50TJ016-032S Side Discharge

Single-Package
Rooftop Units 50/60 Hz
15 to 30 Nominal Tons

Product Data

The 50TJ-S series is a special side discharge version packaged unit with capacities of 15-30
Tons. This unit can be placed on the side of a building with direct ducts to and from conditioned
space, or can be placed on the roof, without a roof curb, and simple Ductwork.
High Efficiency Rooftop Units with:
Dual, electrically and mechanically
independent refrigerant circuits
Scroll compressors on each circuit
TXV refrigerant metering devices
Non-corrosive, sloped condensate
drain pans meet ASHRAE 62-99 (IAQ)
One-inch return air filters
Electric heat (FIOP)
Special Standard Features
Double skin construction.
Pre-coated fin condenser coil, for
extra corrosion protection.
High Efficiency, High Static Blower.

Features/Benefits
Every compact one-piece unit arrives
fully assembled, charged, tested, and
ready to run.

Durable, dependable construction


Designed for durability in any climate,
the weather-resistant cabinets are
constructed of galvanized steel,
bonderized, and all exterior panels are
coated with a pre-painted baked
enamel finish. The paint finish is nonchalking,
and
is
capable
of
withstanding ASTM (American Society
for Testing and Materials) B117 500
hour Salt Spray Test. All internal
cabinet panels are primed, permitting
longer life and a more attractive
appearance for the entire unit. Totally
enclosed condenser-fan motor and
permanently
lubricated
bearings
provide additional unit dependability.

50TJSD-05 PD C

2008

Easy installation

50TJ

All units feature base rail design with forklift


slots and rigging holes for easier
manoeuvring. Durable packaging protects all
units
during
shipment
and
storage.
Convenient side by side openings permit
installation very close to the face of buildings,
or on roof top.
The non-corrosive sloped condensate pan
minimizes residual condensate in off cycle.
An external, field-supplied P-trap is required.
Field-installed electric heaters are available in
two convenient capacities 30 kW or 40 kW.

Indoor-air quality begins with


Carrier rooftops

ASHRAE (American Society of Heating,


Refrigeration and Air Conditioning
Engineers) Standard 62. One-in. filters
provide for grater partical reductionin the
return air.

Simple electrical connections


Terminal boards, located in the base unit
control box, facilitate connections to room
thermostat, outdoor thermostat(s) and
electric heat. Service panels are quickly
removed, permitting easy servicing. Both
power and control connections are made on
the same side of the unit to simplify
installation. In addition, colour-coded wires
permit easy tracing and diagnostics.

Sloped condensate pans minimize biological

growth in rooftop units in accordance with

Table of contents
Features/Benefits.
ModelNumber Nomenclature.
Capacity Ratings.
Physical Data.
Base Unit Dimensions.
PerformanceData (60 Hz)
PerformanceData (50 Hz)
Fan Performance Data
Electrical Data
Typical Wiring Schematic.
Controls...
Application Data
Guide Specifications

Page.
1,2
3
4
5-10
11
12-21
22-31
32-43
44
45-50
51
51
52,53

Model Number Nomenclature

50Co o ling Only/Co o ling


with Optio nal Electric Heat

TJCo nstant Vo lum e


No minal To ns (kW)
01615 To ns (52 kW)
020 18 To ns (63 kW)
02420 To ns (70kW)
02825 To ns (88 kW)
03230 To ns (105 kW)

50TJ

50 TJ 024 5 3 1 S

S Special Features
P ackaging
1 Standard
3 Expo rt

Design Series
1 1st Side Discharge Design
2 2nd Design Series
3 3rd Design Series

Vo ltage
2 380360
5 208/230360
6 460360
9 400350

LEGEND
FIOP Factory-Installed Option
*Refer to 50TJ Price Pages for 50TJ FIOP code table or contact your local Carrier representative for more details.

50TJ

Capacity at ARI* rating condition

NOMINAL
TONS

STANDARD
CFM / L/s

GROSS COOLING
CAPACITY
Btuh

NET COOLING
CAPACITY
(Btuh)/ Kw

TOTAL
WATTS

EER

SOUND
RATING
(Bels)

016

15

6000 / 2831

180,000

176,000 / 52

19,800

8.9

8.8

020

18

6300 / 2973

201,000

192,000 / 57

21,400

9.0

8.8

024

20

8000 / 3870

234,000

225,000 / 66

24,400

9.2

9.5

028

25

8700 / 4105

287,000

275,000 / 81

30,000

9.2

9.5

032

30

10,000 / 4700

338,000

317,000 / 96

35,000

9.0

9.5

UNIT
50TJ

LEGEND
Bels Sound Levels (1 bel = 10 decibels)
db Dry Bulb
EER Energy Efficiency Ratio
*Air Conditioning and Refrigeration Institute.

NOTES:
1. The above net cooling capacity ratings are net values, reflecting the effects of circulating fan heat.

Net Cooling Capacity = Refrigeration Cycle Cooling Indoor Fan Motor Power.

2. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.

AIR QUANTITY LIMITS

UNIT 50TJ

MINIMUM CFM / L/s

MAXIMUM CFM / L/s

016

4500 / 2124

7,500 / 3539

020

4800 / 2265

7,600 / 3586

024

6000 / 2831

10,000 / 4719

028

6700 / 3162

10,700 / 5049

032

8500 / 4011

11,500 / 5427

ELECTRIC RESISTANCE HEATER DATA 50TJ016-032

208

HEATER kW
Unit Voltages
240
380

460

HEATER FLA (PER STAGE)


Unit Voltages
208
240
380
460

HEAT
PER
STAGE

50/50

4800

2265

50/50

5500

2596

50/50

6000

2832

50/50

7000

3304

50/50

7000

3304

016
23 kW

30 kW

19 kW

28 kW

31.3

36.1

14.3

17.3

020
024
028

30 kW

40 kW

25 kW

37 kW

41

49

19

MINIMUM HEATING
CFM
Cfm
L/s

HEATER
STAGES

50TJ

UNIT
50TJ

23

032

NOTE: Use the Multiplication Factors table below to determine heater capacity for your particular voltage.

MULTIPLICATION FACTORS
HEATER RATING
ACTUAL HEATER VOLTAGE
VOLTAGE
200
208
230
240
380
400
240
0.694
0.751
0.918
1.000

480

0.62
0.7

NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.413 = Btuh.

EXAMPLE: 30 kW (at 240 v) heater on 208 v

= 30.0 (0.751 mult factor)

= 22.5

460

0.92

480

ACCESSORY HEATER PART NUMBER


220 V
UNIT 50TJ

400 V

Complete
Kit P.N.

Casing P.N.
(1 Per Kit)

Heater Element P.N.


(2 Per Kit)

Complete Kit
P.N.

Casing P.N.
(1 Per Kit)

Heater Element
P.N. (2 Per Kit)

50TJ600201

50TJ600289

CPHEATER030A00

50TJ600287

50TJ600289

CPHEATER036A00

50TJ600202

50TJ600290

CPHEATER031A00

50TJ600288

50TJ600290

CPHEATER037A00

50TJ600729

50TJ600727

CPHEATER031A00

50TJ600730

50TJ600727

CPHEATER037A00

016
020
024
028
032

Physical data (60Hz) English

50TJ

UNIT 50TJ
NOMINAL CAPACITY (tons)
OPERATING WEIGHT
COMPRESSOR
Quantity...Danfoss Model (Ckt 1 , Ckt 2)
Number of Refrigerant Circuits
Oil (oz) (Ckt 1 , Ckt 2)
Stages of Capacity Control (%)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Circuit 1*
Circuit 2
CONDENSER COIL

016

020

15

18

2... SM100S

1..SM110S,
1..SM100S

1...SM120S,
1..SM110S

1..SM161T,
1...SM120S

2..SM161T,

2
81, 81
50/50

2
106,81
55/45

2
106, 106
55/45
R-22
TXV

2
136, 106
60/40

2
136, 136
50/50

12-8
12-8

Rows...Fins/in.
Total Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.), No. of Blades.
Motor Hp...Rpm
EVAPORATOR COIL

2...16
24.43

Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Motor Hp
Motor Nominal Rpm
Maximum Continuous Bhp
Motor Frame Size
Fan Rpm Range
Fan Pulley Pitch Diameter (in.)
Nominal Fan Shaft Diameter (in.)
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Speed Setting
Factory Speed Setting (rpm)

2...17
18.4

HIGH-PRESSURE SWITCH (psig)


Cut-out
Reset (Auto)
LOW-PRESSURE SWITCH (psig)
Cut-out
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
RETURN-AIR FILTERS
Quantity...Size (in.)

Condenser Motor Efficiency 80%

Evaporator Motor Efficiency 87%

1...16 x 16
Belt
6000
5
1745
5.5
184T
690-840
11.0
1.19
Ball
1200
4.3/5.2

024

028

20
25
For Operating Weights see page 10.
Scroll

17-0
20-8
24-0
14-0
14-0
16-0
Grooved 3/8-in. Copper Tubes, Aluminium Wavy,
Aluminium Pre-Coated, or Copper Plate Fins
3...16
3..16
4...16
24.43
27.44
27.44
Propeller Type
14,200
2...304
11140
Grooved 3/8-in. Copper Tubes, LSW or
Copper Plate Fins, Face Split
3...17
3...17
4...17
18.4
21
21
Centrifugal Type
1...16 x 16
1...18 x 18
1...18 x 18
Belt
Belt
Belt
6300
8000
8700
5
7.5
7.5
1745
1745
1745
5.5
8.2
8.2
184T
213T
213T
765-920
710-810
810-910
10.0
11.0
11.0
1.19
1.38
1.38
Ball
Ball
Ball
1200
1400
1400
4.3/5.2
4.5/5.0
5.2/5.75

032
30

24-0
24-0
4...16
30.00
15,000
2...304
11140
4...17
23.3
1...18 x 18
Belt
10,500
10
1745
11
215T
850-1080
11.0
1.38
Ball
1400
5.4/6.8

11/8
2... SPA 1900
23.8-25
30

11/8
2... SPA 1900
23.8-25
30

13/8
2... SPB 2060
23.8-25
20

13/8
2... SPB 2060
23.8-25
20

13/8
2... SPB 2000
23.8-25
50

21/2
765

21/2
840

21/2
760

21/2
860

21/2
975

426
320
27
44
30 5
45 5

Aluminium
4...(31.5 x 21.5)

Aluminium
4..(36.5 x 21.5)

Physical data (60 Hz) SI

016

020

NOMINAL CAPACITY (kW)


OPERATING WEIGHT
COMPRESSOR
Quantity...Danfoss Model (Ckt 1 , Ckt 2)

52.8

63.3

Number of Refrigerant Circuits


Oil (ml) (Ckt 1 , Ckt 2)
Stages of Capacity Control (%)
REFRIGERANT TYPE
Expansion Device
Operating Charge (Kg)
Circuit 1*
Circuit 2
CONDENSER COIL

2...SM100S
2
2531, 2531
50/50

5.7
5.7

028

70.3
87.9
For Operating Weights see page 10.
Scroll
1..SM110S,
1...SM120S,
1..SM161T,
1..SM100S
1..SM110S
1...SM120S
2
3312,2531
55/45

2
3312, 3312
55/45
R-22
TXV

2
4250, 3312
60/40

032
105
2..SM161T,
2
4250, 4250
50/50

1...400 x 400
Belt
2830
3.7
29
4
184T
11.5-14
280
30
Ball
20
110/131

7.7
8.2
10.9
6.3
6.3
7.3
Grooved 3/8-in. Copper Tubes, Aluminium Wavy,
Aluminium Pre-Coated, or Copper Plate Fins
3...16
3...16
4...16
2.271
2.55
2.55
Propeller Type
6700
2...7624
0.74519
Grooved 3/8-in. Copper Tubes, LSW or
Copper Plate Fins, Face Split
3...17
3...17
4...17
1.71
1.951
1.951
Centrifugal Type
1...400 x 400
1...450 x 450
1...450 x 450
Belt
Belt
Belt
2973
3775
4105
3.7
5.6
5.6
29
29
29
4
6.2
6.2
184T
213T
213T
13-15
11.83-13.5
13.5-15
250
280
280
30
35
35
Ball
Ball
Ball
20
23.33
23.33
110/131
114/129
131/146

1...450 x 450
Belt
4955
7.5
29
8.25
215T
14-18
280
35
Ball
23.33
137/173

28.5
2... SPA 1900
604.5-635
0.5

28.5
2... SPA 1900
604.5-635
0.5

35
2... SPB 2060
604.5-635
0.33

35
2... SPB 2060
604.5-635
0.33

35
2... SPB 2000
660-685
0.83

21/2
12.75

21/2
14

21/2
12.66

21/2
14.33

21/2
16.25

Rows...Fins/in.
Total Face Area (m2)
CONDENSER FAN
Nominal L/s
Quantity...Diameter (mm)..No. of Blades.
Motor BkW...r/s
EVAPORATOR COIL

2...16
2.271

Rows...Fins/in.
2
Total Face Area (m )
EVAPORATOR FAN
Quantity...Size (mm)
Type Drive
Nominal L/s
Motor BkW
Motor Nominal r/s
Maximum Continuous BkW
Motor Frame Size
Fan Rpm Range
Fan Pulley Pitch Diameter (mm)
Nominal Fan Shaft Diameter (mm)
Motor Bearing Type
Maximum Allowable r/s
Motor Pulley Pitch Diameter
Min/Max (mm)
Nominal Motor Shaft Diameter (mm)
Belt, Quantity...Type...Length (mm.)
Pulley Center Line Distance (mm.)
Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Speed Setting
Factory Speed Setting (r/s)

2...17
1.71

HIGH-PRESSURE SWITCH (psig)


Cut-out
Reset (Auto)
LOW-PRESSURE SWITCH (psig)
Cut-out
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (C)
Opens
Closes
RETURN-AIR FILTERS
Quantity...Size (mm.)

024

50TJ

UNIT 50TJ

10.9
10.9
4...16
2.79
7079
2...7624
0.74519
4...17
2.165

426
320
27
44

Aluminium
4...(790 x 546)

-1 1
71

Aluminium
4..(902 x 546)

Condenser Motor Efficiency 80%

Evaporator Motor Efficiency 87%

Physical data (50Hz) English

50TJ

UNIT 50TJ
NOMINAL CAPACITY (tons)
OPERATING WEIGHT
COMPRESSOR
Quantity...Danfoss Model (Ckt 1 , Ckt 2)
Number of Refrigerant Circuits
Oil (oz) (Ckt 1 , Ckt 2)
Stages of Capacity Control (%)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Circuit 1*
Circuit 2
CONDENSER COIL

016

020

15

18

2...SM110S

1..SM120S,
1..SM110S

2
106, 106
50/50

2
106,106
55/45

14-0
14-0

Rows...Fins/in.
Total Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.)No. of Blades.
Motor Hp...Rpm
EVAPORATOR COIL

2...16
24.43

Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Motor Hp
Motor Nominal Rpm
Maximum Continuous Bhp
Motor Frame Size
Fan Rpm Range
Fan Pulley Pitch Diameter (in.)
Nominal Fan Shaft Diameter (in.)
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Speed Setting
Factory Speed Setting (rpm)

2...17
18.4

HIGH-PRESSURE SWITCH (psig)


Cut-out
Reset (Auto)
LOW-PRESSURE SWITCH (psig)
Cut-out
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
RETURN-AIR FILTERS
Quantity...Size (in.)

