s ac distribution systems. Typical emi filters are not well damped. This has a dramatic effect on any voltage disturbances, resulting in oscillations inside the emi filter under any transitional conditions. Severe voltage surges may result from fly-back from saturated inductors looking for a path to release energy. Boost converters can be destroyed by surges causing increased energy storage in input filter, the output capacitor (c) is charged to an unsafe level depending on capacitance value and load levels for the dc/dc converter connected to the output of the boost.

Limitations of commercial UPS equipment


The industry is driven by lowest cost. Users normally don't care about power quality. Users really care about saving data which means that they are satisfied with orderly shut down to protect data files. Most UPS do not have quality battery chargers and chargers are nor designed for long-term back-up. Most UPS equipment does not provide real power conditioning (there are exceptions). Some UPS equipment is poorly protected against surge voltages. Extended back-up requires the addition of expensive rectifier/chargers and battery packs.

About the author


Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in Wisconsin, USA), a manufacturer of UPS, line conditioner, automatic voltage regulator, and dc to ac inverter systems designed to meet the challenging international power conditions.

WP-Power-Supply-Failure-2006-10-16.pdf

Protection of Telecom Sites in Countries with Unstable Ac Mains


White Paper Series 245 Protection of Telecom Sites in Countries with Unstable Ac Mains

White Paper
Author Peter Nystrom President TSi Power Corp

Power Protection in Countries with Unstable Ac Mains Voltages

Protection of Telecom Sites in Countries with Unstable Ac Mains


BACKGROUND
Ac mains voltages frequently fluctuate beyond the IEC assumed standard of a 184 to 264vac input range.
Developing countries often have weak power generation and distribution systems: Frequently resulting in mains voltage fluctuations beyond the 184 to 264vac input range mandated by the European Norm. The underlying IEC standards assume that power generation and distribution are fairly stable and that voltage excursions will not be outside the specified input window of 184 to 264vac. Unfortunately, that is not the case in many developing countries throughout the world. Even industrialized nations have their share of problems with ac mains availability. Mains voltages frequently fluctuate beyond the assumed 184 to 264vac input range. In the U.S. State of California for example, a failed deregulation scheme coupled with the lack of corrective political will led to rolling blackouts that cut power to millions in early 2001. The desired expansion of generation and distribution capacity in developing countries is also constrained by a shortage of capital and, in some cases, political factors as well. Thus, it appears that the quality of ac mains, for developing countries, is at best uncertain into the foreseeable future. The expansion of communications networks, such as cellular radio, direct radio access telephony (wireless in the local loop), paging networks, land mobile radio and satellite telephony stations, has led to a rapid increase of installed sites to support these networks. The proliferation of sites sometimes makes it difficult to place a particular site in an ideal location. The site might then be installed in a remote or difficult-to-access location.
Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi

TSi Power Corporation

The author of this article has worked with infrastructure manufacturers and operators to address power-related reliability problems, which can be very expensive if not addressed properly--especially for remote and hard-to-reach locations. This paper aims to give readers some helpful hints when addressing their own power-related reliability concerns.

246 White Paper Series Protection of Telecom Sites in Countries with Unstable Ac Mains

THE PROBLEM
The power converters used in modern ac-dc rectifiers, UPS and ac-dc switchmode power supplies, are typically based on the IEC input range of 184 to 264vac. Ac induction motors are sensitive to both high and low mains voltage, where low voltage can cause rotor lockup following a dip in mains voltage; and to saturation causing tripping of circuit breakers, as a result of high mains voltage. Transformers and other 50/60Hz magnetics can easily get saturated when exposed to high input voltage, particularly at 50Hz, when the magnetization curve of steel becomes non-linear much quicker than for 60Hz.

Ac induction motors are sensitive to both high and low mains voltage.

Causes of power supply failure


Sags and under-voltages can cause component overheating and destruction of MOS-FETs from over-current. Surges and over-voltages can cause component overheating, destruction of MOS-FETs, or can trigger other electronic components such as SCRs, MOVs and input capacitors may be destroyed if they are rated too close to the line voltage. Component overheating reduces the life and deteriorates the real reliability as opposed to the estimated reliability based on steady-state conditions of the product. False triggering of other components can create nuisance alarm tripping or, worse, can cause overheating or destruction of other components. Typical EMI filters are not well damped. This has a dramatic effect on any voltage disturbances, resulting in oscillations inside the EMI filter under any transitional conditions. Severe voltage surges may result from fly-back from saturated inductors looking for a path to release energy. Boost converters can be destroyed by surges causing increased energy storage in the input filter, when the output capacitor is charged to an unsafe level, depending on capacitance value and the load levels for the dc to dc converter connected to the output of the boost converter.

