Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd. Rating: 6 MW-11 KV Alternator. Doc No: TDC/ALTDATA/MAPL Guranteed Technical Parameters 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 Temperature design reference Relative humidity Atmosphere Location Generator terminal box Phase Side Neutral Side HT cable size BBT location Alternator rotor type Mounting Base plate Sole plates Foundation bolt and anchor bolts Alternator colour shade Generator make Frame designation Applicable standard Nominal output KW rating Rated voltage Voltage variation Rated frequency Frequency variation Combined voltage and frequency variation Rated power factor Full load current Rated speed Number of poles Rotation of Alternator when viewed from DE Number of phase terminals Number of neutral terminals Enclosure protection class, for Generator Enclosure protection class, for Exciter Short ckt ratio Maximum permissible capacitive loading, kVAR Maximum permissible inductive loading, kVAR Steady state 3 ph, Peak SC current Symmetrical short duty and duration of short circuit Sustained 2 ph SC current, kA (at NL excitation) Maximum initial SC current (peak at 110% Volts) 3 ph SC withstand time Ground fault withstand for lamination amp, time Saturation factor Exciter field current at no load Exciter field current at rated load Exciter field current, maximum (50% OL @ 0.3PF) Exciter field voltage at no load Exciter field voltage at rated load Exciter field voltage, maximum (50% OL @ 0.3PF) Main field current at no load 50 99% Hot & humid Indoor Side of Alternator. Side of Alternator. Side of Alternator. 2R x 1C x 300 Sq.mm/Phase NA Cylindrical Horizontal NA Required Required RAL-7032. TDPS TC125 IS-4722, IEEE-519 7500 6000 11000 +/- 10 %. 50 +/- 5 %. +/- 10 %. 0.8 394 1500 Four Clockwise Three Three IP-54. IP-54. 0.50 2959 5699 0.30 0.47 5.7 3.0 100 Amps for 1.0 Secs. 0.88 2.6 8.4 16.9 31 102 199 100 Remarks degC % mm2 KVA KW V % Hz. % % Lag Amps RPM kVAR kVAR kA kA kA Sec Sec Amps Amps Amps Volts Volts Volts Amps page 1 of 6

Alternator Data Sheet

Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd. Rating: 6 MW-11 KV Alternator. Doc No: TDC/ALTDATA/MAPL Guranteed Technical Parameters 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 Main field current at rated load Main field current, maximum Main field voltage at no load Main field voltage at rated load Main field voltage, maximum Max continuous Neg. ph sequence current Neg seq withstand, I2 squre t Max permissible short time unbalance load and time Max deviation from sine wave Effective winding capacitance to earth a. per phase, micro farad. b. all phases connected, together, micro farad. Surge impedance, ohms. Synchronous impedance, ohms. Maximum noise level Stator winding test voltage, KV Field winding test voltage, KV Maximum permissible impact load Insulation class Stator Rotor Exciter armature Exciter field Max temp rise over specified ambient Stator Rotor Type of winding treatment for Stator and rotor Max permissible vibration limit Max harmonic content in output Flux densities in various parts at no load and full load Over load capability, 50%, minutes Over load capability, 10%, hours Efficiency at 25% load, at rated PF. At unitiy PF Efficiency at 50% load, at rated PF. At unitiy PF Efficiency at 75% load, at rated PF. At unitiy PF Efficiency at 100% load, at rated PF. At unitiy PF Critical speed of Generator rotor Ratio of short circuit torque to full load torque Range of adjustment of voltage Earth fault current limited to Earthing mode Auxiliary AC supply
Alternator Data Sheet

Remarks 312 526 75.6 236 399 15% of Rated Amps 20 Refer Negative sequence capability Curve 5.0 (As per IS 4722) 0.0695 0.2086 302.0 32.62 <=85 + 3dB(A) 23.0 1.5 11.3 MVA for 30 Secs Class F Class F F F Class B Class B VPI for Stator and Rotor Ref rotor assembly clause for details, As per IS-12075. 1.50% Tooth < 1.7 T Core < 1.5 T 150% for 30 Secs Amps Amps Volts Volts Volts Amps Sec % micro Farad micro Farad Ohms Ohms dB(A) kV kV MVA -

% Tesla -

110% for One Hr in every 12 Hrs 94.00 94.10 96.20 96.70 96.60 97.50 96.70 97.60 > 2160RPM, Ref. Outline Drg 6.04 +10 100 Amps for 1.0 Secs.
With NGR Current limited to 100Amps. 230 VAC, 50 Hz.