Condenser Motor Efficiency 80%

Evaporator Motor Efficiency 87%

1...16 x 16
Belt
6000
5
1435
5.5
184T
690-840
8 7/8
1.19
Ball
1200
4.3/5.2

024

028

032

20
25
For Operating Weights see page 10.
Scroll
1...SM161T,
1..SM120S
2
136, 106
60/40
R-22
TXV

30

1..SM185W,
1...SM161T

2..SM185W,

2
136, 136
55/45

2
136, 136
50/50

17-8
23-0
25-0
14-8
14-8
17-0
Grooved 3/8-in. Copper Tubes, Aluminium Wavy,
Aluminium Pre-Coated, or Copper Plate Fins
3...16
3...16
4...16
24.43
27.44
27.44
Propeller Type
12,800
2...304
1950
Grooved 3/8-in. Copper Tubes, LSW or
Copper Plate Fins, Face Split
3...17
3...17
4...17
18.4
21
21
Centrifugal Type
1...16 x 16
1...18 x 18
1...18 x 18
Belt
Belt
Belt
6300
8000
8700
5
7.5
7.5
1435
1435
1435
5.5
8.2
8.2
184T
213T
213T
765-920
710-810
810-910
7 7/8
9 5/17
9 5/17
1.19
1.38
1.38
Ball
Ball
Ball
1200
1400
1400
4.3/5.2
4.5/5.0
5.2/5.75

25-0
25-0
4...16
30.00
14,500
2...306
1950
4...17
23.3
1...18 x 18
Belt
10,500
10
1435
11
215T
830-1050
9 5/17
1.38
Ball
1400
5.4/6.8

11/8
2... SPA 1800
23.8-25
30

11/8
2... SPA 1800
23.8-25
30

13/8
2... SPB 2000
23.8-25
20

13/8
2... SPB 2000
23.8-25
20

13/8
2... SPB 1950
23.8-25
50

21/2
765

21/2
840

21/2
760

21/2
860

21/2
955

426
320
27
44
30 5
45 5

Aluminium
4...(31.5 x 21.5)

Aluminium
4..(36.5 x 21.5)

Physical data (50 Hz) SI

016

020

NOMINAL CAPACITY (kW)


OPERATING WEIGHT
COMPRESSOR
Quantity...Danfoss Model (Ckt 1 , Ckt 2)

52.8

63.3

Number of Refrigerant Circuits


Oil (ml) (Ckt 1 , Ckt 2)
Stages of Capacity Control (%)
REFRIGERANT TYPE
Expansion Device
Operating Charge (Kg)
Circuit 1*
Circuit 2
CONDENSER COIL

2...SM110S

028

70.3
87.9
For Operating Weights see page 10.
Scroll
1..SM120S,
1...SM161T,
1..SM185W,
1..SM110S
1..SM120S
1...SM161T

32
105
2..SM185W,

2
3312, 3312
50/50

2
3312, 3312
55/45

2
3312, 3312
60/40
R-22
TXV

2
4250, 4250
55/45

2
4250, 4250
50/50

6.4
6.4

8
6.6

10.5
6.6

11.4
7.7

11.4
11.4

1...400 x 400
Belt
2830
3.7
24
4
184T
11.5-14
224
30
Ball
20
110/131

Grooved 3/8-in. Copper Tubes, Aluminium Wavy,


Aluminium Pre-Coated, or Copper Plate Fins
3...16
3...16
4...16
4...16
2.271
2.55
2.55
2.79
Propeller Type
6040
6843
2...7624
2...7626
0.7516
0.74516
Grooved 3/8-in. Copper Tubes, LSW or
Copper Plate Fins, Face Split
3...17
3...17
4...17
4...17
1.71
1.951
1.951
2.165
Centrifugal Type
1...450 x 450
1...400 x 400
1...450 x 450
1...450 x 450
Belt
Belt
Belt
Belt
4955
2973
3775
4105
7.5
3.7
5.6
5.6
24
24
24
24
8.25
4
6.2
6.2
215T
184T
213T
213T
14-18
13-15
11.83-13.5
13.5-15
236
200
236
236
35
30
35
35
Ball
Ball
Ball
Ball
23.33
20
23.33
23.33
137/173
110/131
114/129
131/146

28.5
2... SPA 1800
604.5-635
0.5

28.5
2... SPA 1800
604.5-635
0.5

35
2... SPB 2000
604.5-635
0.33

35
2... SPB 2000
604.5-635
0.33

35
2... SPB 1950
660-685
0.83

21/2
12.75

21/2
14

21/2
12.66

21/2
14.33

21/2
15.9

Rows...Fins/in.
2
Total Face Area (m )
CONDENSER FAN
Nominal L/s
Quantity...Diameter (mm)No. of Blades.
Motor BkW...r/s
EVAPORATOR COIL

2...16
2.271

Rows...Fins/in.
Total Face Area (m2)
EVAPORATOR FAN
Quantity...Size (mm)
Type Drive
Nominal L/s
Motor BkW
Motor Nominal r/s
Maximum Continuous BkW
Motor Frame Size
Fan r/s Range
Fan Pulley Pitch Diameter (mm)
Nominal Fan Shaft Diameter (mm)
Motor Bearing Type
Maximum Allowable r/s
Motor Pulley Pitch Diameter
Min/Max (mm)
Nominal Motor Shaft Diameter (mm)
Belt, Quantity...Type...Length (mm.)
Pulley Center Line Distance (mm.)
Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Speed Setting
Factory Speed Setting (r/s)

2...17
1.71

HIGH-PRESSURE SWITCH (psig)


Cut-out
Reset (Auto)
LOW-PRESSURE SWITCH (psig)
Cu-out
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (C)
Opens
Closes
RETURN-AIR FILTERS
Quantity...Size (mm.)

024

50TJ

UNIT 50TJ

426
320
27
44
-1 1
71

Aluminium
4...(790 x 546)

Aluminium
4..(902 x 546)

Condenser Motor Efficiency 80%

Evaporator Motor Efficiency 87%

Physical data (cont)


50TJ

OPERATING AND RIGGING WEIGHTS


UNIT
50TJ

016
lb
1628

020
kg
723

lb
1733

BASE UNIT OPERATING WEIGHTS*


024
028
kg
lb
kg
Lb
786
1870
850
2035

032
Kg
923

Lb
2200

Kg
1000

*Base unit weight does not include electric heaters, copper coils or crating.

NOTES:

-For 016 and 020 unit sizes add 75 lb (34 kg) for domestic crating. For 024 and 032 unit sizes add 135 lb (61 kg). For export crating add 500 lb

(227 kg).

- All units are internally isolated against vibration. If extra isolation required, please see dimensional drawing (page- 11) for corner weights.

10

50TJ

11

Performance data (60 Hz)


50TJ

COOLING CAPACITIES ENGLISH


50TJ016 (15 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

50TJ016 (15 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

4500/0.10
57

62

67

72

164
164
13.6
159
159
14.8
154
153
16.1
148
147
17.5
142
142
18.9
140
140
19.3
139
139
19.6

177
146
14.0
170
142
15.2
163
139
16.4
155
135
17.6
148
131
19.0
145
130
19.4
144
129
19.6

193
124
14.4
186
120
15.6
178
117
16.9
170
114
18.2
162
111
19.5
159
110
19.9
157
109
20.2

212
100
15.0
204
98
16.1
195
94
17.4
186
91
18.7
176
88
20.0
173
87
20.4
171
86
20.6

57
183
183
14.3
178
178
15.5
171
171
16.7
164
164
18.1
157
156
19.4
154
154
19.8
153
153
20.0

Evaporator Air Quantity Cfm/BF


5250/0.12
Evaporator Air Ewb (F)
57
62
67
72
171
171
13.9
166
166
15.1
160
160
16.3
154
154
17.7
148
148
19.1
146
146
19.5
144
144
19.8

181
157
14.2
174
152
15.3
167
148
16.6
159
144
17.8
151
140
19.1
148
139
19.5
147
139
19.8

197
132
14.6
190
129
15.8
182
126
17.0
174
122
18.3
165
118
19.7
162
117
20.0
160
116
20.2

Evaporator Air Quantity Cfm/BF


6750/0.15
7500/0.16
Evaporator Air Ewb (F)
62
67
72
57
62
67
188
176
14.4
181
172
15.6
173
168
16.8
165
163
18.1
157
156
19.4
154
154
19.8
153
153
20.0

204
147
14.9
197
144
16.1
189
141
17.3
179
137
18.5
169
133
19.9
166
131
20.2
164
130
20.4

224
116
15.4
216
112
16.6
206
109
17.8
196
105
19.1
185
102
20.4
182
100
20.8

188
188
14.4
182
182
15.6
175
175
16.9
168
168
18.2
160
160
19.5
158
158
19.9
156
156
20.2

190
185
14.5
183
180
15.7
175
175
16.9
168
168
18.2
160
160
19.5
158
158
19.9
156
156
20.2

206
157
14.9
199
151
16.1
190
147
17.4
181
143
18.6
171
140
19.9
168
138
20.4
166
137
20.6
hIdb = hedb -

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
1.
2.

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

12

216
105
15.1
208
102
16.3
200
100
17.6
190
96
18.8
180
93
20.2
177
92
20.6

3.

6000/0.14
57

62

67

72

178
178
14.1
172
172
15.3
166
166
16.6
160
160
17.9
153
150
19.2
151
148
19.6
149
147
19.9

184
169
14.3
178
163
15.5
170
158
16.7
162
155
17.9
153
150
19.2
151
148
19.6
149
147
19.9

202
140
14.7
194
137
15.9
186
133
17.2
177
130
18.5
167
126
19.8
164
125
20.2
162
124
20.4

220
111
15.2
212
107
16.5
204
104
17.7
193
101
18.9
183
97
20.2
179
96
20.6

72
226
120
15.4
218
117
16.7
208
113
17.9
197
109
19.1
187
106
20.4
183
105
20.8

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80

Performance data (60 Hz)

TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

75
85
95
105
115
120
125

50TJ020 (18 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

75
85
95
105
115
120

5400/0.095
62

67

72

191
165
14.3
184
161
15.2
181
162
15.6
176
162
17.8
171
161
19.6
164
155
20.3
153
146
21.3

211
138
14.9
202
135
15.6
199
135
16.0
194
134
18.2
188
134
20.1
181
129
20.8
169
122
21.9

231
111
14.2
224
108
16.2
220
108
16.7
214
107
18.8
208
106
20.7
200
102
21.5
189
96
22.4

62
202
199
14.8
194
194
15.6
192
192
16.0
189
188
18.2
184
184
20.2
177
177
20.9

221
166
15.3
213
162
16.1
208
163
16.5
203
162
18.6
195
162
20.5
187
156
21.1

243
128
15.9
234
125
16.7
230
124
17.0
224
124
19.3
214
122
21.1

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

194
173
14.4
187
170
15.3
184
170
15.6
180
170
17.8
173
168
19.8
166
162
20.4
156
153
21.5

213
145
15.0
206
142
15.8
201
142
16.2
196
142
18.3
189
140
20.3
182
135
20.9
170
128
21.9

235
115
15.6
226
112
16.4
223
112
16.7
217
111
19.0
210
109
20.9
202
105
21.5
191
99
22.3

Evaporator Air Quantity Cfm/BF


8000/0.140
9000/0.150
Evaporator Air Ewb (F)
67
72
62
67

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
1.
2.

Evaporator Air Quantity Cfm/BF


6000/0.105
Evaporator Air Ewb (F)
62
67
72

206
206
14.9
199
199
15.7
197
197
16.2
193
193
18.4
188
188
20.3
181
181
21.1

223
175
15.4
215
172
16.2
210
172
16.6
204
172
18.7
196
171
20.5
188
165
21.3

50TJ

COOLING CAPACITIES ENGLISH (cont)


50TJ020 (18 TONS)
Temp (F)
Air Entering
Condenser
(Edb)

7000/0.120
62

67

72

198
187
14.6
191
183
15.5
188
183
15.8
183
183
18.0
179
179
20.0
172
172
20.7
161
160
21.7

218
155
15.1
209
152
15.9
205
153
16.3
201
152
18.5
193
151
20.4
185
146
21.1
173
138
22.2

239
121
15.7
231
119
16.5
228
118
16.9
219
118
19.1
212
116
21.0
204
111
21.7
193
105
22.6

72
245
133
16.0
237
131
16.8
232
131
17.1
226
130
19.3
217
128
21.2

hIdb = hedb -

3.

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80).

13

Performance data (60 Hz)


50TJ

COOLING CAPACITIES ENGLISH (cont)


50TJ024 (20 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
57
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

50TJ024 (20 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
Kw
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

75
85
95
105
115
120

6,000/0.075

209
209
15.7
203
203
17.0
197
197
18.5
190
190
20.1
183
183
21.7
175
175
23.2
167
167
24.7

57
234
234
16.4
227
227
17.7
220
220
19.2
212
212
20.7
203
203
22.2
194
194
23.8

62

67

72

222
190
16.0
214
186
17.3
207
182
18.7
197
178
20.1
188
173
21.7
178
168
23.2
168
163
24.7

246
160
16.6
237
157
17.9
228
153
19.3
218
149
20.6
207
145
22.1
196
141
23.7
185
137
25.3

270
130
17.2
261
126
18.5
252
123
19.8
241
119
21.3
228
117
22.8
217
111
24.3
206
105
25.8

235
231
16.5
227
226
17.8
220
219
19.2
212
211
20.7
203
203
22.2
194
194
23.8

259
193
17.1
250
189
18.4
239
185
19.8
228
181
21.1
217
177
22.6
204
172
24.1

BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

14

219
219
15.9
212
212
17.3
206
206
18.8
198
198
20.3
191
191
22.0
182
181
23.4
172
172
24.9

228
205
16.2
220
201
17.5
211
196
18.9
202
192
20.2
192
187
21.9
182
181
23.4
172
172
24.9

251
171
16.8
242
168
18.1
233
164
19.4
222
160
20.8
211
156
22.3
200
152
23.8
189
148
25.3

277
136
17.4
267
133
18.7
257
130
20.1
246
126
21.5
233
122
22.9
221
117
24.4
209
112
25.9

Evaporator Air Quantity Cfm/BF


9,000/0.110
10,000/0.120
Evaporator Air Ewb (F)
62
67
72
57
62
67

LEGEND

NOTES:
1.
2.

Evaporator Air Quantity Cfm/BF


7,000/0.085
Evaporator Air Ewb (F)
57
62
67
72

286
149
17.7
276
147
19.0
265
143
20.4
254
139
21.8
240
135
23.2
226
130
24.7

240
240
16.6
233
233
17.9
225
225
19.4
216
216
20.9
207
207
22.4
198
198
3.9

8,000/0.100
57

62

67

72

227
227
16.2
220
220
17.5
213
213
19.0
205
204
20.4
197
197
22.0
188
188
23.6
179
179
25.2

231
219
16.3
224
215
17.6
215
210
19.0
205
204
20.4
197
197
22.0
188
188
23.6
179
179
25.2

256
182
16.9
246
179
18.2
237
175
19.6
226
171
21.0
215
166
22.4
202
162
23.9
189
158
25.4

282
143
17.6
272
140
18.9
261
136
20.2
250
133
21.7
237
128
23.1
224
125
24.6
211
122
26.1

72

240
262
240
203
16.7
17.2
233
252
233
200
18.0
18.5
225
241
225
195
19.4
19.8
216
230
216
191
20.9
21.3
207
218
207
186
22.4
22.6
198
206
198
181
3.9
24.2
hIdb = hedb -

3.

289
156
17.8
279
153
19.2
267
149
20.5
255
145
21.9
242
141
23.3
227
137
24.8
Total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
Under 75
81
82
83
84
85
Over 85
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80).

Performance data (60 Hz)

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

50TJ028 (25 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
KW
TC
SHC
KW

75
85
95
105
115
120

7,000/0.05

256
255
19.1
248
248
21
242
242
23
234
234
25.1
226
226
27.4
221
221
28.7
217
217
29.6

57
283
283
20
275
275
22
267
267
24
257
257
26.1
247
247
28.2
240
240
29.5

62

67

72

271
232
19.5
262
227
21.4
252
223
23.3
241
218
25.3
231
212
27.4
224
209
28.7
219
207
29.6

298
195
20.4
287
191
22.2
277
187
24.1
266
182
26.1
254
178
28.3
246
175
29.6
240
173
30.5

328
158
21.2
317
155
23.1
306
150
25.1
293
146
27
279
141
29.1
275
140
29.7
272
139
30.1

286
279
20.2
278
271
22
267
263
24
257
255
26.1
247
247
28.2
240
240
29.5

312
235
20.9
303
226
22.8
291
222
24.7
279
217
26.7
264
211
28.8
256
208
30.1

BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

266
266
19.5
259
259
21.4
251
251
23.4
243
243
25.5
235
235
27.7
229
229
29
224
224
29.9

277
250
19.7
267
244
21.6
258
240
23.6
247
233
25.6
236
228
27.7
229
223
29
224
219
29.9

304
208
20.6
294
203
22.4
283
199
24.4
272
195
26.4
259
189
28.5
251
186
29.8
245
184
30.7

334
167
21.4
324
162
23.3
312
158
25.3
299
153
27.4
284
148
29.3
280
147
30
277
146
30.5

Evaporator Air Quantity Cfm/BF


10,000/0.08
11,250/0.09
Evaporator Air Ewb (F)
62
67
72
57
62
67

LEGEND

NOTES:
1.
2.