Causes of semiconductor failure


Most semiconductor devices are intolerant to surge voltages in excess of their voltage ratings. A fast surge (high dv/dt) of a few kV per microsecond can cause a semiconductor to fail catastrophically or may degrade it so as to shorten its useful life. Damage occurs when a high reverse voltage is applied to a non-conducting PN junction. The PN junction may avalanche at a small point due to the non-uniformity of the electric field. In this case, thermal runaway can occur because of localized heat buildup and cause a melt-through which destroys the junction.

Mains voltages varying between 160 to 330 vac are common in countries like India and Pakistan.

Mains voltages varying between 160 to 330 vac are common in countries like India and Pakistan, but are also found in many other areas. In such cases, installation of unprotected power systems and equipment can lead to an abnormally high failure rate and loss of revenue for both suppliers and users of telecom hardware.

White Paper Series 247 Protection of Telecom Sites in Countries with Unstable Ac Mains

Mains voltage anomalies can be caused by the following:


Fault clearing: where a short circuit occurs on the line and a protection device clears the fault, typically in around 3 cycles. The clearing of a fault results in a short dip and voltage recovers rapidly if the mains are stable. However, recovery can take much longer if the mains are weak, resulting in a protracted voltage sag. Chronic instability: caused by interaction of voltage stabilizing devices. A good example would be an industrial area with an inadequate incoming power line, thus resulting in unstable mains as loads cycle on and off. Users of power may then install a voltage stabilizer that will draw more current to provide a higher voltage for one facility, with the higher current draw causing a voltage drop for adjacent facilities that in turn draw more power when regulators attempt to correct the mains voltage. The end result can be a total loss of power when current draw exceeds the substations capability to deliver the required current. Weak generation capacity: will also result in fluctuating mains when utility customers compete for available power. Rolling brownouts: can result when the power utility reduces the mains voltage by 10% or more in order to limit power consumption. This approach may work for fixed-resistance loads such as light bulbs, but will not for computer and telecom equipment utilizing switchmode power supplies, as these compensate for low voltage by increasing current draw. The increased current is capable of generating increased internal heat that can lead to power supply failure. Blackouts: can result when the electric utility cuts off power to selected areas in an attempt to protect major parts of the distribution system from interruptions.

Mitigation devices are often applied as a bandage, in the hope that things will get better quickly, to the satisfaction of both the telecom operator and the equipment provider. Unfortunately, applying mitigation devices without understanding the basics can actually aggravate the problem. This is especially true for power-factor-corrected power supplies, as these are more sensitive to mains disturbances than their simpler siblings with rectifier/capacitor inputs. It is the authors experience that power-factorcorrected rectifiers can trip internal protection devices when exposed to rapidly changing mains voltages. Over-voltage protection (surge protection) against surge voltages, and from load switching and lightning, is governed by rational principles, first outlined by IEC-1312 in the early 1990s. The applicable IEC-Standard: IEC Technical Specification 61312-3 Requirements of Surge Protective Devices (SPDs) describes clearly how to coordinate SPDs to ensure that upstream devices (Figure 1) progressively handle more energy than the SPD found on the front-end of a power supply, typically a metal oxide varistor. These sensible coordination principles are not always adhered to, which sometimes results in a lack of coordination between SPDs used in a system. This can lead to the destruction of down stream SPDs that clamp before the upstream SPDs, which in turn causes the destruction of the metal oxide varistors in the power supply itself.

248 White Paper Series Protection of Telecom Sites in Countries with Unstable Ac Mains

FIGURE 1. Coordination of surge protection devices.

UC (SPD1 )=UC (SPD2 )=UC (SPD3 ) LPZ 0


R1 I0

LPZ 1
L1 I1 R2

LPZ 2
L2 I2 R3

LPZ 3
L3 I3

equipment to be protected

SPD 1

SPD 2

SPD 3

Safety earthing systems


Many different earthing systems are in use throughout the world and need to be understood before primary surge protection is implemented. The most common earthing systems are shown below:

TN-S A separate neutral and ground conductor are run throughout.

TN-S
A separate neutral and ground conductor are run throughout. The ground conductor can be the metallic sheath of the power distribution cable or a separate conductor. All exposed-conductive-parts of the installation are connected to ground.

TT
One point of the source of energy is grounded and the exposed-conductive-parts of the installation are connected to independent grounded electrodes.

TN-C
Neutral and ground conductors combine in a single conductor throughout the system. All exposed-conductive-parts are connected to the combined N-G conductor.

IT
A system that has no direct connection between live parts and ground. All exposedconductive-parts of the installation are connected to independent grounding electrodes.

