The document contains specifications for various electrical equipment required for an 11kV indoor vacuum circuit panel, including:
1. The circuit panel will have 2 incoming and 4 outgoing circuits, 1 bus section, 12-15kV breakers rated for 30A maximum.
2. A 33kV, 800A circuit breaker with a breaking capacity of 6.25kA and short time current rating of 25kA.
3. A 33kV outdoor voltage transformer.
4. A 33kV outdoor current transformer with primary of 300A and secondary of 5A for metering and overcurrent protection.
5. A 33kV isolator of the rocking type.
The document contains specifications for various electrical equipment required for an 11kV indoor vacuum circuit panel, including:
1. The circuit panel will have 2 incoming and 4 outgoing circuits, 1 bus section, 12-15kV breakers rated for 30A maximum.
2. A 33kV, 800A circuit breaker with a breaking capacity of 6.25kA and short time current rating of 25kA.
3. A 33kV outdoor voltage transformer.
4. A 33kV outdoor current transformer with primary of 300A and secondary of 5A for metering and overcurrent protection.
5. A 33kV isolator of the rocking type.
The document contains specifications for various electrical equipment required for an 11kV indoor vacuum circuit panel, including:
1. The circuit panel will have 2 incoming and 4 outgoing circuits, 1 bus section, 12-15kV breakers rated for 30A maximum.
2. A 33kV, 800A circuit breaker with a breaking capacity of 6.25kA and short time current rating of 25kA.
3. A 33kV outdoor voltage transformer.
4. A 33kV outdoor current transformer with primary of 300A and secondary of 5A for metering and overcurrent protection.
5. A 33kV isolator of the rocking type.
1. 11kv Indoor vacuum Circuit panel 9-Board Number of Incoming –2 Number of Outgoing –4 Number of Bus-section -1 Breaker data : Rated voltage – 12kv -15kv Impulse withstand Voltage – 75kv-95kv Circuit breaker operating current -30A max.
Description Incoming Outgoing
Ammeters Ammeters Voltage 12kv Not Applicable Current 1250A 630A Rated Breaking Current– 25A 25A Current Transformer 1200/600/5 600/300/5 A Ammeter 0-1300A 0-800A Closing & Opening Switch Applicable Applicable Closing & Opening Switch Applicable Applicable Indicator
Bus Section – All incoming particulars as in above table
Short time withstand current on outgoing = 20KA for 3 seconds Short time withstand current on Incoming = 25KA for 3 seconds Peak withstand current on outgoing = 50KA Peak withstand current on Incoming = 53KA Rated short circuit breaking current outgoing = 20KA Rated short circuit breaking Incoming = 25KA Voltage = 110V D.C 2. 33KV SF 800A 1500MVA Outdoor Circuit Breaker Breaking capacity = 6.25 KA Short time current = 25KA Current Rating = 1600A Closing Coil = 110V D.C SH Trip = 110V D.C 3. 33kv Outdoor 3Phase Voltage Transformer (VT)
Data of the VT = : i.e. ratio
4. 33KV Outdoor Current Transformer (CT)
Data of CT: Primary Current – 300A
Secondary Current - 5A
Current Transformer (Metering) – Ratio : 300/5A
15VA Class 1.0
Current Transformer (Over current protection) – Ratio :300/5A
15VA 5P10
Current Transformer (Different protection) - Ratio: 300/5A
15VA 5P20
5. 33KV Isolator (Rocking Type)
6. Complete Transformer relay and control panel (TCP)
Protection needed :
a. Over current, Earth fault, Over Current (O/C, E/F, O/C)
b. Winding Temperature Trip/Alarm Relay.
c. Oil Temperature Trip/Alarm relay.
d. Bulchoz Trip/Alarm Relay.
e. Differential Trip/Alarm Relay.
Power supply = 110V D.C
Current = 5A
Please note that some Transformer Control Panel (TCP) currently in
use has Inbuilt matching CTs for the differential balancing. We shall only need to input data for stability.
That is to say, if the TCP has all the above listed data we may not need external matching CTs.