Evaporator Air Quantity Cfm/BF


8,000/0.06
Evaporator Air Ewb (F)
57
62
67
72

342
184
21.8
334
177
23.7
321
172
25.7
307
167
27.7
291
162
29.7

292
292
20.3
283
283
22.3
274
274
24.3
264
264
26.3
253
253
28.4
246
246
29.4

50TJ

COOLING CAPACITIES ENGLISH (cont)


50TJ028 (25 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
57

9,000/0.07
57

62

67

72

275
275
19.8
268
268
21.7
260
260
23.7
251
251
25.8
241
241
27.9
235
235
29.2
231
231
30.1

281
265
19.9
272
259
21.8
261
254
23.8
252
246
25.8
241
238
27.9
235
233
29.2
231
229
30.1

308
223
20.7
298
216
20.6
288
210
24.5
275
205
26.5
261
201
28.6
253
197
29.9
247
194
30.8

339
177
21.6
330
170
23.5
317
165
25.5
302
161
27.5
288
156
29.5
284
155
30
281
154
30.3

72

293
316
291
249
20.4
21
284
306
283
243
22.3
22.9
274
294
274
236
24.3
24.9
264
282
264
230
26.3
26.9
253
267
253
225
28.4
29
246
258
246
221
29.4
30.2
hIdb = hedb -

3.

346
197
21.9
337
189
23.9
326
181
25.8
311
175
27.9
294
170
29.9

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
Under 75
81
82
83
84
85
Over 85
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80).

15

Performance data (60 Hz)


COOLING CAPACITIES ENGLISH (cont)

50TJ

50TJ0032 (30 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

8,500/0.07
62

67

72

325
266
24.1
314
261
26.6
302
255
29.5
289
248
32.4
275
243
35.4
271
241
36.3
267
239
36.9

359
234
24.9
346
229
27.6
333
224
30.3
319
218
33.3
303
212
36.3
298
210
37.3
293
206
38.0

395
191
25.9
381
184
28.5
366
180
31.3
350
174
34.3
333
168
37.3

Evaporator Air Quantity Cfm/BF


9,500/0.08
Evaporator Air Ewb (F)
62
67
72
333
297
24.3
321
292
26.8
308
285
29.6
295
278
32.6
280
271
35.6
276
269
36.6
273
267
37.2

367
249
25.2
354
243
27.8
340
238
30.6
325
231
33.6
308
225
36.6
303
223
37.4
298
219
38

404
198
26.1
389
194
28.8
373
189
31.5
357
183
34.5
338
177
37.5

10,500/0.09
62

67

72

339
317
24.4
327
309
27.1
314
303
29.8
301
295
32.8
287
286
36.0
282
281
36.8
280
280
37.5

373
264
25.4
360
258
28.0
345
253
30.8
330
246
33.7
313
239
36.8
306
237
37.6
299
232
38.4

411
210
26.4
396
203
29.0
380
197
31.8
363
191
34.8
342
184
37.8

50TJ0032 (30 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
Kw
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120

62
343
321
24.7
332
313
27.3
320
305
30.1
307
294
33.1
294
282
36.2
289
277
37.2

Evaporator Air Quantity Cfm/BF


11,500/0.1
12,500/0.11
Evaporator Air Ewb (F)
67
72
62
67
376
281
25.5
365
272
28.2
350
266
30.9
333
259
33.9
316
253
36.9
309
250
37.8

416
218
26.6
402
211
29.2
385
205
32.0
367
200
35.0

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
4.
5.

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

16

351
351
24.9
340
340
27.6
449
448
30.4
316
316
33.4
302
302
36.6
297
297
37.4

72

382
420
297
233
25.8
26.7
370
406
289
223
28.4
29.4
354
390
282
217
31.2
32.2
338
370
275
211
34.0
35.1
320

268

37.2

hIdb = hedb -

6.

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80).

Performance data (60 Hz)

24
29
35
41
46
49
52

TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

50TJ016 (51 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49
52

TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

2124/0.10
14

17

19

22

48.0
48.0
13.6
46.5
46.5
14.8
45.1
44.8
16.1
43.3
43.0
17.5
41.5
41.5
18.9
41.0
41.0
19.3
40.7
40.7
19.6

51.8
42.7
14
49.7
41.5
15.2
47.7
40.7
16.4
45.4
39.5
17.6
43.3
38.3
19
42.4
38.0
19.4
42.1
37.7
19.6

56.5
36.3
14.4
54.4
35.1
15.6
52.1
34.2
16.9
49.7
33.4
18.2
47.4
32.5
19.5
46.5
32.2
19.9
45.9
31.9
20.2

62.0
29.3
15
59.7
28.7
16.1
57.1
27.5
17.4
54.4
26.6
18.7
51.5
25.7
20
50.6
25.5
20.4
50.0
25.2
20.6

50.0
50.0
13.9
48.6
48.6
15.1
46.8
46.8
16.3
45.1
45.1
17.7
43.3
43.3
19.1
42.7
42.7
19.5
42.1
42.1
19.8

53.0
45.9
14.2
50.9
44.5
15.3
48.9
43.3
16.6
46.5
42.1
17.8
44.2
41.0
19.1
43.3
40.7
19.5
43.0
40.7
19.8

57.6
38.6
14.6
55.6
37.7
15.8
53.3
36.9
17
50.9
35.7
18.3
48.3
34.5
19.7
47.4
34.2
20
46.8
33.9
20.2

63.2
30.7
15.1
60.9
29.8
16.3
58.5
29.3
17.6
55.6
28.1
18.8
52.7
27.2
20.2
51.8
26.9
20.6

Evaporator Air Quantity L/s/BF


3186/0.15
3540/0.16
Evaporator Air Ewb (C)
17
19
22
14
17
19

14
53.5
53.5
14.3
52.1
52.1
15.5
50.0
50.0
16.7
48.0
48.0
18.1
45.9
45.9
19.4
45.1
45.1
19.8
44.8
44.8
20

Evaporator Air Quantity L/s/BF


2478/0.12
Evaporator Air Ewb (C)
14
17
19
22

55.0
51.5
14.4
53.0
50.3
15.6
50.6
49.2
16.8
48.3
47.7
18.1
45.9
45.6
19.4
45.1
45.1
19.8
44.8
44.8
20

59.7
43.0
14.9
57.6
42.1
16.1
55.3
41.3
17.3
52.4
40.1
18.5
49.4
38.9
19.9
48.6
38.3
20.2
48.0
38.0
20.4

65.5
33.9
15.4
63.2
32.8
16.6
60.3
31.9
17.8
57.3
30.7
19.1
54.1
29.8
20.4
53.3
29.3
20.8

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

55.0
55.0
14.4
53.3
53.3
15.6
51.2
51.2
16.9
49.2
49.2
18.2
47.1
47.1
19.5
46.2
46.2
19.9
45.6
45.6
20.2

50TJ

COOLING CAPACITIES SI
50TJ016 (51 kW)
Temp (C)
Air Entering
Condenser
(Edb)

2832/0.14
14

17

19

22

52.1
52.1
14.1
50.3
50.3
15.3
48.6
48.6
16.6
46.8
46.8
17.9
44.8
44.8
19.3
44.2
44.2
19.7
43.6
43.6
20

53.8
49.4
14.3
52.1
47.7
15.5
49.7
46.2
16.7
47.4
45.4
17.9
44.8
43.9
19.2
44.2
43.3
19.6
43.6
43.0
19.9

59.1
41.0
14.7
56.8
40.1
15.9
54.4
38.9
17.2
51.8
38.0
18.5
48.9
36.9
19.8
48.0
36.6
20.2
47.4
36.3
20.4

64.4
32.5
15.2
62.0
31.3
16.5
59.7
30.4
17.7
56.5
29.6
18.9
53.5
28.4
20.2
52.4
28.1
20.6

22

55.7
60.3
66.1
54.1
45.9
35.1
14.5
14.9
15.4
53.5
58.2
63.8
52.7
44.2
34.2
15.7
16.1
16.7
51.2
55.6
60.9
51.2
43.0
33.1
16.9
17.4
17.9
49.2
53.0
57.6
49.2
41.8
31.9
18.2
18.6
19.1
46.8
50.0
54.7
46.8
41.0
31.0
19.5
19.9
20.4
46.2
49.2
53.5
46.2
40.4
30.7
19.9
20.4
20.8
45.6
48.6

45.6
40.1

20.2
20.6

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

17

Performance data (60 Hz)


50TJ

COOLING CAPACITIES SI (cont)


50TJ020 (61 kW)
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49
52

TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
kW
TC
SHC
KW
TC
SHC
kW
TC
SHC
kW

50TJ020 (61 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2548/0.95
17

19

22

55.9
48.3
14.3
53.8
47.1
15.2
52.8
47.4
15.6
51.7
47.4
17.8
50.1
47.0
19.6
48.0
45.3
20.3
44.9
42.6
21.3

61.7
40.4
14.9
59.1
39.5
15.6
58.3
39.6
16.0
56.8
39.4
18.2
55.1
39.2
20.1
52.9
37.8
20.8
49.5
35.6
21.9

67.6
32.5
14.2
65.5
31.6
16.2
64.2
31.5
16.7
62.7
31.3
18.8
60.8
31.0
20.7
58.4
29.8
21.5
55.2
28.2
22.4

17
59.1
58.2
14.8
56.8
56.8
15.6
56.1
56.1
16.0
55.3
55.0
18.2
53.8
53.8
20.2
51.7
51.7
20.9

Evaporator Air Quantity L/s/BF


2832/0.105
Evaporator Air Ewb (C)
17
19
22
56.8
50.6
14.4
54.7
49.7
15.3
53.8
49.9
15.6
52.5
49.8
17.8
50.7
49.1
19.8
48.7
47.4
20.4
45.7
44.9
21.5

Evaporator Air Quantity L/s/BF


3776/0.140
4248/0.150
Evaporator Air Ewb (C)
19
22
17
19
64.7
48.6
15.3
62.3
47.4
16.1
60.9
47.7
16.5
59.3
47.4
18.6
57.0
47.3
20.5
54.8
45.7
21.1

71.1
37.5
15.9
68.5
36.6
16.7
67.2
36.3
17.0
65.4
36.2
19.3
62.6
35.7
21.1

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

18

62.3
42.4
15.0
60.3
41.5
15.8
58.8
41.5
16.2
57.4
41.5
18.3
55.4
41.0
20.3
53.2
39.5
20.9
49.8
37.3
21.9

60.3
60.3
14.9
58.2
58.2
15.7
57.7
57.7
16.2
56.5
56.5
18.4
55.1
55.1
20.3
52.9
52.9
21.1

68.8
33.6
15.6
66.1
32.8
16.4
65.2
32.7
16.7
63.6
32.6
19.0
61.3
31.9
20.9
59.1
30.8
21.5
55.9
29.2
22.3

3304/0.120
17

19

22

57.9
54.7
14.6
55.9
53.5
15.5
54.9
53.5
15.8
53.4
53.4
18.0
52.3
52.3
20.0
50.2
50.2
20.7
47.2
46.9
21.7

63.8
45.4
15.1
61.2
44.5
15.9
60.0
44.7
16.3
58.7
44.5
18.5
56.4
44.2
20.4
54.2
42.6
21.1
50.7
40.3
22.2

69.9
35.4
15.7
67.6
34.8
16.5
66.7
34.5
16.9
64.3
34.4
19.1
62.0
33.8
21.0
59.6
32.6
21.7
56.3
30.8
22.6

22

65.2
71.7
51.2
38.9
15.4
16.0
62.9
69.3
50.3
38.3
16.2
16.8
61.6
67.8
50.5
38.5
16.6
17.1
59.6
66.0
50.4
38.1
18.7
19.3
57.2
63.6
50.1
37.6
20.5
21.2
55.1

48.4

21.3

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

Performance data (60 Hz)

24
29
35
41
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2832/0.075
14

17

19

22

61.2
61.2
15.7
59.4
59.4
17
57.6
57.6
18.5
55.6
55.6
20.1
53.5
53.5
21.7
51.2
51.2
23.2
48.9
48.9
24.7

65.0
55.6
16
62.6
54.4
17.3
60.6
53.3
18.7
57.6
52.1
20.1
55.0
50.6
21.7
52.1
49.2
23.2
49.2
47.8
24.7

72.0
46.8
16.6
69.3
45.9
17.9
66.7
44.8
19.3
63.8
43.6
20.6
60.6
42.4
22.1
57.3
41.3
23.7
54.0
40.2
25.3

79.0
38.0
17.2
76.4
36.9
18.5
73.7
36.0
19.8
70.5
34.8
21.3
66.7
34.2
22.8
63.5
32.5
24.3
60.3
30.8
25.8

Evaporator Air Quantity L/s/BF


3304/0.085
Evaporator Air Ewb (C)
14
17
19
22
64.1
64.1
15.9
62.0
62.0
17.3
60.3
60.3
18.8
57.9
57.9
20.2
55.9
55.9
21.9
53.3
53.3
23.4
50.4
50.4
24.9

66.7
60.0
16.2
64.4
58.8
17.5
61.7
57.3
18.9
59.1
56.2
20.2
56.2
54.7
21.9
53.3
53.0
23.4
50.4
51.3
24.9

73.4
50.0
16.8
70.8
49.2
18.1
68.2
48.0
19.4
65.0
46.8
20.8
61.7
45.6
22.3
58.5
44.5
23.8
55.3
43.4
25.3

81.1
39.8
17.4
78.1
38.9
18.7
75.2
38.0
20.1
72.0
36.9
21.5
68.2
35.7
22.9
64.7
34.2
24.4
61.2
32.7
25.9

50TJ

COOLING CAPACITIES SI (cont)


50TJ024 (68 kW)
Temp (C)
Air Entering
Condenser
(Edb)

3776/0.100
14

17

19

22

66.4
66.4
16.2
64.4
64.4
17.5
62.3
62.3
19
60.3
60.3
20.5
57.6
57.6
22
55.0
55.0
23.6
52.4
52.4
25.2

67.6
64.1
16.3
65.5
62.9
17.6
62.9
61.4
19
60.0
59.7
20.4
57.6
57.6
22
55.0
55.0
23.6
52.4
52.4
25.2

74.9
53.3
16.9
72.0
52.4
18.2
69.3
51.2
19.6
66.1
50.0
21
62.9
48.6
22.4
59.1
47.4
23.9
55.3
46.2
25.4

82.5
41.8
17.6
79.6
41.0
18.9
76.4
39.8
20.2
73.2
38.9
21.7
69.3
37.5
23.1
65.5
36.6
24.6
61.7
35.7
26.1

50TJ024 (68 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

14
68.5
68.5
16.4
66.4
66.4
17.7
64.4
64.4
19.2
62.0
62.0
20.7
59.4
59.4
22.2
56.8
56.8
23.8

Evaporator Air Quantity L/s/BF


4248/0.110
4720/0.120
Evaporator Air Ewb (C)
17
19
22
14
17
19
68.8
67.6
16.5
66.4
66.1
17.8
64.4
64.1
19.2
62.0
61.7
20.7
59.4
59.4
22.2
56.8
56.8
23.8

