You are on page 1of 3

Allen Bradley DF1, Full Duplex and Half Duplex

1 DESCRIPTION

Doc. No. FS-8700-03

Ver: 1.01 Rev: 8

The DF1 driver allows the FieldServer to transfer data to and from devices over RS-232 using DF1 protocol. The FieldServer can emulate either a Server or Client. FieldServer Mode Client Server Nodes 1 1 Comments One node per port One node per port

FORMAL DRIVER TYPE

Serial Client or Server

COMPATIBILITY MATRIX
Compatible with this driver Yes Yes Yes Yes Yes Yes Yes Yes

FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoCessor ProtoNode

CONNECTION INFORMATION
Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability Error Checking RS-232 Half Duplex 300 to 115200; 9600 (Vendor limitation) 8 (Vendor limitation) 1,2 Odd, Even, None No CRC, BCC (BCC recommended)

DEVICES TESTED
Tested (FACTORY, SITE) Factory Factory Factory Factory Site Site FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 3

Device SLC 5/01 SLC 5/02 SLC 5/03 SLC 5/04 PLC 3 PLC 5

Allen Bradley DF1, Full Duplex and Half Duplex

Doc. No. FS-8700-03

Ver: 1.01 Rev: 8

CONNECTION CONFIGURATIONS

Allen Bradley PLC


COMM 2

FS8917-06

RJ45 CAT 5 Cable FS8915-10

FieldServer

P1

FS-8917-06 Pinouts FS Function RX GND TX RJ45 Pin# 1 4 8 DB9F Pin# 3 5 2 Color White Green Blue

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 3

Allen Bradley DF1, Full Duplex and Half Duplex


7 7.1

Doc. No. FS-8700-03

Ver: 1.01 Rev: 8

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: Data Types Supported


Description (or Device Data Type) Input Output Bit Integer Counter Timer System Status String Float

FieldServer Data Type I O B N C T S St F

7.2

Command Support

The following commands are supported by the FieldServer for the various PLC types. PLC_Type PLC 3 File_Type N F B N F B N F B I O FNC 1 1 1 1 1 1 A2 A2 A2 A2 A2 Read Range Read Range Read Range Read Range Read Range Read Range Read Protracted Typed Logical Read Protracted Typed Logical Read Protracted Typed Logical Read Protracted Typed Logical Read Protracted Typed Logical Read FNC 0 0 2 0 67 26 AA AA AB Write Range Write Range Write Bit Write Range Write Typed Write Read Modify Write Protracted Typed Logical Write Protracted Typed Logical Write Protracted Typed Logical Write Typical Command N7: 3, L5 F12: 3 L5 B3/4: 5 L5 N7: 3, L5 F12: 3 L5 B3/4: 5 L5 N7: 3, L5 B3/4: 5 L7 B3/4: 5 L8 I: 13. L5 O: 13, L5

PLC 5

SLC5

7.3

Unsupported Functions and Data Types


Reason FieldServer is a data transfer device, thus programming messages are not required

Function Programming messages

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 3