TN-C-S
Neutral and ground combine in a single conductor. This system is also known as multiple earthed neutral (MEN). The protective conductor is referred to as the combined neutral and ground conductor. The supply N-G conductor is grounded at a number of points throughout the network and generally as close to the consumers service entrance as possible. All exposed-conductive-parts are connected to the combined N-G conductor.

White Paper Series 249 Protection of Telecom Sites in Countries with Unstable Ac Mains

POSSIBLE SOLUTIONS
The most obvious solution is to design power supplies to withstand a much wider input voltage range, to prevent saturation and resulting energy impulses that cause damage to switching transistors and other circuits. Such changes require more steel in inductors, capacitors with higher voltage ratings, possibly larger circuit boards with greater trace separation, as well as transistors with higher voltage and current ratings. This is not likely, as manufacturers would have to offer special versions with a wide input voltage range or, as a second option, make only power systems that can handle all worldwide markets, regardless of mains quality. This second option is not realistic since customers in countries with a stable mains infrastructure would be penalized. Designing a protection device that can handle an entire power plant, or racks of power systems, is probably a more economical solution that can be used whenever increased immunity is required. Such a solution can also be used to address problems that occur in the field after installation.

The most obvious solution is to design power supplies to withstand a much wider input voltage range.

Considerations for mitigation devices


Mitigation devices may include a complete solution, or components thereof, if system analysis reveals that essential elements already exist. We will present here a complete solution for the readers consideration.

Input range of 160 to 330 vac at 50/60Hz without saturation at 50Hz

Requirements:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Input range of 160 to 330 vac at 50/60Hz without saturation at 50Hz Output range of 184 to 264 vac Over-voltage protection (OVP) with cut-off if output exceeds 264 vac Automatic bypass in case of electronics failure Low impedance Coordinated surge protection Conversion to TN safety earthing system Low weight Reasonable cost High power efficiency and low heat loss

FIGURE 1. An example of a power system for a cellular base station

follows on the next page

250 White Paper Series Protection of Telecom Sites in Countries with Unstable Ac Mains

White Paper Series 251 Protection of Telecom Sites in Countries with Unstable Ac Mains

Limitations of existing technologies


Several technologies are available for mitigation devices, each with a distinct set of advantages and drawbacks. Table 1 below provides a summary:

Table 1: Limitations of existing technologies

Technology
Ferroresonant transformer with isolation

Advantages
Reliability Surge protection Tight regulation Fast regulation Bypass is not required

Drawbacks
Price Stability High impedance Limited voltage input range Frequency sensitive Low efficiency Incompatible with powerfactor-corrected power supplies High weight Bulky Slow response Limited voltage input range Automatic bypass not available Requires added isolation transformer to achieve proper surge protection Medium reliability Limited voltage input range Most do not have OVP Requires added isolation transformer to achieve proper surge protection Requires added isolation transformer to achieve proper surge protection

Tap-switched auto-transformer

Lowest cost High efficiency Low impedance

PWM-regulated buck-boost transformer

Very tight regulation Low impedance Excellent stability Low weight Small size Very high efficiency Some have automatic bypass Very wide input voltage range of 160330vac Low impedance Excellent stability Low weight Small size Very high efficiency Automatic bypass Very tight regulation Low impedance Excellent stability Very high efficiency Some have automatic bypass

Relay-switched buck-boost transformer with autobypass and OVP

Variable transformer with buck-boost transformer

Very slow High weight Bulky Slow regulation Can produce excessive voltage following restart after mains failure Some do not have OVP Requires added isolation transformer to achieve proper surge protection

252 White Paper Series Protection of Telecom Sites in Countries with Unstable Ac Mains

Summary
Many equipment malfunctions can be traced back to inadequate infrastructure for power generation and distribution and inadequate installation practices. The risk of system failure is greater at 50Hz, especially for high mains voltages. A plethora of safety earthing systems and supply voltages make it difficult to create a simple standard for field installation. A standardized system of mitigation devices with ac mains stabilization that also meet the requirements of IEC Technical Specification 61312-3 may be the best way to ensure consistent system performance.

About the Author:


Mr. Peter Nystrom has been active in the power protection industry since 1979 and is the founder of two companies. He has also been active as a consultant to major telecommunication equipment manufacturers for several years. Since 1998, he has been the CEO of TSi Power Corporation (located in the state of Wisconsin, USA), a manufacturer of indoor and outdoor UPS, line conditioners, precision automatic voltage regulator, automatic transfer switches and dc to ac inverter systems designed to meet the challenging international power conditions.

Represented by CareBase Michael Gibson Post Office Box 2987 Glenwood Springs, CO 81602-2987 USA Phone +1 970 945 2770 800 430 2770 (USA.CAN) michaelg@carebase.com www.carebase.com Copyright 2006 TSi