75.8
56.5
17.1
73.2
55.3
18.4
69.9
54.1
19.8
66.7
53.0
21.1
63.5
51.8
22.6
59.7
50.3
24.1

83.7
43.6
17.7
80.8
43.0
19
77.5
41.8
20.4
74.3
40.7
21.8
70.2
39.5
23.2
66.1
38.0
24.7

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

70.2
70.2
16.6
68.2
68.2
17.9
65.8
65.8
19.4
63.2
63.2
20.9
60.6
60.6
22.4
57.9
57.9
3.9

22

70.2
76.7
84.6
70.2
59.4
45.6
16.7
17.2
17.8
68.2
73.7
81.6
68.2
58.5
44.8
18
18.5
19.2
65.8
70.5
78.1
65.8
57.1
43.6
19.4
19.8
20.5
63.2
67.3
74.6
63.2
55.9
42.4
20.9
21.3
21.9
60.6
63.8
70.8
60.6
54.4
41.3
22.4
22.6
23.3
57.9
60.3
66.4
57.9
53.0
40.1
3.9
24.2
24.8
cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

19

Performance data (60 Hz)


50TJ

COOLING CAPACITIES SI (cont)


50TJ028 (85 kW)
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

50TJ028 (85 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3304/0.05
14

17

19

22

74.9
74.6
19.1
72.6
72.6
21.0
70.8
70.8
23.0
68.5
68.5
25.1
66.1
66.1
27.4
64.7
64.7
28.7
63.8
63.8
29.6

79.3
67.9
19.5
76.7
66.4
21.4
73.7
65.2
23.3
70.5
63.8
25.3
67.6
62.0
27.4
65.5
61.2
28.7
64.1
60.7
29.6

87.2
57.1
20.4
84.0
55.9
22.2
81.1
54.7
24.1
77.8
53.3
26.1
74.3
52.1
28.3
72.0
51.2
29.6
70.5
50.6
30.5

96.0
46.2
21.2
92.8
45.4
23.1
89.5
43.9
25.1
85.7
42.7
27.0
81.6
41.3
29.1
80.4
40.9
29.7
79.6
40.6
30.2

14
82.8
82.8
20.0
80.5
80.5
22.0
78.1
78.1
24.0
75.2
75.2
26.1
72.3
72.3
28.2
70.2
70.2
29.5

Evaporator Air Quantity L/s/BF


3776/0.06
Evaporator Air Ewb (C)
14
17
19
22
77.8
77.8
19.5
75.8
75.8
21.4
73.4
73.4
23.4
71.1
71.1
25.5
68.8
68.8
27.7
67.0
67.0
29.0
65.6
65.6
29.9

89.0
60.9
20.6
86.0
59.4
22.4
82.8
58.2
24.4
79.6
57.1
26.4
75.8
55.3
28.5
73.4
54.4
29.8
71.8
53.8
30.7

97.7
48.9
21.4
94.8
47.4
23.3
91.3
46.2
25.3
87.5
44.8
27.4
83.1
43.3
29.3
81.8
42.9
29.9
80.9
42.6
30.3

Evaporator Air Quantity Cfm/BF


4720/0.08
5310/0.09
Evaporator Air Ewb (C)
17
19
22
14
17
19
83.7
81.6
20.2
81.3
79.3
22.0
78.1
77.0
24.0
75.2
74.6
26.1
72.3
72.3
28.2
70.2
70.2
29.5

91.3
68.8
20.9
88.7
66.1
22.8
85.1
65.0
24.7
81.6
63.5
26.7
77.2
61.7
28.8
74.9
60.9
30.1

100.1
53.8
21.8
97.7
51.8
23.7
93.9
50.3
25.7
89.8
48.9
27.7
85.1
47.4
29.7

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

20

81.1
73.2
19.7
78.1
71.4
21.6
75.5
70.2
23.6
72.3
68.2
25.6
69.1
66.7
27.7
67.0
65.2
29.0
65.6
64.2
29.9

85.4
85.4
20.3
82.8
82.8
22.3
80.2
80.2
24.3
77.2
77.2
26.3
74.0
74.0
28.4
72.0
72.0
29.4

4248/0.07
14

17

19

22

80.5
80.5
19.8
78.4
78.4
21.7
76.1
76.1
23.7
73.4
73.4
25.8
70.5
70.5
27.9
68.8
68.8
29.2
67.7
67.7
30.1

82.2
77.5
19.9
79.6
75.8
21.8
76.4
74.3
23.8
73.7
72.0
25.8
70.5
69.6
27.9
68.8
68.2
29.2
67.7
67.3
30.1

90.1
65.2
20.7
87.2
63.2
20.6
84.3
61.4
24.5
80.5
60.0
26.5
76.4
58.8
28.6
74.0
57.6
29.9
72.4
56.8
30.8

99.2
51.8
21.6
96.6
49.7
23.5
92.8
48.3
25.5
88.4
47.1
27.5
84.3
45.6
29.5
83.1
45.2
30.1
82.3
44.9
30.5

22

85.7
92.5
101.2
85.1
72.9
57.6
20.4
21.0
21.9
83.1
89.5
98.6
82.8
71.1
55.3
22.3
22.9
23.9
80.2
86.0
95.4
80.2
69.1
53.0
24.3
24.9
25.8
77.2
82.5
91.0
77.2
67.3
51.2
26.3
26.9
27.9
74.0
78.1
86.0
74.0
65.8
49.7
28.4
29.0
29.9
72.0
75.5

72.0
64.7

29.4
30.2

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s
Where hewb is enthalpy of air entering evaporator coil (kJ/kg)

Performance data (60 Hz)


COOLING CAPACITIES SI (cont)
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4011/0.07
17

19

22

95.3
77.9
24.1
91.9
76.5
26.6
88.4
74.8
29.5
84.6
72.8
32.4
80.5
71.2
35.4
79.3
70.6
36.4
78.2
70.0
37.0

105.1
68.6
25.0
101.4
67.1
27.6
97.4
65.5
30.4
93.4
64.0
33.4
88.8
62.2
36.4
87.2
61.6
37.3
85.6
60.5
38

115.8
55.8
25.9
111.7
54.0
28.6
107.3
52.8
31.3
102.5
51.1
34.3
97.4
49.2
37.3

Evaporator Air Quantity L/s/BF


4483/0.08
Evaporator Air Ewb (C)
17
19
22
97.4
87.1
24.4
94.0
85.4
26.9
90.2
83.6
29.6
86.3
81.6
32.6
82.1
79.4
35.6
80.9
78.7
36.6
79.9
78.2
37.2

107.5
72.8
25.2
103.7
71.3
27.8
99.6
69.7
30.6
95.0
67.8
33.6
90.4
66.0
36.6
88.7
65.4
37.4
87.0
64.1
38.0

118.3
58.1
26.2
114.0
56.9
28.8
109.3
55.2
31.6
104.6
53.6
34.6
99.0
51.7
37.6

50TJ

50TJ032 (105 kW)


4955/0.09
17

19

22

99.2
93.0
24.5
95.8
90.7
27.1
92.0
88.9
29.9
88.2
86.4
32.9
84.0
83.8
36.0
82.7
82.6
36.8
82.2
82.1
37.6

109.2
77.3
25.4
105.6
75.5
28.1
101.0
74.2
30.8
96.5
72.1
33.7
91.7
70.1
36.8
89.8
69.4
37.7
88.0
67.9
38.5

120.4
61.4
26.4
115.9
59.3
29.0
111.2
57.7
31.8
106.3
55.9
34.8
100.3
53.9
37.8

50TJ032 (105 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

17
100.7
94.0
24.7
97.2
91.7
27.4
93.7
89.4
30.1
90.0
86.3
33.1
86.3
82.6
36.2
84.7
81.1
37.2

Evaporator Air Quantity L/s/BF


5426/0.10
5899/0.11
Evaporator Air Ewb (C)
19
22
17
19
110.3
82.4
25.6
106.9
79.7
28.2
102.6
77.8
31.0
97.7
76.0
34.0
92.8
74.0
37.0
90.6
73.3
37.8

121.9
64.0
26.6
117.7
61.9
29.3
112.8
60.1
32.0
104.3
58.6
35.0

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of
cooling capacities as follows:

102.8
102.7
25.0
99.7
99.6
27.6
96.4
96.2
30.5
92.6
92.5
33.5
88.6
88.6
36.6
86.9
86.9
37.4

22

112.1
123.1
87.1
68.3
25.8
26.8
108.5
118.9
84.6
65.4
28.4
29.4
103.9
114.2
82.7
63.6
31.2
32.3
99.0
108.5
80.6
61.9
34.1
35.2
93.8

78.5

37.2

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s
Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

21

Performance Data (50 Hz)


COOLING CAPACITIES ENGLISH

50TJ

50TJ016 (15 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

4500/0.10
62

67

72

167
142
11.3
162
139
12.7
157
137
14.1
148
130
15.7
139
125
17.4
133
121
18.4
127
117
19.3

182
121
11.7
177
118
13
171
115
14.5
162
111
16.2
152
106
17.9
145
102
18.9
138
99
19.7

200
98
13.3
193
96
14.7
188
94
16.3
177
89
18.1
166
85
18.4
159
82
19.4
151
81
20.3

Evaporator Air Quantity Cfm/BF


5250/0.12
Evaporator Air Ewb (F)
62
67
72
172
154
11.5
167
150
12.8
162
147
14.3
153
140
15.9
143
135
17.6
136
131
18.5
130
126
19.4

188
129
1.9
182
126
13.2
176
124
14.6
166
119
16.3
155
113
18
148
110
19
141
106
19.9

206
104
13.4
198
101
14.9
193
99
16.5
180
94
18.3
170
90
18.6
163
86
19.6

6000/0.14
62

67

72

177
162
11.6
171
159
12.6
165
157
14.4
156
150
16
146
144
17.7
140
139
18.7
134
134
19.6

193
137
12
186
134
13.3
180
131
14.7
169
126
16.4
158
121
18.1
151
117
19.1
144
113
20.1

209
109
13.5
204
107
15
197
103
16.6
184
99
18.4
173
94
18.7
165
91
19.8

50TJ016 (15 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

62
180
171
11.7
175
168
13
169
166
14.5
159
158
16.1
150
150
17.9
143
144
18.8
137
138
19.7

Evaporator Air Quantity Cfm/BF


6750/0.15
7500/0.16
Evaporator Air Ewb (F)
67
72
62
67
195
147
12
189
141
13.4
182
139
14.9
172
133
16.5
161
127
18.3
154
124
19.2
146
119
20.1

211
118
13.6
206
113
15.1
200
108
16.7
188
103
18.5
174
98
18.7
166
95
19.8

184
180
11.7
178
176
13.1
172
172
14.6
163
163
16.2
153
154
18
147
148
18.9
140
142
19.9

197
154
12.1
191
151
13.5
186
146
15
174
140
16.6
163
134
18.3
155
129
19.3
148
125
20.1

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
1.
2.

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

22

72

213
125
13.6
209
116
15.2
202
113
16.8
189
107
18.6
177
104
18.8
169
101
19.8

hIdb = hedb -

3.

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80)

Performance Data (50 Hz)

TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

75
85
95
105
115
120
125

50TJ020 (18 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
KW

75
85
95
105
115
120

Evaporator Air Quantity Cfm/BF


6000/0.105
Evaporator Air Ewb (F)
62
67
72

5400/0.095
62

67

72

191
165
14.3
184
161
15.2
181
162
15.6
176
162
17.8
171
161
19.6
164
155
20.3
153
146
21.3

211
138
14.9
202
135
15.6
199
135
16.0
194
134
18.2
188
134
20.1
181
129
20.8
169
122
21.9

231
111
14.2
224
108
16.2
220
108
16.7
214
107
18.8
208
106
20.7
200
102
21.5
189
96
22.4

194
173
14.4
187
170
15.3
184
170
15.6
180
170
17.8
173
168
19.8
166
162
20.4
156
153
21.5

213
145
15.0
206
142
15.8
201
142
16.2
196
142
18.3
189
140
20.3
182
135
20.9
170
128
21.9

7000/0.120
62

67

72

198
187
14.6
191
183
15.5
188
183
15.8
183
183
18.0
179
179
20.0
172
172
20.7
161
160
21.7

218
155
15.1
209
152
15.9
205
153
16.3
201
152
18.5
193
151
20.4
185
146
21.1
173
138
22.2

239
121
15.7
231
119
16.5
228
118
16.9
219
118
19.1
212
116
21.0
204
111
21.7
193
105
22.6

Evaporator Air Quantity Cfm/BF


8000/0.140
Evaporator Air Ewb (F)
62
67
72
202
199
14.8
194
194
15.6
192
192
16.0
189
188
18.2
184
184
20.2
177
177
20.9

221
166
15.3
213
162
16.1
208
163
16.5
203
162
18.6
195
162
20.5
187
156
21.1

243
128
15.9
234
125
16.7
230
124
17.0
224
124
19.3
214
122
21.1

LEGEND

hIdb = hedb -

BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
1.
2.

235
115
15.6
226
112
16.4
223
112
16.7
217
111
19.0
210
109
20.9
202
105
21.5
191
99
22.3

50TJ

COOLING CAPACITIES ENGLISH (cont)


50TJ020 (18 TONS)
Temp (F)
Air Entering
Condenser
(Edb)

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

3.

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80)

23

Performance Data (50 Hz)


COOLING CAPACITIES ENGLISH (cont)

50TJ

50TJ024 (20 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000/0.075
62

67

72

220
188
15.1
212
185
16.7
204
181
18.5
195
176
20.3
185
172
22.1
175
166
24.0

242
159
1.6
234
155
17.2
225
152
19.0
215
148
20.8
205
143
22.7
193
139
24.6

263
126
16.5
254
123
18.2
244
199
20.1
234
116
22.0
223
112
23.9

Evaporator Air Quantity Cfm/BF


7,000/0.085
Evaporator Air Ewb (F)
62
67
72
225
203
15.2
217
199
16.9
209
195
18.7
200
190
20.5
190
185
22.3
180
179
24.2

248
170
15.8
240
167
17.4
230
163
19.2
220
159
21.0
209
155
22.8
197
150
24.7

269
133
16.7
260
130
18.5
250
126
20.3
239
123
22.0
227
119
24.1

8,000/0.100
62

67

72

229
217
15.4
221
213
17.0
213
208
18.8
204
203
20.6
195
194
22.5
185
185
24.4

253
181
15.9
244
177
17.0
234
173
19.3
223
169
21.1
212
165
23.0
200
160
24.9

274
139
16.9
265
136
18.6
254
133
20.4
243
129
22.3
231
125
24.2

50TJ024 (20 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

62

Evaporator Air Quantity Cfm/BF


9,000/0.110
10,000/0.120
Evaporator Air Ewb (F)
67
72
62
67

233
230
15.5
225
224
17.2
218
217
19.0
210
209
20.8
200
200
22.7
191
190
24.6

256
191
16.0
246
187
17.7
237
183
19.4
226
180
21.2
214
174
23.1
201
169
25.0

278
146
17.0
268
142
18.7
257
139
20.5
246
135
22.4
233
131
24.3

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
1.
2.

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

24

238
238
15.7
231
231
17.4
223
222
19.1
214
214
21.0
205
204
22.9
195
194
24.8

72

259
281
202
152
16.1
17.1
250
271
198
149
17.8
18.8
239
260
193
145
19.5
20.6
228
248
189
141
21.3
22.6
216
235
183
137
23.2
24.4
203

178

25.0

hIdb = hedb -

3.

