TYPICAL WIRING DIAGRAM

DEEP SEA ELECTRONICS 7320 INST ALL AT IO N INSTRUCTIONS

053-029 ISSUE 4

ACCESSING THE FRONT PANEL CONFIGURATION EDITOR


Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset Press the Stop/Reset and Info buttons simultaneously. If a module security PIN has been set, the PIN number request is then shown : button.

Press , the first # changes to 0. Press correct value.

(up) or

(down) to adjust it to the

Press (right) when the first digit is correctly entered. The digit you have just entered will now show # for security.

Repeat this process for the other digits of the PIN number. You can press move back to adjust one of the previous digits.

(left) if you need to

When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN. If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed :

EDITING A PARAMETER Enter the editor as described above. Press the left or right buttons to cycle to the section you wish to view/change. Press the up or down buttons to select the parameter you wish to view/change within the currently selected section. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the up or down buttons to change the parameter to the required value. Press to save the value. The parameter ceases flashing to indicate that it has been saved. button.

To exit the editor at any time, press and hold the

Deep Sea Electronics Plc.


Tel:+44 (0)1723 890099 Fax: +44 (0)1723 893303 LO CALL (from UK BT landlines) : Telephone 0845 260 8933 Email: support@deepseaplc.com Web: www.deepseaplc.com

Deep Sea Electronics inc.


Phone: +1 (815) 316-8706 Fax: +1 (815) 316- 8708 TOLL FREE (USA only) : Tel: 1 866 636 9703 Email: dsesales@deepseausa.com Web: www.deepseausa.com

Deep Sea Electronics Plc. (Far East)


Tel:+66 2 670 6228 Fax: +66 2 678 3028 Email: support@deepseaplc.com Web: www.deepseaplc.com

NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: More comprehensive module configuration is possible using the 7xxx series PC configuration software. Please contact us for further details

ADJUSTABLE PARAMETERS (Configuration editor)


Front Panel Configuration Editor Front Panel Configuration Editor

Section Parameter as shown on display


DISPLAY Contrast Language LCD Page Timer Auto Scroll Delay Current Date and time Alt Config Oil Pressure Low Shutdown Oil Pressure Low Pre Alarm Coolant Temperature Low Warning Coolant Temperature High Pre Alarm Coolant Temperature High Shutdown Start Delay Timer Pre Heat Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Timer Engine Under Speed Shutdown Engine Under Speed Shutdown Engine Under Speed Warning Engine Under Speed Warning Engine Over Speed Warning Engine Over Speed Warning Engine Over Speed Shutdown Engine Speed Overshoot Delay Engine Speed Overshoot Fail To Stop Delay Battery Under Voltage Warning Battery Under voltage Warning Delay Battery Under Voltage Battery Over Voltage Warning Battery Over Voltage Warning Delay Battery Over Voltage Warning Charge Alternator Failure Warning Charge Alternator Failure Warning Charge Alternator Warning Delay Charge Alternator Failure Shutdown Charge Alternator Failure Shutdown Charge Alternator Shutdown Delay Droop control Droop control

Factory Settings
53% English 5m 2s hh:mm Default Config 1.03bar 1.17bar 70C 90C 95C 5s 0s 10s 10s 10s 0s 0s 0s 1m Inactive 1200RPM Inactive 1350RPM Inactive 1650RPM 1710RPM 2s 0s 30s Active 1m 10V Active 1m 30V Active 6V 5s Active 4.0V 5s Inactive 4% (Compatible engine ECUs only) 184V 196V 230V 265V 277V 40Hz 42Hz 50Hz 55Hz 57Hz 500A 100% Active 100% 3 Phase, 4 Wire 600A 5A 500A Inactive 10% 0s

Section Parameter as shown on display


MAINS Mains Under Voltage Trip Mains Over Voltage Trip Mains Under Frequency Trip Mains Over Frequency Trip Mains Transient Delay Return Delay Mains Transfer Time LCD Page Timer Auto Scroll Delay Start Delay Timer Pre Heat Timer Crank Duration Timer Crank Rest Timer Safety On Delay Smoke Limiting Smoke Limiting Off Warm Up Timer Cool Down Timer Speed Overshoot Delay Fail To Stop Delay Battery voltage Low Warning Delay Battery Voltage High Warning Delay Return Delay Generator Transient Delay Mains Transient Delay Mains Transfer Time

Factory Settings
184V 276V 45Hz 55Hz 2s 30s 0.7s 5m 3s 5s 0s 10s 10s 10s 0s 0s 0s 1m 2s 30s 1m 1m 30s 0s 2s 0.7s

EDITOR ENGINE

TIMERS

ACCESSING THE RUNNING CONFIGURATION EDITOR


The running editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered.

Press and hold the button to enter the running editor. EDITING A PARAMETER Enter the editor as described above. Press the left or right buttons to cycle to the section you wish to view/change. Press the up or down buttons to select the parameter you wish to view/change within the currently selected section. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the up or down buttons to change the parameter to the required value. Press to save the value. The parameter ceases flashing to indicate that it has been saved. button.

GENERATOR Generator Under Voltage Shutdown Generator Under Voltage Pre Alarm Generator Voltage Nominal Generator Over Voltage Pre Alarm Generator Over Voltage Shutdown Generator Under Frequency Shutdown Generator Under Frequency Pre Alarm Generator Frequency Nominal Generator Over Frequency Pre Alarm Generator Over Frequency Shutdown Full Load Rating Kw Overload Trip Delayed Over Current Delayed Over Current AC System CT Primary CT Secondary Earth CT Primary Earth Fault Trip Earth Fault Trip Generator Transient Delay

To exit the editor at any time, press and hold the

ADJUSTABLE PARAMETERS (Running editor)


Running Editor

Section Parameter as shown on display


DISPLAY ENGINE Contrast Language Manual Frequency Trim (Electronic engines only)

Factory Settings
53% English 0.0Hz

DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4 x 7.1 x 1.6)

PANEL CUTOUT: 220mm x 160mm (8.7 x 6.3)