% % % % % % % % RPM % page 2 of 6

Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd. Rating: 6 MW-11 KV Alternator. Doc No: TDC/ALTDATA/MAPL Guranteed Technical Parameters 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 Duty Conneciton Alternator rotor break away torque Min barring speed Stator shell Whether designed for carrying its lifting tackle attached for transportation Stator shell material of construction Overall dimensions diameter length Stator laminations Materials Thickness of laminations Inter laminaiton insulation type Flux density
Suitable for parallel operation with grid and other Generators

Remarks

Star. 114 12.00 Yes MS Refer Outline Drawings Silicon Steel 0.5 Varnish Tooth < 1.7 T Core < 1.5 T Lap Winding

kg-m RPM mm Tesla Amps/sq. mm Meg Ohms Deg C Deg C Deg C Meg Ohms Deg C Deg C kV kV MVA page 3 of 6

Type of winding Armature conductors Conductor material Copper Current density at max machine capability < 7.5 Insulaton, (Stator winding) Type of insulaiton Mica based, suitable for VPI Class of insulation Class 'F' End coil insulation Class 'F' Min insulaiton resistance required before energize >12 Min polarisation index required before energising (considering 2.0 1min/10 min or 1 min/15 min values) Is insulation as per IEC standard. Class F with Yes Temp rise (by resistance), considering 41deg C as cooling air 79 inlet temperature Temp rise by RTD 84 Cooling media Max outlet temperature of cooling medium (air) 67 Insulation (Rotor winding) Type of insulaiton Nomex based, suitable for VPI Class of insulation F Min insulaiton resistance required before energize >2.0 Min polarisation index required before energising (considering NA 1min/10 min or 1 min/15 min values) Temp rise (by resistance), considering 41deg C as cooling air 89 inlet temperature Temp rise by RTD NA Cooling media Max outlet temperature of cooling medium (air) 67 Test voltages Stator winding 50 Hz 1 min. test voltage 23KV Generator field winding test voltage 1.5KV Pull out power at rated voltage with infinite bus and field set for 9633 kW per Sec at 0.8 PF rated MVA for rated and unity pf Reactances, ( 15% Tolerance on reactance as per IEC: 60034-3) Base MVA 7.5
Alternator Data Sheet

Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd. Rating: 6 MW-11 KV Alternator. Doc No: TDC/ALTDATA/MAPL Guranteed Technical Parameters 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 Xd (sat) Xd (unsat) Xq (sat) Xq (unsat) Xd' (sat) Xd' (unsat) Xq' (sat) Xq' (unsat) Xd'' (sat) Xd'' (unsat) Xq'' (sat) Xq'' (unsat) X2 (sat) X0 (sat) X2 (unsat) X0 (unsat) Armature leakage resistance (sat) Armature leakage resistance (unsat) Maximum fault contribution, MVA Resistances and time constants Armature resistances, 25 degC, ohm/phase Armature resistances, 75 degC, ohm/phase Armature resistances, 100 degC, ohm/phase Field resistances, 25 degC, ohm Field resistances, 75 degC, ohm Field resistances, 100 degC, ohm Effective negative seq resistance ohms Td" secs Tdo" secs Td' secs Tdo' secs Ta secs Intertia Constant: Moment of intertia of Generator Inertia constant "H" at base MVA Moment of intertia of rotor Excitation System Details: Excitation system type Exciter enclosure Field breaker / contactor rating Discharge resistor rating Redundant thyrister circuit, yes/no Exciter rating, KW Exciter nominal response Exciter ceiling voltage at 150% rated load with 0.3 PF Exciter air gap Exciter field resistance at 75'C temperature Cooling system: Cooling method Type of cooler No. of coolers (or section)
Alternator Data Sheet

Remarks 1.99 2.17 1.92 2.18 0.27 0.31 1.92 2.18 0.213 0.213 0.36 0.36 0.287 0.167 0.287 0.190 0.157 0.178 38.74 0.0969 0.1156 0.1249 0.5930 0.7071 0.7641 0.1203 0.035 0.44 0.34 2.57 0.13 -0.42 1065 Brushless IP54 Not in TDPS Scope Not in TDPS Scope NO 86 kW approx <50 199 2.5 12.1 CACW Water to Air 2 x 60% P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. MVA (rms) Ohms Ohms Ohms Ohms Ohms Ohms Ohms Secs Secs Secs Secs Secs kg.Sq.M kW m Secs. Volts mm Ohms page 4 of 6

Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd. Rating: 6 MW-11 KV Alternator. Doc No: TDC/ALTDATA/MAPL Guranteed Technical Parameters 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 Cooler location Loading of Generator with one cooler out Capacity of cooler / section, Kcals / Hr. Cooling water inlet temp Cooling water requirement Cooling water required pressure Cooling air inlet temp Cooling air outlet temp Cooler tube type and material Cooler tube design pressure Water pressure drop across coolers Alternator cooler shall be designed with 10% tube plugging margin Bearings: Bearing type Make Size Mounting Type of lubrication Oil flow rate, (liters / Hr / Bearing) Oil pressure Top of Alternator. Remarks

67% output with one section out 105286 32 degC (Delta T: 5 Deg C) 700 approx 1 to 2 41 approx 67 approx Ad Brass approx 5 kg/cm2 < 1kg / Sq. Cm OK kCals/Hr Deg C LPM kg/Sq.Cm(g) Deg C Deg C kg/Sq.Cm(g) kg/Sq.Cm(g) -

Sleeve bearings, force lubricated

Dum Dum EF22 - 225 End Shield Mounted Forced Oil Lubricated 12 LPM Approx 1 to 2 Kg/Sq.Cm(g) Inlet = 45 degC, Outlet = 60 degC 212 Oil in and oil out temperature approx 213 Oil flow indicators Flow glasses provided Flow control is by orifice of 214 Oil flow regulator, with min flow control various sizes, usually 3.2, 4 and 5 mm dia orifice is supplied 215 Oil pressure indicator, pressure gauge Provided 216 Bearing temp indicator, RTD Provided 217 Bearing clearances 0.303-0.378 mm 218 Axial float +/-10 mm 219 Bearing oil type ISO-VG 46 220 Oil flow visible glass tubes and flow control valves shall be provided for both the bearings 221 Anti Condensation Heaters: 222 Type and numbers Flat / tubilar type 223 Rating 500 W, 1 ph, 230V (2 nos.) Bottom foot of main AC 224 Location Generator 225 Embedded temp detector, (RTD type) 226 Type Duplex RTDs 227 Winding 12 nos. 228 Bearing One number per bearing. 229 Hot air 2 nos. 230 Cold air 2 nos. 231 Dial type spot mounted temperature gauges 232 Coolers Two nos. 233 Bearings: One number / bearing. 234 Water Leakage Detector: 235 Quantity 2 nos page 5 of 6 Alternator Data Sheet

Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd. Rating: 6 MW-11 KV Alternator. Doc No: TDC/ALTDATA/MAPL Guranteed Technical Parameters 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 Location Humidity sensors Quantity Location Rotating Diodes: Normal polarity Reverse polarity PIV Current rating Range Miscellaneous data Air gap, a. Main machine b. Exciter Stator lamination withstand for 100A, secs. Total weight of Generator, MT Stator weight, MT Rotor weight, MT Exciter weight, MT Overall length of stator, mm Overall dia of stator, mm Overall dia of rotor, mm Heaviest lift, MT Weight of cooler, MT Stator shipping dimension mm Rotor shipping dimension mm Exciter shipping dimension mm Clear space required for Alternaotr rotor removal, from ND end of Alternator, mm Other accessories, (shall be included in scope of supply) Dowel pins, cable gland plates Mating flanges for all the water and oil inlet and outlet lines Provision shall be made for measurement of shaft vibration on the Generator DE and NDE end bearings. At least 15 mm of Generator shaft shall be burnished (mirror like finish) at the target area of the vibration probe at both ends for measurement of shaft vibration. Provision shall be made for mounting the vibration probes inside the bearing housing Brush gear arrangement, carbon brushes and 2 nos. sliprings alongwith rotor Earthing brush (for rotor earth fault relays by TEIL) shall be provided on the Alternator. Two nos slip-rings with carbon brushes shall be provided for +ve and ve of Alternator field and one carbon brush shall be provided for earthing of Alternator rotor PMG for AVR Excitation Input Spare items, (to be supplied with Alternator) Cooler tray Not Required NA 6 nos 6 nos 1600 312 240-500 Amps 11 approx 2.5 approx 1 Sec Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings Refer Outline Drawings OK, provided. OK, provided. Volts Amps mm mm MT MT MT MT mm mm mm MT MT mm mm mm meters Remarks

266

OK, provided.

267

OK, provided.

268 269

Not Required

Alternator Data Sheet

page 6 of 6