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
Under 75
81
82
83
84
85
Over 85
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80)

Performance Data (50 Hz)


COOLING CAPACITIES ENGLISH (cont)
Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
120
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,000/0.05
62

67

72

271
231
20.1
262
227
22.2
252
222
24.6
241
216
27.0
229
211
29.5
226
210
30.3
223
208
30.8

299
195
20.8
289
191
23.0
277
186
25.3
266
182
27.8
252
177
30.3
248
175
31.1
244
172
31.9

330
159
21.6
318
154
23.8
305
150
26.1
291
145
28.6
277
140
31.1

Evaporator Air Quantity Cfm/BF


8,000/0.06
Evaporator Air Ewb (F)
62
67
72
277
248
20.3
267
243
22.4
257
238
24.7
246
232
27.2
234
226
29.7
230
224
30.5
227
223
31.0

306
207
21.0
295
203
23.2
283
198
25.5
271
193
28.0
257
188
30.5
252
186
31.2
247
184
32.0

337
165
21.8
324
162
24.0
311
157
26.3
298
153
28.8
282
147
31.3

50TJ

50TJ028 (25 TONS)


9,000/0.07
62

67

72

282
264
20.4
273
258
22.6
262
253
24.9
251
246
27.4
239
238
30.0
235
235
30.7
234
233
31.3

311
220
21.2
300
215
23.4
287
211
25.7
275
205
28.1
261
199
30.7
255
197
31.4
250
193
32.2

342
175
22.0
330
169
24.2
317
164
26.5
302
159
29.0
285
153
31.5

50TJ028 (25 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
120

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

62

Evaporator Air Quantity Cfm/BF


10,000/0.08
11,250/0.09
Evaporator Air Ewb (F)
67
72
62
67

286
279
20.6
277
272
22.8
266
265
25.1
256
256
27.6
245
245
30.2
241
241
31.0

314
235
21.3
304
227
23.5
292
221
25.8
277
216
28.3
264
211
30.8
258
209
31.5

347
182
22.2
335
176
24.4
321
171
26.7
306
167
29.2

293
292
20.8
284
283
23.0
374
374
25.4
263
263
27.9
252
252
30.5
247
247
31.2

319
248
21.5
308
241
23.7
295
235
26.0
281
230
28.4
267
223
31.0

hIdb = hedb -

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
1.
2.

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

Sensible capacity (Btuh)


1.10 x cfm
TIwb = Wet-bulb temperature corresponding to enthalpy of
air leaving evaporator coil.
tIdb = tedb -

3.

72
350
194
22.3
338
186
24.5
325
181
26.9
309
176
29.3

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80)

25

Performance Data (50 Hz)


COOLING CAPACITIES ENGLISH (cont)

50TJ

50TJ0032 (30 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120
125

8,500/0.07
62

67

72

325
266
20.2
314
261
22.3
298
251
24.8
275
236
27.5
250
221
30.4
247
219
31.2
243
217
31.7

359
234
20.9
346
229
23.2
328
221
25.5
303
207
28.3
276
193
31.2
271
191
32.1
268
190
32.7

395
191
21.8
381
184
23.9
361
177
26.3
333
165
29.2
303
153
32.1
298
151
32.9
295
150
33.4

Evaporator Air Quantity Cfm/BF


9,500/0.08
Evaporator Air Ewb (F)
62
67
72
333
297
20.4
321
292
22.5
304
281
24.9
280
264
27.7
255
247
30.6
251
245
31.5
248
243
32.0

367
249
21.2
354
243
23.4
335
235
25.7
309
219
28.6
280
205
31.5
276
203
32.2
273
202
32.6

404
198
21.9
389
194
24.2
368
186
26.5
339
174
29.3
308
161
32.3
302
159
33.0

10,500/0.09
62

67

72

339
317
20.5
327
309
22.8
310
299
25.0
286
280
27.9
261
260
31.0
257
256
31.6
255
255
32.3

373
264
21.3
360
258
23.5
340
249
25.9
314
234
28.6
285
217
31.6
278
216
32.3
274
214
32.8

411
210
22.2
396
203
24.4
375
194
26.7
345
181
29.6
311
167
32.5
305
166
33.3

50TJ0032 (30 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
Kw
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75
85
95
105
115
120

Evaporator Air Quantity Cfm/BF


11,500/0.1
Evaporator Air Ewb (F)
62
67
72
343
321
20.7
332
313
22.9
316
301
25.3
292
279
28.1
268
257
31.1
263
252
32.0

376
281
21.4
365
272
23.7
345
262
26.0
316
246
28.8
288
230
31.7
281
228
32.5

LEGEND
BF Bypass factor
Edb Entering Dry-Bulb
Ewd Entering Wet-Bulb
KW Compressor Motor Power Input
Idb Leaving Dry-Bulb
Iwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Rtuh) Gross
TC Total Capacity (1000 Btuh) Gross
NOTES:
4.
5.

Direct interpolation is permissible. Do not extrapolate.


the following formulas may be used:

tIdb = tedb -

Sensible capacity (Btuh)


1.10 x cfm

TIwb = Wet-bulb temperature corresponding to enthalpy of


air leaving evaporator coil.

26

416
218
22.3
402
211
24.5
380
202
26.9
349
190
29.8
318
177
32.7

hIdb = hedb -

6.

Total capacity (Btuh)


4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
The SHC is based on 80 F edb temperature of air entering
evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
ENTERING AIR DRY-BULB TEMP (F)
BYPASS
79
78
77
76
75
Under 75
FACTOR
81
82
83
84
85
Over 85
(BF)
Correction factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
.10
.98
1.96
2.94
3.92
4.90
shown
.20
.87
1.74
2.62
3.49
4.36
below.
.30
.76
1.53
2.29
3.05
3.82

Interpolation is permissible.
Correction factor = 1.10 x (1-BF) x (edb 80)

Performance Data (50 Hz)


COOLING CAPACITIES SI
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2124/0.10
17

19

22

49
41.6
11.3
47.6
40.8
12.7
46
40
14.1
43.2
38.2
15.7
40.8
36.5
17.4
39
35.4
18.4
37.2
34.2
19.3

53.3
35.5
11.7
51.7
34.7
13
50.1
33.8
14.5
47.3
32.4
16.2
44.4
31
17.9
42.4
30
18.9
40.5
29
19.7

58.7
82.8
13.3
56.5
28.2
14.7
54.9
27.4
16.3
51.8
26.2
18.1
48.7
24.9
18.4
46.6
24
19.4
44.2
23.8
20.3

Evaporator Air Quantity L/s/BF


2478/0.12
Evaporator Air Ewb (C)
17
19
22
50.3
45.1
11.5
49
44
12.8
47.4
43.1
14.3
44.7
41.2
15.9
41.9
39.5
17.6
40
38.3
18.5
38.1
36.9
19.4

54.9
37.8
11.9
53.3
37.1
13.2
51.5
36.2
14.6
48.5
34.7
16.3
45.5
33.2
18
43.5
32.1
19
41.4
31.1
19.9

60.3
30.6
13.4
58.1
29.7
14.9
56.5
28.9
16.5
52.9
27.6
18.3
49.9
26.3
18.6
47.7
25.3
19.6

50TJ

50TJ016 (51 kW)


2832/0.14
17

19

22

51.8
47.5
11.6
50.2
46.7
12.9
48.5
45.8
14.4
45.7
44
16
42.7
42.2
17.7
40.9
40.7
18.7
39.1
39.2
19.6

56.5
40.1
12
54.4
39.3
13.3
52.6
38.5
14.7
49.5
36.8
16.4
46.4
35.3
18.1
44.3
34.3
19.1
42.2
33.1
20.1

61.3
32
13.5
59.7
31.2
15
57.6
30.3
16.6
53.9
28.9
18.4
50.5
27.6
18.7
48.4
26.7
19.8

50TJ016 (51 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

17
52.8
50.2
11.7
51.2
49.4
13
49.4
48.5
14.5
46.6
46.4
16.1
43.9
44.1
17.9
42
42.3
18.8
40.2
40.5
19.7

Evaporator Air Quantity L/s/BF


3186/0.15
3540/0.16
Evaporator Air Ewb (C)
19
22
17
19
57.1
43.1
12
55.5
41.4
13.4
53.3
40.6
14.9
50.3
38.9
16.5
47.1
37.2
18.3
45
36.3
19.2
42.9
35
20.1

61.9
34.7
13.6
60.3
33.1
15.1
58.7
31.5
16.7
55
30
18.5
51
28.7
18.7
48.8
27.8
19.8

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

53.9
52.7
11.7
52.1
51.7
13.1
50.4
50.4
14.6
47.7
47.9
16.2
44.9
45.2
18
43
43.4
18.9
41.2
41.5
19.9

22

75.6
62.4
45.2
36.6
12.1
13.6
56
61.3
44.2
33.8
13.5
15.2
54.4
59.2
42.8
33
15
16.8
51
55.5
41
31.4
16.6
18.6
47.6
51.9
39.2
30.5
18.3
18.8
45.5
49.6
37.9
29.5
19.3
19.8
43.3

36.6

20.1

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
Sensible capacity (kW) X 1000
CIdb = Cedb 1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

27

Performance Data (50 Hz)


50TJ

COOLING CAPACITIES SI (cont)


50TJ020 (61 kW)
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49
52

TC
SHC
KW
TC
SHC
KW
TC
SHC
KW
TC
SHC
kW
TC
SHC
KW
TC
SHC
kW
TC
SHC
kW

50TJ020 (61 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
41
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2548/0.95
17

19

22

55.9
48.3
14.3
53.8
47.1
15.2
52.8
47.4
15.6
51.7
47.4
17.8
50.1
47.0
19.6
48.0
45.3
20.3
44.9
42.6
21.3

61.7
40.4
14.9
59.1
39.5
15.6
58.3
39.6
16.0
56.8
39.4
18.2
55.1
39.2
20.1
52.9
37.8
20.8
49.5
35.6
21.9

67.6
32.5
14.2
65.5
31.6
16.2
64.2
31.5
16.7
62.7
31.3
18.8
60.8
31.0
20.7
58.4
29.8
21.5
55.2
28.2
22.4

Evaporator Air Quantity L/s/BF


2832/0.105
Evaporator Air Ewb (C)
17
19
22
56.8
50.6
14.4
54.7
49.7
15.3
53.8
49.9
15.6
52.5
49.8
17.8
50.7
49.1
19.8
48.7
47.4
20.4
45.7
44.9
21.5

68.8
33.6
15.6
66.1
32.8
16.4
65.2
32.7
16.7
63.6
32.6
19.0
61.3
31.9
20.9
59.1
30.8
21.5

17

19

22

57.9
54.7
14.6
55.9
53.5
15.5
54.9
53.5
15.8
53.4
53.4
18.0
52.3
52.3
20.0
50.2
50.2
20.7
47.2
46.9
21.7

63.8
45.4
15.1
61.2
44.5
15.9
60.0
44.7
16.3
58.7
44.5
18.5
56.4
44.2
20.4
54.2
42.6
21.1
50.7
40.3
22.2

69.9
35.4
15.7
67.6
34.8
16.5
66.7
34.5
16.9
64.3
34.4
19.1
62.0
33.8
21.0
59.6
32.6
21.7

Evaporator Air Quantity L/s/BF


3776/0.140
Evaporator Air Ewb (C)
17
19
22
59.1
58.2
14.8
56.8
56.8
15.6
56.1
56.1
16.0
55.3
55.0
18.2
53.8
53.8
20.2
51.7
51.7
20.9

64.7
48.6
15.3
62.3
47.4
16.1
60.9
47.7
16.5
59.3
47.4
18.6
57.0
47.3
20.5
54.8
45.7
21.1

71.1
37.5
15.9
68.5
36.6
16.7
67.2
36.3
17.0
65.4
36.2
19.3
62.6
35.7
21.1

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

28

62.3
42.4
15.0
60.3
41.5
15.8
58.8
41.5
16.2
57.4
41.5
18.3
55.4
41.0
20.3
53.2
39.5
20.9
49.8
37.3
21.9

3304/0.120

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

Performance data (50 Hz)


COOLING CAPACITIES SI (cont)
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2832/0.075
17

19

22

64.3
55.1
15.1
62.1
54.0
16.7
59.8
53.0
18.5
57.0
51.6
20.3
54.2
50.2
22.1
51.2
48.7
24.0

70.9
46.5
15.6
68.5
45.4
17.2
65.9
44.4
19.0
63.0
43.3
20.8
59.9
42.0
22.7
56.6
40.7
24.6

76.9
36.9
16.5
74.3
36.0
18.2
71.6
35.0
20.1
68.5
33.9
22.0
65.2
32.8
23.9

Evaporator Air Quantity L/s/BF


3304/0.085
Evaporator Air Ewb (C)
17
19
22
65.9
59.5
15.2
63.6
58.4
16.9
61.2
57.1
18.7
58.4
55.8
20.5
55.6
54.3
22.3
52.7
52.3
24.2

72.7
49.7
15.8
70.2
48.8
17.4
67.4
47.7
19.2
64.4
46.5
21.0
61.2
45.3
22.8
57.6
43.8
24.7

78.8
38.9
16.7
76.1
38.0
18.5
73.2
37.0
20.3
70.0
35.9
22.2
66.6
34.7
24.1

50TJ

50TJ024 (68 kW)


3776/0.100
17

19

22

67.2
63.6
15.4
64.9
62.4
17.0
62.4
61.0
18.8
59.7
59.3
20.6
57.1
56.9
22.5
54.3
54.2
24.4

74.1
53.0
15.9
71.4
51.9
17.6
68.6
50.7
19.3
65.3
49.4
21.1
62.1
48.3
23.0
58.4
47.0
24.9

80.3
40.8
16.9
77.5
39.9
18.6
74.4
38.9
20.4
71.1
37.7
22.3
67.6
36.5
24.2

50TJ024 (68 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

17
68.4
67.2
15.5
66.0
65.6
17.2
36.8
36.7
19.0
61.4
61.3
20.8
58.7
58.6
22.7
55.9
55.7
24.6

Evaporator Air Quantity L/s/BF


4248/0.110
4720/0.120
Evaporator Air Ewb (C)
19
22
17
19
75.0
56.0
16.0
72.3
54.8
17.7
69.4
53.6
19.4
66.1
52.6
21.2
62.7
15.1
23.1
59.0
49.6
25.0

81.3
42.8
17.0
78.5
41.7
18.7
75.3
40.6
20.5
71.9
39.5
22.4
68.3
38.3
24.3

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

69.7
69.6
15.7
67.8
67.6
17.4
65.3
65.1
19.1
62.8
62.6
21.0
60
59.8
22.9
57.0
56.9
24.8

22

75.8
82.2
59.1
44.5
16.1
17.1
73.1
79.3
57.9
43.5
17.8
18.8
70.0
76.1
56.7
42.4
19.5
20.6
66.7
72.7
55.4
41.3
21.3
22.6
63.2
68.9
53.7
40.0
23.2
24.4
59.4

52.1

25.0

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


hIdb = hedb Total capacity (kW) X 1000
1.20 X L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

29

Performance data (50 Hz)


COOLING CAPACITIES SI (cont)

50TJ

50TJ028 (85 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3304/0.05
17

19

22

79.4
67.7
20.1
76.6
66.5
22.2
73.7
65.0
24.6
70.5
63.3
27.0
67.1
61.9
29.5
66.1
61.4
30.3
65.2
60.9
30.8

87.6
57.2
20.8
84.5
55.9
23.0
81.2
54.6
25.3
77.8
53.3
27.8
74.0
51.8
30.3
72.7
51.3
31.1
71.5
50.4
31.9

96.5
46.5
21.6
93.1
45.0
23.8
89.4
44.0
26.1
85.4
42.6
28.6
81.2
41.0
31.1

Evaporator Air Quantity L/s/BF


3776/0.06
Evaporator Air Ewb (C)
17
19
22
81.2
72.6
20.3
78.3
71.2
22.4
75.2
69.7
24.7
71.9
68.0
27.2
68.4
66.2
29.7
67.4
65.6
30.5
66.6
65.2
31.0

89.6
60.7
21.0
86.4
59.4
23.2
83.0
58.1
25.5
79.2
56.5
28.0
75.3
55.0
30.5
73.9
54.5
31.2
72.4
53.9
32.0

98.6
48.4
21.8
95.0
47.4
24.0
91.1
46.0
26.3
87.2
44.7
28.8
82.5
43.1
31.3

4248/0.07
17

19

22

82.7
77.5
20.4
79.8
75.6
22.6
76.7
74.1
24.9
73.5
72.0
27.4
70.0
69.8
30.0
68.9
68.8
30.7
68.47
68.4
31.3

91.0
64.4
21.2
88.0
62.9
23.4
84.2
61.8
25.7
80.4
60.1
28.1
76.4
58.4
30.7
74.8
57.8
31.4
73.3
56.6
32.2

100.3
51.2
22.0
96.6
49.4
24.2
92.7
48.1
26.5
88.6
46.6
29.0
83.6
44.9
31.5

50TJ028 (85 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

17
83.9
81.7
20.6
81.0
79.7
22.8
78.1
77.7
25.1
75.0
75.0
27.6
71.9
71.8
30.2
70.6
70.5
31.0

Evaporator Air Quantity L/s/BF


4720/0.08
5310/0.09
Evaporator Air Ewb (C)
19
22
17
19
91.9
68.7
21.3
89.1
66.4
23.5
85.5
64.8
25.8
81.4
63.3
28.3
77.3
61.7
30.8
75.5
61.1
31.5

101.6
53.3
22.2
98.1
51.6
24.4
94.0
50.1
26.7
86.9
48.8
29.2

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

30

85.7
85.6
20.8
83.1
83.0
23.0
80.3
80.2
25.4
77.2
77.1
27.9
73.8
73.8
30.5
72.4
72.4
31.2

22

93.4
102.6
72.6
56.9
21.5
22.3
90.4
99.1
70.5
54.5
23.7
24.5
86.6
95.2
68.9
53.0
26.0
26.9
82.5
90.4
67.2
51.6
28.4
29.3
78.2

65.4

31.0

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s
Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

Performance data (50 Hz)


COOLING CAPACITIES SI (cont)
Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
49
52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4011/0.07
17

19

22

95.3
77.9
20.2
91.9
76.5
22.3
87.2
73.8
24.8
80.4
69.2
27.5
73.3
64.8
30.4
72.2
64.2
31.3
71.2
63.7
31.8

105.1
68.6
21.0
101.4
67.1
23.2
96.0
64.6
25.5
88.7
60.8
28.4
80.8
56.6
31.3
79.4
56.1
32.1
78.4
55.7
32.6

115.8
55.8
21.8
111.7
54.0
24.0
105.8
52.1
26.3
97.4
48.5
29.2
88.6
44.8
32.1
87.2
44.3
32.9
86.3
43.9
33.4

Evaporator Air Quantity L/s/BF


4483/0.08
Evaporator Air Ewb (C)
17
19
22
97.4
87.1
20.5
94.0
85.4
22.6
88.9
82.4
24.9
82.0
77.5
27.7
74.7
72.3
30.6
73.6
71.6
31.5
72.7
71.2
32.0

107.5
72.8
21.2
103.7
71.3
23.4
98.2
68.7
25.7
90.3
64.4
28.6
82.3
60.1
31.5
80.7
59.5
32.2
79.7
59.2
32.6

118.3
58.1
22.0
114.0
56.9
24.2
107.8
54.4
26.5
99.4
50.9
29.4
90.1
47.0
32.3
88.6
46.5
33.1
87.5
46.2
33.6

50TJ

50TJ032 (105 kW)


4955/0.09
17

19

22

99.2
93.0
20.6
95.8
90.7
22.8
90.7
87.7
25.1
83.8
82.1
28.0
76.4
76.3
31.0
75.3
75.2
31.6
74.8
74.7
32.3

109.2
77.3
21.3
105.6
75.5
23.6
99.6
73.2
25.9
91.7
68.5
28.6
83.4
63.8
31.6
81.7
63.2
32.4
80.6
62.7
32.9

120.4
61.4
22.2
115.9
59.3
24.4
109.6
56.9
26.7
101.0
53.1
29.6
91.3
49.0
32.5
89.6
48.5
33.3
88.5
48.1
33.8

50TJ032 (105 kW)


Temp (C)
Air Entering
Condenser
(Edb)
24
29
35
40.5
46
49

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Evaporator Air Quantity L/s/BF


5426/0.10
Evaporator Air Ewb (C)
17
19
22
100.7
94.0
20.7
97.2
91.7
23.0
92.4
88.1
25.3
85.5
82.0
28.1
78.5
75.2
31.1
77.1
73.8
32.0

110.3
82.4
21.5
106.9
79.7
23.7
101.2
76.7
26.0
92.8
72.2
28.9
84.4
67.3
31.8
82.4
66.7
32.5

121.9
64.0
22.3
117.7
61.9
24.6
111.2
59.3
26.9
99.1
55.7
29.8

LEGEND

BF Bypass Factor

Edb Entering Dry Bulb Temperature (C)

Ewd Entering Wet Bulb Temperature (C)

KW Compressor Input (kW)

SHC Sensible Heat Capacity (kW)

TC Total Capacity (kW)

NOTES:

1. Ratings are gross, and do not account for the effects of the evaporator-fan
motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At
any other temperature, correct the SHC read from the table of

cooling capacities as follows:

Corrected SHCkW

= SHC + [1.23 x 10 3 x (1 BF) x (Cdb 26.7) x L/s]

Observe the rule of sign. Above 26.7 C, SHC correction will be

positive; add it to SHC. Below 26.7 C, SHC correction will be nega-tive;

subtract it from SHC.

4. Formulas:
CIdb = Cedb Sensible capacity (kW) X 1000
1.23 X L/s

Leaving wet bulb = wet bulb temperature corresponding to

enthalpy of air leaving coil (hlwb).


Total capacity (kW) X 1000
hIdb = hedb 1.20 X L/s
Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

31

Performance data (cont)


50TJ

FAN PERFORMANCE 50TJ016 UNIT ENGLISH


50TJ016
AIR
FLOW
(CFM)
RPM
4800
5100
5400
5700
6000
686
6300
715
6600
745
6900
774
7200
805
7500
836
50TJ016
AIR
FLOW
(CFM)
4800
5100
5400
5700
6000
6300
6600

RPM
840
856
872
890
910
930
951

0.2
Bhp

Watts

RPM

2.2
2.5
2.9
3.3
3.7
4.2

1833
2100
2389
2711
3056
3444

704
732
759
788
815
844
874

1.2
Bhp
2.2
2.5
2.8
3.1
3.4
3.8
4.2

Watts
1822
2044
2278
2533
2822
3133
3467

RPM
889
903
917
934
952

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


0.4
0.6
0.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp
682
1.6
1300
736
1.8
705
1.8
1500
757
2.0
728
2.1
1711
777
2.3
2.1
1767
752
2.3
1944
799
2.6
2.4
2022
778
2.7
2211
823
2.9
2.8
2289
803
3.0
2500
846
3.3
871
3.7
3.1
2600
830
3.4
2811
895
4.1
3.5
2922
856
3.8
3144
883
4.2
3511
921
4.5
4.0
3289
4.1
3368
911
4.7
3911
948
5.0

RPM
789
807
825
845
867
888
911
934
958

1
Bhp
2.0
2.2
2.2
2.8
3.2
3.5
3.9
4.3
4.8

Watts
1644
1856
1856
2333
2611
2911
3244
3600
3978

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


1.4
1.6
Bhp
Watts
RPM
Bhp
Watts
2.4
2011
937
2.7
2200
2.7
2233
949
2.9
2422
3.0
2467
962
3.2
2678
3.3
2744
3.7
3033

LEGEND

Bhp Brake Horsepower.

FIOP Factory-Installed Option.

Watts Input Watts to Motor.

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

32

Watts
1467
1678
1889
2144
2411
2700
3022
3367
3744
4156

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

Performance data (cont)


FAN PERFORMANCE 50TJ020 UNIT ENGLISH
AIR
FLOW
(CFM)

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


0.4
0.6
0.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp
780
2.4
1956
827
2.6
807
2.7
2233
852
2.9

RPM

0.2
Bhp

Watts

791

2.8

2322

835

3.1

2533

878

6100

779

3.0

2444

822

3.2

2644

864

3.4

2856

906

6400

811

3.4

2778

852

3.6

2989

892

3.9

3211

6700

844

3.8

3144

883

4.1

3367

922

4.3

7000
7300

877
872

4.3
4.5

3556
3744

915
946

4.6
5.1

3789
4222

952
982

4.9
5.4

AIR
FLOW
(CFM)

RPM

1.2
Bhp

Watts

RPM

5200
5500

919
940

3.1
3.4

2544
2833

963
983

5800
6100

963
993

3.8
4.0

3167
3322

RPM

5200
5500
5800

Watts
2144
2422

RPM
874
896

1
Bhp
2.8
3.2

Watts
2344
2633

3.3

2733

921

3.6

2944

3.7

3078

947

4.0

3289

932

4.1

3433

972

4.4

3667

3600

960

4.6

3833

998

4.9

4067

4022
4467

989

5.2

4267

50TJ020
AVAILABLE EXTERNAL STATIC PRESSURE(iwg)
1.4
Bhp
Watts
3.3
3.7

2700
3044

LEGEND

Bhp Brake Horsepower

FIOP Factory-Installed Option

Watts Input Watts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

33

50TJ

50TJ020

Performance data (cont)


50TJ

FAN PERFORMANCE 50TJ024 UNIT ENGLISH


50TJ024
AIR
FLOW
(CFM)
6000
6400
6800
7200
7600
8000
8400
8800
9200
9600
10000
50TJ024
AIR
FLOW
(CFM)
6000
6400
6800
7200
7600
8000
8400

RPM

0.2
Bhp

687
712
740

4.4
5.0
5.6

RPM
722
735
750
764
781
799
818

1.2
Bhp
2.6
2.9
3.3
3.6
4.1
4.5
5.0

Watts

3678
4144
4667

Watts
2144
2400
2700
3011
3367
3756
4178

RPM

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


0.4
0.6
0.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp

672
696
722
746
773

3.7
4.2
4.8
5.4
6.0

RPM
767
778
791
804
819
836
853

1.4
Bhp
2.9
3.2
3.6
3.9
4.4
4.9
5.4

Watts

RPM

1
Bhp

Watts

3.0
3.4
3.9
4.4
4.9
5.5
6.1
6.8

2522
2856
3233
3622
4056
4533
5033
5589

691
707
724
742
762
782
801
824
844
867

2.6
3.0
3.3
3.8
4.2
4.7
5.2
5.8
6.4
7.1

2178
2456
2767
3111
3489
3900
4333
4822
5333
5900

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


1.6
1.8
Watts
RPM
Bhp
Watts
RPM
Bhp
852
3.4
2367
810
3.1
2600
860
3.8
2633
819
3.5
2878
831
3.9
3189
870
4.2
2944
842
4.3
3522
880
4.6
3267
856
4.7
3900
893
5.0
3633
4033
872
5.2
4311
907
5.6
4456
887
5.7
4744
921
6.2

Watts
2844
3122
3444
3789
4178
4600
5100

RPM
892
899
908
917
929
942

2
Bhp
3.7
4.1
4.5
4.9
5.4
5.9

Watts
3089
3378
3711
4067
4456
4889

3100
3500
3956
4433
4967

LEGEND

Bhp Brake Horsepower

FIOP Factory-Installed Option

Watts Input Watts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

34

686
709
731
757
779
805

3.6
4.1
4.6
5.1
5.7
6.4

2978
3356
3778
4244
4733
5278

683
703
725
746
767
790
812
836

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

Performance data (cont)

50TJ028
AIR
FLOW
(CFM)
RPM
6500
7000
779
7500
801
8000
825
8500
850
9000
876
9500
903

0.2
Bhp

4.5
5.2
6.0
7.0

1.2
Bhp
3.6
4.2
4.8
5.4
6.2
7.0

Watts

3700
4322
5000
5756

Watts
2989
3444
3944
4511
5133
5822

RPM

741
774
808
842

RPM
801
819
839
861
884
909

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


0.4
0.6
0.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp

4.8
5.6
6.4
7.3

3978
4611
5311
6078

775
807
839
872

5.1
5.9
6.8
7.7

4256
4911
5622
6400

809
839
864
901

5.5
6.3
7.1
8.1

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


1.4
1.6
1.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp
3.4
2822
842
3.7
3078
881
4.0
3.9
3244
858
4.2
3500
896
4.6
4.5
3711
876
4.8
3978
913
5.1
5.1
4222
896
5.4
4511
5.8
4800
918
6.2
5100
6.6
5444

LEGEND

Bhp Brake Horsepower

FIOP Factory-Installed Option

Watts Input Watts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

Watts

4544
5211
5867
6733

Watts
3322
3767
4256

RPM

788
815
843
871
901

RPM
920

1
Bhp

4.4
5.1
5.9
6.7
7.6

2
Bhp
4.3

Watts

3678
4233
4844
5511
6256

Watts
3589

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

35

50TJ

FAN PERFORMANCE 50TJ028 UNIT ENGLISH


50TJ028
AIR
FLOW
(CFM)
RPM
6500
7000
7500
8000
8500
9000
705
9500
741
10000
776
10500
811

Performance data (cont)


50TJ

FAN PERFORMANCE 50TJ032 UNIT ENGLISH


50TJ032
AIR
FLOW
(CFM)
7500
8000
8500
9000
9500
10000
10500
11000
11500
12000
50TJ032
AIR
FLOW
(CFM)
7500
8000
8500
9000
9500
10000
10500
11000
11500

RPM

0.2
Bhp

Watts

834
868
902

8.3
9.4
10.6

7221
8174
9209

RPM

1.2
Bhp

Watts

840
865
892
918
945
974
1002

5.8
6.6
7.4
8.3
9.4
10.5
11.6

5035
5709
6442
7233
8105
9058
10081

RPM

810
829
863
895
928

RPM
830
852
873
897
922
947
972
1000

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


0.4
0.6
0.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp

6.9
7.7
8.8
9.9
11.1

6100
6674
7581
8547
9593

7.2
8.6
9.2
10.3
11.5

6209
7442
7942
8919
9977

6.7
7.6
8.5
9.6
10.7

AVAILABLE EXTERNAL STATIC PRESSURE(iwg)


1.4
1.6
1.8
Bhp
Watts
RPM
Bhp
Watts
RPM
Bhp
4.8
4174
866
5.2
4465
902
5.5
5.5
4744
886
5.8
5047
920
6.2
6.2
5349
905
6.5
5663
938
6.9
7.0
6035
928
7.3
6360
959
7.7
7.8
6779
952
8.2
7128
982
8.6
8.8
7593
976
9.2
7942
1004
9.6
9.8
8465
1000
10.2
8837
1028
10.6
10.9
9442
1027
11.3
9826

LEGEND

Bhp Brake Horsepower

FIOP Factory-Installed Option

Watts Input Watts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor rpm such that motor maximum bhp and/or watts
is exceeded at the maximum operating cfm.
2. Static pressure losses must be added to external static pressure
before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.

36

828
859
891
922
954

830
858
888
919
949

Watts

RPM

1
Bhp

Watts

5779
6547
7384
8314
9302

833
861
888
916
946
976

6.2
7.1
7.9
8.9
10.0
11.2

5384
6116
6884
7733
8686
9686

Watts
4767
5349
5988
6698
7477
7140
9209

RPM
936
953
970
990
1011
1032
1055

2
Bhp
5.9
6.5
7.3
8.1
9.3
10.0
11.1

Watts
5070
5663
6314
7035
8058
7460
9593

4. Fan performance is based on wet coils, clean filters, and casing


losses.
5. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Carrier representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on page
43.
7. Evaporator Motor Efficiency 87%..

Performance data (cont)


FAN PERFORMANCE 50TJ016 UNIT SI
AIR
FLOW
(L/s)

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


100
150
200
BkW
Watts
r/s
BkW
Watts
r/s
BkW
11.4
1.2
1300
12.3
1.3
11.8
1.4
1500
12.6
1.5
12.1
1.5
1711
13.0
1.7

r/s

50
BkW

Watts

r/s

11.7

1.6

1767

12.5

1.8

1944

13.3

2831
2973

11.4
11.9

1.6
1.9

1833
2100

12.2
12.7

1.8
2.1

2022
2289

13.0
13.4

2.0
2.3

2211
2500

13.7
14.1

3115
3256

12.4
12.9

2.2
2.4

2389
2711

13.1
13.6

2.3
2.6

2600
2922

13.8
14.3

2.5
2.8

2811
3144

14.5
14.9

3398

13.4

2.8

3056

14.1

3.0

3289

14.7

3.2

3511

3539

13.9

3.1

3444

14.6

3.0

3368

15.2

3.5

3911

2265
2407

r/s
14.0
14.3

300
BkW
1.6
1.8

Watts
1822
2044

r/s
14.8
15.1

2548
2690
2831
2973
3115

14.5
14.8
15.2
15.5
15.9

2.1
2.3
2.5
2.8
3.1

2278
2533
2822
3133
3467

15.3
15.6
15.9

2265
2407
2548
2690

Watts
1467
1678
1889

r/s
13.2
13.5
13.8

250
BkW
1.5
1.7
1.7

Watts
1644
1856
1856

1.9

2144

14.1

2.1

2333

2.2
2.4

2411
2700

14.5
14.8

2.4
2.6

2611
2911

2.7
3.0

3022
3367

15.2
15.6

2.9
3.2

3244
3600

15.4

3.4

3744

16.0

3.6

3978

15.8

3.7

4156

50TJ016
AIR
FLOW
(L/s)

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


350
400
BkW
Watts
r/s
BkW
Watts
1.8
2011
15.6
2.0
2200
2.0
2233
15.8
2.2
2422
2.2
2.5
2.7

2467
2744
3033

LEGEND

BkW Brake Kilowatts

FIOP Factory-Installed Option

kW Input Kilowatts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor r/s such that motor maximum bkW and/or watts is
exceeded at the maximum operating L/s.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
Brake Kilowatts and watts range of the motor can be utilized with confidence.
Using your fan motors up to the watts or bkW rating shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

37

50TJ

50TJ016

Performance data (cont)


FAN PERFORMANCE 50TJ020 UNIT SI

50TJ

50TJ020
AIR
FLOW
(L/s)

r/s

50
BkW

Watts

r/s

2453
2595
2737

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


100
150
200
BkW
Watts
r/s
BkW
Watts
r/s
BkW
13.0
1.8
1956
13.8
1.9
13.5
2.0
2233
14.2
2.2

Watts
2144
2422

r/s
14.6
14.9

250
BkW
2.1
2.4

Watts
2344
2633

13.2

2.1

2322

13.9

2.3

2533

14.6

2.5

2733

15.4

2.7

2944

2879

13.0

2.2

2444

13.7

2.4

2644

14.4

2.6

2856

15.1

2.8

3078

15.8

3.0

3289

3020

13.5

2.5

2778

14.2

2.7

2989

14.9

2.9

3211

15.5

3.1

3433

3162

14.1

2.8

3144

14.7

3.0

3367

15.4

3.2

3600

3303
3445

14.6
14.5

3.2
3.4

3556
3744

15.3
15.8

3.4
3.8

3789
4222

2453
2595

r/s
15.3
15.7

300
BkW
2.3
2.6

Watts
2544
2833

2737
2879

16.1
16.6

2.9
3.0

3167
3322

50TJ020
AIR
FLOW
(L/s)

r/s
16.1
16.4

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


350
BkW
Watts
2.4
2700
2.7
3044

LEGEND

BkW Brake Kilowatts

FIOP Factory-Installed Option

kW Input Kilowatts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor r/s such that motor maximum bkW and/or watts is
exceeded at the maximum operating L/s.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

38

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
Brake Kilowatts and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bkW rating shown will
not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

Performance data (cont)

50TJ024
AIR
FLOW
(L/s)
2831
3020
3209
3398
3586
3775
3964

r/s

50
BkW

11.5
11.9
12.3

3.3
3.7
4.2

r/s
12.0
12.3
12.5
12.7
13.0
13.3
13.6

300
BkW
1.9
2.2
2.4
2.7
3.0
3.4
3.8

Watts

3678
4144
4667

Watts
2144
2400
2700
3011
3367
3756
4178

r/s

11.2
11.6
12.0
12.4
12.9

r/s
12.8
13.0
13.2
13.4
13.7
13.9
14.2

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


100
150
200
BkW
Watts
r/s
BkW
Watts
r/s
BkW

2.8
3.2
3.6
4.0
4.5

3100
3500
3956
4433
4967

11.4
11.8
12.2
12.6
13.0
13.4

2.7
3.0
3.4
3.8
4.3
4.8

2978
3356
3778
4244
4733
5278

11.4
11.7
12.1
12.4
12.8
13.2
13.5
13.9

2.3
2.6
2.9
3.3
3.7
4.1
4.5
5.0

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


350
400
450
BkW
Watts
r/s
BkW
Watts
r/s
BkW
14.2
2.6
2.1
2367
13.5
2.3
2600
14.3
2.8
2.4
2633
13.7
2.6
2878
13.9
2.9
3189
14.5
3.1
2.7
2944
14.0
3.2
3522
14.7
3.4
2.9
3267
14.3
3.5
3900
14.9
3.8
3.3
3633
3.6
4033
14.5
3.9
4311
15.1
4.1
4.0
4456
14.8
4.3
4744

LEGEND

BkW Brake Kilowatts

FIOP Factory-Installed Option

kW Input Kilowatts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor r/s such that motor maximum bkW and/or watts is
exceeded at the maximum operating L/s.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

Watts

2522
2856
3233
3622
4056
4533
5033
5589

Watts
2844
3122
3444
3789
4178
4600

250
BkW

Watts

11.5
11.8
12.1
12.4
12.7
13.0
13.4
13.7
14.1
14.5

2.0
2.2
2.5
2.8
3.1
3.5
3.9
4.3
4.8
5.3

2178
2456
2767
3111
3489
3900
4333
4822
5333
5900

r/s
14.9
15.0
15.1

500
BkW
2.8
3.0
3.3

Watts
3089
3378
3711

r/s

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
Brake Kilowatts and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bkW rating shown will
not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

39

50TJ

FAN PERFORMANCE 50TJ024 UNIT SI


50TJ024
AIR
FLOW
(L/s)
2831
3020
3209
3398
3586
3775
3964
4153
4341
4530
4719

Performance data (cont)


FAN PERFORMANCE 50TJ028 UNIT SI

50TJ

50TJ028
AIR
FLOW
(L/s)

r/s

50
BkW

Watts

r/s

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


100
150
200
BkW
Watts
r/s
BkW
Watts
r/s
BkW

Watts

r/s

250
BkW

Watts

3067
3303
3539
3775
4011
3.6

3978

12.9

3.8

4256

13.6

3.8

4233

14.1

4.4

4844

4247

11.8

3.3

3700

12.4

4483

12.4

3.9

4322

12.9

4.2

4611

13.5

4.4

4911

14.0

4.7

5211

14.5

5.0

5511

4719

12.9

4.5

5000

13.5

4.8

5311

14.0

5.1

5622

14.4

5.3

5867

15.0

5.6

6256

4955

13.5

5.2

5756

14.0

5.5

6078

14.5

5.8

6400

15.0

6.1

6733

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


350
400
450
BkW
Watts
r/s
BkW
Watts
r/s
BkW
14.0
2.8
3078
14.7
3.0

Watts
3322

r/s
15.3

500
BkW
3.2

Watts
3589

13.5

4.1

4544

50TJ028
AIR
FLOW
(L/s)

r/s

300
BkW

Watts

r/s

3067
3303

14.3

3.2

3500

14.9

3.4

3767

3539

13.4

3.1

3444

14.0

3.3

3711

14.6

3.6

3978

15.2

3.8

4256

3775
4011

13.8
14.2

3.6
4.1

3944
4511

14.4
14.7

3.8
4.3

4222
4800

14.9
15.3

4.1
4.6

4511
5100

4247

14.6

4.6

5133

15.2

4.9

5444

4483

15.1

5.2

5822

LEGEND

BkW Brake Kilowatts

FIOP Factory-Installed Option

kW Input Kilowatts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor r/s such that motor maximum bkW and/or watts is
exceeded at the maximum operating L/s.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

40

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
Brake Kilowatts and watts range of the motor can be utilized with confidence.
Using your fan motors up to the watts or bkW rating shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

Performance data (cont)

50TJ032
AIR
FLOW
(L/s)
3539
3775
4011
4247
4483
4719
4955
5191
5427

50
BkW

6.2
7.0
7.9

Watts

7200
8200
9200

r/s

300
BkW

Watts

14.0
14.4
14.9
15.3
15.8
16.2
16.7

4.3
4.9
5.5
6.2
7.0
7.8
8.7

5000
5700
6400
7200
8100
9100
10100

r/s

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


100
150
200
BkW
Watts
r/s
BkW
Watts
r/s
BkW

6700
7600
8500
9600

13.8
14.3
14.9
15.4
15.9

5.3
6.4
6.8
7.7
8.6

6200
7400
7900
8900
10000

13.8
14.3
14.8
15.3
15.8
16.3

5.0
5.6
6.4
7.2
8.0
8.9

13.8
14.4
14.9
15.5

5.7
6.5
7.4
8.3

r/s
13.8
14.2
14.6
15.0
15.4
15.8
16.2
16.7
17.1

AVAILABLE EXTENTION STATIC PRESSURE(Pa)


350
400
450
BkW
Watts
r/s
BkW
Watts
r/s
BkW
3.6
4200
14.4
3.8
4500 15.0
4.1
4.1
4700
14.8
4.3
5000 15.3
4.6
4.6
5300
15.1
4.9
5700 15.6
5.2
5.2
6000
15.5
5.5
6400 16.0
5.8
5.8
6800
15.9
6.1
7100 16.4
6.4
6.5
7600
16.3
6.8
7900 16.7
7.1
7.3
8500
16.7
7.6
8800 17.1
7.9
8.1
9400
17.1
8.5
9800 17.6
8.8
9.0
10500

LEGEND

BkW Brake Kilowatts

FIOP Factory-Installed Option

kW Input Kilowatts to Motor

Normal face: refers to the Standard Motor & Drive Package.

Bold-Italic face: requires a field supplied drive package.

For the available fan speeds refer to table in page 42.

NOTES:

1. Do not adjust motor r/s such that motor maximum bkW and/or watts is
exceeded at the maximum operating L/s.
2. Static pressure losses must be added to external static pressure before
entering Fan Performance table.

Watts

r/s

250
BkW

Watts

5800
6500
7400
8300
9300
10400

13.9
14.4
14.8
15.3
15.8
16.3
16.8

4.6
5.3
5.9
6.7
7.5
8.3
9.3

5400
6100
6900
7700
8700
9700
10800

500
BkW
4.4
4.9
5.4
6.1
6.9
7.5
8.3

Watts
5100
5700
6300
7000
8100
7500
9600

Watts
4800
5300
6000
6700
7500
7100
9200
10200

r/s
15.6
15.9
16.2
16.5
16.9
17.2
17.6

3. Interpolation is permissible. Do not extrapolate.


4. Fan performance is based on wet coils, clean filters, and casing losses.
5. Extensive motor and drive testing on these units ensures that the full
Brake Kilowatts and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bkW rating shown will
not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details. For additional information on motor performance,
refer to Evaporator-Fan Motor Performance table on page 43.
7. Evaporator Motor Efficiency 87%.

41

50TJ

FAN PERFORMANCE 50TJ032 UNIT SI


50TJ032
AIR
FLOW
(L/s)
r/s
3539
3775
4011
4247
4483
4719
4955
5191
13.9
5427
14.5
5663
15.0

Performance data (cont)


50TJ

OUTDOOR SOUND POWER


UNIT 50TJ

SOUND
RATING
(60Hz)
8.8 Bels
8.8 Bels
9.5 Bels
9.5 Bels
9.0 Bels

OCTAVE BANDS

A-WEIGHTED
(Db)

016
87.8
020
87.8
024
94.1
028
94.1
032
86.7
LEGEND

Bels Sound Levels (1 bel = 10 decibels)

63

125

250

500

1000

2000

4000

8000

90.8
90.8
98.7
98.7
92.0

88.7
88.7
92.3
92.3
87.3

86.4
86.4
93.8
93.8
83.7

84.3
84.3
90.9
90.9
84.9

83.5
83.5
89.6
89.6
82.9

78.4
78.4
85.9
85.9
76.9

75.6
75.6
80.3
80.3
70.0

66.8
66.8
74.3
74.3
61.4

FAN RPM AT MOTOR PULLEY SETTINGS* ENGLISH


Freq.

60 Hz

50 Hz

Unit 50TJ
016
020
024
028
032
016
020
024
028
032

1/2

690
765
710
810
840
690
765
710
810
830

705
780
720
820
865
705
780
720
820
855

720
795
730
830
890
720
795
730
830
880

MOTOR PULLEY TURNS CLOSE


11/2
2
21/2
3
31/2
735
810
740
840
915
735
810
740
840
905

750
825
750
850
940
750
825
750
850
930

765
840
760
860
965
765
840
760
860
955

780
855
770
870
990
780
855
770
870
980

795
870
780
880
1015
795
870
780
880
1005

41/2

810
885
790
890
1040
810
885
790
890
1030

825
900
800
900
1065
825
900
800
900
1055

840
915
810
910
1090
840
915
810
910
1080

*Approximate fan rpm shown.

*The standard belt size may not cover all the above range.

Other RPMs require a field supplied Drive Package.

FAN R/S AT MOTOR PULLEY SETTINGS* SI


Freq.

60 Hz

50 Hz

Unit 50TJ
016
020
024
028
032
016
020
024
028
032

1/2

11.5
12.8
11.83
13.5
14.0
11.5
12.8
11.8
13.5
13.8

11.75
13.0
12.0
13.7
14.4
11.75
13.0
12.0
13.7
14.3

12.0
13.3
12.15
13.8
14.8
12.0
13.3
12.15
13.8
14.7

*Approximate fan r/s shown.

*The standard belt size may not cover all the above range.

Other RPMs require a field supplied Drive Package.

42

MOTOR PULLEY TURNS CLOSE


11/2
2
21/2
3
31/2
12.25
13.5
12.33
14.0
15.3
12.25
13.5
12.3
14.0
15.1

12.5
13.8
12.5
14.2
15.7
12.5
13.8
12.5
14.2
15.5

12.75
14.0
12.66
14.3
16.1
12.75
14.0
12.66
14.3
15.9

13.0
14.3
12.83
14.5
16.5
13.0
14.3
12.8
14.5
16.3

13.25
14.5
13.0
14.7
16.9
13.25
14.5
13.0
14.7
16.8

41/2

13.5
14.8
13.15
14.8
17.3
13.5
14.8
13.15
14.8
17.2

13.75
15.0
13.33
15.0
17.8
13.75
15.0
13.3
15.0
17.6

14
15.3
13.5
15.2
18.2
14
15.3
13.5
15.2
18.0

EVAPORATOR-FAN MOTOR PERFORMANCE

016

Standard

020

Standard

024

Standard

028

Standard

032

Standard

UNIT
VOLTAGE

MAXIMUM
ACCEPTABLE
CONTINOUS
BHP*

MAXIMUM
ACCEPTABLE
CONTINOUS
BkW*

MAXIMUM
ACCEPTABLE
OPERATING
WATTS

5.5

5,180

5.5

5,180

8.2

6.1

7,900

8.2

6.1

7,900

11

8.6

9,500

208 - 230
380 - 460
208 - 230
380 - 460
208 - 230
380 - 460
208 - 230
380 - 460
208 - 230
380 - 460

MAXIMUM
AMP DRAW

50TJ

UNIT 50TJ

15.8
7.9
15.8
7.9
22.0
13.0
22.0
13.0
28.0
14.6

LEGEND
*Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range of the motors can be
utilized with confidence. Using your fan motors up to the horsepower (brake kilowatt) ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will
not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of
1992 (EPACT) effective October 24, 1997.
BHP Brake Horsepower
BkW Brake Kilowatts
EVAPORATOR-FAN MOTOR EFFICIENCY
UNIT
MOTOR EFFICIENCY (%)
016(5 Hp)
020(5 Hp)
024(7.5 Hp)
028(7.5 Hp)
032(10 Hp)

89.5
89.5
89.5
89.5
90.0

NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.

43

50TJ

Electrical data 50TJ016-032

UNIT

NOMINAL VOLTAGE
VOLTAGE RANGE

COMPRESSOR
NO. 1
NO. 2

OFM

(3PH) (Hz) Min Max RLA LRA RLA LRA Qty Hp FLA (ea)

16

20

24

28

032

230
380
460
400
230
380
460
400
230
380
460
400
230
380
460
400
230
380
460
400

60
60
60
50
60
60
60
50
60
60
60
50
60
60
60
50
60
60
60
50

187
342
414
360
187
342
414
360
187
342
414
360
187
342
414
360
187
342
414
360

253
418
508
440
253
418
508
440
253
418
508
440
253
418
508
440
253
418
508
440

28.8
15
14.7
15.5
30.1
15.3
15.5
19.6
37.8
21.2
17.2
25
41
21.8
21.8
27.2
41
21.8
21.8
27.2

195
123
95
111
225
140
114
125
239
145
125
167
350
151
158
198
350
151
158
198

28.8
15
14.7
15.5
28.8
15
14.7
15.5
30.1
15.3
15.5
19.6
37.8
21.2
17.2
25
41
21.8
21.8
27.2

195
123
95
11
195
123
95
111
225
140
114
125
239
145
125
167
350
151
158
198

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 380
v, 480 v, and 600 v. Heaters are rated at 240 v, 480 v, or 600 v. If
power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly. To determine heater capacity at
actual unit voltage, multiply 240 v, 480 v, or 600 v capacity by
multipliers found in table on page 4.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multi-motor and
combination load equipment (refer to NEC Articles 430 and 440), the
over current protective device for the unit shall be fuse or HACR
breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage Never operate a motor where
a phase imbalance in supply voltage is greater than 2%. Use the
following formula to determine the percent of voltage imbalance.

6.6
3.9
3.3
3.4
6.6
3.9
3.3
3.4
6.6
3.9
3.3
3.4
6.6
3.9
3.3
3.4
6.6
3.9
3.3
3.4

IFM
Hp FLA
5
5
5
5
5
5
5
5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
10
10
10
10

12.8
7.7
6.4
7.6
12.8
7.7
6.4
7.6
19.4
11.7
9.7
11.4
19.4
11.7
9.7
11.4
26.8
16.2
13.4
16.1

POWER
SUPPLY

ELECTRIC HEAT*

TOTAL
FLA/STAGE STAGES MCA
kW
27.5
18.6
27.6
21
27.5
18.6
27.6
21
36.7
24.8
36.8
28
36.7
24.8
36.8
28
36.7
24.8
36.8
28

34.6
14.3
17.2
15
34.6
14.3
17.2
15
47
19
23
20
47
19
23
20
47
19
23
20

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

91
50
47
50
94
50
48
54
110
62
54
69
123
69
61
77
128
74
70
85

MOCP
110
60
60
60
110
60
60
70
130
75
70
85
150
80
75
95
150
90
85
100

% Voltage Imbalance
= 100 x
maximum deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage=
452 + 464 + 455
3
=

1371

= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2% contact your local electric Utility company
3. MCA calculation for 50TJ016-032 units with electric heaters
over 50 kW = (1.25 x IFM amps) + (1.00 x heater FLA).

44

50TJ

Typical Wiring Schematic

Unit Model
50TJ-016-231S
50TJ-024-231S
50TJ-016-531S
50TJ-024-531S
50TJ-016-631S
50TJ-024-631S
50TJ-016-933S
50TJ-024-933S
50TJ-020-231S
50TJ-028-231S
50TJ-020-531S
50TJ-028-631S
50TJ-020-631S
50TJ-032-231S
50TJ-020-933S
50TJ-032-631S

45

50TJ

Typical Wiring Schematic

Unit Model
50TJ-028-933S
50TJ-032-933S

46

50TJ

Typical Wiring Schematic

Unit Model
50TJ-028-531S

47

50TJ

Typical Wiring Schematic

Unit Model
50TJ-032-531S

48

50TJ

Typical Wiring Schematic- (Cont.)

Unit Model
50TJ-016-231S
50TJ-024-531S
50TJ-016-531S
50TJ-024-631S
50TJ-016-631S
50TJ-024-933S
50TJ-016-933S
50TJ-028-231S
50TJ-020-231S
50TJ-028-631S
50TJ-020-531S
50TJ-028-933S
50TJ-020-631S
50TJ-032-231S
50TJ-020-933S
50TJ-032-631S
50TJ-024-231S
50TJ-032-933S

Unit Model
50TJ-028-531S

49

Typical Wiring Schematic -(Cont.)


50TJ

Unit Model
50TJ-032-531S

50

Operating sequence

Cooling, units-When thermostat calls for cooling,


terminals G and Y1 are energized. The indoor
evaporator fan contactor (IFC) and compressor
contactor no. 1 (C1) are energized, and evaporator-fan
motor (IFM), compressor no. 1 and condenser fan(s)
start. The condenser-fan motor(s) runs continuously
while unit is cooling. When the thermostat calls for a
second stage of cooling by energizing Y2, compressor
contactor no. 2 (C2) is energized and compressor no. 2
starts.
Heating, units (50TJ016-028),

Application data
Thermostat
Use of 2-stage cooling thermostat with 3-5 min. time
delay for compressor is recommended for all units. A
2-stage cooling thermostat is required on units if the
economizer is used to provide integrated cooling.
Heating-to-cooling changeover
All units are automatic changeover from heating to
cooling when automatic changeover thermostat and
sub-base are used.
Airflow
Units are draw-thru on cooling and blow-thru on
heating.
Maximum airflow
To minimize the possibility of condensate blow-off from
evaporator, airflow through units should not exceed
500 cfm/nominal ton (67.1 L/s per kW) on size 016-024
units, and 375 cfm/nominal ton (50.3 L/s per kW) on
size 028-032 units.
Minimum airflow
The minimum airflow for cooling is 300 cfm/nominal ton
(40 L/s per kW) on size 016-024 units and 280 nominal
cfm/ton (38 L/s per kW) on size 028-032 units.
Refer to Heating Capacities and Efficiencies table on
page 4 for minimum airflow cfm for heating on size
016-032 units.
Minimum ambient cooling operation temperature
Units are designed to operate at outdoor temperatures
down to 41 F (5 C). To operate at lower outdoor-air
temperatures, contact your local Carrier representative
for appropriate accessory combinations for specific
IMPORTANT: The minimum heating cfm must be
maintained to ensure proper operation in the
Heating mode.
The minimum heating cfm value takes precedence
over the minimum cooling cfm value.

if accessory or optional heater is installed) -Upon a


call for heating through terminal W1, IFC and heater
contactor no. 1 (HC1) are energized. On units
equipped for 2 stages of heat, when additional heat is
needed, HC2 is energized through W2.

IMPORTANT
Field installed thermostat should include time delay
between stages to limit the inrush current during the
unit starting and to ensure proper operation of unit
control.

applications.
Maximum operating outdoor-air temperature
For cooling, this temperature is 125 F (52 C) for all
sizes.
Internal unit design
Due to Carriers internal unit design (draw-thru over the
motor) air path, and specially designed motors, the full
horsepower (maximum continuous bhp) listed in the
Physical Data table and the notes following each Fan
Performance table can be utilized with extreme
confidence. Using Carrier motors with the values listed
in the Physical Data and Fan Performance Data tables
will not result in nuisance tripping or premature motor
failure. The unit warranty will not be affected.
Field-supplied fan drives
If the factorys drive sets must be changed to obtain
other wheel speeds, consult the nearest Browning
Manufacturing Co. sales office with the required new
wheel speed and the data from Physical Data tables
(center distances, motor and fan shaft diameters,
motor horsepower) for a modified drive set selection.
For minor speed changes, the motor sheave should be
adjusted. (Do not reduce the size of the motor sheave;
this will result in reduced belt horsepower ratings and
reduced belt life.)
Copper-fin coils provide increased corrosion rsistance
in moderate coastal environments where industrial air
pollution is not present. All copper coils eliminate bi
metallic contact to eliminate the potential for galvanic
corrosion.
Application in industrial environments is not
recommended due to potential attack from sulfur, sulfur
oxide, nitrogen oxides, carbon and several other
industrial airborne contaminants. In moderate seacoast
environments, copper-fin coils have extended life
compared to standard or pre-coated aluminum-fin
coils.

51

50TJ

Controls

50TJ

Guide Specifications 50TJ016-032

Side-Discharge Packaged Units

Packaged Rooftop Electric Cooling,


Electric Heat, Constant Volume
Application
HVAC Guide Specifications
Size Range: 15 to 30 Tons, Nominal (Cooling)
180,000 to 360,000 Btuh, Nominal
20 to 40 kW (Electric Heat)
68,000 to 136,000 Btuh
Carrier Model Numbers: 50TJ-B/S
Part 1 General
1.01 SYSTEM DESCRIPTION
Unit is an outdoor rooftop (or building side) mounted,
electrically controlled cooling and heating (optional)
unit utilizing scroll hermetic compressors for cooling
duty and electric heat. Unit is specifically designed for
horizontal supply and return ducts, as shown on
drawings. Standard unit shall include a manual
outdoor-air inlet and aluminum filter.
1.02 QUALITY ASSURANCE
A. Unit (016-024) shall be rated in accordance with ARI
Standards 270 and 360 and all units shall be designed
in accordance with UL Standard 1995.
NOTE: The 50TJ028,032-S is beyond the scope of the
ARI certification program.
B. Unit shall be designed to conform to ASHRAE 15.
C. Unit shall be installed without a roof curb.
D. Insulation and adhesive shall meet NFPA 90A
requirements for flame spread and smoke generation.
E. Unit casing shall be capable of withstanding 500hour salt spray exposure per ASTM B117 (scribed
specimen).
F. Unit shall be manufactured in a facility registered to
ISO 9002/BS5750, Part 2.
G. Blower motor and compressor shall have additional
external over-current protection.
H. Condenser coil shall be pre-coated aluminum-fin
coils shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping process to
create an inert barrier between the aluminum fin and
copper tube. Epoxy-phenolic barrier shall minimize
galvanic action between dissimilar metals.
I. Evaporator panels shall be double skin.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturers
recommendations.

Part 2 Products
2.01 EQUIPMENT (STANDARD)
A. General: The 50TJ-S unit shall be a factory
assembled, single piece cooling unit, with optional

52

electric heat. Contained within the unit enclosure shall


be all factory wiring, piping, controls, refrigerant charge
(R-22), and special features required prior to field start
up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and powder painted enamel finish.
2. Indoor blower compartment interior surfaces shall be
insulated with a minimum 1-in. (25 mm) thick, 1 lb (.45
kg) density neoprene coated, fiberglass insulation
coated on the air side.
Evaporator panels shall be double skin so that no
Fiberglass is exposed to air.
3. Cabinet panels shall be easily removable for
servicing.
4. Filters shall be accessible through an access panel.
5. Holes shall be provided in the base rails for rigging
shackles to facilitate overhead rigging.
6. Unit shall have a factory-installed internal
condensate drain connection and a sloped condensate
pan.
7. Condensate pan material shall be fabricated of
minimum spangle steel with a hot-dipped zinc coating
of 5% and will be Polyester Powder Painted.
C. Fans:
1. Indoor blower (evaporator fan):
a. Fan shall be belt driven. Belt drive shall include an
adjustable pulley. The standard fan drive shall have a
factory-installed low-medium static pressure fan drive.
b. Fan wheel shall be made from steel with a corrosion
resistant finish. It shall be a dynamically balanced,
double-inlet type with forward-curved blades.
2. Condenser fans shall be of the direct-driven
propeller type, with corrosion-resistant blades riveted
to corrosion-resistant steel supports. They shall be
dynamically balanced and discharge air upwards.
D. Compressor(s):
1. Fully hermetic, scroll type, internally protected.
2. Factory mounted on rubber grommets, internally
spring mounted for vibration isolation.
3. On electrically and mechanically independent
refrigerant circuits.
E. Coils:
1. Standard evaporator and condenser coils shall have
copper or aluminum plate fins mechanically bonded to
seamless internally grooved copper tubes with all joints
brazed.
F. Refrigerant Components:

Refrigerant circuit components shall include:

1. Thermostatic expansion valve (TXV).


2. Filter driers.
3. Gage port and connections on suction, discharge,
and liquid lines.

G. Filter Section:
Standard filter section shall consist of factory installed
washable aluminum filters.
H. Controls and Safeties:

1. Unit Controls:

a. Capacity control (2-step).

b. Unit shall be complete with self-contained low

voltage control circuit.

2. Safeties:

a. Unit shall incorporate a solid-state compressor

lockout which provides reset capability at the space

thermostat, should any of the following safety devices

trip and shut off compressor:

1) Compressor lockout protection provided for either

internal or external overload.

2) Low-pressure switch.

3) Freeze stats (evaporator coil).

4) High-pressure switch.

5) Phase monitors, prevents scroll compressor from

reverse rotation.

6) Blower motor and compressor shall have additional

external over-current protection.

I. Operating Characteristics:

1. Unit shall be capable of starting and running at 125

F (52 C) ambient outdoor temperature per maximum

load criteria of ARI Standard 360.

2. Unit with standard controls will operate in cooling

down to outdoor ambient temperature of 41 F(5 C).

J. Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single

location.

K. Motors:

1. Compressor motors shall be cooled by refrigerant

gas passing through motor windings and shall have

line break thermal and current overload protection.

2. All fan motors shall have permanently lubricated,

sealed bearings and inherent automatic-reset thermal

overload protection or manual reset calibrated circuit

breakers.

3. All indoor-fan motors 5 hp and larger shall meet the

minimum efficiency requirements as established by the

Energy Policy Act of 1992 (EPACT) effective

October 24, 1997.

Field Installed Options:


1. Head Pressure Control Package:
Consists of an accessory outdoor-air package and a
solid-state control with condenser coil temperature

sensor for controlling condenser-fan motor speed to


maintain condensing temperature between 90 F
(32.2 C) and 100 F (43.3 C) at outdoor ambient
temperature down to 20 F (29.8 C).
2. Low-Ambient Kits:

When used, allows units to operate at lower outdoor

ambient temperatures.

3. Service Options:
a. Non-fused disconnect switch: Shall be internallymounted. The NEC and UL approved non-fuse switch
shall provide unit power shutoff. The control access
door shall be interlocked with the nonfused disconnect.
The disconnect switch must be in the OFF position to
open the control box access door. Shall be accessible
from outside the unit and shall provide power off
lockout capability.
4. Electric Heater Package (Field supplied):
a. Fully assembled for installation.
b. Heater element open coil resistance wire, nickelchrome alloy, 0.29 inches inside diameter, strung
through ceramic insulators mounted on metal frame.
Coil ends are staked and welded to terminal screw
slots.
c. Heater assemblies are provided with integral fusing
for protection of internal heater circuits not exceeding
25 amps each.
d. Auto reset thermo limit controls, magnetic heater
contactors (24 v coil) and terminal block all mounted in
electric heater control box (minimum 18 ga. galvanized
steel) attached to end of heater assembly.
e. All power wiring leads are 10 AWG and control
wiring leads are 18 AWG, both rated at 105 deg. C.
5. Hail Guard, Condenser Coil Grille: Shall protect the
condenser coil from hail, flying debris, and damage by
large objects without increasing unit clearances.
Special Feature (S)
1. Evaporator panels shall be double skin.
2. Condenser coil shall be pre-coated aluminum-fin
coils shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping process to
create an inert barrier between the aluminum fin and
copper tube. Epoxy-phenolic barrier shall minimize
galvanic
action
between
dissimilar
metals.

53

50TJ

Guide Specifications 50TJ016-032


Side-Discharge Packaged Units ( Cont.)

50TJ

NOTES

50TJ

NOTES

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

JAN 2008

50TJSD-05 PD C